1.3THEORY OF OPERATION .............................................................................................................................. 2
5.3MAIN MENU .................................................................................................................................................. 19
7. SERVICE ........................................................................................................................................................... 27
Figure 5 - 1: Face Plate with Operator Key Pad ..................................................................................................... 18
Figure 6 - 1: Model 5358-01 Calibration Adapter ................................................................................................... 24
The Model 5100-XX-IT Toxic Gas Sensor Module is a smart transmitter and member of the IT Series family
and it offers a broad array of features including:
• Integral alphanumeric LED display
• Up to 180 day calibration frequency
• FM Approval for performance and safety
• SIL-2 Certified
• Optional integral alarm relays (3)
• 4-20 mA output
• Modbus
• SMC Sentry interface
• Optional HART interface
®
RTU interface
• 316 Stainless steel enclosure option
• Remote sensor option
• Low maintenance and operation costs
• ATEX Approval (5100-05-IT)
The 5100-XX-IT is designed and approved for installation and operation in hazardous locations.
Members of the 5100-XX-IT Series Toxic Gas family include:
• 5100-03-IT Oxygen Gas Sensor Module
• 5100-04-IT Carbon Monoxide Gas Sensor Module
• 5100-05-IT Hydrogen Sulfide Gas Sensor Module
• 5100-06-IT Chlorine Gas Sensor Module
• 5100-08-IT Chlorine Dioxide Gas Sensor Module
• 5100-10-IT Sulfur Dioxide Gas Sensor Module
• 5100-12-IT Nitrogen Dioxide Gas Sensor Module
• 5100-21-IT Hydrogen Chloride Gas Sensor Module
• 5100-25-IT Ammonia Gas Sensor Module
• 5100-26-IT Hydrogen Fluoride Gas Sensor Module
• 5100-88-IT Carbon Dioxide Gas Sensor Module
®
Registered trademark of Schneider Electric
Page: 1
Model 5100-XX-IT Toxic Gas Sensor Module
1.2 PRODUCT CONFIGURATION
Various module mounting configurations can be implemented without special fixtures. Where applicable,
these options are factory configured prior to shipment. Mounting configuration can be selected by the installer
or field technician and are fully described in this manual. Sensor must always be oriented downward.
1.3 THEORY OF OPERATION
Electrochemical sensors are fuel cell-like devices consisting of an anode, cathode, and electrolyte. The
components of the cell are selected so a subject gas, allowed to diffuse into the cell, will cause a chemical
reaction and generate a current. The cells are diffusion limited so the rate the gas enters the cell is solely
dependent on the gas concentration. The current generated is proportional to the rate of consumption of the
subject gas in the cell.
Sierra Monitor electrochemical sensors provide improved reliability by allowing the gas to diffuse into the
sensor through a capillary port, rather than diffusing through membranes. The result is an extremely stable
sensor with very low temperature and pressure coefficients and the capability to monitor gas as ppm.
1.4 MODES OF OPERATION
1.4.1 SENTRY INTERFACE
IT gas sensor modules can be installed on Sierra Monitor Sentry Model 5000 controllers Ver. 6.XX MFD
after 9/1/95. When it is installed in a Sentry system the IT module must have a unique address which can
be established by setting an address between 1 and 8 on the Module Address Switch accessible from the
cover plate as illustrated in Figure 4-2. Figure 4-7 in this manual provides the wiring terminations for
connections to the Sentry controller.
Note 1: The Model # 5100-88-IT CO2 gas sensor module range is 0-5000 ppm. Therefore, the Sentry
Controller must be configured for a 0-100 % full scale input. The Sentry does not have the ability to
display engineering units up to 5000. The alarm set points need to be set as a percentage of full
scale. Example, a 2500 ppm alarm set point is equal to 50% scale.
When the module is operated in conjunction with a Sentry controller, the alarm relay setup (See section
5.3) should be set to “Sentry”, allowing the Sentry controller to manage alarm relay action rather than the
5100-XX-IT Gas Sensor Module.
