Sierra Monitor Corporation 3600I Instruction Manual

Page 1
3600I
MODEL 3600I
TRIPLE IR (IR3) FLAME DETECTOR
APPLICABILITY & EFFECTIVITY
Effective for all Model 3600I Detectors manufactured after June 1, 2010.
Rev. 3 August 2010
Page 2
3600I
ABOUT THIS GUIDE
This guide describes the Model 3600I Triple IR (IR3) Flame Detector and its features and provides instructions on how to install, operate and maintain the detector.
This guide includes the following chapters and appendixes:
Chapter 1, Introduction, provides a general overview of the product, principles of
operation, and performance considerations.
Chapter 2, Installing the Detector, describes how to install the detector including
preparations before installation, wiring and mode settings.
Chapter 3, Operating the Detector, describes how to power-up and test the
detector. The chapter also lists safety precautions you should take when operating the detector.
Chapter 4, Maintenance and troubleshooting, describes basic maintenance
procedures, and troubleshooting and support procedures.
Appendix A, Specifications: Lists the detectors technical and other specifications.
Appendix B, Wiring Instructions, lists the wiring instructions for connecting the
detector and also provides examples of typical wiring configurations.
Appendix C, RS-485 Communication Network, provides an overview of the RS-
485 communications network.
Appendix D, Accessories, describes the accessories available for the detector.
Appendix E, SIL-2 Features, describes the special conditions to comply with the
requirements of EN 61508 for SIL 2 according to TUV.
Page: ii
Page 3
ABBREVIATIONS AND ACRONYMS
Abbreviation Meaning
ATEX Atmosphere Explosives AWG American Wire Gauge BIT Built In Test EMC Electromagnetic Compatibility EOL End of Line FOV Field of View HART Highway Addressable Remote Transducer-communication
protocol IAD Immune at Any Distance IECEx International Electrotechnical Commission Explosion IPA Isopropyl Alcohol IR Infrared JP4 Jet Fuel Latching Refers to relays remaining in the ON state even after the ON
condition has been removed LED Light Emitting Diode LPG Liquefied Petroleum Gas mA MilliAmps (0.001 amps) MODBUS Master-slave messaging structure N.C. Normally Closed N.O. Normally Open N/A Not Applicable NFPA National Fire Protection Association NPT National Pipe Thread SIL Safety Integrity Level UNC Unified Coarse Thread VAC Volts Alternating Current
3600I
Page: iii
Page 4
3600I
TABLE OF CONTENTS
1 INTRODUCTION .......................................................................................................................... 1
1.1 OVERVIEW ......................................................................................................................... 1
1.2 MODEL AND TYPES .......................................................................................................... 2
1.3 FEATURES AND BENEFITS .............................................................................................. 4
1.4 PRINCIPLES OF OPERATION ........................................................................................... 4
1.4.1 HYDROCARBON FIRE DETECTION ............................................................................. 4
1.4.2 HEATED OPTICS ........................................................................................................... 5
1.4.3 HART PROTOCOL ......................................................................................................... 5
1.4.4 RS-485 MODBUS ........................................................................................................... 5
1.4.5 PRODUCT CERTIFICATION .......................................................................................... 6
1.5 PERFORMANCE CONSIDERATIONS ............................................................................... 6
1.5.1 DETECTION SENSITIVITY ............................................................................................. 6
1.5.2 CONE OF VISION ........................................................................................................... 8
1.5.3 FALSE ALARMS PREVENTION ................................................................................... 10
1.5.4 VISUAL INDICATORS .................................................................................................. 11
1.5.5 OUTPUT SIGNALS ....................................................................................................... 12
1.5.6 DETECTOR STATUS ................................................................................................... 13
1.5.7 AUXILIARY RELAY AS END-OF-LINE RESISTOR ..................................................... 14
1.6 INTERNAL DETECTOR TESTS ....................................................................................... 14
1.6.1 CONTINUOUS FEATURE TEST .................................................................................. 14
1.6.2 BUILT-IN-TEST (BIT) .................................................................................................... 15
2 INSTALLING THE DETECTOR ................................................................................................ 18
2.1 GENERAL GUIDELINES .................................................................................................. 18
2.2 UNPACKING THE PRODUCT .......................................................................................... 19
2.2.1 CHECKING THE PRODUCT TYPE .............................................................................. 19
2.3 REQUIRED TOOLS .......................................................................................................... 19
2.4 CERTIFICATION INSTRUCTIONS ................................................................................... 20
2.5 INSTALLATION CABLES .................................................................................................. 21
2.5.1 CONDUIT INSTALLATION ........................................................................................... 21
2.6 INSTALLING THE TILT MOUNT (PART NO. 3600I) ........................................................ 22
2.6.1 TILT MOUNT SPECIFICATIONS .................................................................................. 22
2.6.2 TILT MOUNT ASSEMBLY ............................................................................................ 23
Page: iv
Page 5
3600I
2.7 CONNECTING THE DETECTOR ..................................................................................... 24
2.7.1 VERIFYING THE DETECTOR WIRING ....................................................................... 25
2.8 CONFIGURING YOUR DETECTOR ................................................................................. 27
2.8.1 SENSITIVITY ................................................................................................................. 28
2.8.2 ALARM DELAY ............................................................................................................. 28
2.8.3 ADDRESS SET-UP ....................................................................................................... 28
2.8.4 FUNCTION SET-UP ...................................................................................................... 29
2.8.5 HEATED OPTICS ......................................................................................................... 29
3 OPERATING THE DETECTOR ................................................................................................. 30
3.1 POWERING UP................................................................................................................. 30
3.2 SAFETY PRECAUTIONS ................................................................................................. 31
3.2.1 DEFAULT FUNCTIONS SETTINGS ............................................................................. 31
3.3 TESTING PROCEDURES ................................................................................................ 32
3.3.1 AUTOMATIC BIT TEST ................................................................................................ 32
3.3.2 MANUAL BIT TEST ....................................................................................................... 32
3.3.3 TESTING WITH FIRE SIMULATOR MODEL 20/20-310 .............................................. 32
4 MAINTENANCE AND TROUBLESHOOTING .......................................................................... 34
4.1 MAINTENANCE ................................................................................................................ 34
4.1.1 GENERAL PROCEDURES ........................................................................................... 34
4.1.2 PERIODIC PROCEDURES ........................................................................................... 35
4.1.3 KEEPING MAINTENANCE RECORDS ........................................................................ 35
4.2
TROUBLESHOOTING .................................................................................................. 36
Page: v
Page 6
3600I
APPENDICES ................................................................................................................................... 37
A SPECIFICATIONS ..................................................................................................................... 38
A.1 TECHNICAL SPECIFICATIONS ....................................................................................... 38
A.2 ELECTRICAL SPECIFICATIONS ..................................................................................... 39
A.3 OUTPUTS ......................................................................................................................... 39
A.4 MECHANICAL SPECIFICATIONS .................................................................................... 41
A.5 DIMENSIONS .................................................................................................................... 41
A.6 WEIGHT ............................................................................................................................ 41
A.7 ENVIRONMENTAL SPECIFICATIONS ............................................................................ 42
B WIRING INSTRUCTIONS .......................................................................................................... 43
B.1 GENERAL INSTRUCTIONS FOR ELECTRICAL WIRING ............................................... 43
B.2 TYPICAL WIRING CONFIGURATIONS ........................................................................... 44
C RS-485 COMMUNICATION NETWORK ................................................................................... 48
C.1 RS-485 OVERVIEW .......................................................................................................... 48
D ACCESSORIES ......................................................................................................................... 49
D.1 LONG RANGE IR3 FIRE SIMULATOR ............................................................................ 49
D.1.1 UNPACKING ................................................................................................................. 49
D.1.2 OPERATING INSTRUCTIONS ..................................................................................... 50
D.1.3 RANGE .......................................................................................................................... 51
D.1.4 CHARGING THE BATTERY ......................................................................................... 51
D.1.5 TECHNICAL SPECIFICATIONS ................................................................................... 52
D.2 TILT MOUNT - P/N 3600-001 ........................................................................................... 52
D.3 WEATHER PROTECTION - P/N 777163 ......................................................................... 53
D.4 LASER DETECTION COVERAGE POINTER - P/N 777166 ............................................ 54
D.5 AIR SHIELD - P/N 777161 ................................................................................................ 54
E SIL-2 FEATURES ...................................................................................................................... 55
E.1 3600I FLAME DETECTOR ................................................................................................ 55
E.1.1 SAFETY RELEVANT PARAMETERS .......................................................................... 55
E.1.2 GUIDELINES FOR CONFIGURING, INSTALLING, OPERATING AND
SERVICE ................................................................................................................................... 55
LIMITED WARRANTY ...................................................................................................................... 57
Page: vi
Page 7
3600I
LIST OF FIGURES
Figure 1: Horizontal Field of View ....................................................................................................... 8
Figure 2: Vertical Field of View ........................................................................................................... 9
Figure 3: Indication LED: Indication LED .......................................................................................... 11
Figure 4: Detector with Tilt Mount ..................................................................................................... 22
Figure 5: Tilt Mount Assembly ........................................................................................................... 23
Figure 6: Tilt Mount Assembly (dimensions in mm and inches) ........................................................ 23
Figure 7: Detector with Cover Removed ........................................................................................... 25
Figure 8: Wiring Terminals ................................................................................................................ 44
Figure 9: Typical Wiring for 4 Wire Controllers (Using Option 1 or 2 Wiring) ................................... 45
Figure 10: 0-20mA Wiring Option 1 (Sink 4-Wire) - Default .............................................................. 46
Figure 11: 0-2mA Wiring Option 1 (Converted to Source 3-Wire) .................................................... 46
Figure 12: 0-20mA Wiring Option 1 (Unisolated Sink 3-Wire) .......................................................... 47
Figure 13: 0-20mA Wiring Option 2 and 3 (Source 3-Wire) .............................................................. 47
Figure 14: RS-485 Networking .......................................................................................................... 48
Figure 15: IR3 Long Range Fire Simulator 20/20-310 ...................................................................... 49
Figure 16: 3600I IR3 Detector Target Point ...................................................................................... 50
Figure 17: Tilt Mount ......................................................................................................................... 52
Figure 18: Weather Protection .......................................................................................................... 53
Figure 19: Laser Detection Coverage Pointer ................................................................................... 54
Figure 20: Air Shield .......................................................................................................................... 54
Page: vii
Page 8
3600I
LIST OF TABLES
Table 1: Wiring Options ....................................................................................................................... 3
Table 2: Sensitivity Range Levels ....................................................................................................... 7
Table 3: Fuel Sensitivity Ranges ......................................................................................................... 8
Table 4: Immunity to False Alarm Sources ....................................................................................... 10
Table 5: Welding Immunity Distance ................................................................................................. 11
Table 6: LED Indications ................................................................................................................... 11
Table 7: Available Output Types ....................................................................................................... 12
Table 8: Detector Status .................................................................................................................... 13
Table 9: Output Signals versus Detector State ................................................................................. 13
Table 10: Results of a Successful BIT .............................................................................................. 16
Table 11: Results of an Unsuccessful BIT ........................................................................................ 16
Table 12: Results of a Successful Manual BIT ................................................................................. 17
Table 13: Results of an Unsuccessful Manual BIT ........................................................................... 17
Table 14: Tools .................................................................................................................................. 19
Table 15: USA Version ...................................................................................................................... 22
Table 16: European Version ............................................................................................................. 22
Table 17: Model 3600I Wiring Options .............................................................................................. 26
Table 18: Sensitivity Settings ............................................................................................................ 28
Table 19: Functions ........................................................................................................................... 29
Table 20: Default Function Values .................................................................................................... 31
Table 21: Results of Successful Fire Simulator Test ........................................................................ 33
Table 22: Troubleshooting Table ...................................................................................................... 36
Table 23: Electrical Specifications .................................................................................................... 39
Table 24: Contact Ratings ................................................................................................................. 40
Table 25: 20 mA Current Output ....................................................................................................... 40
Table 26: Electromagnetic Compatibility (EMC) ............................................................................... 42
Table 27: Maximum DC resistance at 68°F (20ºC) for copper wire .................................................. 43
Table 28: Wiring length in feet (meter) .............................................................................................. 43
Table 29: Wiring Connections ........................................................................................................... 45
Table 30: Sensitivity Ranges ............................................................................................................. 51
Page: viii
Page 9
In this chapter…
Overview page 1 Model and Types page 2 Features and Benefits page 4 Principles of Operation page 4 Performance Considerations page 6 Internal Detector Tests page 14
1.1 OVERVIEW
The Model 3600I is a flame detector that utilizes improved IR3 technology to provide state-of-the-art fire protection. The 3600I uses patented digital signal processing to analyze the spectral and dynamic characteristics of the measured infrared radiation, to identify fire events with exceptional sensitivity and extreme immunity to false alarms.
