Bijlmansweid 2 1934RE Egmond aan den Hoef The Netherlands
Phone +31 72 5071400 Fax +31 72 5071401
ASIA HEADQUARTERS
Room 618, Tomson Centre, Bldg. A
188 Zhang Yang Road
Pu Dong New District, Shanghai, P.R. China
Phone: + 8621 5879 8522 Fax: +8621 5879 8586
IM-24-HP 0-1
Table of Contents Series 24-HP Instruction Manual
Customer Notice
Unless you have specifically ordered Sierra’s optional O2 cleaning, this flow meter
may not be fit for oxygen service. Sierra Instruments, Inc., is not liable for any
damage or personal injury, whatsoever, resulting from the use of Sierra Instruments standard mass flow meters for oxygen gas. You are responsible for cleaning the mass flow meter to the degree required for your oxygen flow application.
TRADEMARKS
Innova-Mass™ is a trademark of Sierra Instruments, Inc. Other product and company
names listed in this manual are trademarks or trade names of their respective manufacturers.
0-2 IM-24-HP
Series 24-HP Instruction Manual Table of Contents
Table of Contents
Chapter 1 Introduction
Innova-Mass™ Vortex Mass Flow Meters .......................................... 1-1
Using this Manual ......................................................................... 1-1
Note and Safety Information ......................................................... 1-2
Receipt of System Components .................................................... 1-2
Agency approval for hazardous location installations varies between flow meter models.
Consult the flow meter nameplate for specific flow meter approvals before any hazardous
location installation.
Hot tapping must be performed by a trained professional. U.S. regulations often require a
hot tap permit. The manufacturer of the hot tap equipment and/or the contractor performing the hot tap is responsible for providing proof of such a permit.
All flow meter connections, isolation valves and fittings for cold/hot tapping must have the
same or higher pressure rating as the main pipeline.
For Series 241 insertion flow meter installations, an insertion tool must be used for any
installation where a flow meter is inserted under pressure greater than 50 psig.
To avoid serious injury, DO NOT loosen a compression fitting under pressure.
To avoid potential electric shock, follow National Electric Code or your local code when
wiring this unit to a power source. Failure to do so could result in injury or death. All AC
power connections must be in accordance with published CE directives. All wiring procedures must be performed with the power Off.
Before attempting any flow meter repair, verify that the line is not pressurized. Always
remove main power before disassembling any part of the mass flow meter.
Caution!
Calibration must be performed by qualified personnel. Sierra Instruments, Inc., strongly recommends that you return your flow meter to the factory for calibration.
In order to achieve accurate and repeatable performance, the flow meter must be installed with the specified minimum length of straight pipe upstream and downstream of
the flow meter’s sensor head.
When using toxic or corrosive gases, purge the line with inert gas for a minimum of four
hours at full gas flow before installing the flow meter.
For Series 241 insertion flow meter installations, the sensor alignment pointer must point
downstream in the direction of flow.
The AC wire insulation temperature rating must meet or exceed 85°C (185°F).
0-6 IM-24-HP
Series 24-HP Instruction Manual Chapter 1 Introduction
Chapter 1 Introduction
Innova-Mass™ Multi-Parameter Vortex Mass Flow Meters
The Sierra Instruments’ Series 240 In-Line and the Series 241 Insertion
Innova-Mass™ Vortex Flow Meters provide a reliable solution for
process flow measurement. From a single entry point in the pipeline, Innova-Mass meters offer precise measurements of five parameters including mass flow, volumetric flow, temperature, pressure and fluid density.
The unique Innova-Mass design reduces fugitive emissions, wiring, startup time and work-force requirements.
Innova-Mass digital electronics allows reconfiguration for most gases,
liquids and steam with generous rangeability. The meter outputs a pulse
signal for remote totalization and up to three 4-20 mA analog signals for
monitoring your choice of the five process variables. The local keypad/display provides instantaneous flow rate, total flow, temperature,
pressure and density in engineering units.
The Sierra Series 240 and 241 Innova-Mass Meters’ simple installation
combines with an easy-to-use interface that provides quick set up, long
term reliability and accurate mass flow measurement over a wide range
of flows, pressures and temperatures.
Using This Manual
This manual provides information needed to install and operate both the
Series 240 In-Line and Series 241 Insertion Innova-Mass Flow Meters.
The four chapters of this manual cover these areas:
• Chapter 1 includes the introduction and product description
• Chapter 2 provides information needed for installation
• Chapter 3 describes system operation and programming
• Chapter 4 covers troubleshooting and repair
The product specifications are found in Appendix A. Appendix B contains a glossary of terms. Appendix C provides reference fluid calculations. Appendix D provides wiring and configuration information for the
Energy meter option.
