Sierra Monitor Corporation 3100-01 User Manual

MODEL 3100-XX
FLAME DETECTOR
Sierra Monitor Corporation
1991 Tarob Court, Milpitas, CA 95035
(408) 262-6611, Toll Free: 800-727-4377
Fax: 408-262-9042
MODEL 3100-XX
Flame Detector
This manual provides instructions for the following Sierra Monitor products:
Model Description 3100-01 Flame Detector - Standard 3100-02 Flame Detector - Enhanced Relay 3100-03 Flame Detector - Enhanced Relay 3100-04 Flame Detector - Enhanced Relay 3100-05 Flame Detector - Enhanced Relay 3100-06 Flame Detector - Flame Detector - 4-20mA
The instructions are effective for the above models as of March 1, 1997
Applicability & Effectivity
Instruction Manual Part Number: T15007
Rev. C2
Instruction Manual
TABLE OF CONTENTS
SECTION PAGE
1. PRODUCT DESCRIPTION 1
2. OPERATION 2
2.1 General 2
2.2 Field-of-View 3
2.3 Range 3
2.4 Environment 3
2.5 Configuration 3
2.6 LED operation 4
2.7 Relay operation 5
3. INST ALLATION 7
3.1 General Precautions 7
3.2 Housing and Conduit 7
3.3 Connection 7
3.4 T esting 8
4. MAINTENANCE 8
4.1 Lens Cleaning 8
5. TROUBLESHOOTING 9
6. SPECIFICATIONS 11
7. W ARRANTY 11 APPENDICES A. FIGURES
A-1 - Exploded V iew 12 A-2 - Housing Dimensions 12 A-3 - Common Wiring Configurations 13 A-4 - Enhanced Series Wiring Connections 14
B. TABLES 15
B.1 Dip Switch Settings 15 B.2 Connectors 16 B.3 V erify/Aux. Relay Configurations 16
B.4 Fault T able 17 C. WIRING CONNECTIONS 18 INDEX 19
Table of Contents
Instruction Manual
1. PRODUCT DESCRIPTION
1.1 Introduction
All versions of the Model 3100 Flame Detector Se­ries utilize Ultraviolet, Infrared and V isible spectrum to provide continuous and reliable flame detection. The microprocessor in the Model 3100 is config­ured with state-of-the-art fire algorithms and con­tinuously analyzes the data from the sensor array for individual intensity values, change of intensity values, relationship of intensity values and frequency signature correlations. Each algorithm is designed to recognize a different type of flame signature from the detectors while rejecting common false sources. When the conditions of any one of the several fire algorithms are met the Model 3100 declares a fire.
1.2 Fault Diagnostics
The micro-processor is also continuously perform­ing system tests looking for any faults which would impair its ability to accurately detect a flame and declare an alarm. The systems being tested include: input power, sensor circuits, relay circuits, and sev­eral other internal systems. The Model 3100 Flame Detector also performs a through the lens test of the sensor and lens systems. All faults are recorded in non-volatile memory and may be retrieved by a trained technician.
1.3 Configuration
The Model 3100-01 has a Fire Relay and a Fault Relay which may be connected as normally open or normally closed contacts. Models 3100-02, -03, ­04, and -05 have in addition to the Fire and Faults relays a Fire Verify system and an Auxiliary Fault system. The Fire Verify system adds a “field ad­justable” level of certainty to the declaration of a verified fire. The Auxiliary Fault system will acti­vate the Aux. Relay for the Lens Test fault. This allows a separate indication for the most common fault (a dirty lens). A technician can know immedi­ately what is wrong and how to fix it (i.e. wipe the lens) without reading codes, consulting manuals, or wading through a process of complex diagnostics. The 3100-06 has an industry standard 4-20 mA out­put and no relays.
The Model 3100 detector is mounted in a NEMA 4X explosion proof housing, rated for Class I Divi­sion 1 & 2 Groups B, C, D, Class II Division 1 & 2 Groups E, F, G, and Class III locations. The elec­tronics are mounted inside an aluminum cup to pro­tect the electronics during installation. All switch settings and indicators are located on the front of the Model 3100 detector module allowing field ad­justments to be made without removing the detec­tor module from the housing.
Each Model 3100 detector is calibrated and tested to respond to a 1 square foot Kerosene fire at 80 feet with a Field-of-View of 120°. The Model 3100 detector has four sensitivity settings and six verify levels.
FIGURE 1-1: Model 3100 Series Flame Detector
Model 3100 Series Flame Detector (11/04)
Model
Fire
Rela
y
Fault
Relay
Verify Relay
Aux.
Relay
3100-01 X X None None 3100-02 X X N/O N/C 3100-03 X X N/C N/O 3100-04 X X N/O N/O 3100-05 X X N/C N/C 3100-06 4-20 mA signal only
Models and Functions
Page: 1
Instruction Manual
2. OPERATION
2.1 General
When the Model 3100 Flame Detector is powered up, the microprocessor checks the configuration switch settings and configures the detector. The mi­croprocessor then runs a full series of self tests. After the self test process is complete and all tests are passed, the detector is ready to detect a fire.