3600I
1 INTRODUCTION
All 3600 series detectors include a heated optical window for improved performance in icing, snow and condensation conditions.
Detection performance can be easily adapted to all environments, applications and requirements, by changing the detector’s configuration parameters. Adjusting these parameters, as well and performing other maintenance and monitoring tasks, is possible by means of RS485-based Modbus communication or HART communication (in models with 0-20mA output).
The detector enclosure is ATEX certified EExd flameproof with an integral, segregated, rear, EExe terminal compartment (avoiding exposure of the sensors and electronics to surrounding environment). Hence the combined approval EExde IIB + H2 T5 (75°C) or T4 (85°C).
The 3600 detectors are designed to operate as a stand-alone unit directly connected to an alarm system or an automatic fire extinguishing system. The detector can also be a part of a more complex system, where many detectors and other devices are integrated through a common control unit.
Page: 1
Page 10
1.2 MODEL AND TYPES
The 3600I is provided in various configurations depending on:
Wiring options
Temperature ranges
Type of cable entries
Housing type
Required approval
The configuration detail is included in the product part number on the product label and takes the form: 3600I XXXXX, where XXXXX defines the model according to the above requirements.
To modify the default or pre-ordered configuration and perform maintenance tasks, please refer to the HART Protocol TM777030, the RS-485 Manual TM 777050 or TM777060.
The Part Numbers are defined as:
40/40I X XXXX
3600I
3600I
Table 1 describes the wiring options in detail.
Ex Approval
Housing
Electrical Entries
Temperature
Wiring Configuration
F – FM / CSA C - ATEX / IECEx
S - Stainless Steel A - Aluminum
1 - M25 2 - ¾" NPT
1 - 75°C 2 - 85°C
See Table 1
Page: 2
Page 11
3600I
Table 1: Wiring Options
Wiring Option
1 Power Manual BIT
2 Power Manual BIT
3 Power Manual BIT
4 Power Manual BIT
5 Power Manual BIT
Note: Wiring option 1 is default. The mA 'Sink' output can be altered to 'Source' type, with a link between terminals 1 and 8. No other wiring options can be changed on site.
For example, product number 3600I-321SC has the following options:
Wiring Option: 3 (Power, Manual BIT, RS-485, 0-20mA (Source) with HART
Protocol, Fault Relay (N.O.), Alarm Relay (N.O., N.C.))
Temperature Range: 2 (85°C)
Cable Entry: 1 (M25)
Connections Provided
Fault Relay
N.C.
Fault Relay
N.C.
Fault Relay
N.O.
Fault Relay
N.C.
Fault Relay
N.O.
Alarm Relay
N.O.
Alarm Relay
N.O., N.C.
Alarm Relay
N.O., N.C.
Alarm Relay
N.O.
Alarm Relay
N.O.
0-20mA Sink RS-485 -
0-20mA Source RS-485 HART
0-20mA Source RS-485 HART
Auxiliary N.O. RS-485 -
Auxiliary N.O. RS-485 -
Housing : S (Stainless Steel)
Approval: C (ATEX, IECEx)
Note: Check your specific part numbers against the information in Checking the Product Type on page 19.
Page: 3
Page 12
1.3 FEATURES AND BENEFITS
Detection Range: Up to 215 ft. (65m) for a 1 ft2 (0.1m2) n-heptane fire.
Ultra High Immunity to False Alarms: See Table 4 on page 10.
Advanced Digital Processing of the Dynamic Characteristics of Fire: Flickering,
threshold correlation and ratio.
Multi IR Channels: Between 3-5 microns
Field Programmable Sensitivity: Four ranges to avoid zone crossover.
Built In Test (BIT): Manual and Automatic (see Built-In-Test (BIT) on page 15).
Heated Window: Prevents effects of icing, snow, condensation.
Electrical Interface:
Dry contact relays
Communication network RS-485
0-20mA output
HART Protocol: Communication protocol (see HART Protocol on page 5).
3600I
EExde: Integral junction box for easy wiring.
SIL-2: TÜV approved.
Hazardous Area Certification: ATEX, IECEx, FM.
1.4 PRINCIPLES OF OPERATION
This section describes the 3600I principles of operation and includes:
Hydrocarbon Fire Detection, page 4
Heated Optics, page 5
HART Protocol, page 5
RS-485 Modbus, page 5
Product Certification, page 6
1.4.1 HYDROCARBON FIRE DETECTION
The Model 3600I detector is designed to detect flames in which carbon dioxide (CO2) is produced in the combustion process. These include all hydrocarbon flames, as well as other types of flames and burning materials such as wood or alcohol.
The detector’s principle of operation is based on patented IR3 technology. This technology identifies the unique spectral signature that hot CO namely a peak of the intensity at wavelengths 4.2 to 4.7µ.
has in the infrared (IR),
2
Page: 4
Page 13
The IR3 technique utilizes few infrared sensors, each sensitive to its own wavelength range. The first sensor is sensitive to wavelengths within the emission peak of hot CO The other two sensors are sensitive to wavelengths above and below this peak. The fourth IR sensor is sensitive to a different band within the emission peak of hot CO the event of fire, the signal measured in the first sensor is significantly higher than those measured in the second two sensors. In order to issue a fire alarm, the detector requires that this occurs, as well as other conditions (for example, radiation is flickering in frequencies typical of flames). The signal of this sensor is compared to those of the other three. This increases sensitivity for some types of flames. (For example, gas flames).If exposed to non-fire radiation sources, the specific conditions required does not occur, and the detector does not react.
1.4.2 HEATED OPTICS
The 3600 Flame Detectors use heated optics. The heater increases the temperature of the optical surface by 5-8°F (~3-5°C) above the ambient temperature to improve performance in icing, condensation and snow conditions.
The heated optics can be set to one of the following:
Not operated
On continuously
3600I
.
2
. In
2
Automatic, per temperature change (default): you can define the start temperature below which the window is heated. (The default is 41°F (5°C). This temperature can be defined between 32°F (0°C) to 122°F (50°C). The heating stops when the temperature is 27°F (15°C) above the start temperature.
For more information, see Configuring your Detector on page 27.
1.4.3 HART PROTOCOL
The 3600 Flame Detectors use the HART Protocol.
HART Communication is a bi-directional industrial field communication protocol used to communicate between intelligent field instruments and host systems. HART is the global standard for smart process instrumentation and the majority of smart field devices installed in plants worldwide are HART-enabled. HART is available in wiring options 2 and 3, see Table 1.
HART technology is easy to use and very reliable.
Through the HART connection, you are able to perform:
Detector set-up
Detector troubleshooting
Detector health and status
For more details, refer to the HART Manual TM 777030.
1.4.4 RS-485 MODBUS
For more advanced communications, the 3600 detector has an RS 485 Modbus­compatible output that provides data communication from a network (up to 247 detectors) to a host computer or universal controller for central monitoring. This feature allows for reduced installation costs, easy maintenance and local or remote diagnostic tools.
Page: 5
Page 14
1.4.5 PRODUCT CERTIFICATION
The 3600I Flame Detectors have the following certifications:
ATEX, IECEX, page 6
SIL-2 Approved, page 6
1.4.5.1 ATEX, IECEX
The 3600I Flame Detector is certified to:
ATEX Ex II 2 GD per SIRA 07ATEX 1149 and IECEx SIR. 07.0085.
3600I
EExde IIB + H
T5 Ambient Temp. -55°C to +75°C.
T4 Ambient Temp. -55°C to +85°C.
This product is suitable to use in hazardous zones 1 and 2 with IIB + H vapors present.
.
