Siemens TC100 User Manual

Operating Instructions 11/2012
SICLOCK TC100
Plant Central Clock
SICLOCK
s
s
Preface, Table of Contents
Safety instructions
SICLOCK® TC100 Plant Central Clock
Operating Instructions
Description
Hardware description
Operation planning
Mounting
Connection
Configuration Tool
Parameter assignment
Parameter assignment and operation of the device
Parameter table
Service and maintenance
Messages
Technical data
Dimension drawing
Circuit diagrams
Spare parts / accessories
Annex
ESD guidelines
List of icons
Glossary, Index
11/2012
A2B00094941-02

Safety notices

This manual contains information that must be observed to ensure your personal safety and to prevent property damage. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring to property damage only, have no safety alert symbol. Depending on the hazard level, warnings are displayed in descending order as follows:.
Danger
indicates that death or serious injury will result if proper precautions are not taken.
Warning
indicates that death or serious injury may result if proper precautions are not taken.
Caution
with a warning triangle indicates that minor personal injury can result if proper precautions are not taken.
Caution
without a warning triangle means that material damage can occur if the appropriate precautions are not aken.
Notice
means an undesirable result or state can occur if the corresponding instruction is not followed.
In the event of a number of levels of danger prevailing simultaneously, the warning corresponding to the highest level of danger is always used. A warning with a warning triangle indicating risk of physical injury may also include a warning of the risk of damage to property.
Qualified personnel
The associated device/system may only be installed and used in conjunction with this documentation. Only qualified personnel should be allowed to commission and operate the device/system. For the pur­pose of the safety information in this documentation, a “qualified person” is someone who is authorized to energize, ground, and tag equipment, systems, and circuits in accordance with established safety procedures.
Intended use
Please note the following:
Warning
This equipment is only allowed to be used for the applications described in the catalog and in the technical description, and only in conjunction with non-Siemens equipment and components recommended by Siemens. Correct transport, storage, installation and assembly, as well as careful operation and maintenance, are required to ensure that the product operates sa
Registered Trademarks
All designations with the trademark symbol ® are registered trademarks of Siemens AG. Other designa­tions in this documentation may be trademarks whose use by third parties for their own purposes can vio­late the rights of the owner.
Disclaimer of liability
We have checked that the contents of this publication agree with the hardware and software described here. Nevertheless, we cannot assume responsibility for any deviations that may arise. The information given in this publication is reviewed at regular intervals and any corrections that might be necessary are made in the subsequent editions.
fely and without faults.
Siemens AG I IA CE EDM Frauenauracher Strasse 98 D-91056 Erlangen Germany
© Siemens AG 2010 Technical data subject to change.

Preface

This document contains the information required for operating and assigning parameters to the SICLOCK TC100 central plant clock.
Area of application
This manual is valid for the SICLOCK and processor version V1.0 in conjunction with the SICLOCK TC100 Configuration Tool version 1.0 or higher.
Recycling and disposal
Die The SICLOCK TC100 is low in contaminants and can therefore be recycled. For ecologically compatible recycling and disposal of your old device, contact a certificated disposal service for electronic scrap.
Technical Assistance
®
TC100 product with firmware version V1.0
If you have Phone:
any technical questions, please contact Technical Assistance:
+49 (911) 895-59 00 Monday to Friday, 8 am – 5 pm CET
Fax:
E-Mail:
+49 (911) 895-59 07
siclock@siemens.com
The latest information on SICLOCK products, product support and FAQs can be found on the Internet:
http://www.siemens.de/siclock (German)
http://www.siemens.com/siclock (international)
SICLOCK
®
TC100 Operating Instructions
Preface-3© Siemens AG 2010 All Rights Reserved
Preface
Preface-4
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Table of Contents

Preface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preface-3
1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
2.1 Layout of the SICLOCK TC100 hardware . . . . . . . . . . . . . . . . . . . . 2-12
2.2 External synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
2.3 Time receivers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
2.3.1 Plant synchronization via Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
2.4 Time management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
2.5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
2.6 Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
3 Hardware description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
3.1 Exterior design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
3.2 Connection elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
3.3 Operator controls and displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-19
3.4 Scope of supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
4 Operation planning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
4.1 Overview of operation planning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
4.2 Transport / storage conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
4.3 Unpacking and checking the delivery . . . . . . . . . . . . . . . . . . . . . . . . 4-26
4.4 Mounting position and fastening . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27
4.4.1 Installation guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27
4.4.2 Permissible mounting position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28
4.4.3 Type of fixation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28
5 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
5.1 Overview of mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
6 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-31
6.1 Overview of connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-31
6.2 Connecting the power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-32
SICLOCK
®
TC100 Operating Instructions
Contents-5© Siemens AG 2010 All Rights Reserved
Table of Contents
6.3 Connecting external synchronization . . . . . . . . . . . . . . . . . . . . . . . . 6-33
6.3.1 SICLOCK GPS1000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-35
6.3.2 SICLOCK DCFRS Industrial version . . . . . . . . . . . . . . . . . . . . . . . . . 6-36
6.3.3 SICLOCK GPSDEC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-37
6.3.4 Third-party systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-38
6.4 Connecting alarm and warning outputs. . . . . . . . . . . . . . . . . . . . . . . 6-39
7 Configuration Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-41
7.1 Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-44
7.2 General functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-46
7.2.1 Connect / disconnect online connection . . . . . . . . . . . . . . . . . . . . . . 7-47
7.2.2 Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-48
7.3 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-49
7.3.1 Sorting Parameter tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-53
7.3.2 Hiding / showing Parameter table entries . . . . . . . . . . . . . . . . . . . . . 7-53
7.3.3 Editing parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-54
7.3.4 Reading / writing parameters, setting to factory defaults . . . . . . . . . 7-56
7.4 Archive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-57
7.4.1 Sorting the Archive table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-60
7.4.2 Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-61
7.5 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-62
8 Parameter assignment and operation of the device . . . . . . . . . . . . . . . . . 8-65
8.1 Status display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-66
8.2 Operation and parameter assignment. . . . . . . . . . . . . . . . . . . . . . . . 8-68
8.2.1 One-button operation with the MODE button . . . . . . . . . . . . . . . . . . 8-68
8.2.2 Network settings on the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-70
8.2.3 Readout versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-71
9 Parameter assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-73
9.1 Connecting external synchronization . . . . . . . . . . . . . . . . . . . . . . . . 9-74
9.1.1 Radio clocks via terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-74
9.1.2 Operation as NTP client . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-75
9.1.3 Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-75
9.2 Connecting time receivers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-76
9.2.1 NTP server service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-76
9.2.2 SIMATIC mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-77
9.3 General settings on the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-78
9.3.1 Time management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-78
9.3.2 Synchronization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-79
9.3.3 Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-80
9.3.4 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-80
9.3.5 Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-81
9.3.6 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-81
10 Parameter table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-83
Contents-6
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Table of Contents
11 Service and maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-89
11.1 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-89
11.2 Restoring factory defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-89
11.3 Software update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-90
12 Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-91
13 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-95
14 Dimension drawing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-99
15 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-101
15.1 Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-101
16 Spare parts / accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-103
AAnnex. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-105
A.1 Directives and declarations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-105
A.2 Certificates and approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-106
B ESD guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-107
B.1 Electrostatic sensitive devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-107
B.2 Electrostatic charging of persons . . . . . . . . . . . . . . . . . . . . . . . . . . . B-108
B.3 Fundamental measures to protect against static discharge . . . . . . . B-109
C List of icons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-111
D Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-113
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index-119
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
Contents-7
Table of Contents
Contents-8
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Safety instructions 1

