Hazardous voltage.
Will cause death or serious injury.
Keep Out.
Qualied personnel only.
Disconnect and lock off all power before
working on this equipment.
• Only qualified licensed electricians should install or service SPDs
• Hazardous voltages exist within SPDs
• SPDs should never be installed or serviced when energized
• Use appropriate safety precautions including Personal Protection Equipment
• Failure to follow these instructions can result in death, serious injury, and/or equipment damage.
• This manual shall be read in entirety prior to installing
NOTICE
CONDUCTING DIELECTRIC AND/OR
HI-POTENTIAL TESTING WILL CAUSE
INTERNAL DAMAGE TO TPS3 UNIT.
Do not perform dielectric or high potential
tests with the TPS3 unit installed.
Bonding and Grounding Hazard
Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National
Electrical Code (NEC®) and all applicable codes.
Verify that the neutral terminal (XO) on the secondary side of distribution transformers are grounded to the system ground
in accordance with the NEC® and all applicable codes.
During installation into an electrical system the SPD must not be energized until the electrical system is completely installed,
inspected and tested. All conductors must be connected and functional including the neutral (if required). The voltage
rating of the SPD and system must be verified before energizing the SPD.
Failure to follow these guidelines can lead to abnormally high voltages at the SPD. This may cause the SPD to fail. The
warranty is voided if the SPD is incorrectly installed and/or if the neutral conductor in the service entrance equipment or
downstream of separately derived systems is not bonded to ground in accordance with the NEC®.
Do Not Hi-Pot Test SPDs
Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage such as
high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage
than their rated Maximum Continuous Operating Voltage (MCOV) must be conducted with the SPD disconnected from the
power source. For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing highpotential testing and then reconnected after test completion.
Failure to disconnect SPD and associated components during elevated voltage testing will damage the SPD and will void
the warranty.
Qualified Person ................................................................................................................................................................1
Do Not Hi-Pot Test SPDs .....................................................................................................................................................1
Voltage Rating ..................................................................................................................................................................2
General Information ..............................................................................................................4
Precautionary Statement Regarding SPDs on Ungrounded Systems ....................................................................................4
System Grounding.............................................................................................................................................................4
Dead Front Modification Instruction Changes for P1SPD ....................................................................................................4
P1 Dead Front Knockout Plate Removal Instructions ...........................................................................................................4
UL 1283 Required Language Concerning the Installation of EMI Filters .............................................................................10
W Option Suffix: .............................................................................................................................................................10
Troubleshooting & Service ...............................................................................................................................................12
Abnormal N-G Voltage Indicators .....................................................................................................................................12
Module Replacement & Service .......................................................................................................................................12
Technical Support ...........................................................................................................................................................12
Figures
Figure 1: SPD Types ..........................................................................................................................................................2
Figure 2: Dead Front Modification Instruction ...................................................................................................................4
Figure 4: 400/600 Amp S1/S2 and all SE Panels - TPS3 01 Unit with the NK Accessory Kit ..................................................6
Figure 5: 250 Amp Max Revised P1 Panels .........................................................................................................................7
Figure 6: SPD & Neutral Riser Connection Details for Revised P1 Panels .............................................................................8
Figure 7: P4, P5 and Front Connected Distribution Switchboards .......................................................................................9
Figure 8: Service Section Switchboards and Low Voltage Switchgear .................................................................................9
Figure 9: Installation in an MCC ......................................................................................................................................10
Table 1: Type Designations ...............................................................................................................................................2
Table 2: Model Number Decoder .......................................................................................................................................3
Table 3: Contents for Installation in Lighting Panelboards Type P1, P2, P3 ..........................................................................5
Table 4: Contents for Installation in 400/600 Amp S1/S2 and all SE Panels .........................................................................6
Table 5: Content for Installation in Lighting Panelboards Revised P1 ..................................................................................7
Introduction
Thank you for choosing Siemens TPS3 Surge Protective Device (SPD).
This is a high quality, high energy surge suppressor designed to protect
sensitive equipment from damaging transient overvoltages.
Proper installation is important to maximize performance. Please follow
the steps outlined herein.
These instructions do not purport to cover all details or variations in
equipment, nor to provide for every possible contingency to be met in
connection with installation, operation or maintenance. Should further
information be desired or should particular problems arise which are
not covered sufficiently for the purchaser’s purposes, the matter should
be referred to the local Siemens sales office.
Do Not Hi-Pot Test SPDs
This entire user manual should be read prior to beginning installation.
These instructions are not intended to replace national or local codes.
Follow all applicable electrical codes to ensure compliance. Installation
of this SPD should only be performed by qualified electrical personnel.
All Siemens SPDs are extensively tested in accordance with industry
standards such as ANSI/IEEE C62.41.1, C62.41.2, C62.45, C62.62,
C62.72, UL 1449, UL 1283, IEC 61643, etc.
Warning & Safety Information
This equipment contains hazardous voltages. Death, serious injury,
or property damage can result if safety instructions are not followed.
Only qualified personnel should work on or around this equipment
after becoming thoroughly familiar with all warnings, safety notices,
and maintenance procedures contained herein.
The successful and safe operation of this equipment is dependent upon
proper handling, installation, operation, and maintenance.