2
1.4.5.2 SIL-2 APPROVED
The 3600I Flame Detector is certified to SIL-2 requirement per IEC 61508.4, Chapter
3.5.12.
The alert condition according to SIL-2 can be implemented by:
Alert signal via 0-20mA current loop.
or
Alert signal via alarm relay and fault relay.
For more details and guidelines for configuring, installing, operating and service –
see SIL-2 Features on page 55 and TÜV Report No. 968/EZ348.00/009.
1.5 PERFORMANCE CONSIDERATIONS
This section describes performance aspects of the 3600I and includes:
gas group
2
Detection Sensitivity, page 6
Cone of Vision, page 8
False Alarms Prevention, page 10
Visual Indicators, page 11
Output Signals, page 12
Detector Status, page 13
Auxiliary Relay as End-of-Line Resistor, page 14
1.5.1 DETECTION SENSITIVITY
Detection sensitivity is the maximum distance at which the detector reliably detects a specific size of fire and typical type of fuel (standard fire).
Page: 6
Page 15
1.5.1.1 STANDARD FIRE
Defined as a 1ft2 / 0.1m2 n-heptane pan fire, with maximum wind speed of 6.5 ft/sec (2 m/sec).
1.5.1.2 SENSITIVITY RANGES
The detector has four user-selectable sensitivity ranges. For each range there are two response levels.
WARNING (Pre-alarm)
ALARM
The detection distance, for the WARNING level, is approximately 10% higher than the ALARM distance.
Alarm response times for a standard fire at a specified range are shown Table 2.
Table 2: Sensitivity Range Levels
Level Response Time (sec) Sensitivity Range- ft (m)
1 3 50 (15) 2
Default
3 8 150 (45) 4 10 215 (65)
5 100 (30)
3600I
For some typical ambient conditions the Zeta parameter as defined in NFPA 72 for the detector is 0.005 (1/meter).
Note: Zeta parameters may vary significantly with changes in temperature, air pressure, humidity, visibility conditions, and so on.
1.5.1.3 OTHER FUELS
The detector reacts to other types of fire as follows:
The baseline fire refers to n-heptane 1ft
For fuel fire – standard pan fire size: 1ft
For gas flame – 20 inch (0.5m) high, 8 inch (0.2m) width plume fire.
Maximum Response Time: 10 sec.
2
(0.1m2) and is defined as 100% sensitivity.
2
(0.1m2).
Page: 7
Page 16
Table 3: Fuel Sensitivity Ranges
3600I
Type Of Fuel
Gasoline
N-Heptane
JP4 70% Kerosene 70% Diesel Fuel 70% Alcohol 95% 60% IPA 60% Methanol 55% Methane 45% LPG 45% Paper 35% Polypropylene 15%
1.5.2 CONE OF VISION
Horizontal: 100°
Percent of Max. Distance at each Sensitivity
Range
100%
100%
Figure 1: Horizontal Field of View
Page: 8
Page 17
3600I
Vertical: +50° (down) , -45° (up)
Figure 2: Vertical Field of View
Page: 9
Page 18
1.5.3 FALSE ALARMS PREVENTION
To prevent false alarms, the detector will not alarm or react to the radiation sources specified in Table 4.
Table 4: Immunity to False Alarm Sources
3600I
Radiation Source
Indirect or reflected sunlight IAD Vehicle headlights (low beam) conforming to MS53023-1 IAD Incandescent frosted glass light, 300 W IAD Fluorescent light with white enamel reflector, standard office or
shop, 70 W (or two 35 W) Electric arc [12mm (15/32") gap at 4000 V alternating current, 60
Hz] Arc welding [6 mm (5/16") rod; 210 A] See Table 5 Ambient light extremes (darkness to bright light with snow,
water, rain, desert glare and fog) Bright colored clothing, including red and safety orange IAD Electronic flash (180 watt-seconds minimum output) IAD Movie light, 625 W quartz DWY lamp (Sylvania S.G.-55 or
equivalent) Blue-green dome light conforming to M251073-1 IAD Flashlight (MX 991/U) IAD Radiation heater, 3000 W >3 (1) Radiation heater, 1000 W with fan IAD Quartz lamp (1000 W) >3 (1) Mercury vapor lamp IAD Grinding metal IAD Lit cigar >1 (0.3) Lit cigarette >1 (0.3) Match, wood, stick including flare up >13 (4)
Immunity Distance ft (m)
IAD
IAD
IAD
>6.5 (2)
Notes:
IAD = Immune at Any Distance.
All sources are chopped from 0 to 20 Hz.
Page: 10
Page 19
Table 5: Welding Immunity Distance Sensitivity Setting Detection Range Immunity Distance
1 50 ft (15m) >6 ft (2m) 2 100 ft (30m) >12 ft (4m) 3 150 ft (45m) >17 ft (6m) 4 215 ft (65m) >25 ft (7.5m)
1.5.4 VISUAL INDICATORS
One 3-color LED indicator is located inside the detector window, as shown in Figure 3. The detector statuses are listed in Table 6.
Table 6: LED Indications Detector Status LED color LED mode
Fault, BIT Fault Yellow 4 Hz - flashing Normal Green 1 Hz - flashing Warning Red 2 Hz - flashing Alarm Red Steady
3600I
Figure 3: Indicator LED
Indicator LED
Page: 11
Page 20
1.5.5 OUTPUT SIGNALS
Outputs are available according to the default configuration or the wiring options selected for the 3600I IR3 Detector. Determine the outputs for your model according to Table 7.
The detector incorporates several types of output suitable to different control systems:
0-20mA (stepped) with HART
Relays (Alarm, Fault, Auxiliary)
RS-485 Modbus
Table 7: Available Output Types
Output Type Version Detector Status
3600I
Alarm relay 3600I – Options 1XXXX, 4XXXX,
5XXXX
3600I – Options 2XXXX, 3XXXX The relay is N.O. and N.C. Auxiliary relay 3600I – Options 4XXXX and 5XXXX The relay is N.O. Fault relay 3600I – Options 1XXXX, 2XXXX,
4XXXX
3600I – Options 3XXXX, 5XXXX The relay is N.O. energized 0-20mA current
output
RS-485 All versions Modbus Protocol
3600I – Option 1XXXX SINK Option, (can be changed to
3600I – Options 2XXXX and 3XXXX SOURCE Option with HART
The relay is N.C.
The relay is N.C. energized
Source – see Figure 10, Figure 101 and Figure 102)
protocol
Page: 12
Page 21
1.5.6 DETECTOR STATUS
The possible detector function statuses are listed in Table 8. A more detailed fault analysis can be seen via HART or RS485.
Table 8: Detector Status Status Description
Normal Normal operation. BIT Built-In-Test being performed. Warning Fire detected - changed to Warning (pre-alarm state). Alarm Fire detected - changed to Fire Alarm state. Latched Alarm (Optional) BIT Fault A fault is detected during BIT sequence or other electric failure.
Fault A fault is detected when the power supply is too low or due to a
In each state, the detector activates different outputs, as specified in Table 9.
The alarm outputs remain latched on following detection of a fire that has already been extinguished.
The detector will continue to detect for fire.
software fault or electrical failure. The detector will NOT detect fire in this condition.
3600I
Table 9: Output Signals versus Detector State Detector
State
LED Indicator
LED Mode
Alarm Relay
Auxiliary Relay
Fault Relay
mA output
Normal Green 1Hz Off Off On 4 mA Warning Red 2Hz Off On
(1)
Alarm Latch
BIT Fault Warning at
Red Constant On On On 20 mA
(2)
Red Constant On Off On 20 mA
(3)
Yellow 4Hz Off Off Off 2 mA
Red 2Hz Off On
(4)
On 16 mA
(4)
On
On 20 mA
(4)
Off 16 mA
BIT Fault Alarm at BIT
Red Constant On On Off 20 mA
Fault Fault Yellow 4Hz Off Off Off 0 mA
Notes:
1 The alarm outputs are activated while alarm conditions exist and will stop
approximately 5 seconds after the fire is no longer detected.
2 The Alarm state can be optionally latched via programmed function. (Default is non-
latching).
3 The detector will remain in BIT Fault state until it has passed a successful BIT. 4 The Auxiliary Relay can be activated at the Warning level or Alarm level, depending
on programmed function.
5 The outputs depend on the wiring options.
Page: 13
Page 22
1.5.6.1 OPTIONAL LATCHING
Alarms are set as non-latching by default. However, the detector includes a latched alarm output capability, which operates according to the programmed function.
If selected, upon detection of a fire, the detection signal is latched until a manual reset is performed (disconnecting the power supply or performing a manual BIT (see Manual BIT on page 16).
Latching affects the Alarm Relay, 0-20mA output, the Alarm LED (the Auxiliary Relay will be latched only when the programmable function Auxiliary Relay is set to YES.
Notes:
The Auxiliary Relay is available only in Model 3600I – 4XXXX and 5XXXX
The 0-20mA is available only in Model 3600I – 1XXXX, 2XXXX, 3XXXX
1.5.7 AUXILIARY RELAY AS END-OF-LINE RESISTOR
The Auxiliary Relay can be used as End-of-Line (EOL) resistance in Model 3600I­4XXXX, and 5XXXX only. In this case, the Auxiliary Relay is active as long as the detector is not in Fault state.
1.6 INTERNAL DETECTOR TESTS
3600I
The detector performs two types of self tests:
Continuous Feature Test, page 14
Built-In-Test (BIT), page 15
1.6.1 CONTINUOUS FEATURE TEST
During normal operation, the detector tests itself continuously and indicates a fault if a failure is found. This type of test complies with SIL-2 requirements.
The detector continuously tests:
Input voltage level
All internal regulator voltage level
Voltage level status of sensor and sensor circuitry for noise or disconnection in the
electronic circuitry
0-20mA level output
Relays and heater operation
Processor Watch dog
Software
Memory
Oscillator frequency
Page: 14
Page 23
Response to Fault Indication
If a failure is found, the detector indicates by:
Fault relay:
Opens in wiring option 1, 2, and 4
Closes in wiring option 3 and 5
0-20mA: indicates Fault (0mA or 2mA) in wiring option 1, 2, 3
LED – Yellow flashes (4 Hz)
Correcting the Fault
The fault indications remain until the detector’s power is removed. The fault indications return if the fault is still found when power is restored.
