Sierra 215 User Manual

INNOVA-SWITCH™ SERIES
INSTRUCTION MANUAL
Model 215 Mass Flow/Level Switch
( Model FS4200 Series – Mass Flow Switch / Model LS3200 Series – Point Level Switch )
Document IM 215
Rev-A.1
February 2006
Sierra Instruments, Inc., Headquarters
5 Harris Court, Building L
Monterey, California, USA 93940
Toll Free: 800-866-0200 (USA only)
Phone: 831-373-0200 ; Fax: 831-373-4402
Website: www.sierrainstruments.com
Sierra Europe, European Headquarters
Bijlmansweid 2
1934RE Egmond a/d Hoef
The Netherlands
Phone: +31 72 5071 400 ; Fax: +31 72 5071 401
Sierra Asia, Asia-Pacific Headquarters
100 Jaingnan Daidao Suite 2303
Guangzhou, China
Phone: +86 20 3435 4870, Fax: +86 20 3435 4872
IM-215 Rev-A.1 Series Innova-Switch™ Page 2 of 42
BEFORE STARTING
SIERRA INSTRUMENTS appreciates your choosing our product for your liquid level or liquid/gas flow switching application. We are committed to providing reliable, quality instrumentation to our customers.
To ensure the maximum and intended benefit of this instrument, we encourage you to read this brief operation and maintenance manual in its entirety prior to unpacking and installing the unit.
The following precautions should be noted immediately:
WHEN INSTALLING YOUR INNOVA-SWITCH™ INTO A PIPE OR VESSEL USE A 1 1/8 INCH
(28.575mm) OPEN-END WRENCH TO TIGHTEN AT THE HEX FLATS OF THE MNPT OF A STANDARD SWITCH. (IF YOU HAVE A NON-STANDARD SWITCH AN ALTERNATE SIZE WRENCH MAY BE REQUIRED). DO NOT USE THE INSTRUMENT HEAD TO TIGHTEN THE SWITCH TO THE MOUNTING PORT. ROTATION OF THE INSTRUMENT HEAD WITH RESPECT TO THE SENSOR BODY CAN CAUSE INTERNAL WIRING DAMAGE (SEE FIGURES 1).
THE SWITCH BODY MUST BE ORIENTED TO HAVE THE TWIN SENSORS PARALLEL TO
THE LEVEL BEING DETECTED WHEN THE SENSOR IS INSTALLED HORIZONTALLY FOR POINT LEVEL APPLICATIONS. LIKEWISE, FOR FLOW APPLICATIONS, THE SWITCH BODY MUST BE ORIENTED TO HAVE THE TWIN SENSORS PERPENDICULAR TO THE FLOW BEING DETECTED. DUE TO THE PIPE THREAD MOUNTING, IT MAY BE NECESSARY TO MAKE A TRIAL FIT, ADD OR REMOVE TEFLON TAPE OR OTHER PIPE THREAD SEALANT, AND REINSTALL TO ACHIEVE A SATISFACTORY SEAL WITH THE SENSORS PROPERLY ORIENTED. FOR VERTICAL INSTALLATION OF SENSORS FOR POINT LEVEL DETECTION THE ORIENTATION MAKES NO DIFFERENCE. PROPER ORIENTATION IS MARKED ON THE SWITCH BODY FOR REFERENCE (SEE FIGURE 5).
A GROUND WIRE MUST BE ATTACHED TO THE GROUND SCREW LOCATED INSIDE THE
INSTRUMENT ENCLOSURE FOR PROPER OPERATION. FOR CENELEC/CE OPTION THE GROUND SCREW IS LOCATED OUTSIDE THE BODY OF THE INSTRUMENT ENCLOSURE (SEE FIGURE 6).
BE SURE TO APPLY THE PROPER VOLTAGE AS CONFIGURED AT THE FACTORY. DO
NOT APPLY 115 VAC TO 24 VDC VERSIONS OR 24 VDC TO 115 VAC VERSIONS. (LIKEWISE 230 VAC).
