Sierra Monitor 5100 User Manual

T wo types of gas sensor modules are available for the Sentry Gas Risk Management System. For the more common gases such as Combustible Gas, Oxygen, Carbon Monoxide, Hydrogen Sul­fide, Chlorine and Ammonia, Sierra Monitor offers the IT Series Smart Gas Sensor Modules. More information on the IT Series is available in the spe­cific IT Series data sheets. For certain gases Si- erra Monitor offers the 5100 Series Gas Sensor Modules described in this data sheet.
Sierra Monitor toxic gas sensor modules utilize elec­trochemical technology to achieve the most accu­rate and reliable monitoring of gas concentration. All Sentry 5100 Series sensor modules easily in­terface to the Sentry controller. Each module has a unique address, which allows signals from mul­tiple modules to be multiplexed for communication with the controller on the same cable. All Sierra Monitor gas sensor modules are designed for hos­tile or hazardous environments and are in enclo­sures approved for Div. 1, Class 1, Groups C, D locations.
Sentry
Gas Sensor Modules
SENTRY FEA TURES INCLUDE:
Digital Signal Transmission Serial communication to the controller enables multiplexing sensor modules on a signal cable, significantly reducing installation costs. This assures RFI and EMI immunity over extended distances.
One-Person, Non-intrusive Calibration In the calibra­tion mode, sensors continue to monitor for hazardous conditions until calibration gas is applied. All adjustment s are made automatically after calibration gas has been re­moved. Sentry notifies the operator of calibration comple­tion and allows acceptance or rejection of the calibration at the controller keypad. There are no manual adjust­ments required at the sensor module.
Sierra Monitor Corp. 1991 T arob Ct., Milpitas, CA 95035, USA, 408-262-661 1, 800-727-4377, F AX: 408-262-9042
Web Site: http://www.sierramonitor.com E-Mail: sales@sierramonitor.com
Low Sensitivity Check Automatic, post-calibration check of sensor for proper output. Low sensitivity alpha­numeric message warns of need for sensor maintenance.
Power Up & Calibration Delays At st art-up or calibra­tion the output of the sensor is locked out and remains locked for five minutes to avoid erroneous readings during the warm-up period and after calibration.
Diagnostic Information The alphanumeric display on the Sentry Controller provides easy to understand diag­nostic messages.
© 2009 by Sierra Monitor Corporation
Sentry
Gas Sensor Modules
Electrochemical
Electrochemical sensors are fuel cell-like devices consist­ing of an anode, cathode, and electrolyte. The compo­nents of the cell are se­lected so a subject gas allowed to diffuse into the cell will cause a chemical reaction and generate a current. The cells are dif­fusion limited, so the rate at which the gas enters the cell is solely depen­dent on the gas concentration. The current generated is proportional to the rate of consumption of gas in the cell.
Unlike other electrochemical sensors where gas diffuses through membranes into the cell, Sierra Monitor sensors allow gas to diffuse into the sensor through a simple cap­illary. The result is an extremely stable sensor with very low temperature and pressure coefficients.
Common Specifications for All 5100 Series Sensors
Communication to Controller: SentryBus PSG Zero Drift: Less than 5% per year Calibration Frequency: 90 Days Recommended Transmission: Digital – RFI, EMI immune Warranty: 2 years Housing: Explosion proof (NEMA 7)
(Div. 1, Class 1, Groups C,D) Optional upgrade to Group B, NEMA 4X
Dimen sio n: 7.6 X 4.6 X 4.2 inches
(19.3 X 11.7 X 10.7 cm) Note that 5100-26 is larger
Weight: 2.7 lb. (1.3 Kg)
SENSORS
GAS SENSOR SPECIFICA TIONS
Gas Model Sensor Range Time Sensor Operating Relative
Number Type Response Life Temperature Humidity
Carbon Monoxide 5100-16 Electrochem 0-2,000 PPM 90% <35 sec. 2 yr. 4 (Hydrogen Tolerant to 2,000 PPM H2) Nitric Oxide 5100-19 Electrochem 0-20 PPM 90% <15 sec. 3 yr. 4 Hydrogen Cyanide 5100-22 Electrochem 0-20 PPM 90% <70 sec. 2 yr. 4 Ethylene Oxide 5100-27 Electrochem 0-20 PPM 90% <90 sec. 2 yr. 4
o
to 122 o F (-20 o to 50 o C) 15-99% RH
o
to 122 o F (-20 o to 50 o C) 15-99% RH
o
to 122 o F (-20 o to 50 o C) 15-99% RH
o
to 122 o F (-20 o to 50 o C) 15-99% RH
Sierra Monitor Corp. 1991 T arob Ct., Milpitas, CA 95035, USA, 408-262-661 1, 800-727-4377, F AX: 408-262-9042