IM-24-HP 1-1
Chapter 1 Introduction Series 24-HP Instruction Manual
Note and Safety Information
We use note, caution and warning statements throughout this book to
draw your attention to important information.
Warning!
This statement appears with
information that is important to
protect people and equipment
from damage. Pay very close
attention to all warnings that
apply to your application.
Caution!
This statement appears with
information that is important
for protecting your equipment
and performance. Read and
follow all cautions that apply
to your application.
Receipt of System Components
When receiving a Sierra mass flow meter, carefully check the outside
packing carton for damage incurred in shipment. If the carton is damaged, notify the local carrier and submit a report to the factory or distributor. Remove the packing slip and check that all ordered components are
present. Make sure any spare parts or accessories are not discarded with
the packing material. Do not return any equipment to the factory without
first contacting Sierra Customer Service.
Technical Assistance
If you encounter a problem with your flow meter, review the configuration information for each step of the installation, operation and set up procedures. Verify that your settings and adjustments are consistent with factory recommendations. Refer to Chapter 4, Troubleshooting, for specific
information and recommendations.
If the problem persists after following the troubleshooting procedures
outlined in Chapter 4, contact Sierra Instruments, Technical Support at
(888) 386-7835 or (303) 682-9999 between 8:00 a.m. and 5:00 p.m.
MST. When calling Technical Support, have the following information
on hand:
•the flow range, serial number and Sierra order number (all
marked on the meter nameplate)
•the problem you are encountering and any corrective action
taken
•application information (gas, pressure, temperature and pip-
ing configuration)
Note
This statement appears with a
short message to alert you to
an important detail.
1-2 IM-24-HP
Series 24-HP Instruction Manual Chapter 1 Introduction
How the Innova-Mass Vortex Mass Flow Meter Operates
Figure 1-1. In-Line Vortex Multi-Parameter Mass Flow Meter
Sierra Series 240 and 241 Innova-Mass™ Multi-Parameter Vortex Mass
Flow Meters use a unique sensor head to monitor mass flow rate by directly measuring three variables–fluid velocity, temperature and pressure.
The built-in flow computer calculates the mass flow rate and volumetric
flow rate based on these three direct measurements. The velocity, temperature and pressure sensing head is built into the vortex meter’s flow
body. To measure fluid velocity, the flow meter incorporates a bluff
body (shedder bar) in the flow stream and measures the frequency of vortices created by the shedder bar. Temperature is measured using a platinum resistance temperature detector (PRTD). Pressure measurement is
achieved using a solid-state pressure transducer. All three elements are
combined into an integrated sensor head assembly located downstream of
the shedder bar within the flow body.
Velocity Measurement
The Innova-Mass vortex velocity sensor is a patented mechanical design
that minimizes the effects of pipeline vibration and pump noise, both of
which are common error sources in flow measurement with vortex flow
meters. The velocity measurement is based on the well-known Von Karman vortex shedding phenomenon. Vortices are shed from a shedder bar,
and the vortex velocity sensor located downstream of the shedder bar
senses the passage of these vortices. This method of velocity measurement
has many advantages including inherent linearity, high turndown, reliability and simplicity.
IM-24-HP 1-3
Chapter 1 Introduction Series 24-HP Instruction Manual
Vortex Shedding Frequency
Von Karman vortices form downstream of a shedder bar into two distinct
wakes. The vortices of one wake rotate clockwise while those of the other wake rotate counterclockwise. Vortices generate one at a time, alternating from the left side to the right side of the shedder bar. Vortices interact with their surrounding space by over-powering every other nearby
swirl on the verge of development. Close to the shedder bar, the distance
(or wave length) between vortices is always constant and measurable.
Therefore, the volume encompassed by each vortex remains constant, as
shown below. By sensing the number of vortices passing by the velocity
sensor, the Innova-Mass™ Flow Meter computes the total fluid volume.
Velocity sensor
Vortex shedder bar
Flow
Constant
wave length
Vortices
Figure 1-2. Measurement Principle of Vortex Flow Meters
Vortex Frequency Sensing
The velocity sensor incorporates a piezoelectric element that senses the
vortex frequency. This element detects the alternating lift forces produced by the Von Karman vortices flowing downstream of the vortex
shedder bar. The alternating electric charge generated by the piezoelectric element is processed by the transmitter’s electronic circuit to obtain
the vortex shedding frequency. The piezoelectric element is highly sensitive and operates over a wide range of flows, pressures and temperatures.