1.4.2 MODBUS OPERATION
An RS-485 Modbus RTU serial interface allows direct connection to standard PLCs and DCSs. The
Module Address Switch (section 4.5) allows the user to select up to 15 different Modbus addresses. Also,
an additional 254 Modbus addresses are available via menu selection. Figure 4-7 in this manual provides
the wiring terminations for Modbus connections. The 5100-XX-IT provides the wiring terminations for
Modbus connections.
1.4.3 ANALOG OPERATION
The analog 4-20 mA interface allows direct connection to standard controller and distributed system. The
module is an active current source.
The standard configuration is set up for a 3-wire non-isolated connection. An optional 4-wire isolated
connection is also available and can be enabled by changing JP1 and JP2. (Figure 4.6)
1.4.4 REMOTE SENSOR (APPENDIX D)
The Remote Sensor option can be used to remotely mount some sensors up to 15’ from the transmitter
(refer to Appendix D for allowable distances).
1.4.5 HART CONNECTION (APPENDIX F)
A HART interface option is available. Refer to Appendix F for information.
Page: 2
Model 5100-XX-IT Toxic Gas Sensor Module
1.4.6 REMOTE ALARM RESET
An input is available for connection of remote alarm reset. Figure 4-8 provides the wiring termination for
connecting the remote alarm reset. This only resets local alarms, not Sentry alarms.
1.4.7 OPTIONAL INTEGRAL RELAYS
The optional relays are integral to the gas sensor module and are rated as SPDT, 250VAC, 5 Amps* for
the High Alarm and Low Alarm relays and SPDT, 250 VAC, 0.25 Amp for the Trouble relay.
* HART option alarm relays are all SPDT, 250VAC, 2 Amp
If the gas sensor module is provided with the optional relays, it will include Terminal P4 on the interface
board (Figure 4-3 and 4-4). Relay output connections are on P4.
1.5 MECHANICAL
The sensor module is comprised of the following three primary components:
ENCLOSURE
Standard on the 5100-XX-IT is an explosion-proof, rain-tight cast aluminum electrical housing (Figure 1-3)
with three ¾” FNPT conduit hubs. The 5100-XX-IT-SS has a 316 Stainless Steel enclosure (Figure 1-2).
Both enclosure covers have a viewing window. The design of the enclosure allows 3-way mounting
choices as shown in figure 1-3.
TRANSMITTER ELECTRONICS
Electronic Assembly consisting of one printed circuit board assembly mounted under a cover plate,
plugged into one field termination board. Connectors for wiring for power, signal interface and alarm
relays are located on the bottom of the termination board.
SENSOR ASSEMBLY
The sensor assembly includes an explosion proof housing containing the gas sensor and a wiring harness
for connection to the transmitter. The sensor assembly threads into one hub of the enclosure. The
exposed end of the sensor assembly is threaded to allow connection of a rain-shield or calibration gas.
1.6 INTERCONNECT WIRING
Not supplied with the sensor module, but necessary to the installation and operation is the shield cable which
connects the module to its power source and controller. Before this wiring is installed it is important to read
and understand the control system installation instructions to determine wiring requirements and alternatives.
1.7 POWER REQUIREMENTS
The modules operate on DC power between 10 VDC and 30 VDC. Regulated DC power must be supplied
from a separate source or from an approved Sentry or IT controller.
Page: 3
Model 5100-XX-IT Toxic Gas Sensor Module
Figure 1 - 2: Model 5100-05-IT-S1 (and S2) Toxic Gas Sensor – Stainless Steel Enclosure, Dimensions
Figure 1 - 1: Model 5100-XX-IT Toxic Gas Sensor Module – Mounting Options
(Valid for all except 5100-25/26-IT – See Appendix G)
Page: 4
Model 5100-XX-IT Toxic Gas Sensor Module
Figure 1 - 3: Model 5100-05-IT-A1 (and A2) Toxic Gas Sensor – Cast Aluminum Enclosure, Dimensions
(Valid for all except 5100-25/26-IT – See Appendix G)
Module installation must be such that it is mounted vertical with sensor pointing downward.