Caution
Please observe the safety instructions on the back of the cover sheet of this docu­mentation. You should not expand your device unless you have read the relevant safety instructions.
If you have questions about the validity of the installation in the planned environ­ment, please contact your service representative.
Repairs
Only authorized personnel are permitted to repair the device.
Warning
Unauthorized opening and improper repairs can cause considerable damage to property or danger for the user.
System expansions
Only install system expansion devices designed for this device. The installation of other expansions can damage the system and violate the radio-interference suppression regulations.
Contact your technical support team or where you purchased your PC to find out which system expansion devices may safely be installed.
Caution
If you install or exchange system expansions and damage your device, the war­ranty becomes void.
SICLOCK
®
TC100 Operating Instructions
1-9© Siemens AG 2010 All Rights Reserved
Sicherheitshinweise
Safety information
Siemens offers IT security mechanisms for its automation and drive product po folio in order to support the safe operation of the plant/machine. Our products are also continuously developed further with regard to IT security. We therefore recommend that you keep yourself informed about updates and upgrades for our products and always use the latest version of each product. For information on this topic, refer to: Industry Online Support (http://www.siemens.com/automa­tion/csi_de_WW). You can register for a product-specific newsletter here.
For the safe operation of a plant/machine, however, it is also necessary to integ­rate the automation components into an overall IT security concept for the entire plant/machine which corresponds to state-of-the-art IT technology. You can find information on this at: Industrial Security (http://www.siemens.com/industrialse­curity).
Products used from other manufacturers should also be taken into account here.
Network security
In order to protect the entire plant from attack ding measures must be taken.
Caution
Failures or damage to your overall system
Unauthorized persons can gain entry into your network via the Ethernet ports and make changes to the SICLOCK TC100 parameterization. This can result in the time being adjusted. Individual or even all clients to be synchronized can be remo­ved from the synchronization cycle. This has the potential to cause failures or damage throughout the plant.
s on network security, corres
rt-
pon-
Please adhere to the following safety measures:
Ensure that your network is protected against unauthorized access by instal-
ling a firewall at all Ethernet ports.
Change the default password immediately after commissioning.
Limit the number of people to whom this password is known to the absolute
minimum.
Change the password regularly.
1-10
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Battery
Safety Information
This device is fitted with a Lithium battery. Batteries may only be replaced by qualified personnel. See Battery (Chapter 11.1).
Caution
There is the risk of an explosion if the battery is not replaced as directed. Replace only with the same type or with an equivalent type recommended by the manu­facturer. Dispose of used batteries in accordance with local regulations.
Warning
Risk of explosion and release of harmful substances!
For this reason, do not throw lithium batteries into open fires, do not solder on the cell body, do not open, do not short circuit, do not reverse polarity, do not heat above 100°C, dispose of correctly, and protect against direct sunlight, dampness and dew.
EGB directives
Modules containing electrostatic sensitive devices (ESDs) can be identified by the following label:
Strictly follow the guidelines mentioned below when handling modules which are sensitive to ESD:
Before working with modules with ESDs, you must discharge all your personal static
(e.g. by touching a grounded object).
All devices and tools must be free of static charge.
Always pull the mains connector before you install or remove modules which
are sensitive to ESD.
Handle modules fitted with ESDs by their edges only.
Do not touch any pins.
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100
1-11
Safety Information
1-12
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Description 2

Modern automation systems are made up of a multitude of computers, controllers and systems, that exchange data with one another. In order to operate such sys­tems in real time, it is absolutely essential to synchronize the clock times of all the components involved. This particularly applies to error tracing if event messages are time stamped, and cause and effect have to be identified by a reliable chro­nological order.
As a central plant clock, SICLOCK TC100 supplies the various plant components with a precise, reliable clock time, which is usually obtained from one or more external synchronizations with official or statutory times of day, usually GPS or DCF77 radio clocks.
SICLOCK TC100 distributes the time solely via Ethernet.
Note
Use one single device as the central clock for the whole plant, which supplies the clock time to all the other devices.
Exception: Redundant operation of the central plant clock
SICLOCK
®
TC100 Operating Instructions
2-1© Siemens AG 2010 All Rights Reserved
Description

2.1 Layout of the SICLOCK TC100 hardware

The following diagram shows an application example of a SICLOCK TC100, with a SICLOCK GPS1000 as the radio clock and an NTP server as an additional external synchronization.
Figure 2-1 Application Example
2-1
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

2.2 External synchronization

SICLOCK TC100 can be externally synchronized to the applicable, statutory nati­onal time or GMT in order to automate or minimize manual interventions, such as daylight saving time changes and leap seconds.
External synchronizations can be GPS or DCF77 radio clocks, servers (e.g. the time signal from an NTP server), SICLOCK TC400 devices, SICLOCK TC100 devices or other signal sources. They are connected to the RADIO CLOCK of the device.
The Ethernet port supports NTP servers as external synchronizations.
Possible RADIO CLOCKS are:
SICLOCK GPS1000
SICLOCK GPSDEC
(SICLOCK GPSDEC has been discontinued, please use SICLOCK GPS1000)
LOCK DCFRS
SIC
Third-party products can be connected passively via TTY. The following protocols are supported:
Description
Demodulated DCF77
Serial:
Meinberg format (time-zone dependent)
Meinberg format (time-zone independent)
NMEA (0183/ZDA)
Get more information
Connecting external synchronization (Chapter 9.1)
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
2-1
Description

2.3 Time receivers

The time receivers in the plant are connected solely via Ethernet.

2.3.1 Plant synchronization via Ethernet

Physical access
An Ethernet port with the following specification is provided to enable physical access to the network:
100Base-TX via RJ-45 socket
Protocols
The following protocols are implemented:
NTP server according to RFC2030
Any/unicast mode
Any/unicast mode with local time
Multicast mode
Multicast mode with local time
Time synchronization in the SIMATIC procedure
PCS7-compatible mode
S5-compatible mode
Thetime message frames can be transmitted to each Ethernet port individu­ally either every second or every 10 seconds.
2-1
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

2.4 Time management

The SICLOCK TC100 has a range of functions for generating the valid plant time from the external synchronization. This includes the option of setting times zones and the parameterizable generation of daylight saving.
Time security through protected synchronization
If a discontinuity of longer than five seconds occurs in the external synchroniza­tion, the protected synchronization is activated, and the synchronization is not executed for safety reasons.
Time security through microstep mode
A time difference between the external synchronization and the device, such as can occur as the result of a brief loss of loss of radio contact or switching to a sub­stitute synchronization, is run down automatically in microstep mode that is imper­ceptible to the operation of the plant. No time jump occurs.
Description
More detailed information and the options for parameter assignment for protected synchronization and microstep mode are described in the chapter
Synchronization (Chapter 9.3.2).
Note
Parameterize the plant time at one single point within the synchronization hierar­chy, ideally on the central plant clock.

2.5 Commissioning

Commissioning can be subdivided into the following steps:
1. Mounting (Chapter 5)
2. Connection (Chapter 6)
3. Assignment of an IP address to the device
Parameter assignment and operation of the device (Chapter 8)
4. Parameter assignment (Chapter 9)
With few exceptions, the settings are made with the Configuration Tool, see Configuration Tool (Chapter 7).
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
2-1
Description

2.6 Redundancy

Redundant external synchronization
Up to four time servers can be run on the SICLOCK TC100 for external synchro­nization via NTP. However, they must all be in the same IP network.
Radio clocks cannot be connected redundantly to a SICLOCK TC100.
The order of priority among the external synchronizations (radio clock or NTP ser­ver), and thus the redundancy behavior, can be set with parameters, see
Redundancy (Chapter 9.1.3).
Redundant SICLOCK TC100 central plant clocks
A number of SICLOCK TC100s can be run as redundant time servers in a single network.
You will find more detailed information in the chapters Configuration Tool (Chapter 7) and Parameter table (Chapter 10).
You can find more information on redundancy in „Application Note 01
08“ on http://www.siemens.com/siclock under "FAQ".
2-1
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Hardware description 3

The layout of the hardware, together with the connectors, operator controls and displays are described in this chapter.

3.1 Exterior design

The display and operator controls together with the connectors on the SICLOCK TC100 are shown in the following figures.
Figure 3-1 Perspective view of the SICLOCK TC100 showing the front panel and ventilation grille
(1) Panel with operator and display controls
(2) Ventilation grille
SICLOCK
®
TC100 Operating Instructions
3-1© Siemens AG 2010 All Rights Reserved
Hardware description

3.2 Connection elements

The following figure shows the connectors on the SICLOCK TC100.
Figure 3-2 SICLOCK TC100 - layout of connectors
(1) Terminal X1 - 24V supply voltage
(2) Terminal X2 - connecting terminal for radio clocks, outputs and alarm
See also Terminal assignment (Chapter 15.1).
(3) Ethernet port
3-
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

3.3 Operator controls and displays

The display and LEDs on the front panel show the current operating state. The keypad can be used for the basic operation of the device. A Web-based Configu­ration Tool is available for more extensive configuration options, see Configuration Tool (Chapter 7).
Hardware description
Figure 3-3 SICLOCK TC100 front view
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
3-
Hardware description
Table 3-1 Meanings of the displays and operator controls
Name Color (LED) Meaning
Displays
POWER Green Operational readiness
SYNC Green SICLOCK TC100 is externally synchronized.
FAULT Red Alarm
The associated message text is shown in the display.
Flashing red Warning
The associated message text is shown in the display.
LINK Green The physical connection has been made, transmission and
reception are possible.
ACTIVE Green Display of the data traffic for the particular port
RADIO CLOCK Yellow Incoming signal from the radio clock
Display Display of the time, date and synchronization, or message
text in the case of an error
Operator controls
MODE Call and edit the basic parameter list
Acknowledge messages
For more detailed information see Parameter assignment and operation of the device
(Chapter 8)
.
3-2
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

3.4 Scope of supply

Table 3-2 Scope of supply of the individual versions of the device
2XV9450-2AR22
Hardware description
SICLOCK TC100 single device with terminal strips connecte
d to X1 and X2
2XV9450-2AR50 (SICLOCK TC100 GPS1000 package)
SICLOCK TC100 single devi
ce with terminal strips connected to X1 and X2
SICLOCK GPS1000 radio clock with mounting frame and lightning protection
2XV9450-2AR26 (SICLOCK TC100 DCF77 package)
SICLOCK TC100 single device with terminal strips connected to X1 and X2
SICLOCK DCFRS industrial version of the radio clock, complete with mounting frame
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
3-2
Hardware description
3-2
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Operation planning 4

