DANFOSS DRIVE MODEL VLT 5000 SERIES/ SIEMENS MM440
PPO TYPE 5
Byte 1 Byte 1 Byte 1 Byte 1 Byte 1
word 1
Word 2
word 3
word 4
word 5
word 6
word 7
word 8
word 9
PCA
IND
PCV
PVA
CTW /
STW
MRV /
MAV
PCD 3
PCD 4
PCD 5
PCD
PCD 6
PCD 7
PCD 8
PCD 9
PCD 10
Byte 2 Byte 2 Byte 2 Byte 2 Byte 2
Byte 3 Byte 3 Byte 3 Byte 3 Byte 3
Byte 4 Byte 4 Byte 4 Byte 4 Byte 4
Byte 5 Byte 5 Byte 5 Byte 5
Byte 6 Byte 6 Byte 6 Byte 6
Byte 7 Byte 7 Byte 7 Byte 7
Byte 8 Byte 8 Byte 8 Byte 8
Byte 9 Byte 9 Byte 9 Byte 9
Byte 10 Byte 10 Byte 10 Byte 10
Byte 11 Byte 11 Byte 11 Byte 11
Byte 12 Byte 12 Byte 12 Byte 12
Byte 13 Byte 13
Byte 14 Byte 14
Byte 15 Byte 15
Byte 16 Byte 16
Byte 17 Byte 17
Byte 18 Byte 18
Byte 19 Byte 19
word 10
Byte 20 Byte 20
Byte 21
word 11
Byte 22
Byte 23
word 12
Byte 24
Byte 25
word 13
Byte 26
Byte 27
word 14
Byte 28
PPO TYPE 1
word 1
PCA
Word 2 IND
word 3
PVA
word 4
CTW /
word 5
STW
MRV /
word 6
MAV
PCV
PCD
PPO TYPE 2
word 1 PCA
Word 2 IND
word 3
PVA
word 4
CTW /
word 5
STW
MRV /
word 6
MAV
word 7 PCD 3
word 8 PCD 4
word 9 PCD 5
word 10 PCD 6
LEGEND
PPO → PARAMETER PROCESS DATA OBJECT
PCV → PARAMETER CHARACTERSTICS VALUE
PCA → PARAMETER CHARACTERSTICS(BYTE 1,2)
IND → SUBINDEX
PVA → PARAMETER VALUE
PCV
PCD
PPO TYPE 3
CTW /
word 5
STW
PCD
MRV /
word 6
MAV
EXPLANATION--> A PPO consist of parameter portion
(PCV/PKW) and process data portion (PCD/PZD). The PCV part
is used for reading and/or updating of parameters. It is futher
devided into PCA, IND and PVA.The PCA defines what you
would like to do with parameters. IND is only used for accessing
the arrayed parameters.The PVA holds the data you are writing
to a parameter or a data you are reading from the parameters.
The PCD portion consist of fixed part (4 bytes) and a
parameterizable part (8 or 16 bytes). The CTW and MRV are
transmitted to the frequency converter in the fixed portion,
whereas the STW and MAV are transmitted by the frequency
PCD → PROCESS DATA
STW → STATUS WORD(FromDrive)
CTW → CONTROL WORD (To drive)
converter.
In the parameterizable portion the user select which parameter
are to be transmitted to the frequency converter and which are to
be transmitted by the frequency converter
PPO TYPE 4
CTW /
word 5
STW
MRV /
word 6
MAV
word 7 PCD 3
word 8 PCD 4
word 9 PCD 5
word 10 PCD 6
PCD
MAV → MAIN ACTUAL VALUE (FREQUENCY FROM DRIVE)
→ MAIN REFERENCE VALUE (FREQUENCY TO DRIVE)
MRV
IN SIEMENS PCV IS EQUIVALENT TO PKW AND PCD EQUIVQLENT TO PZD.
e-mail:manmeetvirdi@gmail.com