All modes of operation are indicated by two LEDs located on the front of the detector. Normal Mode is indicated by a brief flash of the LEDs every 8 seconds. With the device in Normal Mode it is constantly monitoring the environment and ready to detect a fire.
When a fire is detected the flame detector will acti­vate the Fire Relay and turn on both LEDs. If the device is configured for “Latching” Mode the de­vice will remain in Alarm Mode until power is re­moved. In “Fire Following” Mode the Fire Relay will reset when the Fire Probability Algorithm de­termines there is no longer a fire.
The self test system is continuously monitoring the internal systems. When a fault is detected the Fault Relay is de-energized. In Fault Mode the LEDs
will flash a code indicating the type of fault. A fault indication may mean the device is unable to detect a fire or that a device has become unreliable. (i.e. a “Voltage Low” fault) For most faults the detector will return to Normal Mode when the fault condi­tion is corrected.
The Model 3100 Series comes in several versions. The basic version 3100-01 does not have the Verify or the Auxiliary Relay systems. The enhanced Mod­els 3100-02, -03, -04 and -05 have the Verify and Auxiliary Relay systems. These versions represent the different configurations (Normally Open or Closed contacts) of the V erify and Auxiliary Relays. The Auxiliary Relay provides a separate relay out­put for the Lens Test Fault. The Verify system is activated when a fire is declared. A V erified Fire is declared when the conditions of the Verify Fire Al­gorithm are met. All other functions are the same as the basic Model 3100-01.
The 3100-06 does not have relay outputs. It uses a 4-20 mA current circuit. The detector's status de­termines the amount of current flow through the circuit.
Page: 2
Figure 2-1: Model 3100 Series Field of View
Model 3100 Series Flame Detector (11/04)
Instruction Manual
SW1 SW2 SW3 SW4 SW5
SW1 Shown in off position SW2 Shown in on position
Figure 2-2: Configuration Switches
2.2 Field-of-V iew (See Figure 2-1)
Optical Flame Detectors must be able to “see” the fire to declare an alarm. Any obstruction between the detector and the threat area will impair the de­tectors ability to cover the threat area. An obstruc­tion is anything that is not transparent to the sensor elements of the detector. UV sensors and some types of IR sensors cannot see through glass or plas­tics. The 3100 series of Flame Detectors has a 120° Field of V iew .
When covering a large area the detectors should be located to provide overlapping fields of view to in­sure complete coverage.
2.3 Range
The size of fire and type of materials which consti­tute the threat will affect the detector’s range. Dif­ferent materials produce different amounts of the radiant energy used by the detector to “see” the fire. Also, the range of the detector is a function of the fire size. Using the square of the distance rule, if the device will detect a one sq. ft. fire at 60 feet, to detect a 1/4 size fire (aprox. 6 sq. in.) the devices must be within 30 feet. The Model 3100 Detector is optimized to a 1 sq. ft. Kerosene fire at 80 feet with the sensitivity settings set to maximum sensi­tivity .
2.4 Environment
All optical flame detectors sense radiant energy at some frequency or frequencies within their Field­of-View. Any source which radiates energy at the same frequency or frequencies used by the detector
SW9 SW8 SW7 SW6
to sense a fire may impact the detector’s ability to “see” the fire. Care should be taken to minimize radiant energy sources within the detectors Field­of-View. Because of the variety of environments and conditions, a factory trained technician or quali­fied P.E. should be consulted before deciding on the location of devices. The Model 3100 Detector uses an Ultraviolet sensor (180 - 260 nanometers), an Infrared sensor (.715 - 3.5 microns), and a Vis­ible sensor (480 - 560 nanometers).
2.5 Configuration (See Figure 2-2)
All of the 3100 Series models have field adjustable configuration switches located on the front face of the detector. The factory settings are shown in italic text. The enhanced models have additional con­figuration options for the Verified Fire.
2.5.1 Sensitivity
All versions have several sensitivity settings available. The sensitivity settings are 20, 40, 60, and 80 feet. Each setting is optimized to alarm on a 1 sq. ft. Kerosene fire within 5 seconds. Switches 1 and 2 control the sensi­tivity. The factory default is 80 feet. (SW1
and SW2 are off.)
Note: Different fuels emit energy at different rates. For example; a fire involving fuel oil does not emit energy at the same rate as gaso­line. Consequently, the Model 3100 will be able to respond to a gasoline fire at a little greater distance than it will to a fuel oil fire. Similary, a fire involving acetone will be seen at a greater distance than one involving gaso-
line.