1-4 IM-24-HP
Series 24-HP Instruction Manual Chapter 1 Introduction
Flow Velocity Range
To ensure trouble-free operation, vortex flow meters must be correctly
sized so that the flow velocity range through the meter lies within the
measurable velocity range (with acceptable pressure drop) and the linear
range.
The measurable range is defined by the minimum and maximum velocity
using the following table.
Vmin
Vmax 300 ft/s 30 ft/s
Vmin
Vmax 91 m/s 9.1 m/s
GasLiquid
37
25
ρ
ft/s
ρ
m/s
1 ft/s
0.3 m/s
English
Metric
ρ
(lb/ft3)
ρ
(kg/m3)
The pressure drop for series 241 insertion meters is negligible. The pressure
drop for series 240 in-line meters is defined as:
2
ΔP = .00024 ρ V
ΔP = .000011 ρ V
English units (ΔP in psi, ρ in lb/ft3, V in ft/sec)
2
Metric units (ΔP in bar, ρ in kg/m3, V in m/sec)
The linear range is defined by the Reynolds number. The Reynolds number is the
ratio of the inertial forces to the viscous forces in a flowing fluid and is defined
as:
Where
Re =
ρ V D
μ
Re = Reynolds Number
ρ = mass density of the fluid being measured
V = velocity of the fluid being measured
D = internal diameter of the flow channel
μ = viscosity of the fluid being measured
The Strouhal number is the other dimensionless number that quantifies the
vortex phenomenon. The Strouhal number is defined as:
Where
St = Strouhal Number
f = frequency of vortex shedding
d = shedder bar width
V = fluid velocity
IM-24-HP 1-5
St =
f d
V
Chapter 1 Introduction Series 24-HP Instruction Manual
As shown in Figure 1-3, Innova-Mass™ meters exhibit a constant
Strouhal number across a large range of Reynolds numbers, indicating a
consistent linear output over a wide range of flows and fluid types. Below this linear range, the intelligent electronics in Innova-Mass automatically corrects for the variation in the Strouhal number with the Reynolds
number. The meter’s smart electronics corrects for this non-linearity via
its simultaneous measurements of the process fluid temperature and pressure. This data is then used to calculate the Reynolds number in real
time. Innova-Mass meters automatically correct down to a Reynolds
number of 5,000.
0.3
Corrected range
Linear range
0.2
0.1
Strouhal Number, St
0.0
34
10
10
5000
5
1010
Reynolds Number, Re
10
6
10
7
8
Figure 1-3. Reynolds Number Range for the Innova-Mass
Temperature Measurement
Innova-Mass Flow Meters use a 1000 ohm platinum resistance temperature
detector (PRTD) to measure fluid temperature.
1-6 IM-24-HP
Series 24-HP Instruction Manual Chapter 1 Introduction
Pressure Measurement
Innova-Mass Flow Meters incorporate a solid-state pressure transducer
isolated by a 316 stainless steel diaphragm. The transducer itself is micro-machined silicon, fabricated using integrated circuit processing technology. A nine-point pressure/temperature calibration is performed on
every sensor. Digital compensation allows these transducers to operate
within a 0.3% of full scale accuracy band within the entire ambient temperature range of -4°F to 140°F. Thermal isolation of the pressure transducer ensures the same accuracy across the allowable process fluid temperature range of -40°F to 750°F.
Flow Meter Configurations
Innova-Mass™ Vortex Mass Flow Meters are available in two
configurations:
• Series 240 in-line flow meter (replaces a section of the pipeline)
• Series 241 insertion flow meter (requires a “cold” tap or a “hot” tap
into an existing pipeline)
Both the in-line and insertion configurations are similar in that they both
use identical electronics and have similar sensor heads. Besides installation differences, the main difference between an in-line flow meter and
an insertion flow meter is their method of measurement.
For an in-line vortex flow meter, the shedder bar is located across the entire diameter of the flow body. Thus, the entire pipeline flow is included
in the vortex formation and measurement. The sensing head, which directly measures velocity, temperature and pressure is located just downstream of the shedder bar.
Insertion vortex flow meters have a shedder bar located across the diameter of a short tube. The velocity, temperature and pressure sensor are located within this tube just downstream of a built-in shedder bar. This entire assembly is called the insertion sensing head. It fits through any entry port with a 1.875 inch minimum internal diameter.