FOR OPTIMUM OPERATION, CALIBRATION MUST BE ACCOMPLISHED AT ACTUAL
PROCESS TEMPERATURE AND PRESSURE CONDITIONS IN GASES AND AT ACTUAL PROCESS TEMPERATURE CONDITIONS IN LIQUIDS.
DO NOT SANDBLAST OR ABRASIVE CLEAN THE SENSING PROBES. THE SENSING
PROBES COULD BE DAMAGED BY ABRASIVES.
ALL DIMENSIONS GIVEN IN THIS MANUAL ARE IN INCHES (AND MILLIMETERS).
If you have any questions prior to or during installation and calibration, please do not hesitate to call the factory for assistance. We want to ensure the very best possible installation and operational results for your benefit.
IM-215 Rev-A.1 Series Innova-Switch™ Page 3 of 42
The electronic assemblies contained in the Innova-Switch™ models are configured for specific voltages and have specific modifications to accommodate the various agency approvals. When ordering spare electronics, replacements, or exchanges in the field please ensure you identify the specific configuration you have by noting the boxes marked on the transformer configuration tag.
NOTICE
This manual covers the following model numbers:
Innova-Switch™ Series Models
215 - FS4200
215 - LS3200
Agency Approvals
Explosion-Proof rating
Mass Flow Switch
Point Level Switch
CENELEC European
EEX d IIB T4 (Killark Enclosure) EEx d IIC T4 (Akron Electric Enclosure) See Figure 1A and 1B
FS42CN
LS32CN
CSA Canadian Standards
T4A Class I, Group B,C,D Class II, Group E, F, G (Both Akron Electric and Killark)
FS42CS
LS32CS
Non-Approved
Non-Explosion Proof
FS42NX
LS32NX
(Ref. Section CE 3.2.3 wiring)
EMC Directive: 89/336/EEC
Option-CE
Option-CE
SPECIAL NOTICE
IM-215 Rev-A.1 Series Innova-Switch™ Page 4 of 42
TABLE OF CONTENTS
1.0 INTRODUCTION
2.0 DESCRIPTION
2.1 LEVEL SWITCHING
2.2 FLOW SWITCHING
3.0 INSTALLATION
3.1 MECHANICAL INSTALLATION
3.2 ELECTRICAL INSTALLATION
3.2.1 LOCAL ELECTRONICS (LE OPTION/STANDARD)
3.2.2 REMOTE ELECTRONICS (RE) OPTION
3.2.3 CE OPTION FILTER BOARD CONNECTOR PLATE WIRING (CE OPTION)
4.0 OPERATION AND CALIBRATION OF THE Innova-Switch™ SWITCH FOR FLOW APPLICATIONS
4.1 PRE-OPERATIONAL CHECKS
4.2 L.E.D. AND RELAY STATUS LOGIC (FAIL-SAFE)
4.3 CALIBRATION – FLOW
5.0 OPERATION AND CALIBRATION OF THE Innova-Switch™ SWITCH FOR POINT LEVEL
APPLICATIONS
5.1 PRE-OPERATIONAL CHECKS
5.2 L.E.D. AND RELAY STATUS LOGIC (FAIL-SAFE)
5.3 CALIBRATION – LEVEL
6.0 MAINTENANCE AND TROUBLE SHOOTING
6.1 CLEANING
6.2 TROUBLE SHOOTING
6.2.1 POWER AND CONTINUITY VERIFICATION
6.2.2 SENSOR/ELECTRONICS FUNCTIONALITY VERIFICATION
7.0 SPECIFICATIONS
8.0 WARRANTY AND SERVICE
8.1 WARRANTY
8.2 SERVICE
8.3 SPARE PARTS LIST
9.0 APPENDIX
9.1 VOLUME FLOW CONVERSION CHART
9.2 FLOW CONVERSION CHART
9.3 FLOW OF WATER THROUGH SCHEDULE 40 STEEL PIPE (AVAILABLE IN PRINTED MANUAL ONLY)
10 OPTIONS
10.1 LIVETAP (LT)
10.2 VARIABLE INSERTION (VI)
10.3 THERMOCOUPLE OUTPUT (TO)
10.4 RTD OUTPUT(RT)
10.5 SANITARY (3A1)
IM-215 Rev-A.1 Series Innova-Switch™ Page 5 of 42
1.0 INTRODUCTION
The SIERRA INSTRUMENTS Innova-Switch™ Switch is the state-of-the-art in
gaseous and liquid flow switching or liquid level control. Flow or level detection is accomplished by using a high resolution thermal differential technique. The sensor wetted parts are of durable 316L series stainless steel, all welded construction with no moving parts. The switch is easy to install and adjust, giving reliable, low maintenance performance in the most demanding applications.