1.6.2 BUILT-IN-TEST (BIT)
The detector’s Built-In-Test (BIT) also checks the following:
Electronics circuitry
Sensors
Window cleanliness
3600I
The detector can be set to perform the BIT in the following modes:
Automatically and manually
Manually only
Note: In Manual BIT, the outputs may also be tested and Control System ‘inhibit’ should be applied if this could initiate other systems.
1.6.2.1 HOW THE BIT OPERATES
The detector's status remains unchanged if the result of a BIT is the same as the current status (NORMAL or BIT Fault)
the detectors’ status is changed (from Normal to BIT Fault or vice versa) if the BIT differs from the current status
Note: In ‘BIT Fault’ status the detector can continue to detect a fire.
Page: 15
Page 24
1.6.2.2 AUTOMATIC BIT
The detector automatically performs a BIT every 15 minutes. A successful BIT sequence does not activate any indicator.
The results of a successful and unsuccessful BIT are listed in Table 10 and Table 11.
Table 10: Results of a Successful BIT Output Result
Fault relay Model 1XXX, 2XXX, 4XXX Wiring options 1, 2, 4: remains
CLOSED
Model 3XXX, 5XXX Wiring options 3 and 5: remains OPEN
0-20mA output Wiring option 1, 2, 3: Normal (4 mA) Power LED Green, Flashing, 1 Hz On (Normal)
Table 11: Results of an Unsuccessful BIT Output Result
Fault relay Wiring option 1, 2, 4: changes to Open
Wiring option 3 and 5: changes to Closed
0-20mA output Wiring option 1, 2, 3: BIT Fault (2mA) Power LED Yellow, Flashing, 4 Hz BIT procedure Performed every 1 minute
3600I
1.6.2.3 MANUAL BIT
The BIT is manually initiated by momentarily connecting Terminal 3 with Terminal 2 (or a switch across these terminals in the safe area).
If the BIT is unsuccessful, all outputs will function as described for Automatic BIT, but the BIT is now automatically executed every 1 minute. This continues until a successful BIT occurs, when the detector will resume normal operation.
The results of a successful and unsuccessful Manual BIT are listed in Table 12 and Table 13.
Page: 16
Page 25
3600I
Table 12: Results of a Successful Manual BIT Output Result
FAULT relay Wiring options 1, 2, and 4: remains CLOSED (Normal)
Wiring options 3 and 5: remains OPEN (Normal)
ALARM relay Activated for 3 sec (only when the function Alarm BIT is set to YES) AUXILIARY
relay 0-20mA output Wiring option 1, 2, 3:
POWER LED Green, Flashing, 1 Hz
Table 13: Results of an Unsuccessful Manual BIT Output Result
FAULT relay Wiring option 1, 2, 4: changes to OPEN
0-20mA output Wiring option 1, 2, 3: Indicates BIT FAULT (2mA) POWER LED Yellow, Flashing, 4 Hz
For wiring options 4 and 5: is activated for 3 sec (only when the function Auxiliary BIT is set to YES)
Initiates 20 mA only when the function Alarm BIT is set to YES
Initiates 16 mA when the function Auxiliary BIT is set to YES
and the function Alarm BIT is set to NO
Wiring option 3 and 5:changes to CLOSED
1.6.2.4 MANUAL BIT ONLY SELECTED
The BIT is initiated manually by momentarily connecting Terminal Number 3 with Terminal Number 2 or a switch across these terminals in the safe area.
Page: 17
Page 26
3600I
2 INSTALLING THE DETECTOR
In this chapter…
General Guidelines page 18 Unpacking the Product page 19 Required Tools page 19 Certification Instructions page 20 Installation Cables page 21 Installing the Tilt Mount (part no. 3600 page 22 Connecting the Detector page 24 Configuring your Detector page 27
This chapter provides basic guidelines for installing the detector. It does not attempt to cover all of the standard practices and codes of installation. Rather, it emphasizes specific points of consideration and provides some general rules for qualified personnel. Wherever applicable, special safety precautions are stressed.
2.1 GENERAL GUIDELINES
To ensure optimal performance and an efficient installation, consider the following guidelines:
Sensitivity: To determine the level of sensitivity, consider the following:
Size of fire at the required distance to be detected
Type of flammable materials
Wiring:
The wire gauge must be designed according to the distance from the detector to
the controller and the number of detectors on the same power line. See Wiring Instructions on page 43.
To fully comply with EMC directive and protect against interference caused by
RFI and EMI, the cable to the detector must be shielded and the detector must be grounded. The shield should be grounded at the detector end.
Spacing and Location: The number of detectors and their locations in the protected area are determined by:
Size of the protected area
Sensitivity of the detectors
Obstructed lines of sight
Cone of view of the detectors
Environment:
Dust, snow or rain can reduce the detectors sensitivity and require more
maintenance activities.
Page: 18
Page 27
The presence of high intensity flickering IR sources may affect sensitivity.
Aiming the Detector:
The detector should be aimed toward the center of the detection zone and have
a completely unobstructed view of the protected area.
Whenever possible, the detector face should be tilted down at a 45º angle to
maximize coverage and prevent accumulation of dust and dirt.
Do not start an installation unless all conceivable considerations regarding
detection location have been taken into account.
Installation should comply with NFPA 72E or any other local and International regulations and standards, as applicable to flame detectors and installation of Ex approved products.
2.2 UNPACKING THE PRODUCT
Upon receipt of your detector, check and record the following:
1 Verify the appropriate Purchase Order.
Record the Part Number (P/N) and Serial Number of the detectors, and the installation date in an appropriate Log-book.
3600I
2 Open the package before installation and visually inspect the detector. 3 Verify that all components required for the detector installation are readily available
before beginning the installation. If the installation is not completed in a single session, secure and seal the detectors and conduits / cable entries.
2.2.1 CHECKING THE PRODUCT TYPE
Check that your product has the configuration / options that you ordered. Check the detailed part number on the label and compare this information with the descriptions contained in Model and Types on page 2.
2.3 REQUIRED TOOLS
The detector can be installed using general-purpose common tools and equipment. Table 14 lists the specific tools required to install the detector.
Table 14: Tools Tool Function
Hex Key 3/16 inch Mount the detector on the tilt mount.
Open and close detector cover (for wiring).
Flat Screw Driver 4 mm Connect ground terminal. Flat Screw Driver 2.5 mm Connect wires to the terminal blocks.
For wiring, use color-coded conductors or suitable wire markings or labels. 12 to 20 AWG (0.5 mm² to 3.5 mm²) wires may be used for site wiring. The selection of wire gauge should be based on the number of detectors used on the same line and the distance from the control unit, in compliance with specifications (see General Instructions for Electrical Wiring on page 43).
Page: 19
Page 28
2.4 CERTIFICATION INSTRUCTIONS
Warning: Do not open the detector, even when isolated, when flammable
atmosphere present.
Use the following certification instructions:
The cable entry point may exceed 167°F (75°C). Suitable precautions should be taken when selecting the cable.
The equipment may be used with flammable gases and vapors with apparatus groups IIA and IIB + H2:
T5 in the ambient temperature range: –67°F (–55°C) to +167°F (+75°C).
T4 in the ambient temperature range: –67°F (–55°C) to +185°F (+85°C).
Installation shall be carried out by suitably trained personnel in accordance with the
applicable code of practice such as. EN 60079-14:1997.
Inspection and maintenance of this equipment shall be carried out by suitably trained personnel in accordance with the applicable code of practice such as EN 60079-17.
3600I
Repair of this equipment shall be carried out by suitably trained personnel in accordance with the applicable code of practice such as EN 60079-19.
The certification of this equipment relies upon the following materials used in its construction:
Enclosure: 316L Stainless Steel or Aluminum
Window: Sapphire Glass
If the equipment is likely to come into contact with aggressive substances, then it is
the responsibility of the user to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of protection provided by the equipment is not compromised:
Aggressive substances: acidic liquids or gases that may attack metals, or
solvents that may affect polymeric materials.
Suitable precautions: regular checks as part of routine inspections or
establishing from the material’s data sheets that it is resistant to specific chemicals.
Page: 20
Page 29
2.5 INSTALLATION CABLES
Follow the following guideline for the cable installation:
All cables to the detector must be well shielded in order to comply with EMC requirement (see Technical Specifications on page 52).
Ground the detector to the nearest ground point (not more than 3m from the detector location).
Install the detector with the cable entries placed downwards.
2.5.1 CONDUIT INSTALLATION
The conduit used for the cabling must comply with the following:
To avoid water condensation water in the detector, install the detector with the conduits placed downward, that include drain holes.
When using the optional tilt mount, use flexible conduits for the last portion connecting to the detector.
For installations in atmospheres as defined in group B of the NFPA 72E, seal the conduits inlets.
3600I
When pulling the cables through the conduits, ensure that they are not tangled or stressed. Extend the cables about 30 cm. (12 in.) beyond the detector location to accommodate wiring after installation.
After the conductor cables have been pulled through the conduits, perform a continuity test.
Page: 21
Page 30
2.6 INSTALLING THE TILT MOUNT (PART NO. 3600-001)
The Tilt Mount enables the detector to be rotated up to 60º in all directions.
Figure 4 shows the Detector mounted on the Tilt Mount.
3600I
Figure 4: Detector with Tilt Mount
2.6.1 TILT MOUNT SPECIFICATIONS
Table 15: USA Version Item Qty Type Location
Tilt Mount 1 3600-001 Screw 4 ¼" 20 UNC x ¾" Detector – Holding plate Spring Washer 4 No. ¼" Detector - Holding plate
Table 16: European Version Item Qty Type Location
Tilt Mount 1 3600-001 Screw 4 M6 x 1 x 20 mm Detector – Holding plate Spring Washer 4 M6 Detector - Holding plate
Page: 22
Page 31
2.6.2 TILT MOUNT ASSEMBLY
Figure 5 shows the Tilt Mount Assembly.
Figure 5: Tilt Mount Assembly
3600I
TiltHoldingPlate
TiltMount
Horizontal LockingScrew
VerticalLocking Screw
DetectorHolding Plate
Figure 6 shows the Tilt Mount Assembly with dimension in both millimeters and inches.