4.1 Overview of operation planning

SICLOCK TC100 is designed for stationary use in weather-proof locations in an industrial environment.
The operating conditions surpass the requirements of DIN IEC 60721-3-3.
Class 3M3 (mechanical requirements)
Class 3K3 (climatic requirements)
General notes on operation
Caution
The device is approved for operation in closed rooms only. The guarantee is void if this stipulation is ignored.
Condensation
When transporting the device at low temperatures, ensure that no moisture gets on or into the device. This also applies if the device is subjected to extreme chan­ges in temperature.
Commissioning
Allow the device to slowly adjust to room temperature before commissioning the device. However, do not expose the device to direct heat radiation. In the event of greater temperature differences, harmful condensation can be avoided by lea­ving the device in its transport packaging.
If condensation develops, wait 12 hours before you switch on the device (for a temperature difference of 20°C). For greater temperature differences, the waiting time is correspondingly longer.
Avoid extreme ambient conditions. Protect your device against dust, moisture and heat. Refer to Technical data (Chapter 13).
Do not place the device in direct sunlight.
SICLOCK
®
TC100 Operating Instructions
4-2© Siemens AG 2010 All Rights Reserved
Operation planning
Use in residential areas, and operation in the public network
If you use the SICLOCK TC100 in residential areas or in the public network, you must ensure that it complies with the limit value class B according to EN 55022 with regard to the emission of radio interference.
Note
This is a Class A system. The equipment may cause RF interference in residential areas or the public network. In this case, the operating company may be required to take appropriate measures.
The following measures are recommended to ensure the interference complies with limit value class B:
Install the SICLOCK TC100 in grounded control cabinets / control boxes
Use filters in the supply lines
Usage with additional measures
SICLOCK TC100 must not be used in the following exemplary cases without additional measures:
At locations with a high level of ionizing radiation
In aggressive environments caused, for example, by
The development of dust
Corrosive vapors or gases
Strong electric or magnetic fields
Damp and wet rooms
Severe oscillations, shocks, vibrations
High levels of radiant heat
In systems that require special monitoring, such as.
Elevators
Electrical plants in potentially hazardous areas
One additional measure could be to install the SICLOCK TC100 in a cabinet or housing.
4-2
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

4.2 Transport / storage conditions

Despite the device's rugged design, its internal components are sensitive to severe vibrations and shock. You must therefore protect the device from severe mechanical stresses.
You should always use the original packaging for shipping and transporting the device.
Unpack the device at its installation location.
Do not transport the device when it is mounted.
Follow the instructions for temporary storage under Battery (Chapter 11.1) in Service and maintenance.
The following information applies to modules transported or stored in their original packaging.
The ambient conditions for transport comply with IEC 60721-3-2, class 2K4.
The mechanical environmental conditions for transport comply with IEC 60721-3-2, class 2M2.
Operation planning
Caution
Risk of damage to the device!
If the device is transported in extreme weather conditions with large fluctuations in temperature, care must be taken to ensure that no moisture forms on or in the device (condensation).
If you notice any condensation, wait around 12 hours before switching on the device.
Notice
Adhere to these stipulations each time the device is transported, otherwise the guarantee is void.
Table 4-1 Shipping and storage conditions
Type of condition Permissible range
Free fall (in transport packaging)
Temperature
Atmospheric pressure
Maximum rate of temperature
<= 1 m
-40 °C to +70 °C
From 1080 to 660 hPa (corresponds to an altitude from -1000 to 3500m)
20 °C/h
change
Relative humidity
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
10 to 95 % (at 25°C without condensation)
4-2
Operation planning

4.3 Unpacking and checking the delivery

The device is completely assembled, tested and packed in the factory, and has no internal transport locks.
If there are large temperature differences between the means of transport and the unpacking site, we recommend leaving the device in its transport packaging to avoid harmful condensation.
Procedure
Please check the packaging material for transport damage upon delivery.
If any transport damage is present at the time of delivery, lodge a complaint
with the responsible shipping company. Have the shipper confirm the trans­port damage immediately.
Unpack the device.
Keep the packaging material in case you have to transport the device again.
Notice
The packaging protects the device during transport and storage. Transport the device only in its original packaging!
Please keep the accompanying documentation in a safe place. You will need
the documentation when you start up the device for the first time.
Check the package contents for completeness and any visible transport
damage. Check for completeness using the enclosed "Contents of Delivery" list.
Notify the responsible delivery service immediately if the packages contents
are incomplete or damaged.
Warning
Ensure that a damaged device is neither inadvertently installed nor brought into operation.
4-2
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

4.4 Mounting position and fastening

4.4.1 Installation guidelines

Before installing the device, read the following general notes relating to installation.
Warning
Danger, high voltage!
Disconnect the power supply from the control cabinet before opening it. Ensure that the power to the control cabinet cannot be switched on accidentally.
Locate the device / display in an ergonomically advantageous position for the
user. Choose a suitable installation height.
Operation planning
Position the device / display so that it is not exposed to direct sunlight or other
strong sources of light.
Ensure that there is adequate free space in the control cabinet for air circula-
tion and heat transport. Maintain a clearance of 100mm above and below the device. Connection cables increase these clearances correspondingly.
Install the device in a position that does not block the air vents in the housing.
Also provide enough free space to be able to remove the device.
Fit struts in the control cabinet to stabilize the mounting cut-out. Install struts
where necessary.
Install the device in such a way that it cannot pose any danger by, for example,
falling out.
During assembly, please comply with the approved installation positions.
See Dimension drawing (Chapter 14).
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
4-2
Operation planning

4.4.2 Permissible mounting position

Only a horizontal mounting position is permitted, that is the display is read from a horizontal viewing direction. The ventilation is inadequate in all other mounting positions.
Figure 4-1 Horizontal mounting position

4.4.3 Type of fixation

The housing can be fixated by snap-on mounting to a standard mounting rail or to a SIMATIC S5 DIN rail.
See Overview of mounting (Chapter 5.1).
4-
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Mounting 5

5.1 Overview of mounting

Figure 5-1 SICLOCK TC100 - view of mounting
SICLOCK TC100 must be mounted in an easily accessible position in the control cabinet.
The housing can be fixated by snap-on mounting to a standard mounting rail (EN 50022-35) or to a SIMATIC S5 DIN rail (6ES5 710-8maxx).
A clearance of 100mm must be maintained above the device so that it can be hooked in and out, and to facilitate unimpeded heat dissipation.
A clearance of at least 100mm must be maintained under the device for the pro­cess signal plug.
We recommend mounting a suitable cable channel below this clearance.
Note
Ensure that the snap-on mounting is locked correctly.
See also Dimension drawing (Chapter 14).
SICLOCK
®
TC100 Operating Instructions
5-© Siemens AG 2010 All Rights Reserved
Mounting
5-3
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Connection 6

6.1 Overview of connection

Notice
Only connect peripheral devices suitable for an industrial environment.
Caution
Strictly adhere
Ensure that the installation complies with the following conditions:
The device may only be connected to 24 VDC power supply systems which
meet the requirements of a safe extra-low voltage with protective separation according to SELV. The conductor cross-section selected must be large enough so that if there is a short circuit in the SICLOCK TC100 no damage can be caused by an overheated cable. For the conductor cross-section, see Connecting the power supply (Chapter 6.2).
Avoid extreme ambient conditions as far as possible.
Protect the device against dust, moisture, heat and severe vibrations.
Do not place the device in direct sunlight.
Install the device in such a way that it cannot pose any danger, for example by
falling down.
Do not cover the ventilation slots
Permissible mounting position (Chapter 4.4.2).
to the specifications for peripheral equipment.
SICLOCK
®
TC100 Operating Instructions
6-3© Siemens AG 2010 All Rights Reserved
Connection

6.2 Connecting the power supply

The power supply is connected to terminal strip X1, and muss pass through a slow-blow 1A fuse. The device does not have a power switch.
Figure 6-1 Connecting the power supply
Note before connecting the device
Warning
The device may only be connected to 24 VDC power supply systems which meet the requirements of a safe extra-low voltage with protective separation (SELV); a protective conductor must also be connected. The conductors must be able to withstand the short-circuit current of the 24 VDC power supply, so that a short cir­cuit will not damage the cable. Only cables with a cross-section between a mini­mum of 0.25 mm
2
connected.
Notice
The 24 VDC power supply must match the input specification of the device
Technical data (Chapter 13).
Caution
Ensure that the functional grounding is connected correctly.
It is essential to ensure the correct polarity with direct current.
Functional check
(AWG23) and a maximum of 2.50 mm2(AWG13) may be
6-3
After switching on, the POWER LED must light up green.
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