The sensing head of an insertion vortex flow meter directly monitors the
velocity at a point in the cross-sectional area of a pipe, duct, or stack (referred to as “channels”). The velocity at a point in the pipe varies as a function of the Reynolds number. The insertion vortex flow meter computes the
Reynolds number and then computes the total flow rate in the channel. The
output signal of insertion meters is the total flow rate in the channel. The
accuracy of the total flow rate computation depends on adherence to the
piping installation requirements given in Chapter 2. If adherence to those
guidelines cannot be met, contact the factory for specific installation advice.
IM-24-HP 1-7
Chapter 1 Introduction Series 24-HP Instruction Manual
Flow Meter Electronics
Innova-Mass Flow Meter electronics are available mounted directly to
the flow body, or remotely mounted. The electronics housing may be
used indoors or outdoors, including wet environments. Power requirements are 100 milliamps at 12-36 VDC. An optional AC powered unit is
available. Three analog output signals are available for your choice of
three of the five process variables: mass flow rate, volumetric flow rate,
temperature, pressure or fluid density.
Innova-Mass Flow Meters include a local 2 x 16 character LCD display
housed within the enclosure. Local operation and reconfiguration is accomplished using six pushbuttons operated via finger touch. For hazardous locations, the six buttons can be operated with the electronics enclosure sealed using a hand-held magnet, thereby not compromising the integrity of the hazardous location certification.
The electronics include nonvolatile memory that stores all configuration
information. The nonvolatile memory allows the flow meter to function
immediately upon power up, or after an interruption in power.
1-8 IM-24-HP
Series 24-HP Instruction Manual Chapter 2 Installation
Warning!
Consult the flow meter namep-
late for specific flow meter ap-
provals before any hazardous
location installation.
Chapter 2 Installation
Installation Overview
Sierra’s Innova-Mass Vortex Flow Meter installations are simple and
straightforward. Both the Series 240 In-Line and Series 241 Insertion type
flow meter installations are covered in this chapter. After reviewing the
installation requirements given below, see page 2-3 for Series 240 installation instructions. See page 2-6 for Series 241 installation instructions.
Wiring instructions begin on page 2-19.
Flow Meter Installation Requirements
Before installing the flow meter, verify the installation site allows for
these considerations:
1. Line pressure and temperature will not exceed the flow meter
rating.
2. The location meets the required minimum number of pipe diame-
ters upstream and downstream of the sensor head as illustrated
Figure 2-1.
3. Safe and convenient access with adequate overhead clear-
ance for maintenance purposes.
4. Verify that the cable entry into the instrument meets the
specific standard required for hazardous area installations.
5. For remote installations, verify the supplied cable length is
sufficient to connect the flow meter sensor to the remote
electronics.
Also, before installation check your flow system for anomalies such as:
• leaks
• valves or restrictions in the flow path that could create distur-
bances in the flow profile that might cause unexpected flow rate
indications
IM-24-HP 2-1
Chapter 2 Installation Series 24-HP Instruction Manual
Unobstructed Flow Requirements
Select an installation site that will minimize possible distortion in the flow
profile. Valves, elbows, control valves and other piping components may
cause flow disturbances. Check your specific piping condition against the
examples shown below. In order to achieve accurate and repeatable performance install the flow meter using the recommended number of
straight run pipe diameters upstream and downstream of the sensor.
Note: For liquid applications in vertical pipes, avoid installing with flow
in the downward direction because the pipe may not be full at all points.
Choose to install the meter with flow in the upward direction if possible.
AB
AB
C'C
Flow meter
Flow conditioner
(if used)
Example 1.
One 90° elbow before meter
Flow meter
Example 4.
Reduction before meter
AB
AB
C'
C
Flow meter
Flow conditioner
(if used)
Example 2.
Two 90° elbows before meter in one plane
Example 5.
Expansion before meter
C'C
Flow meter
Flow conditioner
(if used)
AB
AB
C'
C
Flow meter
Flow conditioner
(if used)
Example 3.
Two 90° elbows before meter out of plane (if three
90° bends present, double recommended length)
Example 6.