Figure 6: Tilt Mount Assembly (dimensions in mm and inches)
Page: 23
Page 32
To install the Tilt Mount and Detector:
1 Place the tilt mount in its designated location and secure it with four (4) fasteners
through four (4) holes 7 mm in diameter. Use the 4 screws and spring washers according to the kit (see Table 15 and Table 16).
Note: Removing the detector for maintenance purpose does not require the Tilt Mount to be removed).
2 Unpack the detector.
3600I
3 Place the detector with its conduit/cable entries pointing downwards on the holding
plate of the tilt mount. Secure the detector with mount.
4 Release the Horizontal and Vertical Locking Screws using
the detector can be rotated. Point the detector towards the protected area and make certain that the view of the area is unobstructed. Secure the detector in that position by tightening the locking screws on the tilt mount. (Make sure the detector is in the correct position.). The detector is now correctly located, aligned and ready to be connected to the system.
2.7 CONNECTING THE DETECTOR
This section describes how to connect the electric cabling to the detector (Figure 7).
To connect the detector to the electrical cables
1 Disconnect the power. 2 Remove the back cover of the detector by removing four (4) socket head-screws in
the cover bolts. The terminal chamber is now revealed.
3 Remove the protective plug mounted on the Detector Conduit/Cable entry; pull the
wires through the Detector Inlet.
4 Use a ¾" – 14 NPT explosion-proof conduit connection or M25x1.5 flameproof
gland to assemble the cable / conduit to the detector.
5
/16" 18 UNC x 1" screw to the tilt
3
/16" Hex Key such that
Page: 24
Page 33
3600I
Terminal Chamber
Terminals
Internal Earth Terminal
Earth Terminal
Detector Holding Screw
Conduit / Cable Inlet
Figure 7: Detector with Cover Removed
5 Connect the wires to the required terminals on the Terminal Board according to the
wiring diagram (Figure 7) and Table 17.
6 Connect the grounding (earth) wire to the ground (earth) screw outside the detector
(Earth Terminal). The detector must be well grounded to earth ground.
7 Verify the wiring. Improper wiring may damage the detector. 8 Check the wires for secure mechanical connection and press them neatly against
the terminal to prevent them from interfering while closing the back cover (Figure 7).
9 Place and secure the detector’s back cover by screwing the four (4) socket-head-
screws in the Cover Bolts (Figure 4).
2.7.1 VERIFYING THE DETECTOR WIRING
The detector has five output wiring options within the EExde integral terminal section of the enclosure. There are 12 terminals labeled 1-12.
For more information on the wiring options, see Wiring Instructions on page 43.
For mA wiring options see Figure 10, Figure 11, Figure 12, and Figure 13.
For relay connection options see Figure 9.
Table 17 describes the function of each terminal for all the wiring options.
Page: 25
Page 34
Table 17: Model 3600I Wiring Options
3600I
Wire Terminal No.
Option 1 Default
Option 2 Option 3 Option 4 Option 5
1 +24 VDC +24 VDC +24 VDC +24 VDC +24 VDC 2 0 VDC 0 VDC 0 VDC 0 VDC 0 VDC 3 Manual BIT Manual BIT Manual BIT Manual BIT Manual BIT 4
Fault Relay
5
N.C.
6 Alarm Relay
N.O.
Fault Relay
N.C.
Alarm Relay
N.O.
Fault Relay
N.O.
Alarm Relay
N.O.
Fault Relay
N.C.
Alarm Relay
N.O.
7 Alarm Relay C Alarm Relay C Alarm Relay C Alarm Relay C Alarm Relay
8 0-20mA
In
9 0-20mA Out 0-20mA
10 RS-485+
(1)
11 RS-485-
(1)
12 RS-485 GND RS-485
Alarm Relay
N.C.
Out*
RS-485+
(1)
RS-485-
(1)
GND
Alarm Relay
N.C.
0-20mA
Out*
RS-485+
(1)
RS-485-
(1)
RS-485
GND
Auxiliary
N.O.
Auxiliary C Auxiliary C
RS-485+
(1)
RS-485-
(1)
RS-485
GND
* Available with the HART protocol.
Fault Relay
N.O.
Alarm Relay
N.O.
C
Auxiliary
N.O.
RS-485+
(1)
RS-485-
(1)
RS-485
GND
Notes:
RS-485 is used for communication network as specified in Appendix C (Terminals 10, 11, 12) and to connect (in safe area) to PC/Laptop for configuration/diagnostics.
Alarm relay:
N.O. energized contact in wiring options 1, 4, 5.
N.O. and N.C. energized in options 2 and 3.
0-20mA is ‘Sink’ in option 1 and ‘Source’ in option 2 and 3.
0-20mA ‘Source’ in options 2 and 3 available with the HART protocol.
In Wiring Option 1, link Terminals 1 and 8 to change the mA output to ‘Source’.
The Fault output is N.C. energized SPST relay. The contacts are closed when the
Detector is in its normal operational condition in options 1, 2 and 4, and available as N.O. energized in options 3 and 5.
The Auxiliary output is N.O. energized (SPST) relay. The Auxiliary Relay may act in parallel with the ALARM relay to activate another external device or it may provide a warning signal, depending on the function configuration.
Page: 26
Page 35
2.8 CONFIGURING YOUR DETECTOR
You can reprogram the function setup using the RS-485 connection or using the Hart Protocol as follows:
Sierra Monitor Host Software: The Sierra Monitor Host Software is for use on a PC or laptop. Refer to Manual TM777050 for programming instructions. The Host software enables you to change the functions.
Handheld Unit: Refer to Manual 777060 for programming instructions when using the Handheld Unit. The connection to the Handheld is fast and intrinsically safe. It enables you to change the functions in situ with no need to remove the detector.
Note: Sierra Monitor can provide a suitable cable (P/N 794079-5) with integral RS485/USB converter to connect between the Detector and a PC/laptop.
Hart Protocol: Refer to Manual TM 777030 for programming instructions.
These functions enable you to set:
Sensitivity
Alarm Delay
Time Delay for Anti Flare mode
Address Setup
3600I
Mode of Operation
Heated Optics Operation
The factory Default settings listed for each function are:
Sensitivity 30
Alarm Delay – A
Alarm Latch – No
Auxiliary Relay – No
Automatic BIT – Yes
Alarm BIT – No
Auxiliary BIT – No
EOL – No
Heated Optics – Auto
Temperature – 41°F (5°C)
Page: 27
Page 36
2.8.1 SENSITIVITY
The detector offers four (4) sensitivity settings. The settings refer to an n-heptane or gasoline fire of 1ft² (0.1m²), from low sensitivity of 50 ft (15m) to 215 ft (65m). For other types of fuel sensitivity, refer to Table 3.
Table 18: Sensitivity Settings
Sensitivity Setting Detector Distance - feet Detector Distance - meters
15 50 15
30 (default) 100 30
45 150 45 60 215 65
2.8.2 ALARM DELAY
The detector is equipped with an Alarm Delay option, which provides programmable time delays with settings at:
Antiflare* (default)
*The Antiflare mode is selected to prevent false alarms in locations where fast flares may be present. The Time Delay for fire alarms in this mode ranges from 2.5 to 15 seconds (usually, less than 10 seconds).
3600I
Other delays settings are available:
0, 3, 5, 10, 15, 20 or 30 seconds
When an Alarm (Detection) level condition occurs, the detector delays the execution of the Alarm outputs by the specified period of time. The detector then evaluates the condition for 3 seconds. If the Alarm level is still present, the Alarm outputs are activated. If this condition no longer exists, the detector returns to its standby state.
The Alarm delay option affects the output relays and the 0-20mA. The LEDs and outputs indicate warning levels during the delay time only if the fire condition exists.
2.8.3 ADDRESS SET-UP
The detector provides up to 247 addresses that can be changed with RS485 communication link or HART Protocol.
Page: 28
Page 37
2.8.4 FUNCTION SET-UP
You can select the desired functions as detailed in the following table.
Table 19: Functions Function Setting
Alarm Latch Yes: Enable Alarm latching.
No: Disable Alarm latching (default).
Auxiliary Relay** Yes: Activate Auxiliary Relay at Warning level.
No: Activate Auxiliary Relay at Alarm level (default).
Automatic BIT Yes: Perform Automatic & Manual Bit (default).
No: Perform Manual Bit only.
Alarm BIT Yes: Successful Manual Bit activates the Alarm Relay
No: Successful Manual Bit does not activate the Alarm
Auxiliary BIT** Yes: Successful Manual Bit activates the Auxiliary Relay
No: Successful Manual Bit does not activate the
EOL** Yes: Auxiliary Relay is used as End of Line.
No: Auxiliary Relay operates in accordance with
3600I
for approximately 3 seconds (default).
Relay.
for approximately 3 seconds (default).
Auxiliary Relay.
Function 2 and 5 (default).
Note: ** only available in Model 3600I-4XXXX and 5XXXX
2.8.5 HEATED OPTICS
The heated optics can be defined as one of the following modes:
Heated Mode
OFF: Not operated
On: Continuously
AUTO: Per temperature change
In AUTO mode, the default HEAT ON setting is 41°F (5°C). Heating stops when the temperature is 27°F (15°C) above the start temperature.
You can define the start temperature below which the window will be heated. The temperature can be defined between 32°F and 122°F (0°C to 50°C).
Page: 29
Page 38
3 OPERATING THE DETECTOR
In this chapter…
Powering Up page 30 Safety Precautions page 31 Testing Procedures page 32
This chapter describes how to power up and test the detector. It also includes some very important safety checks that you should make before operating the detector.
3.1 POWERING UP
This section describes how to power up the detector. Follow these instructions carefully to obtain optimal performance from the detector over its life cycle:
To power up the detector:
1 Turn on the power.
3600I
2 Wait approximately 60 seconds for the detector to finish the start-up procedure.
Applying power initiates the following sequence of events:
The yellow LED flashes at 4 Hz.
BIT is executed.
If successful, the green LED flashes at 1 Hz and the FAULT relay contacts close, mA output is 4 mA.
3 Enter to Normal mode.
Note: The majority of detectors are used in the default non-latching alarm mode. Only
perform a Reset when the Latching alarm option has been programmed.