2.0 DESCRIPTION
The Innova-Switch™ uses a thermal differential technique to sense changes in the
heat transfer characteristics of a media. Figures 1A and 1B show the outline of the Innova-Switch™. The sensor consists of a pair of matched Resistance Temperature
Detectors (RTD's) encased in twin 316L series stainless steel tubes. One RTD is self-heated using a constant DC current. The other RTD is unheated to provide an accurate process temperature reference. The thermal differential created between the heated and reference RTD pair is a function of the density and/or velocity of the media with which the sensor is in contact. Other physical properties may have a secondary effect as well. The differential is greatest at a no flow (or dry) condition and decreases as the rate of flow increases (or as a liquid quenches the sensor/wet condition).
The SIERRA INSTRUMENTS sensor excitation method relies on constant current to
the heated and reference sensors. Thus power to the heated sensor is not constant but changes linearly with temperature as the sensor resistance changes. Temperature compensation is accomplished by using the amplified reference sensor voltage that also changes linearly with temperature, as a dynamic reference. During calibration dry/no flow and wet/full flow conditions are impressed across the trip point potentiometer. Since this reference is not fixed but is set with respect to the reference sensor voltage, as temperature changes the trip point potentiometer voltage changes with temperature exactly the same as that of the heated sensor voltage with which it is being compared. Thus full temperature compensation is achieved with non-constant power.
IM-215 Rev-A.1 Series Innova-Switch™ Page 6 of 42
FIGURE 1A LS3200/FS4200 Innova-Switch™ OUTLINE DIAGRAM STANDARD 2.0
INCH INSERTION (KILLARK ENCLOSURE – NEMA 4-EExd 11B, T4)
IM-215 Rev-A.1 Series Innova-Switch™ Page 7 of 42
FIGURE 1B LS3200/FS4200 Innova-SwitchOUTLINE DIAGRAM STANDARD 2.0
INCH INSERTION (AKRON ELECTRIC ENCLOSURE NEMA 4X EexdIIC, T4)
IM-215 Rev-A.1 Series Innova-Switch™ Page 8 of 42
2.1 LEVEL SWITCHING
The thermal differential created between the heated and reference unheated RTD pair is
a function of the liquid or gas medium with which the sensor is in contact.
The point level measurement application uses the heat transfer differences between two
media to detect liquid level. For example, air has a relatively poor heat transfer characteristic so the heated sensor will become relatively hot. If the sensor is then immersed in water, the relatively high heat transfer characteristics of water will cool the heated RTD surface causing a decrease in the signal output.
This same rational applies for any two media in contact with the sensor. Each medium
will have its own characteristic heat transfer properties. As long as there is a reasonable difference in the heat transfer properties between the two media, the Innova-Switch™ can discriminate between them. Figure 2A shows the relative signal output of the Innova-Switch™sensor to a range of different media. The maximum difference in output occurs between vacuum and liquid metal. However, a significant difference occurs between water and hydrocarbon liquids so the Innova-Switch ™ can be used to detect a water/hydrocarbon liquid-liquid interface. In general, the interface between any two media with differing heat transfer properties can be detected.
Thermal Differential Theory of Operation
Note: Probe tips contain
matched RTD’s one of which is self-heated with about 400mw of power. The other provides temperature compensation.