Regulator or valve partially closed before meter
(If valve is always wide open, base length
requirements on fitting directly preceding it)
C'C
Flow conditioner (if used)
Flow meter
Minimum Required
Upstream Diameters
No Flow
Conditioner
With Flow Conditioner
Example A A C C´ B B
1 10 D N/A N/A N/A 5 D 5 D
2 15 D 10 D 5 D 5 D 5 D 5 D
3 25 D 10 D 5 D 5 D 10 D 5 D
4 10 D 10 D 5 D 5 D 5 D 5 D
5 20 D 10 D 5 D 5 D 5 D 5 D
6 25 D 10 D 5 D 5 D 10 D 5 D
D = Internal diameter of channel. N/A = Not applicable
Minimum Required
Downstream Diameters
No Flow
Conditioner
With Flow
Conditioner
Figure 2-1. Recommended Pipe Length Requirements for Installation, Series 240 and 241
2-2IM-24-HP
Series 24-HP Instruction Manual Chapter 2 Installation
Series 240 In-Line Flow Meter Installation
Install the Series 240 In-Line Flow Meter between two conventional pipe
flanges as shown in Figures 2-3 and 2-4. Table 2-1 provides the recommended minimum stud bolt lengths for wafer-style meter body size and
different flange ratings.
The meter inside diameter is equal to the same size nominal pipe ID in
schedule 80. For example, a 2” meter has an ID of 1.939” (2” schedule
80). Do not install the meter in a pipe with an inside diameter smaller than the inside diameter of the meter. For schedule 160 and higher
pipe, a special meter is required. Consult the factory before purchasing
the meter.
Series 240 Meters require customer-supplied gaskets. When selecting
gasket material make sure that it is compatible with the process fluid and
pressure ratings of the specific installation. Verify that the inside diameter
of the gasket is larger than the inside diameter of the flow meter and adjacent piping. If the gasket material extends into the flow stream, it will disturb the flow and cause inaccurate measurements.
Flange Bolt Specifications
Stud Bolt Lengths for Each Flange Rating (inches)
Line Size Class 150 Class 300 Class 600
1 inch 6.00 7.00 7.50
1.5 inch 6.25 8.50 9.00
2 inch 8.50 8.75 9.50
3 inch 9.00 10.00 10.50
4 inch 9.50 10.75 12.25
Table 2-1. Minimum Recommended Stud Bolt Lengths for Wafer Meters
The required bolt load for sealing the gasket joint is affected by several
application-dependent factors, therefore the required torque for each application may be different. Refer to the ASME Pressure Vessel Code
guidelines for bolt tightening standards.
1
34
2
1
8
6
5
34
7
2
4
10
4-bolt8-bolt12-bolt
1
12
8
6
5
9
3
7
11
2
Figure 2-2. Flange Bolt Torquing Sequence
IM-24-HP 2-3
Chapter 2 Installation Series 24-HP Instruction Manual
Wafer-Style Flow Meter Installation
Install the wafer-style meter between two conventional pipe flanges of the
same nominal size as the flow meter. If the process fluid is a liquid, make
sure the meter is located where the pipe is always full. This may require
locating the meter at a low point in the piping system. Note: Vortex flow
meters are not suitable for two-phase flows (i.e., liquid and gas mixtures).
For horizontal pipelines having a process temperature above 300° F,
mount the meter at a 45 or 90-degree angle to avoid overheating the electronics enclosure. To adjust the viewing angle of the enclosure or display/keypad, see page 2-17.
Caution!
When using toxic or cor-
rosive gases, purge the
line with inert gas for a
minimum of four hours
at full gas flow before
installing the flow meter.
Figure 2-3. Wafer-Style Flow Meter Installation
When installing the meter make sure the section marked “inlet” is positioned
upstream of the outlet, facing the flow. This ensures that the sensor head is
positioned downstream of the vortex shedder bar and is correctly aligned to
the flow. Installing the meter opposite this direction will result in completely
inaccurate flow measurement. To install the meter:
1. Turn off the flow of process gas, liquid or steam. Verify that the line
is not pressurized. Confirm that the installation site meets the required
minimum upstream and downstream pipe diameters.
2. Insert the studs for the bottom side of the meter body between the pipe
flanges. Place the wafer-style meter body between the flanges with the
end stamped “inlet” facing flow. Center the meter body inside the diameter with respect to the inside diameter of the adjoining piping.
3. Position the gasket material between the mating surfaces. Make sure
both gaskets are smooth and even with no gasket material extending into the flow profile. Obstructions in the pipeline will disturb the flow and
cause inaccurate measurements
Place the remaining studs between the pipe flanges. Tighten the nuts in
4.
the sequence shown in Figure 2-2. Check for leaks after tightening the
flange bolts
2-4IM-24-HP
Series 24-HP Instruction Manual Chapter 2 Installation
Flange-Style Flow Meter Installation
Install the flange-style meter between two conventional pipe flanges of
the same nominal size as the flow meter. If the process fluid is a liquid,
make sure the meter is located where the pipe is always full. This may require locating the meter at a low point in the piping system. Note: Vortex
flow meters are not suitable for two-phase flows (i.e., liquid and gas mixtures). For horizontal pipelines having a process temperature above 300°
F, mount the meter at a 45 or 90-degree angle to avoid overheating the
electronics enclosure. To adjust the viewing angle of the enclosure or display/keypad, see page 2-17.