To reset a detector when in it is in a LATCHED ALARM state:
Do one of the following:
Disconnect power (Terminal Number 1 or Terminal Number 2).
or
Initiate a Manual BIT.
Page: 30
Page 39
3.2 SAFETY PRECAUTIONS
After powering-up, the detector requires almost no attention in order to function properly, but the following should be noted:
Follow the instructions in this guide and refer to the drawings and specifications.
Do not expose the detector to radiation of any kind unless required for testing
purposes.
Do not open the detector housing, while power is applied.
Do not open the electronic compartment. This part should be kept closed at all
times and only opened in the factory. Opening the electronic component side invalidates the warranty.
You should only access the wiring compartment to wire or remove the detector or access RS485 terminals for maintenance.
Disconnect or disable external devices, such as automatic extinguishing systems before carrying out any maintenance.
3.2.1 DEFAULT FUNCTIONS SETTINGS
Table 20 lists the default function configuration supplied with the detector.
3600I
Table 20: Default Function Values Function Value Notes
Sensitivity 30 Alarm Delay A Anitflare Alarm Latch No Auxiliary Relay No In wiring options 1, 2, 3 the Auxiliary Relay is not
available. This function is not used. Automatic BIT Yes Alarm BIT No Auxiliary BIT No In wiring options 1, 2, 3 the Auxiliary Relay is not
available. This function is not used. EOL No In wiring options 1, 2, 3 the Auxiliary Relay is not
available. This function is not used. Heat Mode Auto Heat On 41°F (5°C) The detector starts heating the window for any
temperature below this value (in degrees
Celsius).
In order to change the default function use:
P.C with Sierra Monitor software, refer to Manual 777050 for instructions.
Handheld unit, refer to Manual 777060 for instructions.
USB cable with 485 converter (1 m) part number 794079-5.
HART Protocol, refer to Manual 777030 for instructions.
Page: 31
Page 40
3.3 TESTING PROCEDURES
This section describes the proof testing procedure for proper operation of the detector. The detector can be tested using the Manual Built-in-Test or the Sierra Monitor IR3 Fire Simulator - 20/20-310.
The detector performs internal test continuously and automatic BIT test every 15 minutes for more details refer to Built-In-Test (BIT) on page 15.
This section includes the following topics:
Automatic BIT Test, page 32
Manual BIT Test, page 32
Testing with Fire Simulator Model 20/20-310, page 32
3.3.1 AUTOMATIC BIT TEST
Check that the indicators show normal conditions. See Powering Up on page 30.
3.3.2 MANUAL BIT TEST
Important: If the function setup Alarm BIT and/or Auxiliary BIT are set to Yes (default No), the Alarm, Auxiliary Relay and 0-20mA outputs are activated during a Manual BIT.
Therefore, automatic extinguishing systems or any external devices that may be activated during BIT must be disconnected.
3600I
To perform a Manual BIT:
1 Verify that the detector is Normal Mode. 2 Initiate Manual BIT. The results of successful and unsuccessful manual BITs are
detailed in Table 12 and Table 13.
3.3.3 TESTING WITH FIRE SIMULATOR MODEL 20/20-310
The Fire Simulator Model 20/20-310 can be used to simulate exposure of the detector to a real fire condition. The detector is exposed to radiation at the required detection level. As a result, the detector will generate a Fire Alarm signal. See Long Range IR3 Fire Simulator on page 49 for more information.
Important: If the detector is exposed to a fire simulator, the Alarm and Accessory Relays and 0-20mA are activated during the simulation. Therefore, automatic extinguishing systems or any external devices, which may be activated during this process, must be disconnected.
To perform Fire Simulator Test:
1 Power up the system and wait up to 60 seconds for the detector to turn to a normal
state. The Power LED turns on.
2 Aim the Sierra Monitor Fire Simulator Model 20/20-310 at the target point of the
detector (Figure 14), in a way that the radiation emitted by it is facing directly towards the detector. (See Long Range IR3 Fire Simulator on page 49).
3 Press the operation button once. After few seconds, a successful test shows the
results shown in Table 21.
Page: 32
Page 41
3600I
Table 21: Results of Successful Fire Simulator Test Component Action Notes
0-20mA Turn to 20mA For a few seconds and then return to 4mA Alarm Relay Activated for a few seconds and then returns to Normal Auxiliary Relay Activated for a few seconds and then returns to Normal Fault Relay Remains active
during the test
LED Red, steady
The detector is now ready for operation.
Page: 33
Page 42
4 MAINTENANCE AND TROUBLESHOOTING
In this chapter…
Maintenance page 34 Troubleshooting page 36
This chapter deals with preventive maintenance, describes possible faults in detector operation and indicates corrective measures. Ignoring these instructions may cause problems with the detector and may invalidate the warranty. Whenever a unit requires service, please contact Sierra Monitor or its authorized distributor for assistance.
4.1 MAINTENANCE
This section describes the basic maintenance steps that should be taken to keep the detector in good working condition and includes the following topics:
General Procedures, page 34
Periodic Procedures, page 35
3600I
Keeping Maintenance Records, page 35
4.1.1 GENERAL PROCEDURES
Maintenance should be performed by suitably qualified personnel, who are familiar with local codes and practice. Maintenance requires ordinary tools.
4.1.1.1 CLEANING
The detector must be kept as clean as possible. Clean the viewing window and the reflector of the Flame Detector periodically.
The frequency of cleaning operations depends upon the local environmental conditions and specific applications. The fire detection system designer will give his recommendations.
To clean the detector viewing window and reflector:
1 Disconnect power to the detector before proceeding with any maintenance including
window/lens cleaning.
2 Use water and detergent, and then rinse the viewing window with clean water. 3 Where dust, dirt or moisture accumulates on the window, first clean it with a soft
optical cloth and detergent, and then rinse with clean water.
Page: 34
Page 43
4.1.2 PERIODIC PROCEDURES
In addition to preventive cleaning and maintenance, the detector should be functionally tested every six months or as dictated by local codes and regulations. These tests should also be carried out if the detector has been opened for any reason.
4.1.2.1 POWER-UP PROCEDURE
Perform Power-Up procedure every time power is restored to the system. Follow the instructions described in Powering Up on page 30.
4.1.2.2 FUNCTIONAL TEST PROCEDURE
Perform a functional test of the detector as described in Internal Detector Tests on page
14.
4.1.3 KEEPING MAINTENANCE RECORDS
It is recommended that maintenance operations performed on a detector are recorded in a Log-book. The record should include the following:
Installation date, and contractor
Serial and tag no.
3600I
Entries for every maintenance operation performed, including the description of the operation, date and personnel ID.
If a unit is sent to Sierra Monitor or a distributor for service, a copy of the maintenance records should accompany it.
Page: 35
Page 44
4.2 TROUBLESHOOTING
This section is intended to be a guide to correct problems which may happen during normal operation.
Table 22: Troubleshooting Table Problem Cause Corrective Action
3600I
LEDs Off Fault Relay at N.O 0­20mA at 0mA
Yellow LED flashes at 4 Hz Fault Relay at N.O 0­20mA at 0mA
Yellow LED flashes at 4 Hz Fault Relay at N.O 0­20mA at 2mA
Red LED constantly on
Alarm Relay at On 0­20mA at 20mA
No power at the unit Check that the correct power is
sent to the detector.
Check power polarity.
Check wiring in the detector.
Send the detector back for
repairs.
Fault Detector
Low Voltage
Faulty Detector
Check the voltage at the
detector; verify at least 24V at the detector terminal.
Send the detector back for
repairs.
BIT Fault
Faulty Detector
If no fire exists, then,
Clean detector window.
Re-power the detector.
Replace the detector.
Perform Reset to the detector.
detector alarm latched
Alarm condition Check cause for alarm.
If no alarm, re-power the
detector.
Send the detector back for
repairs.
Page: 36
Page 45
3600I
APPENDICES
Page: 37
Page 46
A SPECIFICATIONS
In this appendix…
Technical Specifications page 38 Electrical Specifications page 39 Outputs page 39 Mechanical Specifications page 41 Dimensions page 41 Weight page 41 Environmental Specifications page 42
A.1 TECHNICAL SPECIFICATIONS
3600I
Spectral Response
Detection Range
(at highest Sensitivity Setting for
2
(0.1m2) pan fire)
1ft
Response Time
Adjustable Time Delay
Sensitivity Ranges
Fields of View
Built-In-Test (BIT)
Three IR Bands
Fuel ft / m Fuel ft / m
n-Heptane 215 / 65 Kerosene 150 / 45
Gasoline 215 / 65 Ethanol 95% 135 / 40
Diesel Fuel 150 / 45 Methanol 115 / 35
JP5 150 / 45 IPA (Isopropyl
Alcohol)
Methane* 100 / 30 Polypropylene
Pellets
LPG* 100 / 30 Office Paper 33 / 10
* 20" (0.5m) high, 8" (0.2m) width plume fire
Typically 5 seconds
Up to 30 seconds
2
4 Sensitive ranges for 1 ft 50 ft (15m) to 215 ft (65m)
Horizontal 100°, Vertical 95°
Automatic (and Manual)
(0.1m2) n-heptane pan fire from
135 / 40
16 / 5
Page: 38
Page 47
A.2 ELECTRICAL SPECIFICATIONS
Table 23: Electrical Specifications
3600I
Operating Voltage Status All
Outputs
Power Consumption (Max. 24VDC)
Maximum Current (Max. 24VDC)
Power Consumption (Max. 18-32VDC)
Maximum Current (18-32VDC)
Normal 1.61W 1.56W
Normal when Heater On 2.28W 2.16W
Alarm 2.64W 2.28W
Alarm when Heater On 3.24W 2.88W
Normal 70mA 65mA
Normal when Heater On 95mA 90mA
Alarm 110mA 95mA
Alarm when Heater On 135mA 120mA
Normal 1.95W 1.85W
Normal when Heater On 2.56W 2.45W
Alarm 3.04W 2.56W
Alarm when Heater On 3.68W 3.2W
Normal 90mA 85mA
Normal when Heater On 105mA 100mA
Alarm 130mA 115mA
Without 0­20mA
Electrical Input Protection
A.3 OUTPUTS
Electrical Interface
Alarm when Heater On 160mA 145mA
The input circuit is protected against voltage­reversed polarity, voltage transients, surges and spikes according to MIL-STD-1275B
There are five output-wiring options. These options must be defined at the factory per the customer order and cannot be changed at the customer facility.