6.3 Connecting external synchronization

The signal from the connected radio clock is automatically detected, and dis­played in the parameter /Inputs/Input 1/Status (0.20.02)
Connection
.
Figure 6-2 Circuit diagrams for a passive and an active radio clock
Table 6-1 Terminal assignment of radio clock inputs
Terminal Description
X2-1 RADIO CLOCK GND
X2-2 RADIO CLOCK 1A
X2-3 RADIO CLOCK 1B
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
6-3
Connection
Functional check
The incoming signal of the radio clock is indicated on the front panel by the "RADIO CLOCK" LED.
The status of the radio clock is displayed in the parameter /Inputs/Input 1/Status (0.20.02)
Possible states:
GPS (SICLOCK GPS1000 and SICLOCK GPSDEC)
GPS (disturbed)
DCF77 (SICLOCK DCFRS and SICLOCK GPSDEC)
DCF77 (disturbed)
Serial
.
The signal reception is temporarily disturbed.
The signal reception is temporarily disturbed.
Meinberg
Meinberg format being received
NMEA
NMEA format being received
Telegram (disturbed)
Error detected in telegram or loss of telegram
No signal
The connection of individual sources of external synchronization is described in the following.
6-3
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

6.3.1 SICLOCK GPS1000

The GPS receiver GPS1000 is connected according to Figure 6-3.
;
5$',2&/2&.*1'
5$',2&/2&.$
5$',2&/2&.%
Connection
/LJKWQLQJSURWHFWLRQ
PD[P
Figure 6-3 Connection of the radio clock SICLOCK GPS1000 to RADIO CLOCK 1
We recommend using a two-wire, shielded cable, e.g. LiYCY 2x1 mm² as the radio clock cable. One end of the cable shielding must be connected to a suitable point at the place of installation.
No further assignment of parameters to the GPS1000 is required.
Warning
Provide lightning protection for the GPS aerial in outdoor areas.
Functional check
The "RADIO CLOCK" LED on the front panel must flash at about 1Hz when the GPS1000 is received correctly.
The parameter /Inputs/Input 1/Status (0.20.02) three minutes reception.
must change to "GPS" after about
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
6-3
Connection

6.3.2 SICLOCK DCFRS Industrial version

The industrial version of the SICLOCK DCFRS radio clock included in the DCF77 package is connected as shown in Figure 6-4. In this case the polarity is irrele­vant.
PD[P
;
5$',2&/2&.*1'
5$',2&/2&.$ 5$',2&/2&.%
Figure 6-4 Connection of the radio clock SICLOCK DCFRS industrial version to
Warning
When used outdoors, a lightning conductor must also be installed.
Note
One end of the shielding of the radio clock cable must be connected to a suitable point at the place of installation.
Functional check
The "RADIO CLOCK" LED on the front panel must flash at about 1Hz when the SICLOCK DCFRS is received correctly.
The parameter /Inputs/Input 1/Status (0.20.02) about three minutes reception.
Note
If possible select a location for the aerial where there is no electromagnetic inter­ference on the DCF77 carrier frequency, because this is crucial for the quality of reception. Do not mount the aerial anywhere near electric drives, neon tubes, monitors or other emitters of interference.
RADIO CLOCK 1
must change to "DCF77" after
6-3
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

6.3.3 SICLOCK GPSDEC

(SICLOCK GPSDEC has been discontinued, please use SICLOCK GPS1000)
A SICLOCK GPSDEC decoder is connected as shown in Figure 6-5.
;
5$',2&/2&.*1'
5$',2&/2&.$
5$',2&/2&.%
Connection
'&)77<

PD[P
Figure 6-5 Connection of the radio clock SICLOCK GPSDEC to RADIO CLOCK 1
Caution
A SICLOCK GPSDEC may only be operated as an active radio clock.
Operation as a passive radio clock leads to the destruction of the SICLOCK GPSDEC.
Table 6-2 Recommended assignment of parameters to the GPSDEC decoder for
Functional check
The "RADIO CLOCK" LED on the front panel must flash at about 1Hz when the GPSDEC is received correctly.
The parameter /Inputs/Input 1/Status (0.20.02) after about three minutes reception.
synchronizing a SICLOCK TC100
Parameter Setting
Time difference from GMT 00:00
Daylight saving time change „none“
X1.5-8 (DCF77TTY) „DCF without ZZB“
must change to "GPS" or "DCF77"
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
6-3
Connection

6.3.4 Third-party systems

Third-party systems can also be used for external synchronization of the SICLOCK TC100 if the following conditions are fulfilled.
Prerequisites
Active radio clock signal with 20mA rated current
Supported signals:
Demodulated DCF77
Serial:
Meinberg format (time-zone dependent), Meinberg format (time-zone independent), NMEA (0183/ZDA)
Functional check
The parameter /Inputs/Input 1/Status (0.20.02)
must change to "Meinberg",
"NMEA" or "DCF77" after about three minutes reception.
6-
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

6.4 Connecting alarm and warning outputs

During operation, the SICLOCK TC100 automatically carries out a range of func­tion tests. If an error occurs, the device generates corresponding messages on the display. A distinction is made between alarms and warnings.
There is an alarm output and a warning output for external monitoring on terminal X2.
;
;
;
Figure 6-6 Alarm output X2-7 and warning output X2-8
Table 6-3 Parameters affecting the alarm behavior
/Synchronization/Extended/Monitoring/Monitor Synchronization Status (0.09.14)
Connection
/Network Settings/Ethernet 1/Extended Settings Adapter 1/Monitor Link Status (0.05.09)
/NTP Client/Monitoring/Monitor Server (0.18.04)
/Environment/Extended/Temperature/Monitoring (0.24.01)
Example:
Set the alarm output if there is no external synchronization.
Use the Configuration Tool to set the parameter entry /Synchronisation/Exen­ded/Monitoring/Monitor Synchronization Status (0.09.14) = "Alarm" to activate monitoring / alarm output in case of error.
Note
The contacts are designed as wire-break-proof, normally closed contacts. If there is an alarm or warning, the corresponding contact opens.
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
6-
Connection
6-4
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Configuration Tool 7

The SICLOCK TC100 Configuration Tool is available to make it easier to assign parameters and configure the SICLOCK TC100. The tool can be called from an Internet browser as a Web interface.
With the Configuration Tool you can, among other things, view and change para­meters online and offline, view archives, search them with specific filter criteria, and load, backup and change the parameter assignments of the SICLOCK TC100 device.
Figure 7-1 SICLOCK TC100 Configuration Tool
(1) Toolbar of the Configuration Tool
(2) Working area of the Configuration Tool
You can make settings and assign parameters in the Parameter tab, and check and search for events in the Archive tab.
SICLOCK
®
TC100 Operating Instructions
7-4©Siemens AG 2010 All Rights Reserved
Configuration Tool
Preconditions
PC
Minimum screen resolution of 1280x1024
Java Runtime of at least V1.4.0 or higher
Web browser, e.g. Microsoft Internet Explorer
Connection with the Ethernet port on the device
SICLOCK TC100
Assignment of an IP address to the device
A valid IP address must be assigned to the Ethernet port of the device. The device is supplied with the address 192.168.1.10 and subnet mask
255.255.255.0. See also Network settings on the device (Chapter 8.2.2).
The PC and device must be in the same subnetwork.
Parameters, entries and lists
A parameter is defined as a group of related values. Each of these values is ter­med an entry in its parameter.
Similar parameters can form a list. Such lists are indicated by [ ].
Notice
Entries can be individually edited, but not individually read or written. A parameter is always read or written with all its entries. If it is a list, the complete list is read or written.
Parameters are identified by their unique parameter number. The parameter number always has three parts, e.g. 0.05.12. Example: parameter /Display/Display (0.10.01)
with the entries "Language" and
"Time":
7-4
Figure 7-2 Parameter display
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Working with the Configuration Tool
How to start the Configuration Tool:
1. Open the Web browser
2. Enter the address of the device port, e.g. 192.168.1.10
3. If necessary, confirm the installation and execution of the applet with "Yes" and/or "Always".
−> The Configuration Tool is started and displayed in the browser.
Note
Take note of the information in your browser concerning restrictions as a result of high security settings.
How to assign parameters to the SICLOCK TC100 with the Configuration Tool:
1. Connect the Configuration Tool to the SICLOCK TC100 with the button
Configuration Tool
2. In the case of a new assignment of parameters to the device, load the para­meters into the Configuration Tool with the button, or open an existing parameter file (*.u600) with the button .
3. Assign parameters to the SICLOCK TC100 according to your hardware con­figuration and requirements. In online mode, changes become immediately effective in the device.
4. Back up the configuration as a parameter file (*.u600) on your PC with the
button.
Note
In order to be able to fall back on the last version of the SICLOCK TC100 para­meter assignment, we recommend backing up the current parameter assignment of SICLOCK TC100 as a *.u600 file before you make any changes.
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
7-4
Configuration Tool