NOTE
Page: 5
Model 5100-XX-IT Toxic Gas Sensor Module
2. CAUTIONS & WARNINGS
2.1 INTRODUCTION
Although the IT Transmitter Modules are designed and constructed for installation and operation in industrial
applications including “hostile” environments, caution should be taken to insure that the installation is made in
compliance with this instruction manual and that certain procedures and conditions are avoided. This chapter
discusses the necessary cautions. Read the entire chapter prior to installation of the equipment.
2.2 GAS SENSOR MODULES - GENERAL
Avoid installing sensor modules where they will be unnecessarily exposed to wind, dust, water (i.e. direct hose
down), shock, or vibration. Observe temperature range limitations.
Sensors may be adversely affected by prolonged exposure to certain materials. Loss of sensitivity, or
corrosion, may be gradual if such materials are present in low concentrations. These materials include:
Halides (compounds containing chlorine, fluorine, bromine, iodine), acid vapors, caustic liquids or mists.
Care has been taken by the manufacturer to ship modules in protective packaging to avoid contamination prior
to installation. It is recommended that the modules remain protected during installation and that the covering
be removed immediately prior to system start-up.
During normal use the O
, CO, H2S, and SO2 sensors are protected from dirt and oil contamination by a
2
sintered metal cover. If this cover becomes clogged, the response of the sensor will be reduced. Protect the
sensor from contamination by careful placement, or by use of rain shields and dust shields.
Sensor modules must not be painted. Paint may contain compounds which will contaminate the sensor. Paint
will cause clogging of the sintered metal cover and will cause difficulties during attachment of the calibration
head or other maintenance activity. It is recommended that the module be tagged
2.3 WIRING
"DO NOT PAINT".
The manufacturer recommends that extra caution be taken where the installation is near any sources of
electromagnetic or radio frequency interference. Precautions include:
• Avoid running sensor module cable close to high power cables, radio transmission lines, or cables
subject to pulses of high current.
• Avoid running cables near large electric motors or generators.
• When the sensor module is to be operated in analog (4-20mA output) mode shielded cable is required.
• When shielding is used, it is recommended that shields be grounded at the controller and nowhere
else.
•All splices must be via either a termination hardware system or soldered. Improperly spliced cable can
result in corrosion, resistance changes and system errors. The use of wire nuts and crimp-on
connectors is unacceptable.
Installation and wiring must be in accordance with the National Electrical Code.
Voltage AC conductors are not to be run in the same conduit as voltage DC
NOTE
conductors.
2.4 CALIBRATION FREQUENCY
The 5100-XX-IT calibration frequency is six months (180 days). However, prudent gas detector maintenance
practices normally suggest a simple recalibration following incidences of exposure to high levels of gas that
would lead to alarm activation within any system utilizing the output of the gas sensor module.
Page: 6
Model 5100-XX-IT Toxic Gas Sensor Module
3. QUICK START
3.1 OVERVIEW
The gas sensor module has been supplied factory calibrated and ready for immediate installation and
operation. An installer familiar with installation and operation of gas detection products can use this section to
begin immediate use of the module.
3.2 WIRING
See section 4.2 to determine if 3-wire or 4-wire operation is necessary.
Provide two conductor twisted shielded wiring from the power supply/control device to the sensor module
location. Use wire that is 18 AWG or larger.
3.3 MODULE INSTALLATION
The sensor can be mounted in a variety of configurations supported by the conduit. See figure 1-3 to
determine which configuration is best for your specific application. The default configuration enables the
modules to be put in line with other modules with the sensor element below the transmitter. To change the
configuration simply remove the transmitter and rotate to the appropriate configuration and remount the
standoffs and transmitter.
The module is designed to be installed on a ¾” conduit. Two important warnings:
• The installation must meet any hazardous environment codes for electrical equipment.
• The sensor module enclosure mounting must be spaced far enough from any vertical surface
to allow removal and replacement of the sensor assembly which is threaded into one ¾”
conduit entry.
• Sensor housing must be oriented vertically pointing downward.
