Sierra Monitor 5100-28-IT User Manual

Sentry IT Gas Sensor Module
IT Combustible - Infrared
Proven Technology
Proven Support
Information Technology (IT) at the component level! An Infrared (IR) Combustible Gas Sensor Module is network-enabled to provide the interface needed to your plant-wide control system, whether it be 4-20 mA, Modbus, HART, relay contacts or SentryBus. This USA-made, stand-alone smart gas sensor module is loaded with features you need. As usual, Sierra Monitor A gas detector with a Sierra Monitor pedigree, Factory Mutual approved and ready to Manage Your Gas Risk. The 5100-28-IT provides all the built-in features desired by instrumentation and safety professionals, including:
FM Approval for performance and safety
• SIL-2 Certified
Modbus RTU RS-485 interface
4-20 mA output
• HART interface
SMC Sentry digital bus interface
• Optional Integral alarm relays – Alarm, Warning and Trouble
Aluminum or 316 Stainless Steel enclosure
Annual calibration frequency
%LEL or % volume
Interface to multiple protocols
Integral scrolling LED display
Optional remote sensor
The 5100-28-IT can be used as a 4-20 mA component or as a Modbus RTU node. For higher level system capability the module can interface directly to Sierra Monitor’s Sentry Controller. As part of a Sentry system the user gains capability of system Modbus serial communications, extensive diagnostic features, area and zone alarm management, WebServer interface and multiplexing sensor connections.
Factory Mutual (FM) Approval for performance, electrical safety and environmental parameters including Class I, Div. 1, Groups C, D and Class I, Zone 1, Group IIC. The 5100-28-IT is also SIL-2 Certified and meets NFPA-72 requirements for gas detectors.
How It Works
Most combustible gases absorb infrared light energy at defined wavelengths, providing an absorption signature for that gas. The principle of an infrared detector is based upon the absorption of the infrared light at a specific wavelength as it passes through the gas. The more of the absorbing gas that is present, the more light is absorbed. The detector measures the energy from an infrared light beam at a wavelength that is absorbed by the gas and compares it to the energy emitted by the source. The difference in energy received by the detector indicates the level of gas in the atmosphere.
Features Benefits
Non-intrusive calibration, menu driven system Able to easily and quickly calibrate module without
declassifying the area
Network compatible with Modbus, 4-20mA, Sentry
bus, HART, relay interface
Easy to install in a variety of field applications plus easy to obtain critical safety information wherever needed
FM Approved for performance and hazardous
area operation, Class I, Div. 1, Group C, D, with NEMA 4X enclosure rated for -40
o
to 176oF areas
For safe and reliable operation in hazardous areas
SIL-2 Certified Meets long term reliability design standards Local scrolling display Ease of calibration and easy access to gas
concentration, relay status and diagnostics
Sierra Monitor Corporation 1991 Tarob Ct. Milpitas, CA 95035 (408) 262-6611 (800) 7 27-4377 Fax: (408) 262-9042
Web site: www.sierramonitor.com E-Mail: sales@sierramonitor.com
Sentry IT Gas Sensor Module
X
IT Combustible - Infrared
Specifications:
Sensor type: Infrared, Dual Wavelength Performance
Dual Range: Default: 0-100% LEL Methane User Setting: 0-100% by vol. Methane Repeatability: +/-1% LEL Accuracy: +/- 1% for 0-50% LEL range +/- 2% for 51-100% LEL range Sensor Life: Typically >5 years Heated Sensor: Heated cell to prevent condensation Response Time: T90<10sec*
Output:
Display: Fixed and Scrolling LED Signal Outputs: Sentry digital bus Analog 4-20 mA Linear 3-wire Non-Isolated 4-wire Isolated Serial RS-485 Modbus RTU Relay : Optional
Options:
Relays: 5 amp Alarm, Warning (0.25 amp Trouble) 5A@ 250 VAC, 5A@ 30VDC (Alarm, Warning) Board includes auxiliary connection for Sentry
HART: Termination board includes HART, Modbus RS-
Power: Power consumption: 3 watts Input voltage: 24 VDC nominal: 10-30VDC
Operating Range:
Ambient Temp Range: -40 Relative Humidity: 0-99% Non-Condensing
multiplexing 485, 4-20mA, Digital Input, 2A Relay output, No
Sentry Bus
o
to 140oF (-40o to 60oC)
Construction:
Dimensions: (H x W x D) (A1 & A2) 7.8 x 5.7 x 3.9 in. (19.8 x 14.5 x 9.9 cm) (S1 & S2) 7.5 x 4.4 x 4.9 in. (19 x 11 x 12 cm) Weight: (A1 & A2) 3.4 lb. (1.5 Kg) (S1 & S2) 7.2 lb. (3.3 Kg) Enclosure: Epoxy coated Aluminum or 316 Stainless Steel Housing: AL or SS (same as enclosure) Hazardous Area Classification: Explosion proof, Class 1, Div. I, Groups C, D Class I, Zone 1
Warranty: 2 years Approvals: FM Approval 6320 Combustible Gas Detector Performance
FM Approval 3600 Class I Div. 1, Groups C, D SIL-2 Certified Certified by Lloyd's Register (IEC 61508) CSA For enclosure in hazardous locations ABS Certificate of Compliance CQST
Specifications subject to change without notice * T60<10 sec NRTL Approved option for noise suppression
Group IIC, IP66, IP65, NEMA 4X, T6 TA = - 40
o
C to 85oC II2 GD, Ex d IIC
Ordering Information:
Relay/Connection
Model Enclosure
Output
Gas Type
5100-28-IT - XX - XX -XX -
- A1 = AL ¾” NPT - 01 = No Relays (std) - 01 = Methane (Std.) - 0 = Standard - 0 = None
- A2 = AL M20 x 1.5 - 02 = Relays Option - 2 = Conformal - 1 = Remote
- S1 = SS ¾” NPT - 05 = HART Option Transmitter Sensor
- S2 = SS M20 x 1.5
Accessories:
5311-00 Rainshield 5311-02 Rainshield with calibration port
Calibration Accessories: 5358-01 Calibration Head, Standard 5360-00 Calibration Gas Delivery Fitting
Calibrators High Capacity: 1250-01 Gas Sensor Calibration Kit, Type A (CO, H 1260-02 Combustible Gas 50% LEL Gas Cylinder Type A
S)
2
Sensor Protection
- X
Remote Option
Rev. 5/13
Sierra Monitor Corporation 1991 Tarob Ct. Milpitas, CA 95035 (408) 262-6611 (800) 727-4377 Fax: (408) 262-9042
Web site: www.sierramonitor.com E-Mail: sales@sierramonitor.com
Loading...