7.1 Menus

Table 7-1 Menus in the Configuration Tool
Menu / function Meaning / note
File
Open Loads a parameter assignment/an archive from the local file system
See also General functions (Chapter 7.2).
Save Saves a parameter assignment/an archive to a local file system
See also General functions General functions (Chapter 7.2).
End Exits application
Link See also Connect / disconnect online connection (Chapter 7.2.1).
Connect Connects to a device
Disconnect Disconnects from a device
Data transfer
(online connection required)
See also Connect / disconnect online connection (Chapter 7.2.1).
Download parameters from device
Update the parameters from the device
Upload parameters to the device
Download archive Loads the complete archive from the connected device onto the PC
Update archive Requests/updates the archive of a connected device
View
Parameters Changes to parameter view
Archive/events Changes to the archive/events view
Language Selects one of the languages available for the user interface
Loads all parameters from a connected device onto the PC
See also Parameters (Chapter 7.3).
Updates all the parameters so far loaded on the PC with the values from the connected device
See also Parameters (Chapter 7.3).
Writes all parameter from the PC into the connected device
See also Parameters (Chapter 7.3).
See also Archive (Chapter 7.4).
See also Archive (Chapter 7.4).
See also Parameters (Chapter 7.3).
See also Archive (Chapter 7.4).
Depending on the version, more languages could be offered for selection:
English (standard language)
German
The language/naming of parameters and archives are supplied by the device. Provided that the device recognizes the language set in the Configuration Tool, the parameters and archives will be displayed in this language. If the device does not recognize the language, the display will be in the standard language.
7-4
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Table 7-1 Menus in the Configuration Tool
Menu / function Meaning / note
?
Help… Calls Help system
Version… Displays version information for the Configuration Tool
Configuration Tool
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
7-4
Configuration Tool

7.2 General functions

The toolbar of the Configuration Tool provides general functions for the parame­ters and the archive. You can also acknowledge events, and authorize yourself in the Configuration Tool.
Table 7-2 Possible operations and displays in the toolbar of the Configuration Tool
Field / button Meaning / instruction
Loads a parameter assignment/an archive from the local file system
The file must be in the U600 format (*.u600). The parameter assignment
Open
Save
IP address
Connect to device
Disconnect from device
and the archive are loaded from the file when it is opened.
Notice
The currently loaded data (parameter assignment and archive) are overwritten.
Saves a parameter assignment/an archive to a local file system
The data (parameter assignment and archive) are saved in U600 format (*.u600).
IP address of the SICLOCK TC100
Enter the IP address of the device here.
Connects to a device
The connection is established to the device with the given IP address.
Disconnects from device
The connection is terminated.
Die aufgebaute Verbindung wird getrennt.
See also Connect / disconnect online connection (Chapter 7.2.1).
Authorization - password
Authorize
Event
(online connection required)
Confirm event
(online connection required)
Enter a password to enable a higher access level
Password supplied with device: "2222"
See also Authorization (Chapter 7.2.2).
Executes authorization with the password entered
Events currently pending in the device
In online mode, the events pending in the device are shown (e.g. warnings, alarms, etc.)
In offline mode, the display contains no information.
Acknowledges pending event
In online mode, an acknowledgment for the pending event is sent to the device. Provided that it is acknowledgeable, the device deletes the event from the display. Non-acknowledgeable events (persistent indications) remain in the display.
7-4
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Table 7-2 Possible operations and displays in the toolbar of the Configuration Tool
Field / button Meaning / instruction
Acknowledges all pending events
In online mode, an acknowledgment for all pending events is sent to the
Confirm all events
Ignore event
device. An acknowledgment is made, even if the cause of the event is still pending. This enables, e.g., persistent alarms to be deactivated.
Rejects the pending event
The event display is deleted without interaction with the device.

7.2.1 Connect / disconnect online connection

How to establish an online connection to the SICLOCK TC100:
1. Enter the IP address of the device in the toolbar.:
Configuration Tool
2. Start establishing the connection by clicking the icon next to the IP address field.
−> The Configuration Tool changes into online mode:
How to terminate the online connection to the SICLOCK TC100:
1. Click next to the IP address field.
−> The Configuration Tool changes into offline mode:
Note
The connection to the device is terminated after about two hours without operator input.
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
7-4
Configuration Tool

7.2.2 Authorization

There are authorization levels for each parameter, which allow or forbid read and write accesses to the parameter. The operator interface initially starts with the lowest authorization level, which mostly only allows read access to parameters.
You obtain more rights by inputting the corresponding password.
The user can change the password.
Parameter /System/Authorization For Standard Protection (2.06.02)
Note
The combination "0000" is not permitted as a password. Setting the password to "0000" disables access with this authorization level. Access is then only possible using the service password. The service password can be requested from Tech­nical Assistance by an authorized person.
The device is supplied with the password: "2222"
The current authorization level is indicated by the color of the password field.
Write protection - red entry field
In this authorization level, the user typically has only read access to standard parameters.
Standard protection - green entry field
In this authorization level, the user typically also has read access to extended parameters and write access to standard parameters.
Online mode
Authorization is executed directly on the device, i.e. the device assigns an appro­priate authorization level.
Offline mode
You can authorize yourself for a higher authorization level with a password, pro­vided that it is included in the loaded offline authorization parameters.
7-
Note
In offline mode, it is not possible to authorize oneself with a password that is pre­sent in the device but is not included in the offline authorization parameters.
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

7.3 Parameters

You can set and transfer parameters to the SICLOCK TC100 in the Parameter tab of the Configuration Tool in both offline and online modes.
Configuration Tool
Figure 7-3 SICLOCK TC100 Configuration Tool - Parameters
(1) Toolbar of the parameter tab
(2) Parameter tree
(3) Parameter table
(4) Parameter info
©Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
7-
Configuration Tool
Table 7-3 Possible operations and displays in the Parameter tab
Field / button Meaning / instruction
Outputs parameter assignment in a text file.
The currently displayed parameter assignment is output in a text file. The
Print table in text file
Download parameters
(online connection required)
data can be further processed, e.g., with Excel.
Notice
Parameter assignments cannot be restored from these text files. In order to restore a parameter assignment, it must have previously been saved in U600 format.
See open/save in General functions (Chapter 7.2).
Loads the parameters of the connected device
The parameters of the connected device, including its description data (e.g. texts in all languages), are loaded. This can take several minutes. The parameter assignment is also implicitly reloaded from the device.
Notice
The displayed parameter assignment data are overwritten. The archived data are not accepted from the device, i.e. the displayed archived data are retained.
See also Connect / disconnect online connection (Chapter 7.2.1).
Update parameters
(online connection required)
Upload parameters
(online connection required)
Observe actual values
(online connection required)
Loads the parameters of the connected device without parameter description
The parameters of a connected device are loaded without the description data. This can take several minutes.
Notice
The displayed parameter assignment data are overwritten. The archived data are not accepted from the device, i.e. the displayed archived data are retained.
See also Connect / disconnect online connection (Chapter 7.2.1).
Transfers the writable values of the loaded parameters to the connected device
The following values/parameters are not transferred into the device:
Values of write-protected parameters
Operationally critical parameters
Display parameters
Command parameters
To transfer the parameter, an online connection must be established to the device and the Confiiguration Tool correspondingly authorized. See also
Connect / disconnect online connection (Chapter 7.2.1) and Authorization (Chapter 7.2.2).
Current values / states of actual values observed
After observation has been activated, the current values and/or states are readout from the device cyclically, and the displays in the Parameter tree and the Parameter table are updated.
See also Connect / disconnect online connection (Chapter 7.2.1).
7-5
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Table 7-3 Possible operations and displays in the Parameter tab
Field / button Meaning / instruction
Parameter tree Tree display of parameters
The parameters are subordinated in the trees of the individual menus and submenus.
Online mode:
In online mode, you can open a context menu with a right mouse click on the parameter / entry. The following functions are available:
Read individual parameters
Write individual parameters
Set parameters to factory settings
See Reading / writing parameters, setting to factory defaults (Chapter 7.3.4).
Icons:
Write protection – the parameter cannot be edited
The current authorization level does not allow write access to this parameter.
Master level
The current authorization level allows reading, editing and writing of the parameter.
Master level without upload– operationally critical parameter
The current authorization level allows reading, editing and writing of the parameter.
In order to change such parameters in the device, you have to select the parameter explicitly and write it individually.
See Reading / writing parameters, setting to factory defaults (Chapter 7.3.4)
Display parameters
Display parameters can only be read, and are typically actual values.
In order to update the display of actual values, activate automatic update
.
Entry – this is a parameter entry
Parameter Table Tabular display of the parameters
You can edit the parameter values in this display, see Editing parameters (Chapter 7.3.3).
Online mode:
In online mode, you can open a context menu with a right mouse click on the parameter/entry. The following functions are available:
Read individual parameters
Write individual parameters
Set parameters to factory settings
See Reading / writing parameters, setting to factory defaults (Chapter 7.3.4).
Configuration Tool
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
7-5
Configuration Tool
Table 7-3 Possible operations and displays in the Parameter tab
Field / button Meaning / instruction
Number Unique, three-part parameter number, e.g. 000.005.00012
Parameter Related values are grouped in a parameter.
Parameter lists are displayed with square brackets after the parameter name, e.g. "Leap second[20]".
Entry The individual values of a parameter are each defined as an entry in a
parameter.
Note
Entries can be individually edited but not individually read or written. The complete parameter is always read or written with all its entries. If it is in a list, the complete list is read or written.
Value Numerical value or setting of the parameter entry
Write protection – the parameter cannot be edited
The current authorization level does not allow write access to this parameter.
Master level
The current authorization level allows reading, editing and writing of the parameter.
Master level without upload – operationally critical parameter
The current authorization level allows reading, editing and writing of the parameter.
In order to change such parameters in the device, you have to select the parameter explicitly and write it individually. See Reading / writing parameters, setting to factory defaults (Chapter 7.3.4).
Display parameters
Display parameters can only be read, and are typically actual values. In order to update the display of actual values, activate automatic update
.
Parameter info Information about the selected parameter
Information on the selected parameter / entry is displayed here.
Note
If the Configuration Tool is not authorized or is used with lower authorization rights, not all the parameters will be displayed. This restriction concerns, e.g., set­tings under "System“.
Furthermore, the access rights change with the authorization level.
7-5
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