• If module is installed outdoors it is recommended that it be sheltered from direct sunlight.
3.4 TRANSMITTER INSTALLATION
To install the transmitter printed circuit assembly into the housing, carefully turn the faceplate so that the
printing is in the correct horizontal position for the mounting configuration and slide the assembly over the two
stand-offs in the enclosure.
Hand tighten the two captive panel thumb screws into the stand-offs. Replace the enclosure cover prior to
providing power to the transmitter
•If the transmitter is installed in a classified hazardous area, replace the threaded cover prior to
providing power.
3.5 START-UP & OPERATION
To begin operation of the sensor module activate the instrument loop with 14-30 VDC. Each time the sensor
module is powered up it will perform a warm-up for approximately 1.0 minutes (60 seconds). During this time
the display will read “Starting”. The loop output will be held at 4 mA.
NOTE: If the sensor is uncalibrated, the startup display will state “UNCALIB” instead of “STARTING”
NOTE: The 5100-06-IT, 5100-08-IT, 5100-25-IT, 5100-26-IT and 5100-88-IT require 300 seconds warm-up
period
After the warm-up period has expired, the display will indicate the gas concentration. Also, the instrument loop
will be released to output current in the range of 4 to 20 mA. The actual current is linear with the gas
concentration and depends on the selected range. For instance, when the range of 0 to 50 PPM has been
selected, a current of 4 mA corresponds to 0 PPM and a current of 20 mA corresponds to 50 PPM.
3.6 ZERO STABILIZATION
All electrochemical sensors require at least 30 minutes on power prior to calibration. This allows the electrode
potentials to equilibrate, resulting in a stable zero signal level.
Page: 7
Model 5100-XX-IT Toxic Gas Sensor Module
4. INSTALLATION
4.1 SENSOR MODULE LOCATIONS
All modules are tagged to indicate the configuration including the sensor module number
Identify all components during unpacking and install using the factory configuration.
All IT modules are factory pre-configured and calibrated.
The gas sensor module utilizes a diffusion type sensor which
should be located close to either the expected source or
destination of the gas hazard. If the gas is heavier than air, the
sensor module should be installed within 24 inches of the ground
or floor. If it is lighter than air, move it above 6’.
After optimum locations are determined based on the above
recommendations, consideration should be given to placing the
sensor modules in locations which are accessible for calibration
service. Slight adjustments to the location of the sensor module
may have little impact on effectiveness but major effect on
accessibility.
• Modules should be placed close to the potential source
of gas.
• Modules should be placed in areas accessible for
calibration.
• Sensors should be pointed down and the conduit
should include an inverse trap to reduce moisture
(condensation) from accumulating in the electronics
enclosure.
• Remote calibration fitting (5360-00) should be used to
facilitate calibration gas delivery. Run polyurethane tubing (1/4” O.D. x 1/8” I.D.) from fitting to an
accessible location.
Figure 4 - 1: Typical Mounting Options
NOTE
Model Gas Gas Density
N/A Air 1.00
5100-04-IT CO 0.97
5100-05-IT H2S 1.19
5100-06-IT Cl2 2.49
5100-08-IT ClO2 3.09
5100-10-IT SO2 2.26
5100-12-IT NO2 2.12
5100-21-IT HCl 1.27
5100-25-IT NH3 0.60
5100-26-IT HF 1.86
5100-88-IT CO2 1.53
Table 4 - 1: Specific Graities
Page: 8
Model 5100-XX-IT Toxic Gas Sensor Module
4.2 WIRING
4.2.1 ANALOG 4-20 MA OPERATION (FIGURE 4-6)
For a 3-Wire non-isolated connection, set jumpers, located on the bottom of the transmitter board, to the
lower position as illustrated in Figure 4-6. Verify that both jumpers are in the position marked by 3-wire.
When using a 3-wire connection, a minimum of an 18 AWG, 3 conductor shielded cable must be used. A
cable shield must never be used as a conductor. Larger gauge wire is recommended with distances over
1000’. Connect wires as shown in figure 4-4.