Caution!
When using toxic or corro-
sive gases, purge the line
with inert gas for a mini-
mum of four hours at full
gas flow before installing
the flow meter.
Figure 2-4. Flange-Style Flow Meter Installation
When installing the meter make sure the flange marked “inlet” is positioned
upstream of the outlet flange, facing the flow. This ensures that the sensor
head is positioned downstream of the vortex shedder bar and is correctly
aligned to the flow. Installing the meter opposite this direction will result in
completely inaccurate flow measurement. To install the meter:
1. Turn off the flow of process gas, liquid or steam. Verify that the line
is not pressurized. Confirm that the installation site meets the required
minimum upstream and downstream pipe diameters.
2. Seat the meter level and square on the mating connections with the flange
marked “inlet” facing the flow. Position a gasket in place for each side.
Make sure both gaskets are smooth and even with no gasket material extending into the flow profile. Obstructions in the pipeline will disturb the
flow and cause inaccurate measurements.
3. Install bolts in both process connections. Tighten the nuts in the se-
quence shown in Figure 2-2. Check for leaks after tightening the flange
bolts.
IM-24-HP 2-5
Chapter 2 Installation Series 24-HP Instruction Manual
Series 241 Insertion Flow Meter Installation
Prepare the pipeline for installation using either a cold tap or hot tap method described on the following pages. Refer to a standard code for all
pipe tapping operations. The following tapping instructions are general in
nature and intended for guideline purposes only. Before installing the meter, review the mounting position and isolation value requirements given
below.
Mounting Position
Allow clearance between the electronics enclosure top and any other obstruction when the meter is fully retracted.
Isolation Valve Selection
An isolation valve is available as an option with Series 241 meters. If you
supply the isolation valve, it must meet the following requirements:
1. A minimum valve bore di-
ameter of 1.875 inches is required, and the valve’s body
size should be two inches.
2-inch min.
Normally, gate valves are
used.
2. Verify that the valve’s body
2-inch
valve size
and flange rating are within
the flow meter’s maximum
operating pressure and tem-
Isolation Valve Requirements
perature.
3. Choose an isolation valve with at least two inches existing between
the flange face and the gate portion of the valve. This ensures that the
flow meter’s sensor head will not interfere with the operation of the
isolation valve.
1.875-inch min.
valve bore
2-6 IM-24-HP
Series 24-HP Instruction Manual Chapter 2 Installation
Caution!
When using toxic or
corrosive gases, purge
the line with inert gas
for a minimum of four
hours at full gas flow
before installing the
flow meter.
Warning!
All flow meter connec-
tions, isolation valves and
fittings for cold tapping
must have the same or
pressure rating as
higher
the main pipeline.
Cold Tap Guidelines
Refer to a standard code for all pipe tapping operations. The following
tapping instructions are general in nature and intended for guideline purposes only.
1. Turn off the flow of process gas, liquid or steam. Verify that the line
is not pressurized.
2. Confirm that the installation site meets the minimum upstream and
downstream pipe diameter requirements. See Figure 2-1.
3. Use a cutting torch or sharp cutting tool to tap into the pipe. The pipe
opening must be at least 1.875 inches in diameter. (Do not attempt to
insert the sensor probe through a smaller hole.)
4. Remove all burrs from the tap. Rough edges may cause flow profile
distortions that could affect flow meter accuracy. Also, obstructions
could damage the sensor assembly when inserting into the pipe.
5. After cutting, measure the thickness of the cut-out and record this
number for calculating the insertion depth.
6. Weld the flow meter pipe con-
nection on the pipe. Make sure
this connection is within ± 5°
perpendicular to the pipe centerline.
7. Install the isolation valve (if
used).
8. When welding is complete and all fittings are installed, close the
isolation valve or cap the line. Run a static pressure check on the
welds. If pressure loss or leaks are detected, repair the joint and retest.
9. Connect the meter to the pipe process connection.
10. Calculate the sensor probe insertion depth as described on the follow-
ing pages. Insert the sensor probe into the pipe.
IM-24-HP 2-7
Chapter 2 Installation Series 24-HP Instruction Manual
Warning!
Hot tapping must be
performed by a trained pro-
fessional. US. regulations of-
ten require a hot tap permit.