7.3.1 Sorting Parameter tables

How to sort a Parameter table by number or parameter:
1. Click the "Number" or "Parameter" column with the mouse.
−> The table is sorted into alphabetical order according to the clicked column.
2. Click the "Number" or "Parameter" column again with the mouse to reverse the alphabetical order.
−> The alphabetical order of the column is reversed in comparison to the cur­rent sorting in ascending or descending alphabetical order.
The current sorting order is shown by an arrow alongside the column header:

7.3.2 Hiding / showing Parameter table entries

Configuration Tool
How to hide and show parameter entries:
1. 1.Click with the mouse on the icon on the left-hand side of the table next to the parameter.
−> The entries of the parameter are displayed.
2. 2.Click with the mouse on the .icon on the left-hand side of the table next to the parameter.
−> The entries of the parameter are hidden.
Figure 7-4 Parameter table with shown and hidden entries
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
7-5
Configuration Tool

7.3.3 Editing parameters

Precondition for editing a parameter entry
It must be a writable entry ( ).
How to change the values of a parameter entry:
1. Show the entries of the desired parameters in the Parameter table, see Hiding / showing Parameter table entries (Chapter 7.3.2).
2. Click the "Value" column of the parameter entry with the mouse.
−> The dialog for editing the entry opens.
An entry can be canceled with ESC.
Figure 7-5 of an editing dialog drop down list box
You can enter new values for parameters with units without entering the unit. Any units entered are ignored, only the numerical value is accepted.
Figure 7-6 Example of an editing dialog with a numerical entry
Note
In online mode, the value is sent to the device when the entry has been completed.
7-5
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Configuration Tool
How you check whether the value has been accepted by the device:
1. In online mode, select the entry of the changed parameter as described above.
−> The current value is displayed in the device.
Note
Depending on the parameter/entry and operating state, the device checks whe­ther it can accept the changed value. If the device rejects the new value, it is reset to the old value.
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
7-5
Configuration Tool

7.3.4 Reading / writing parameters, setting to factory defaults

In online mode, you can read or write an individual parameter, or reset it to the factory setting.
How to activate the functions "Read parameter", "Write parameter" and "Reset parameter to factory settings":
1. Ensure that the Configuration Tool is connected to the device. See Connect / disconnect online connection (Chapter 7.2.1).
2. Select the desired parameter / entry from the Parameter tree or Parameter table.
3. Right-click the parameter or entry.
−> The context menu opens.
Select the desired function with a left mouse click.
Figure 7-7 Context menu for reading, writing and resetting parameters
7-5
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

7.4 Archive

In the Archive tab of the Configuration Tool, you can load archived data from the device, and save the data in a file, as well as evaluate and search the data with filter functions.
Configuration Tool
Figure 7-8 SICLOCK TC100 Configuration Tool - Archives
(1) Toolbar of the Archive tab
(2) Archive table
(3) Include filter (shows events)
(4) Exclude filter (hides events)
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
7-5
Configuration Tool
Table 7-4 Possible operations and displays in the Archive tab
Field / button Meaning / instruction
Outputs the archive in a text file.
The currently displayed Archive table is output in a text file. Events hidden by
Print table in text file
Download archive
(online connection required)
Update archive
(online connection required)
the filter are not output. The data can be further processed, e.g., with Excel.
Notice
Archives cannot be restored from these text files. In order to restore an archive, it must have previously been saved in U600 format.
See open/save in General functions (Chapter 7.2).
Loads the archive of the connected device
The archive of the connected device, including its description data (e.g. texts in all languages), is loaded. This can take several minutes. The parameter assignment is also implicitly reloaded from the device.
Notice
The currently loaded data (parameter assignment and archive) are overwritten.
See also Connect / disconnect online connection (Chapter 7.2.1).
Loads the archive of the connected device without the parameter description
The archive of a connected device is loaded without the description data. The loading process without the description data is quicker than "Download archive". The parameter assignment is also implicitly reloaded from the device.
Notice
The currently loaded data (parameter assignment and archive) are overwritten.
See also Connect / disconnect online connection (Chapter 7.2.1).
View reduced to incoming / outgoing
Switch Exclude-Include view
Clear Include filter
Clear Exclude filter
Displays only incoming and outgoing events
Only persistent indications (typically alarms) are displayed in the Archive table. This gives you a compact overview of important operational malfunctions. The hidden events are displayed in the Exclude window of the filter.
In order to display all events again, delete the Include filter.
See Filters (Chapter 7.4.2).
Switches an event from the Include to the Exclude filter, and vice versa
The events selected in the Include and Exclude filters are in each case moved into the other filter.
See Filters (Chapter 7.4.2).
Removes all events from the Include filter
The events are moved into the Exclude filter.
See Filters (Chapter 7.4.2).
Removes all events from the Exclude filter
The events are moved into the Include filter.
See Filters (Chapter 7.4.2).
7-
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Table 7-4 Possible operations and displays in the Archive tab
Field / button Meaning / instruction
Archive table Events are shown in tabular form.
Persistent indications trigger an incoming and an outgoing event, and are highlighted in color:
red = incoming
green = outgoing
Typically, alarms are implemented in the device as persistent indications.
Type Event type:
System
Application
Information
Alarm
Note:
Each type of event is managed in its own buffer in the device. If a buffer is full, the next message of this type overwrites the oldest message in the buffer.
See also Messages (Chapter 12).
Time Tripping event in the device, time base UTC
Configuration Tool
Event Message triggered by device.
The sum of all events forms the archive of the device.
Information Optional information accompanying the event. +/- ++ (incoming)
Event marked as incoming (persistent indication, e.g. alarm)
-- (outgoing)
Event marked as outgoing (persistent indication, e.g. alarm)
Include filter Events shown in the Archive table.
See Filters (Chapter 7.4.2).
Exclude filter Events not shown in the Archive table.
See Filters (Chapter 7.4.2).
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
7-
Configuration Tool

7.4.1 Sorting the Archive table

How to sort the Archive table by time or event:
1. Click the "Time" or "Event" column with the mouse.
−>The table is sorted into alphabetical order according to the clicked column.
2. Click the "Time" or "Event" column again with the mouse to reverse the alpha­betical order.
−> The alphabetical order of the column is reversed in comparison to the cur­rent sorting in ascending or descending alphabetical order.
The current sorting order is shown by an arrow alongside the column header:
7-6
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

7.4.2 Filters

You can show and hide specific events by means of a filter to make searching the archive easier. All the events listed in the Include window are displayed in the Archive table, all the events listed in the Exclude window are not displayed.
Changing the assignment of an event from the Include to the Exclude filter, or vice versa:
1. Click on the event in the Include or Exclude window.
−> The selected event is highlighted blue.
2. Click the button.
−> The event is moved from the Include into the Exclude filter, or vice versa.
How to select and move multiple events in the filters:
1. Hold the CTRL button down while you select the events in the filter with mouse clicks.
−> The selected event is highlighted blue, and the blue highlighting of previ­ously selected events is retained.
Configuration Tool
2. Click the button.
−> The events are moved from the Include into the Exclude filter, or vice versa.
How to select and move successive events in the filters:
1. Click the first item in the group of events with the mouse.
2. Hold the SHIFT key down, and click the last item in the group of events with the mouse.
−> These two events and all those lying between them are selected.
3. Click the button.
−> The events are moved from the Include into the Exclude filter, or vice versa.
How to remove all events from the Include or Exclude filter:
1. Click the button above the Include or Exclude filter.
−> The contents of the Include or Exclude filter are removed. The events so removed are now available for selection in the other filter.
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
7-6
Configuration Tool