For a 4-Wire isolated connection, set jumpers, located on the bottom of the transmitter board, to the upper
position as illustrated in Figure 4-4. Verify that both jumpers are in the position marked by 4-wire. When
using a 4-wire connection, a minimum of 2 each of an 18 AWG, 2 conductor twisted/shielded pair cable
must be used. A cable shield must never be used as a conductor. Larger gauge wire is recommended
with distances over 1000’. Connect wires as shown in figure 4-4.
4.2.2 MODBUS OPERATION USING RS-485 CONNECTION
Use a minimum of 18 AWG, 2 conductor for DC power connection. No shield required. In addition use a
minimum of 24 AWG, low capacitance, shielded data cable for RS485 half duplex communication. The
installation may be planned in a manner which provides up to 32 sensor modules on a single home run.
Standard default RS485 Setting are: 38,400 baud, 8 bits, 1 stop bit, no parity
TERMINATION RESISTOR JUMPERS:
Termination resistors are used in RS-485 wire runs to provide impedance matching. The IT series
modules use a 120 Ohm resistor for this function. The cable being used for this RS-485 connection must
have a minimum of 100 Ohm impedance with a maximum of 120 Ohms.
Installations where the cable length is under 100’, termination resistors may not be required. In
installations where the cable length is greater than 100’, it is recommended to place the termination
jumpers on the first device and last device on the RS-485 wire run. Termination jumpers must be removed
from all other modules connected between the first and last device. The first device in the RS-485
multiplexed bus is usually a gas controller or PLC. Factory term resistor setting is “not enabled.”
BIAS JUMPERS: (BIAS A, BIAS B)
Bias resistors are used to force RS-485 receiver outputs to a known (fail-safe) state, when the bus is idle.
Bias jumpers are always installed in pairs as the bias must be placed on both the TX A and TX B lines.
Sierra Monitor’s IT series of toxic gas sensors automatically apply the bias jumpers, and are factory
installed so that the bias is always enabled.
4.2.3 SENTRY OPERATION USING SMC SENTRY CONNECTION (FIGURE 4-7)
Use a minimum of 18 AWG, 3-conductor cable up to 2000’. The cable may or may not be shielded. We
recommend shielded cable in circumstances that there could be RF or EM interference present. Shield to
be terminated and grounded only at the Sentry controller. Shield must be cut and dressed at the module
end so that no part of it comes in contact with the conduit or ground.
Be sure to follow all local electric code and safety requirements when installing the 5100-XX-IT Gas Sensor Module
4.2.4 GENERAL
NOTE
Install conduit as required by local code or construction specifications. Provide for splice boxes where
multiple modules will be wired to a single run. Pull conductors of the correct gauge wire from the controller
to each splice box and from the respective splice box to each planned module location. See for proper
wire termination in the splice box. Twisted wire secured with wire nuts is not an acceptable splice.
The drain wire of shielded cable must NOT be used as one of the conductors.
Installation and wiring must be in accordance with the National Electrical Code. Temperature
rating of cable wire must be at least 75oC. If cable runs through higher temperature
environments, it must be specified for that environment.
NOTES
Page: 9
Model 5100-XX-IT Toxic Gas Sensor Module
4.3 ENCLOSURE INSTALLATION
To protect the transmitter and sensor assembly they should be removed from the enclosure and preserved
until final installation and wiring termination.
Number
of
modules
1
2
3
4
Maximum length of wire run (feet)
500 1,000 2,000 3,000 5,000
18 18 16 16 14
18 18 14 12 xx
18 16 12 xx xx
16 14 12 xx xx
Table 4 - 2:Minimum Wire Gauges
Prior to installation and wiring:
1. Remove the transmitter from the module housing by:
• Unscrew the two captive panel screws on the faceplate.
• Lift the transmitter out of the enclosure.
• Unplug the sensor cable from transmitter connector P2.
• Remove the sensor assembly from the enclosure hub.
2. Install the module enclosure onto the end of the supply conduit and/or bolt into position as required.
When enclosure earth grounding is required for the installation a grounding lug is located in
the base of the enclosure. Install the earth ground under the green ground screw.