The heated RTD responds to the heat transfer coefficient of the media with which it is in contact. Gases with low heat transfer result in a high differential temperature between the heated and reference tips.
When the heated tip makes contact with a liquid with higher heat transfer the differential temperature drops and the lower differential results in a switch trip to indicate liquid.
IM-215 Rev-A.1 Series Innova-Switch™ Page 9 of 42
FIGURE 2A: RELATIVE CHANGE IN RESPONSE OF A HEATED RTD IMMERSED
IN VARIOUS MEDIA
2.2 Flow Switching
Most mass flow monitoring techniques calculate mass indirectly by measuring
volumetric flow such as gallons per minute or cubic cm per second, then either measure density separately or calculate it from temperature measurements of the fluid and, finally, combine density and volumetric flow to obtain mass flow. The SIERRA INSTRUMENTS thermal-differential technique is one of two methods that directly measure the mass flow. For ease of comparison most flow applications are presented in terms of velocity which is independent of the flow cross sectional area (i.e. feet per second (FPS)). The true mass flow equivalent would be FPS multiplied by density but for simplicity FPS is used and density effects are ignored. This is normally not critical for flow switching applications.
IM-215 Rev-A.1 Series Innova-Switch™ Page 10 of 42
When the sensor is inserted into a liquid or gas the heated RTD is strongly affected
by the velocity of the medium. Flow past the heated RTD changes the heat transferred from the surface of the sensor. This cooling effect reduces the temperature of the sensor. The Innova-Switch™ compares this change to a preset flow trip point to switch the output. Figure 2B shows the model FS4200 signal change vs. flow rate for air, light hydrocarbon liquids, and water. The signal change vs velocity has the same general shape for all three media but the change is larger for air and the sensitive range is different for each. For air and most gaseous media the range is 0.1 to 500 feet per second (FPS). For most liquid media the range is 0.01 to 5 FPS. Appendices in section 9.0 contain flow conversion information to facilitate conversion from various units and pipe dimensions into flow velocity in feet per second.
Gas Or Liquid Flow
Note: The fluid velocity and
heat absorption ability determine the differential between the tips. Their combination determines the measurable velocity. In water velocities from 0.01 to 5 FPS are measurable, whereas in air velocities of
0.1 to 500 FPS can be measured.
For a no flow condition the thermal differential between the two tips is high because of relatively low heat transfer.
Flow across the tips decreases the thermal differential because of the higher heat transfer of flowing fluids. This differential is compared with the trip point.
When the lower differential matches the customer select flow velocity trip point (set point) the switch relay and red LED are tripped.
When flow is above the trip point the differential is smaller than at the set point and the
relay and Led remain tripped.
IM-215 Rev-A.1 Series Innova-Switch™ Page 11 of 42
FIGURE 2B Innova-Switch™ MODEL FS4200 FLOW RESPONSE FOR THREE MEDIA
IM-215 Rev-A.1 Series Innova-Switch™ Page 12 of 42
Figure 3.A shows a block diagram of the Innova-Switch™ switch.
Once the switch is set to respond to the minimum and maximum flow rates (or wet vs.
dry conditions), the trip point is set by adjusting the Trip Adjust Potentiometer. Solid state electronics transform the flow (or wetting) induced temperature differential into a voltage that is compared to a control voltage. Matching voltages cause actuation of a relay to indicate a change in state (flow vs. no-flow or dry vs. wet).
FIGURE 3A: Innova-Switch™ SERIES S BLOCK DIAGRAM MODELS LS32CS/FS42CS, LS32CN/FS42CN, LS32NX/FS42NX
IM-215 Rev-A.1 Series Innova-Switch™ Page 13 of 42
Figure 3B shows a block diagram of the Innova-Switch™ with the addition of an EMC filter required for the CE options (see section 7.0).
FIGURE 3B: Innova-Switch™ MODELS WITH THE CE OPTION SWITCH BLOCK DIAGRAM
Loading...
+ 28 hidden pages