See General Instructions for Electrical Wiring on page 43 for the wiring/terminal diagram for each option.
Unless otherwise specified, the default is Option 1. The wiring arrangement is identified on the detector by the part number (see Model and Types on page 2).
Option 1: Power, RS-485, 0-20mA (Sink), Fault I Relay (N.C),
Alarm Relay, (N.O) (see Figure 7).
Option 2: Power, RS-485, 0-20mA (Source) and HART
protocol, Fault Relay (N.O), Alarm Relay, (N.O), (N.C).
Option 3: Power, RS-485, 0-20mA (Source) and HART
Protocol, Fault Relay (N.O), Alarm Relay (N.O, N.C).
Page: 39
Page 48
Electrical Outputs
3600I
Option 4: Power, RS-485, Fault Relay (N.C), Auxiliary Relay
(N.O), Alarm Relay, (N.O).
Option 5: Power, RS-485, Fault Relay (N.O), Auxiliary Relay
(N.O), Alarm Relay, (N.O).
Dry Contact Relays
Table 24: Contact Ratings
Relay Name Type Normal
Position
Maximum Ratings
Alarm DPST N.O., N.C. 2A at 30 VDC or
0.5A at 250 VAC
Auxiliary SPST N.O. 5A at 30 VDC or
250 VAC
Fault * SPST N.C. or N.O 5A at 30 VDC or
250 VAC
Notes:
The Fault relay (in wiring options 1, 2, 4) is normally
energized closed during normal operation of the detector. The relay is de-energized open if a fault condition or low voltage situation occurs.
* In wiring options 3, 5 the relay is normally energized
open during normal operation of the detector. The relay is de-energized close contact if a fault condition or low voltage situation occurs.
0-20mA Current Output: The 0-20mA can be Sink or Source
according to the wiring option source (see General Instructions for Electrical Wiring on page 43). The maximum permitted load resistance is 600Ω.
Table 25: 20 mA Current Output
State Output
Fault 0 +1 mA BIT Fault 2 mA±10% Normal 4 mA±10% Warning 16 mA±5% Alarm 20 mA±5%
HART Protocol
The HART is a digital communication signal at a low level on top of the 0-20mA. This is a bi-directional field communication protocol used to communicate between intelligent field instruments and the host system. HART is available in wiring options 2 and 3.
Through HART protocol the detector can:
Display set-up
Reconfigure the set-up
Display detector status and definition
Perform detector diagnostics
Troubleshoot
For more details refer to HART Manual 777030.
Page: 40
Page 49
3600I
Communication Network: The detector is equipped with an
RS-485 communication link that can be used in installations with computerized controllers.
The communications protocol is Modbus compatible.
This protocol is a standard and widely used.
It enables continuous communication between a standard
Modbus controller (Master device) and a serial Network of up to 247 detectors.
Headed Optics
The front window can be heated to improve performance in icing, condensation and snow conditions. The heater increases the temperature of the optical surface by 5-8°F (3-5°C) above the ambient temperature. The heated optics can be configured in three ways:
Off: The optics are not heated
On: The optics are heated continuously
Auto: Operated only when the change of temperature requires
the heating. (default)
In Auto mode the start heating temperature can be defined between 32°F - 122°F (0°C - 50°C). The detector stops heating the window when the temperature is 27°F (15°C) above the start temperature.
A.4 MECHANICAL SPECIFICATIONS
Enclosure
Hazardous Area Approvals
Water and Dust Tight
Electronic Modules Electrical Connection
(two entries)
Stainless Steel 316 or Aluminum, heavy duty copper free (less than-1%), red
epoxy enamel finish
FM, CSA
Class I Div. 1 Groups B, C and D; Class II/III Div. 1 Groups E, F and G.
ATEX, IECEx ; EX II 2 GD, EExde IIB + H2 T5 (75°C),
T4 (85°C)
NEMA 250 type 6p.
IP 66 and IP 67 per EN 60529
Conformal coated
x ¾" - 14NPT conduit
or
2 x M25 (ISO)
A.5 DIMENSIONS
4" x 4.6" x 6.18" (101.6 x 117 x 157 mm)
A.6 WEIGHT
Stainless Steel: 6.1 lb. (2.8 kg) Aluminum: 2.8 lb. (1.3 kg)
Page: 41
Page 50
A.7 ENVIRONMENTAL SPECIFICATIONS
The 3600I is designed to withstand harsh environmental conditions.
High Temperature
Low Temperature
Humidity
Salt Fog
Dust
Vibration
Mechanical Shock
Electromagnetic Compatibility (EMC)
Designed to meet MIL-STD-810C, method 501.1
procedure II
Operating temperature: +167°F (+75 °C)
Storage temperature: +185 °F (+85 °C)
Designed to meet MIL-STD-810C, method 502.1,
procedure I
Operating temperature: -57°F (-50°C)
Storage temperature: -65°F (-55°C)
Designed to meet MIL-STD-810C, method 507.1,
procedure IV
Relative humidity of up to 95% for the operational
temperature range
Designed to meet MIL-STD-810C, method 509.1,
procedure I
Exposure to a 5% Salt Solution Fog for 48 hours
Designed to meet MIL-STD-810C, method 510.1,
procedure I
Exposure to a dust concentration of 0.3 frames/cubic
ft. at a velocity of 1750 fpm, for 12 hours
Designed to meet MIL-STD-810C, method 514.2,
procedure VIII
Vibration at an acceleration of 1.1g within the
frequency range of 5-30 Hz, and an acceleration of 3g within the frequency range of 30-500 Hz
Designed to meet MIL-STD-810C, method 516.2,
procedure I
Mechanical Shock of 30g half-sine wave, for 11 msec
See Table 26
3600I
Table 26: Electromagnetic Compatibility (EMC) Test Standard Level Per
Electrostatic Discharge ESD IEC 61000-4-2 IEC 61326-3 Radiated EM Field IEC 61000-4-3 IEC 61326-3 Electrical Fast Transients IEC 61000-4-4 IEC 61326-3 Surge IEC 61000-4-5 IEC 61326-3 Conducted Disturbances IEC 61000-4-6 IEC 61326-3 Power Ferq. Magnetic Field IEC 61000-4-8 IEC 61326-3 Radiated Emission IEC 61000-6-3 EN 55022 Conducted Emission IEC 61000-6-3 EN 55022 Immunity to Main Supply Voltage Variations MIL-STD-1275B
To fully comply with EMC directive and protect against interference caused by RFI and EMI, the cable to the detector must be shielded and the detector must be grounded. The shield should be grounded at the detector end.
Page: 42
Page 51
B WIRING INSTRUCTIONS
In this appendix…
General Instructions for Electrical Wiring page 43 Typical Wiring Configurations page 44
B.1 GENERAL INSTRUCTIONS FOR ELECTRICAL WIRING
Follow the instructions detailed in this section for determining the correct wire gauge to be used for the installation.
1 Use Table 27 to determine the required wire gauge /size for general wiring, such as
relay wiring. Calculate the permitted voltage drop with respect to load current, wire gauge and length of wires.
Table 27: Maximum DC resistance at 68°F (20ºC) for copper wire
AWG # mm2 Ohm per 100 ft Ohm per 100 m
26 0.12 - 0.15 4.32 14.15 24 0.16 - 0.24 3.42 11.22 22 0.30 - 0.38 1.71 5.60 20 0.51 - 0.61 1.07 3.50 18 0.81 - 0.96 0.67 2.20 16 1.22 - 1.43 0.43 1.40 14 1.94 - 2.28 0.27 0.88 12 3.09 - 3.40 0.17 0.55 10 4.56 - 6.64 0.11 0.35
3600I
2 Use Table 28 to select wire gauge for power supply wires. DO NOT connect any
circuit or load to detectors’ supply inputs.
Select Number of detectors connected in one circuit.
Select wiring Length per your installation requirements.
Refer to Power Supply Range for voltage extreme applied.
Table 28: Wiring length in feet (meter)
Number of
Detectors
24 18 16 14 - - 22-32 20 18 16 14 - - 22-32 16 20 18 16 14 - 22-32 12 20 18 16 14 - 20-32
8 20 18 16 14 - 20-32
4 and less 20 18 16 16 14 20-32
Ft (m) 164 (50) 328 (100) 492 (150) 656 (200) 820 (240)
Recommended Wire Diameter (AWG)
Max. Length from Power Supply to Last Detector
Power Supply
Range (VDC)
Page: 43
Page 52
B.2 TYPICAL WIRING CONFIGURATIONS
This section describes examples of typical wiring configurations.
3600I
Figure 8: Wiring Terminals
Page: 44
Page 53
3600I
Table 29: Wiring Connections Wiring Option Detector
Model
1 3600I-1XXXX Fault Relay
2 3600I-2XXXX Fault Relay
3 3600I-3XXXX Fault Relay
4 3600I-4XXXX Fault Relay
5 3600I-5XXXX Fault Relay
Terminals
5 8 9
0-20mA (Sink) 0-20mA (Sink)
(N.C)
(N.C)
(N.O)
(N.C)
(N.O)
Alarm Relay
(N.C)
Alarm Relay
(N.C)
Auxiliary Relay
(N.O)
Auxiliary Relay
(N.O)
0-20mA Duct
0-20mA Duct
Auxiliary Relay
Auxiliary Relay
Source
Source
(C)
(C)
Figure 9: Typical Wiring for 4 Wire Controllers (Using Option 1 or 2 Wiring)
Page: 45
Page 54
Figure 10: 0-20mA Wiring Option 1 (Sink 4-Wire) - Default
3600I
Figure 11: 0-2mA Wiring Option 1 (Converted to Source 3-Wire)
Page: 46
Page 55
3600I
Figure 12: 0-20mA Wiring Option 1 (Unisolated Sink 3-Wire)
Figure 13: 0-20mA Wiring Option 2 and 3 (Source 3-Wire available with the HART protocol)
Note: There are no 0-20mA outputs in wiring options 4 and 5.