Model 3100 Series Flame Detector (11/04)
Page: 3
Instruction Manual
LED 1
(2 locations)
Configuration Switches
Figure 2-3: Model 3100 Series Detector Module (Front)
2.5.2 Verify Control
The Enhanced Model 3100-02, -03, -04, ­05 and -06 have the Verified Fire function. The Verify Control switches allow the user to select the verify level, disable the verify function, or make the Verify Relay operate in parallel with the Fire Relay. The verify function in enabled when the detector de­clares an alarm. The verify level sets the degree of certainty required to declare a veri­fied fire. The lowest level (1) is the lowest certainty (fastest) and the highest level (6) is the greatest certainty (slowest) of a fire. The verify function enables an algorithm which evaluates the fire signature over time to de­termine the degree of certainty. When the degree of certainty exceeds the level set by the configuration switches a Verified Fire is declared and the Verify Relay is energized. Switches 3, 4, and 5 control the verify func­tion. The factory default is verify disabled
and set to level 0. (SW3, SW4 and SW5 are off.)
2.5.3 Latching Control
The latching controls allow the detector or individual relay outputs to be set to “Latch­ing” or “Fire Following”. “Latching” causes the relay to stay energized until power is re­moved from the detector. “Non-latching” al­lows the relay to reset (de-energize) when a flame is not present for a short period of time.
For the detector to be set to "Non-latching" both Fire Output and Verify Output must be set to "Non-latching". If either the fire out-
LED 2
Mounting Screw
put or the verify output is set to "Latching" then the detector will be set to "Latching".
When the detector is set to "Latching" the LED's will indicate an alarm until the device is reset regardless of the fire or verify relay output settings.
The Verify Relay is automatically configured as “Latching” if the Fire Relay is set to “Latch­ing”. SW6 sets the Fire Relay Output, SW7 sets the Verify Relay Output and SW8 sets the Detector Mode. To set the detector to "Non-latching", SW6, SW7 and SW8 must be set to "Non-latching. The factory defaults
are “Latching” (SW6 and SW7 ar e off.)
2.5.4 Other Configuration Switches
The last configuration switch (SW9) must be in the off position. The factory default set-
ting is off.
2.6 LED operation (See Figure 2-3)
The status of all versions of the flame detectors can be determined from the LEDs located behind the lens on the front of the detector. The LEDs will flash at intervals or remain on to indicate the detec­tors status. (Fault Mode, Normal Mode, Alarm Mode, Verified Fire Mode, and on power up the Configuration Settings).
2.6.1 Power Up
At power up all versions of the flame detec­tor will begin flashing the LEDs. The LEDs will flash 8 consecutive patterns which indi­cates the positions of the configuration switches. Each pattern indicates the position
Page: 4
Model 3100 Series Flame Detector (11/04)
Instruction Manual
Figure 2-4: Model 3100 Series Detector Module (Back)
(“on” or “off”) of a switch (SW1-SW8). The first flash pattern indicates the position of the first switch (SW1), with each consecu­tive flash indicating the position of the next switch in order. The flash pattern is as fol­lows: only one LED “on” indicates a switch in the “off” position, both LEDs “on” indi­cates a switch in the “on” position. The po­sition of SW9 is not indicated. If SW9 is in the “on” position the detector will power up in fault mode.
2.6.2 Normal
In Normal Mode the LEDs will flash briefly every 8 seconds. Whenever the device is in any other mode the “flash every 8 seconds” is suspended until the detector returns to Normal Mode.
2.6.3 Fire
When any version of the Model 3100 de­clares a fire, both LEDs will come “on” and stay “on”. If the detector is set to "Latching" the LED's will remain "on" and stay "on" until the detector is powered down. If the detector is set to "Non-latching" the LED's will reset to "Normal Mode" when the fire is no longer being detected. If the Verified Fire is declared (Verify Fire is only on the En­hanced Models) the LEDs will blink “off” briefly every second. If the detector is set to "Latching" the LED's will remain in this state until the detector is powered down.
2.6.4 Fault
When the detector has power and is in Fault Mode LED1 (the left LED when facing the detector with the configuration switches be­low the LEDs) will be on for 5 seconds while the LED2 (the right LED) will be off see Table B.4 on page 12. The LED will turn "off" and LED 2 will begin flashing 1/2 sec­onds "on" and 1/2 second "off" a number of times. The number of times LED2 flashes indicates the type of fault. This cycle is re­peated until the fault is corrected. Only the highest number fault is indicated. Once a fault is corrected the next highest level fault will be indicated until all faults are cured. Except for fault level 2 and 3, a fire indica­tion will override a fault indication. The de­tector is disabled if a fault 2 or 3 is indicated.
2.7 Relay operation (See Figure 2-4)
The Model 3100-01 has two relays, the enhanced Models 3100-02, -03, -04 and -05 have four relays. The function of the Fire and Fault Relays is the same on all models. The Verify Relay and Aux. Relay is only available on the enhanced models. All relay connections are made at the connectors lo­cated on the back of the flame detector module.
2.7.1 Fire Relay
The Fire Relay will energize whenever the detector declares a fire. Depending on the configuration setting, the relay will: “Latch-
Model 3100 Series Flame Detector (11/04)
Page: 5
Loading...
+ 16 hidden pages