4.4 TRANSMITTER AND SENSOR INSTALLATION
NOTE
When all pre-wire is complete:
1. Install sensor assembly in the open hub on the module enclosure. The sensor assembly thread
must be fully seated into the hub and tightened to maintain explosion proof assembly.
2. Connect the wires which return to the controller to interface board connectors P1, P2, P3 and P4
according to Figure 4-3 and Table 4-4.
3. Connect the sensor assembly cable to top transmitter board connector P2.
4. Align the headers between the top transmitter board and the lower interface board and push
together.
5. Turn rotary switch to correct sensor address if required.
6. Carefully return the transmitter to the enclosure installing it over the two stand-off’s. Tighten the
retaining screws into the stand-offs.
7. Cycle power to accept module address change.
P1 PCB Label Function
1
2 IN - Digital Input SW -
3
4 IN - 4-20 mA Input -
5 GND Ground
6
7 OUT - 4-20 mA Output -
Switch
4-20
4-20
IN + Digital Input SW +
IN + 4-20 mA Input +
OUT + 4-20 mA Output +
Page: 10
Model 5100-XX-IT Toxic Gas Sensor Module
P2 PCB Label Function
1
2 - RS 485 (-) (B)
3 S RS 485 shield (Isolated GND)
4
5 - RS 485 (-) (B)
6 S RS 485 shield (Isolated GND)
P3B PCB Label Function
1 P VDC Power
2 S Sentry Signal or Communication
3 G VDC Ground
P3A
4 P VDC Power
5 S Sentry Signal or Communication
6 G VDC Ground
P4 Connections are only available when the optional Relays are included
P4 PCB Label Function
1
2 COM Low Alarm Relay COM
3 N/O Low Alarm Relay NO
4
5 COM High Alarm Relay COM
6 N/O High Alarm Relay NO
7
8 COM Trouble Alarm Relay COM*
9 N/O Trouble Alarm Relay NO*
* Trouble relay is fail safe so it is energized for normal operation,
functions are labeled for normal operation.
RS 485
RS 485
WARNING
ALARM
TRBL
+ RS 485 (+) (A)
+ RS 485 (+) (A)
N/C Low Alarm Relay NC
N/C High Alarm Relay NC
N/C Trouble Alarm Relay NC *
8. Establish the module address according to section 4.5.
The starting delay period normally takes approximately 3 minutes but under some
circumstances can take longer.
For optimum performance, it is recommended that a calibration be performed after 24 hours of
NOTES
operation.
Page: 11
Model 5100-XX-IT Toxic Gas Sensor Module
4.5 MODULE ADDRESS SWITCH
For digital interface applications the module address switch (or Modbus node) Figure 4-2 must be set per
Table 4-3:
POSITIONADDRESSPOSITIONADDRESS
1 Sensor 1 9 Sensor 09
2 Sensor 2 A Sensor 10
3 Sensor 3 B Sensor 11
4 Sensor 4 C Sensor 12
5 Sensor 5 D Sensor 13
6 Sensor 6 E Sensor 14
7 Sensor 7 F Sensor 15
8 Sensor 8 0
Table 4 - 3: Sensor Module Address
Switch Positions
NOTES
For Sentry applications only sensor addresses 1-8 are allowed. If using Modbus output sensor
addresses 1-15 are available. Position 0 allows the Modbus Address to be set by software
menu, in the range 16-254.
Software
Menu
Figure 4 - 2: Transmitter Face Plate
Page: 12
Model 5100-XX-IT Toxic Gas Sensor Module
Figure 4 - 3: Interface Board Connectors
Figure 4 - 4: RS-485: Termination, BIAS Jumper
Page: 13
Model 5100-XX-IT Toxic Gas Sensor Module
Figure 4 - 5: mA Circuit Types
Page: 14
Model 5100-XX-IT Toxic Gas Sensor Module
Figure 4 - 6: 4-20 mA Circuit Type Connections for 5100-XX-IT
Page: 15
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.