Qualified Person
For the purposes of this manual and product labels, a QUALIFIED
PERSON is one who is familiar with the installation, construction, and
operation of this equipment, and the hazards involved. In addition, he
or she has the following qualifications:
(a) Is trained and authorized to energize, deenergize, clear,
ground and tag circuits and equipment in accordance with
established safety practices.
(b) Is trained in the proper care and use of personal protective
equipment (PPE) such as rubber gloves, hard hat, safety
glasses or face shields, flash clothing, etc. in accordance with
established safety practices.
(c) Is trained in rendering first aid.
Any factory or on-site testing of power distribution equipment that
exceeds normal operating voltage such as high-potential insulation
testing, or any other tests where the suppression components
will be subjected to higher voltage than their rated Maximum
Continuous Operating Voltage (MCOV) must be conducted with
the SPD disconnected from the power source. For 4-wire systems,
the neutral connection at the SPD must also be disconnected prior
to performing high-potential testing and then reconnected after
test completion.
Failure to disconnect SPD and associated components during
elevated voltage testing will damage the SPD and will void the
warranty.
Limited Warranty
Siemens warrants its AC Panel protection products against defective
workmanship and materials for 10 years. Liability is limited to the repair
or replacement of the defective product at Siemens’ option. A Return
Material Authorization number (RA#) must be given by the company
prior to the return of any product. Returned products must be sent
to the factory with the transportation charges prepaid. In addition,
the company also warranties unlimited replacement of modular and
component parts within the warranty period previously described.
The company specifically disclaims all other warranties, expressed or
implied. Additionally, the company is not responsible for incidental or
consequential damages resulting from any defect in any product or
component thereof.
The sales contract contains the entire obligation of Siemens. This
instruction manual shall not become part of or modify any prior existing
agreement, commitment or relationship.
Unpacking & Preliminary Inspection
Danger
For the purposes of this manual and product labels, DANGER indicates
an imminently hazardous situation, which, if not avoided, will result
in death or serious injury.
Notice
For the purposes of this manual and product labels, NOTICE indicates
a potentially hazardous situation which, if not avoided, could result in
damage to the equipment but does not create a potential for personal
injury.
1
Inspect the entire shipping container for damage or signs of mishandling
before unpacking the unit. Remove the packing material and further
inspect the unit for any obvious shipping damages. If any damage was
found and is a result of shipping or handling, immediately file a claim
with the shipping company and forward a copy to your local Siemens
sales office.
Storage
The unit should be stored in a clean, dry environment. Storage
temperature is -55ºC (-67ºF) to +85ºC (+185ºF). Avoid exposing the
unit to areas of high condensation. All of the packaging materials
should be left intact until the unit is ready for installation. If the unit
has been stored for an extended period of time, it may be necessary
to clean the unit and make a complete inspection of the unit prior to
installing and placing into service.
Industry Standards Changes - 2009
Siemens TPS3 SPDs have the following Type designations
UL 1449 Third Edition and 2008 NEC® Article 285 generated substantial
changes.
• The term TVSS changed to SPD
• Types 1, 2, 3 & 4 SPDs are created
• UL 1449 clamping voltage performance testing changed from
500A to 3,000A
• UL 1449 added new Nominal Discharge Current testing (I nominal,
or In), which consists of more rigorous duty-cycle testing
The SPD Type category is important to understand before installing
any SPD. Type 1 and 2 SPDs are fully UL Listed devices whereas Type
4 SPDs are UL Recognized devices.
Type 1 – Installed on line or load side of the Main Overcurrent Protection
(OCP), similar to obsolete products known as Secondary Surge Arrestors,
except now includes rigorous safety testing. Includes all OCP & safety
disconnectors inside the SPD.
Type 2 – Installed on load side of the Main OCP, similar to previous
products known as TVSS. May or may not require external OCP.
Type 3 – Point of Utilization, direct plug in type devices, surge strips,
etc. Theses devices are intended for installation 10 meters from the
panel (rationale based on IEEE Cat. A location).
Type 4 – Surge suppression components, could be a basic component
or a complete module. Type 4 components can be tested for Type 1,
Type 2 or Type 3 applications.
Figure 1: SPD Types
NEC® Art 285 & UL 1449-3
SPD Types: Types 1, 2, 3, & 4
Based on Location within electrical distribution system
(also coincides with ANSI / IEEE C62.41.2 - 2002 Categories C, B & A)
Table 1: Type Designations
SIEMENS TPS3 SERIESTYPE RATING
TPS3 01 & L1Type 1 Component Assembly
TPS3 02 & L2Type 1 Component Assembly
TPS3 05 & L5Type 1
TPS3 06 & L6Type 1 Component Assembly
For further information, please review latest editions of NEC® Art. 285,
UL 1449, contact your local Siemens sales office or contact Siemens
TPS Tech Support at (888) 333-3545.
Equipment Performance
As SPDs sense overvoltage, they create a momentary internal short
circuit, thereby redirecting harmful surge energy to earth ground.
SPDs are capable of repeating this function repeatedly. For optimum
protection, staged surge suppression should be implemented at the
service entrance and all other distribution or panelboard locations
feeding sensitive equipment.
Voltage Rating
Prior to installing the TPS3 SPD, verify that the unit has the correct
voltage rating for the equipment installed by checking the nameplates
of both the equipment and TPS3 module. The service type should
match the intended power source. See Table 2 on the following page
for voltage applications.
2
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.