7.5 Troubleshooting

Frequent questions about the SICLOCK TC100 Configuration Tool and solutions to problems are listed below.
Table 7-5 Solutions to problems with the Configuration Tool
Question / problem Cause / remedy
Authorization not possible in offline mode
The data do not include any authorization parameters. An online authorization has to be made.
See Authorization (Chapter 7.2.2).
No connection can be established to the device
Check whether the IP address has been set correctly in the Configuration
Tool.
Check whether there is a network connection
Check whether the TCP:2155 port is enabled for the connection or is already
being used for another application.
See also Connect / disconnect online connection (Chapter 7.2.1).
An event cannot be acknowledged
It is a persistent indication that is queued in the device.
See also General functions (Chapter 7.2).
No interaction with the device in online mode (hourglass)
The connection to the device has been terminated and has to be re-established.
See also Connect / disconnect online connection (Chapter 7.2.1).
Parameter cannot be edited
The parameter is a display parameter
See Parameters (Chapter 7.3)
The current authorization level is too low
See Authorization (Chapter 7.2.2)
The parameter has no value.
In this case, the parameter has to be read from the device again.
Parameters and archives are displayed in a different language to that of the operator interface
The language set in the Configuration Tool is not available in the device.
See Menus (Chapter 7.1)
Parameters are not written by upload
These are operationally critical parameters , that are explicitly excluded from an upload.
Such parameters have to be written individually.
See Parameters (Chapter 7.3) and Reading / writing parameters, setting to factory defaults (Chapter 7.3.4)
7-6
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Table 7-5 Solutions to problems with the Configuration Tool
Question / problem Cause / remedy
Parameters are displayed without values
The authorization level has been raised after a download, so that parameters with a higher authorization are visible. However no values are returned for a request with a lower authorization.
You can update these values with the button, and read them individually.
See
Parameters (Chapter 7.3), Authorization (Chapter 7.2.2) and Reading / writing parameters, setting to factory defaults (Chapter 7.3.4).
Configuration Tool
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
7-6
Configuration Tool
7-6
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Parameter assignment and operation
of the device 8
SICLOCK TC100 has a two-line, alphanumeric LCD display with background lighting and auto­matic contrast control for displaying the date and time, messages and status.
You can use the MODE button to readout and change parameters important for commissioning.
.
Figure 8-1 Front view of SICLOCK TC100
SICLOCK
®
TC100 Operating Instructions
8-6© Siemens AG 2010 All Rights Reserved
Parameter assignment and operation of the device

8.1 Status display

When the device is switched on, operation and status display are not possible for a brief ramp-up time.
SICLOCK TC100
.......
Figure 8-2 Device ramp-up display after switch on
The time, date and current synchronization state are shown during operation.
09:48:26 → NTP
Fr, 01. Oct. 2010
Figure 8-3 Example of display during operation
Table 8-1 Possible synchronization states
Display Description
Q No external synchronizationNTP External synchronization via NTP active.DCF1
GPS1
1)
1)
External synchronization active via DCF signal to RADIO CLOCK.
External synchronization active via GPS signal to RADIO CLOCK.
MBG1 External synchronization active via Meinberg telegram to
RADIO CLOCK.
NME1 External synchronization active via NMEA telegram to
RADIO CLOCK.
2)
--1 flashing
1) If the display flashes, no valid signal is currently being received.
2) This occurs when the timeout selected for switching to the substitute
synchronization is longer than the monitoring timeout for the external synchronization.
The timeout for switching to the substitute synchronization can be set with the following parameter entry:
/Redundancy/Redundancy/Timeout (0.09.10)
The timeout for the external synchronization can be set with the following parameter entry:
/Inputs/Input 1/Monitoring/Timeout (0.20.01)
The external synchronization to the RADIO CLOCK has not supplied a signal for more than 30 minutes (default setting), and a switch has not yet been made to a substitute synchronization.
8-6
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Status display with queued message
Parameter assignment and operation of the device
EVENT event-text event-text..
Figure 8-4 Example of display during operation with error
19/09/2010 10:41:27
event-text event-text..
The top line shows the message type and the date / time alternately. The mes­sage text is shown scrolling through the bottom line.
When a message arrives, the background lighting is automatically switched on for 10 minutes.
Table 8-2 Possible types of message
Display Description
INFO Current message is an info message
WARNING Current message is a warning
EVENT Other messages, e.g. an alarm
Note
Queued messages can be acknowledged by a long press on the MODE button.
If a current, unacknowledgable, persistent indication is pending, you can tempora­rily change to the status display with a short press on the MODE button.
Background lighting
Each time the button is pressed, the background lighting of the display is switched on for 10 minutes.
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
8-6
Parameter assignment and operation of the device

8.2 Operation and parameter assignment

8.2.1 One-button operation with the MODE button

The MODE button enables restricted operation and important parameters to be read out directly on the device. This mainly involves the network settings required to commission the device.
There are three different operational actions for the MODE button:
Short button press A definite button press, but for less than 3 seconds.
As a rule, a short button press is used to "turn the page". An action that can be executed by a short button press is indicated by a short arrow pointing to the right in the top right-hand corner of the display.
See examples 1 to 4.
Long button press: A definite button press for longer than 3 seconds.
The action addressed by the long button press is executed after this time has elapsed. As a rule, a long button press is used to "accept" a setting. An action that can be executed by a long button press is indicated by a long arrow pointing to the right in the bottom right-hand corner of the display.
See examples 1 to 4.
No button press:: If there is no button press for 45 seconds, the operating level is
exited automatically.
See example 4.
Example 1:
IP address ->
192.168.001.011 -->
Figure 8-5 Example 1 of one-button operation
The display shows the readout of the currently set IP address. A short button press "turns the page" to readout the next parameter. A long button press can accept the parameter "IP address" in a programming mode.
8-
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Parameter assignment and operation of the device
Example 2:
IP Gateway ->
000.000.000.000
Figure 8-6 Example 2 of one-button operation
The display shows the readout of the currently set IP gateway. A short button press "turns the page" to readout the next parameter. A long button press is not possible in this mask (no long arrow on the right).
Example 3:
-> Select -->Reset
192.168.001.010 ?
Figure 8-7 Example 3 of one-button operation
The display shows the programming mode of a parameter, in this case an IP address. A short button press can "turn the page" to another possible value
Select). A long button press can reset the parameter to the selected value
(
Reset).
(
Example 4:
Next -> Exit -->
Figure 8-8 Example 4 of one-button operation
At the end of the lists of pages, in most cases the operating level can be exited by selecting "Exit" with a long button press, instead of having to wait for the auto­matic exit after the timeout.
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
8-
Parameter assignment and operation of the device

8.2.2 Network settings on the device

One-button operation can be used to read out the network settings of the device, and settings can be made to the extent required for commissioning.
The following can be set and/or readout:
IP address, selection from the list offered
Subnet mask, selection from list offered
Gateway, read only.
The following diagram shows the setting options:
.
11:46:48 ->GPS1 Mo, 4. Oct. 2010
short
long
long
Level 1:
Level 2:
45s
IP adress ->
192.168.001.010 -->
45s
->Selection -->Reset
192.168.001.010 ?
Accept value
Figure 8-9 Assigning network settings
On level 2, one of the predefined selection values can be selected for the network setting.
For IP addresses:
192.168.001.010
short
IP subnet ->
255.255.255.000 -->
short
->Selection -->Reset
192.168.001.011 ?
short
IP Gateway ->
000.000.000.000
short
...
8-7
192.168.001.011
192.168.002.020
192.168.002.021
For subnet masks:
255.255.255.000
255.255.254.000
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
In this way, you can add your own values to the list of options, and assign any IP addresses:
For this purpose, you need a notebook or PC with an Ethernet connection to the device. The notebook must already be in the desired IP subnet.
1. Open a CMD shell on the notebook.
2. Press the button until the list of options is displayed (operating level 2, IP address flashes, only in this status can new values be added).
3. Now trigger a ping on the notebook with at least 4 attempts to the desired IP address (e.g. ping –n 5 192.168.1.43).
4. The ping is not answered by the device, but the destination address is added to the list of options, and can be accepted by a long button press.

8.2.3 Readout versions

The relevant software versions can be readout by one-button operation:
Parameter assignment and operation of the device
11:46:48 ->GPS1 Mo, 4. Oct. 2010
V
/HYHO
Figure 8-10 Readout versions
IP address ->
The following versions can be readout:
Firmware version TC100
Core version TC400
Core version U300
Processor version
VKRUW
VKRUW
Version ->
VKRUW
Firmware 1.53467192.168.001.010 -->
VKRUW

© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
8-7
Parameter assignment and operation of the device
8-7
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Parameter assignment 9

Frequently required settings are described in the following.
Get more information
Parameter table (Chapter 10)
Configuration Tool (Chapter 7)
SICLOCK
®
TC100 Operating Instructions
9-7© Siemens AG 2010 All Rights Reserved
Parameter assignment

9.1 Connecting external synchronization

The external synchronizations can be connected to SICLOCK TC100 via Ethernet as an NTP server and/or as a radio clock via point-to-point connections.
The prerequisite for operation is at least one external synchronization. Additional external synchronizations can serve as substitute synchronizations in the event of a fault, see Redundancy (Chapter 2.6).
GPS and DCF77 radio clocks, cable distribution installations, atomic clocks and other signal sources can serve as external synchronizations.
Get more informationen
Synchronization (Chapter 9.3.2).