The manufacturer of the hot
tap equipment and/or the con-
tractor performing the hot tap
is responsible for providing
proof of such a permit.
Warning!
All flow meter connections,
isolation valves and fittings for
hot tapping must have the
same or higher pressure rat-
ing as the main pipeline
Hot Tap Guidelines
Refer to a standard code for all pipe tapping operations. The following
.
tapping instructions are general in nature and intended for guideline purposes only.
1. Confirm that the installation site meets the minimum upstream and
downstream pipe diameter requirements.
2. Weld a two inch mounting adapter on the pipe. Make sure the mount-
ing adapter is within ± 5° perpendicular to the pipe centerline (see
previous page). The pipe opening must be at least 1.875 inches in diameter.
3. Connect a two inch process connection on the mounting adapter.
4. Connect an isolation valve on the process connection. The valve’s full
open bore must be at least 1.875 inches in diameter.
5. Hot tap the pipe.
6. Close the isolation valve. Run a static pressure check on the welds. If
pressure loss or leaks are detected, repair the joint and re-test.
7. Connect the flow meter to the isolation valve.
8. Calculate the sensor probe insertion depth as described on the follow-
ing pages. Insert the sensor probe assembly into the pipe.
Check upstream and
downstream piping
requirements
Weld mounting
adapter
Connect process
connection
(flange or NPT)
Connect
isolation valve
Hot tap pipe
FLOW
Test for leaks,
purge pipe
Connect meter to
valve, calculate
insertion depth,
install flow meter
Figure 2-5. Hot Tap Sequence
2-8IM-24-HP
Series 24-HP Instruction Manual Chapter 2 Installation
Flow Meter Insertion
The sensor head must be properly positioned in the pipe. For this reason,
it is important that insertion length calculations are carefully followed. A
sensor probe inserted at the wrong depth in the pipe will result in inaccurate readings.
Insertion flow meters are applicable to pipes 2 inch and larger. For pipe
sizes ten inches and smaller, the centerline of the meter’s sensing head is
located at the pipe’s centerline. For pipe sizes larger than ten inches, the
centerline of the sensing head is located in the pipe’s cross section five
inches from the inner wall of the pipe; i.e., its “wetted” depth from the
wall to the centerline of the sensing head is five inches.
Insertion flow meters are available in three probe lengths:
Standard Probe configuration is used with most flow meter process
connections. The length, S, of the stem is 29.47 inches.
Compact Probe configuration is used with compression fitting process
connections. The length, S, of the stem is 13.1 inches.
12-Inch Extended Probe configuration is used with exceptionally lengthy
flow meter process connections. The length, S, of the stem is 41.47 inches.
Warning!
An insertion tool must be
used for any installation
where a flow meter is
inserted under pressure
greater than 50 psig.
Use the Correct Insertion Formula
Depending on your flow meter’s process connection, use the applicable
insertion length formula and installation procedure as follows:
•Flow meters with a compression type connection (NPT or flanged)
follow the instructions beginning on page 2-10.
•Flow meters with a packing gland type connection (NPT or flanged)
configured with an insertion tool, follow the instructions beginning on
page 2-12.
• Flow meters with a packing gland type connection (NPT or flanged)
without an insertion tool, follow the instructions beginning on page
2-15.
IM-24-HP 2-9
Chapter 2 Installation Series 24-HP Instruction Manual
Installing Flow Meters with a Compression Connection*
Use the following formula to determine insertion length for flow meters
(NPT and flanged) with a compression process connection. The installation procedure is given on the next page.
Insertion Length Formula
I = S – F – R – t
Where:
I = Insertion length.
S = Stem length – the distance from the center of the sensor head to the base
of the enclosure adapter (S = 29.47 inches for standard probes; S = 13.1
inches for compact; S = 41.47 inches for 12-inch extended).
F = Distance from the raised face of the flange or top of NPT stem housing to
the outside of the pipe wall.
R = Pipe inside diameter ÷ 2 for pipes ten inches and smaller.
R = Five inches for pipe diameters larger than ten inches.
t = Thickness of the pipe wall. (Measure the disk cut-out from the tapping
procedure or check a piping handbook for thickness.)
To install a Series 241 meter with a standard probe (S = 29.47 inches) into a 14
inch schedule 40 pipe, the following measurements are taken:
F=3 inches
R=5 inches
t=0.438 inches
The insertion length for this example is 21.03 inches. Insert the stem through
the fitting until an insertion length of 21.03 inches is measured with a ruler.