Page: 47
Page 56
C RS-485 COMMUNICATION NETWORK
In this appendix…
RS-485 Overview page 48
C.1 RS-485 OVERVIEW
By using the RS-485 network capability of the IR3 detector and additional software, it is possible to connect up to 32 detectors in an addressable system with four (4) wires only (2 for power and 2 for communication). Using repeaters, the number of detectors can be much larger (32 detectors for each repeater) up to 247 on the same four (4) wires. When using the RS-485 network, it is possible to read each detector status (FAULT, WARNING, and ALARM) and to initiate a BIT to each detector individually.
For more details, consult Sierra Monitor.
3600I
Figure 14: RS-485 Networking
Page: 48
Page 57
D ACCESSORIES
In this appendix…
Long Range IR3 Fire Simulator page 49 Tilt Mount - P/N 3600-001 page 52 Weather Protection - P/N 777163 page 53 Laser Detection Coverage Pointer - P/N 777166 page 54 Air Shield - P/N 777161 page 54
This appendix describes the accessories that can help you maximize fire detection with the IR3 flame detector:
D.1 LONG RANGE IR3 FIRE SIMULATOR
The IR3 Long Range Fire Simulator 20/20-310 is designed specifically for use with IR3 flame detectors. The Fire Simulator emits IR radiation in a unique sequential pattern corresponding to and recognizable by the IR3 detector as fire. This allows the IR3 detectors to be tested under simulated fire conditions without the associated risks of an open flame.
3600I
There is an optional beam collimator, model no. 20/20-190, specially designed for extended test range.
Figure 15: IR3 Long Range Fire Simulator 20/20-310
D.1.1 UNPACKING
Verify that you have received the following contents:
Delivery form
Page: 49
Page 58
Fire Simulator with integral batteries
Battery charger
Optional Beam Collimator
Storage case
D.1.2 OPERATING INSTRUCTIONS
Warning: Do not open the Fire Simulator to charge the batteries or for any other reason
in a hazardous area. Caution: The following test simulates a real fire condition and may activate the
extinguishing system or other alarms. If this is not desired, disconnect/inhibit them before the test and reconnect after the simulation.
To simulate a fire:
1 Aim the Fire Simulator towards the detector’s Target Point.
3600I
Target Point
Figure 16: 3600I IR3 Detector Target Point
2 When testing keep a distance of at least 50 cm (20 inches) from the detector. 3 Press the operation button once. Fire simulation lasts for 20 seconds. The detector
sends an alarm signal (solid red LED).
4 Wait 20 seconds before repeating the test. 5 Verify that the optical window is clean.
Page: 50
Page 59
D.1.3 RANGE
Table 30: Sensitivity Ranges
3600I
Sensitivity Detection Range
(ft / m)
1 (Low) 50 / 15 3.8 / 1.2 7 / 2.2 2 100 / 30 7 /2.2 14.5 / 4.5 3 150 / 45 10 / 3.2 22 / 7 4 (High) 215 / 65 14.5 / 4.5 29 / 9
Notes:
The minimum distance from the detector is 20 inches (50 cm).
The optional beam collimator is fitted for Extended Range.
At extreme temperatures, there is a 15% maximum reduction in the range.
Important: Keep the Fire Simulator in a safe place when not in use.
D.1.4 CHARGING THE BATTERY
The Fire Simulator uses NiCd batteries as a rechargeable power source. When the batteries are fully charged, the simulator operates for at least 60 times without recharging. An internal buzzer is sounded when the voltage from the batteries is lower than the required operational level.
To charge the battery:
Standard Test Range (ft / m)
Extended Test Range (ft / m)
1 Place the Fire Simulator on a table in a safe area. 2 Turn the sealed plug (next to the operation button) counter-clockwise with a suitable
wrench.
3 Connect the battery charger. 4 Charge for a maximum of 14 hours. 5 Disconnect the charger. 6 Tighten the sealed plug clockwise.
Page: 51
Page 60
D.1.5 TECHNICAL SPECIFICATIONS
3600I
Mechanical
Electrical
Environment
Physical
Explosion Proof Enclosure:
NFPA (designed to meet)
Class I, Division 1 & 2 Groups B, C and D
Class II, Division 1 & 2 Groups E, F and G
ATEX EX II2G NEMKO 02ATEX255
EExd IIB T5 50°C per En 50-014 & EN50-018
Power: 8 VDC Max.
6 x Rechargeable 1.2 VDC NiCd Batteries
Current: 2.5A Avg.
Charge: 400 mA for 14 Hours
Temperature Range:-4 to +122ºF (-20 to +50ºC)
Vibration Protection: 1g (10-50hz)
Water and Dust: IP 67 per EN 60529
Dimensions: 11.5 x 10.1 x 3.9 in
(292 x 258 x 100 mm)
Weight; 7.5 lb. (3.4 Kg)
D.2 TILT MOUNT - P/N 3600-001
The Tilt mount provides accurate directional selection for optimum area coverage.
Figure 17: Tilt Mount
Page: 52
Page 61
D.3 WEATHER PROTECTION - P/N 777163
The weather protector protects the detector from different weather conditions, such as snow and rain.
3600I
Figure 18: Weather Protection
Page: 53
Page 62
D.4 LASER DETECTION COVERAGE POINTER - P/N 777166
The Laser Detection Coverage Pointer evaluates detector coverage on-site. The device is an add-on accessory that enables designers and installers to optimize detector location and assess the actual coverage of installed detectors.
The device is universal and can be used with all 3600 Optical Flame Detectors.
3600I
Figure 19: Laser Detection Coverage Pointer
D.5 AIR SHIELD - P/N 777161
The Air Shield enables you to install the detector in dirty areas and using compressed air, keep the window clean. This prevents the accumulation of dirt on the window and enables the detector to continue to operate under harsh conditions.
Figure 20: Air Shield
Page: 54
Page 63
E SIL-2 FEATURES
In this appendix…
3600I Flame Detector page 55
E.1 3600I FLAME DETECTOR
This appendix details the special conditions to comply with the requirements of EN 61508 for SIL 2.
The 3600I Flame Detector can only be used in low or high demand mode applications, see IEC 61508.4, Chapter 3.5.12.
E.1.1 SAFETY RELEVANT PARAMETERS
Perform the following functional checks of the detector:
Alternative 1: Functional check of the detector every 180 days:
HFT: 0
3600I
PFD: 3.0 x 10 -4 ( 3% of SIL-2) if only Alarm Relay is used for alerting.
PFD: 3.2 x 10 -4 ( 3.2% of SIL-2) if 0-20mA – interface is used as alarm.
PFH: 1.5 x 10 –7 1/h ( 14.9% of SIL-2) for 0-20mA application.
SFF: 95% fulfills the conditions of EN 61508 for SIL2
Alternative 2: Functional check of the detector every 365 days:
HFT: 0
PFD: 4.5 x 10 -4 ( 4.5% of SIL-2) if only Alarm Relay is used for alerting.
PFD: 4.9 x 10 -4 ( 4.9% of SIL-2) if 0-20mA – interface is used signal current
as alarm.
PFH: 1.5 x 10 –7 1/h ( 14.9% of SIL-2) for 0-20mA application.
SFF: 95% fulfills the conditions of EN 61508 for SIL2
E.1.2 GUIDELINES FOR CONFIGURING, INSTALLING, OPERATING AND
SERVICE
The alert conditions according to SIL 2 can be implemented by an:
Alert signal via 20mA current loop or
Alert signal via alarm relay and the fault relay
E.1.2.1 CONDITIONS FOR SAFE OPERATING
1 The flame detector shall consist only of the approved hardware and software
modules.
2 The 24V power supply must fulfill the requirements for PELV / SELV of EN 60950. 3 The automatic BIT (Built-In-Test) must be activated.
Page: 55
Page 64
4 The set-up parameters must be verified (as described in
Using the 0-20mA Interface for Alerting on page 55, point 1 and in Using the Alarm Relay Contact for Alerting on page 56, point 1) and the function of the 3600 Flame
Detector (flame detection, function of the 0-20mA interface, relay functions) must be checked completely.
E.1.2.2 USING THE 0-20MA INTERFACE FOR ALERTING
1 The following parameters shall be set:
AUTOMATIC BIT test = on
Connected to 0-20mA Terminals
2 The following allowed output current must be supervised with an accuracy of ± 5%:
Normal State = 4mA
Warning State = 16mA
Alarm State = 20mA
3 The output current must be supervised regarding the over-and under run of the 0-
20mA.
4 The 0-20mA can be used as low and high demand mode.
3600I
E.1.2.3 USING THE ALARM RELAY CONTACT FOR ALERTING
1 The following parameters shall be set:
AUTOMATIC BIT Test = on
Connected to N.C contact of Alarm Relay Terminals
Connected to Fault Relay Terminals
2 The relay contacts (“alarm” – and “faulty relay”) must be protected with a fuse rated
at 0.6 of the nominal specified relay contact current.
3 The maximum contact rating that is allowed per SIL-2 is 30VDC. 4 It is to be considered that the contact of the Alarm Relay opens if there is a fire
alarm.
5 During the forwarding and evaluation of the alarm it must be noted that the relay
contact opens.
6 The alarm relay can be used as low demand only.
E.1.2.4 OTHER
1 The complete function of the flame detector (flame detection, function of the 0-
20mA interface, the relays) must be examined at least every six or twelve months (see Safety Relevant Parameters on page 55, when the flame detector must be switched OFF and ON.
2 The window of the sensor must be examined at appropriate time intervals for partial
contamination.
3 The HART and the RS 485 interfaces must not be used for the transmission of the
safety-related data.
Page: 56
Page 65
LIMITED WARRANTY
SIERRA MONITOR CORPORATION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. SMC will repair or replace without charge any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by SMC personnel.
All warranties hereunder are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without SMC approval or which have been subjected to accident, improper maintenance, installation or appli­cation, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables (i.e. calibration gases, batteries, sensors), nor to any damage resulting from battery leakage.
In all cases SMC’s responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instruction shall be a condition of this warranty.
Except for the express warranty stated above, SMC disclaims all warranties with regard to the products sold hereunder including all implied warranties of merchantability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of SMC for damages including, but not limited to, consequential damages arising out of/or in connection with the use or performance of the product.
3600I
Page: 57
Loading...