*All dimensions are in inches
2-10IM-24-HP
Series 24-HP Instruction Manual Chapter 2 Installation
Insertion Procedure for Meters with a Compression Connection
Caution!
The sensor alignment
pointer must point
downstream, in the
direction of flow
Warning!
To avoid serious injury,
DO NOT loosen the
compression fitting
under pressure
Figure 2-7. Flow Meter with Compression Type Fitting
1. Calculate the required sensor probe insertion length.
2. Fully retract the stem until the sensor head is touching the bottom of
the stem housing. Slightly tighten the compression nut to prevent
slippage.
.
3. Bolt or screw the flow meter assembly into the process connection.
Use Teflon tape or pipe sealant to improve the seal and prevent seizing on NPT styles.
4. Hold the meter securely while loosening the compression fitting. In-
sert the sensor into the pipe until the calculated insertion length, I, is
measured between the base of the enclosure adapter and the top of
.
the stem housing, or to the raised face of the flanged version. Do
not force the stem into the pipe.
5. Align the sensor head using the sensor alignment pointer. Adjust the
alignment pointer parallel to the pipe and pointing downstream.
6. Tighten the compression fitting to lock the stem in position. When
the compression fitting is tightened, the position is permanent.
IM-24-HP 2-11
Chapter 2 Installation Series 24-HP Instruction Manual
Installing Flow Meters with a Packing Gland Connection*
Use the formula below to determine the insertion depth for flow meters
(NPT and flanged) equipped with an insertion tool. To install, see the next
page for instructions for meters with a permanent insertion tool. For meters with a removable insertion tool, see page 2-14.
Insertion Length Formula
I = F + R + t – 1.35
Where:
I = Insertion length.
F = Distance from the raised face of the flange or
top of the process connection for NPT style
meters to the top outside of the process pipe.
R = Pipe inside diameter ÷ 2 for pipes ten inches &
smaller.
R = Five inches for pipe diameters larger than ten
inches.
t = Thickness of the pipe wall. (Measure the disk
cut-out from the tapping procedure or check a
piping handbook for thickness.)
Figure 2-8. Insertion Calculation (Meters with Insertion Tool)
Example 1: Flange Style Meters:
To install a Series 241 Flow Meter into a 14 inch schedule 40 pipe, the following measurements are taken:
F = 12 inches
R = 5 inches
t = 0.438 inches
The example insertion length is 16.09 inches.
Example 2: NPT Style Meters:
The length of thread engagement on the NPT style meters is also subtracted in
the equation. The length of the threaded portion of the NPT meter is 1.18
inches. Measure the thread portion still showing after the installation and subtract that amount from 1.18 inches. This gives you the thread engagement
length. If this cannot be measured use .55 inch for this amount.
F = 12 inches
R = 5 inches
The example insertion length is 15.54 inches.
*All dimensions are in inches.
t = 0.438 inches
2-12IM-24-HP
Series 24-HP Instruction Manual Chapter 2 Installation
Insertion Procedure for Flow Meters with Permanent Insertion Tool
Caution!
The sensor alignment
pointer must point
downstream, in the
direction offlow.
Note
If line pressure is above
500 psig, it could require
up to 25 ft lb of torque to
insert the flow meter.
Do not confuse this with
possible interference
in the pipe.
Figure 2-9. Flow Meter with Permanent Insertion Tool
1. Calculate the required sensor probe insertion length (see previous
page). Measure from the depth marker arrow down the stanchion and
scribe a mark at the calculated insertion depth.
2. Fully retract the flow meter until the sensor head is touching the bot-
tom of the stem housing. Attach the meter assembly to the two inch
full-port isolation valve, if used. Use Teflon tape or pipe sealant to
improve seal and prevent seizing on NPT style.
3. Loosen the two packing gland nuts on the stem housing of the meter.
Loosen the stem lock bolt adjacent to the sensor alignment pointer.
Align the sensor head using the sensor alignment pointer. Adjust the
alignment pointer parallel to the pipe and pointing downstream. Tighten
the stem lock bolt to secure the sensor position.
4. Slowly open the isolation valve to the full open position. If necessary,
slightly tighten the two packing gland nuts to reduce the leakage
around the stem.
5. Turn the insertion tool handle clockwise to insert the sensor head into
the pipe. Continue until the top of the upper retractor bracket aligns
with the insertion length position scribed on the stanchion. Do not
force the stem into the pipe.
6. Tighten the packing gland nuts to stop leakage around the stem. Do
not torque over 20 ft-lb.
IM-24-HP 2-13
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.