9.1.1 Radio clocks via terminals

A radio clock can be connected, see also Terminal assignment (Chapter 15.1).
Monitoring
Status display
Serial formats
The input signal of the radio clock can be monitored with the parameter /Inputs/Input 1/Monitoring (0.20.01)
, and an alarm or warning output after expiry
of the monitoring time.
See Connecting external synchronization (Chapter 6.3).
The parameter /Inputs/Input 1/Framing (0.20.03)
shows the automatically detec-
ted framing for serial formats.
There are entries for baud rate, data bits, parity and stop bits.
9-7
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

9.1.2 Operation as NTP client

Four IP addresses of NTP servers can be assigned for SICLOCK TC100 as an NTP client.
The servers are queried regularly, and a preferred server is selected according to a strict selection strategy.
For the strategy in the event of loss of server, see Redundancy (Chapter 2.6).
NTP Client
You activate the client service with the parameter /NTP Client/NTP Client (0.18.01)
IP addresses of the NTP servers
You can specify four IP addresses of NTP servers with the parameter /NTP Client/NTP Server List[4] (0.18.02). The address 0.0.0.0 indicates that no server has been entered.
Parameter assignment
.
DNS names are not supported.
Current NTP server
The currently selected NTP server is displayed with the parameter /NTP Client/Active Server (0.18.03). The address 0.0.0.0 indicates that no server has been entered.
Monitoring the server
Monitoring of the NTP servers can be set up with the parameter /NTP Client/Monitoring/Monitor Server (0.18.04)

9.1.3 Redundancy

The priority in the event of loss of an external synchronization is defined by the setting of the parameter /Redundancy/Redundancy (0.09.10)
Setting "Master (radio clocks preferred to NTP)"
RADIO CLOCK is always accepted
NTP is used when RADIO CLOCK is not available.
.
:
Setting "Slave (NTP preferred to radio clocks)"
RADIO CLOCK is used when NTP is not available.
NTP is always accepted.
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
9-7
Parameter assignment

9.2 Connecting time receivers

The following options are available for connecting the time receivers::
Ethernet connection via NTP Server
Ethernet connection via SIMATIC Verfahren
The following sections describe the parameter assignment options.

9.2.1 NTP server service

An NTP server is available at the Ethernet port. The NTP server supports the modes Any/unicast and Multicast according to RFC2030.
Any / unicast (standard mode)
This mode is used by, e.g., PCs.
Multicast
You activate the NTP server in Any/unicast mode with the parameter entry /NTP Server/NTP Server/Operation (0.16.01)
= "On". The settings "Off" and "Only
when synchronized" are also available as options.
The setting "Only when synchronized" enables conditional operation. The server service is only active when the device is externally synchronized.
This mode has to be set explicitly for each subnet.
You can set Multicast mode for up to four subnets with the parameter /NTP Server/Multicast[4]/Multicast[x]/Mode (0.16.02)
.
You define the Multicast IP address that will be used with the parameter entry "Multicast address", e.g. 192.168.2.255.
Setting options for parameter entry mode:
Off
10s – Standard mode, that is the coded time is time-zone independent
60s – Standard mode, that is the coded time is time-zone independent
10s with local time – for receivers without their own calendar
60s with local time – for receivers without their own calendar
9-7
You define the Multicast IP address that will be used with the parameter entry "Multicast address".
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

9.2.2 SIMATIC mode

SIMATIC mode is supported at the Ethernet port by two protocols:
PCS7-compatible mode
S5-compatible mode
The setting is made with the parameter /SIMATIC Mode/Ethernet 1 (0.15.01)
Mode
You set the send clock between 0 s, 1 s and 10 s with the parameter entry /SIMATIC Mode/Ethernet 1/Mode (0.15.01)
Send condition
You define whether the signal is always output or only when synchronized with the parameter entry /SIMATIC Mode/Ethernet 1/Send Condition (0.15.01)
Parameter assignment
.
.
.
Destination address
You define the send address of the SIMATIC mode with the parameter entry /SIMATIC Mode/Ethernet 1/Destination Address (0.15.01) address FF:FF:FF:FF:FF:FF is typically set.
. The broadcast
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
9-7
Parameter assignment

9.3 General settings on the device

The important general settings are described in the following, e.g. the time adjust­ment, the synchronization response etc.
You will find a list of all the setting options in Parameter table (Chapter 10).

9.3.1 Time management

Note
Change the plant time at one single, central point, ideally on the central plant clock.
Setting the time manually
You can set the time in the device optionally with one of the following parameters:
Parameter /Time/Local Time (0.09.04)
Parameter /Time/UTC Time (0.09.02) (uniform universal time)
Parameter /Time/TAI Time (0.09.03)
Time zone
You define the offset from UTC to the zone time, without any daylight saving, with the parameter /Time/Time Zone (0.09.06)
Note
If the external synchronization already contains a time zone (e.g. DCF77 contains CET/CEST), this is taken into account on reception.
If the time zone is not defined by the external synchronization (e.g. serial tele­grams), then no further time zone correction is made.
Difference between TAI and UTC
You can readout the difference between atomic time TAI and universal time UTC in seconds with the parameter /Time/Extended/Atomic Time TAI/Offset from UTC to TAI (0.09.01).
(atomic time)
.
9-
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Daylight saving
Leap seconds
Parameter assignment
The device makes the daylight saving change automatically at the parameterized switching times.
Parameter /Time/Extended/Daylight Saving (0.09.07)
Note
The preset switching times are consistent with the regulations currently valid in the European Union.
The setting "Change = No" suppresses the time change, and the plant is operated with standard time.
The calendar rule for the daylight saving time change can be defined worldwide via a parameter.
You define the leap-second calendar with the parameter /Time/Extended/Leap Seconds[20] (0.09.05)
.

9.3.2 Synchronization

Synchronizaion status
You can readout the various information about the current synchronization status via the parameter /Synchronization/Synchronization Status (0.09.09)
Protected synchronization
If a discontinuity of longer than 5 seconds occurs in the external synchronization, the protected synchronization is activated. The synchronization is disabled, and an alarm is triggered, which is pending as long as the discontinuity in the external synchronization continues.
The pending synchronization disable can be ignored once and the "Protected Synchronization" alarm cleared with the parameter entry /Synchronization/Exten­ded/Protected Synchronization/Ignore/Clear Alarm (0.09.12) = "Yes".
Note
This synchronizes unconditionally with the external time, and a time jump can occur in the plant operation.
If required, disconnect the active external synchronization in advance or delete the server address for NTP client operation from the parameter /NTP Client/NTP Server List[4] (0.18.02)
.
.
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
9-
Parameter assignment
Microsteps
If a difference occurs between the input synchronization (e.g. radio clock) and the device up to a tolerance threshold of several seconds, this difference is not adjus­ted immediately as this would lead to a time jump in the time synchronization.
This difference is run down incrementally in microsteps, which are significantly below the time resolution of typical plants, and so remain unnoticed by the plant operation. This process may take up to several hours.
The run down of the time difference in microstep mode can be interrupted once with the parameter entry /Synchronization/Extended/Microsteps/Ignore/Cancel (0.09.13) = "Yes".
This causes immediate synchronization with the external time, and a time jump
occurs in the plant operation.
Note
Avoid time jumps in the plant operation.
The "Ignore microstep mode" command is suitable, e.g. for the first input synchro­nization during commissioning.
Monitoring
You define whether the device outputs an alarm or a warning in the absence of external synchronization with the parameter /Synchronization/Extended/Monitoring (0.09.14)

9.3.3 Display

You change the language and the representation of the time with the parameter /Display/Representation (0.10.01) TAI.

9.3.4 System

You define and can change the password for standard protection with the para­meter /System/Authorization For Standard Protection (2.06.02)
You use the parameter /System/Reset (0.06.04) factory defaults. This does not reset parameters such as network addresses, authorizations etc.
.
. The time can be shown as UTC, local time or
.
to reset the parameters to the
9-8
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

9.3.5 Temperature

You activate the monitoring of the module temperature with the parameter entry /Environment/Extended/Temperature/Monitoring (0.24.01)
You can set the following values:
Alarm
Warning
No monitoring
The current module temperature is shown in the parameter entry /Environment/Status/Temperature (0.24.02)

9.3.6 Battery

You can switch the battery off for storage with the parameter entry /Environment/Extended/Battery/Switch Off (0.25.01) lengthen the life of the battery in storage.
Parameter assignment
.
.
, and so substantially
After a minimum operating period of 30 minutes after Power Up, SICLOCK TC100 checks once
whether the battery is switched off. If necessary, the battery
is then switched on automatically, and a message is output.
Notice
If the supply voltage is switched
off while the battery is switched off, the SICLOCK
TC100 loses the hardware time and the archives.
This command may only be executed by qualified personnel.
See Battery (Chapter 11.1).
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
9-8
Parameter assignment
9-8
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Parameter table 10

Table 10-1 List of SICLOCK TC100 parameters
Access1)
/ no.
Time
Local time Time and date
0.09.04
UTC time Time and date
0.09.02
Time zone Offset from UTC to zone time Min:
0.09.06
Time / Extended
Daylight saving time Change Min:
0.09.07
Specified date for daylight saving
0.09.08
Leap seconds[20] Time and date
Parameter Eintry Value range / default
UTC-12:00 h
Max:
Default:
Max:
Default:
Changeover time from standard time to daylight saving
Changeover time from daylight saving to standard time
Hours Min:
Specification for changing from standard time to daylight saving
Specification for changing from daylight saving back to standard time
Min:
Max:
Default:
Min:
Max:
Default:
Max:
Default:
UTC+14:00 h
UTC+01:00 h
Yes
No
Yes
February, third Sunday, 00:00 h
Specified date and time
March, last Sunday, 02:00 h
February, third Sunday, 00:00 h
Specified date and time
October, last Sunday, 03:00h
+1 h
+2 h
+1 h
0.09.05
SICLOCK
®
TC100 Operating Instructions
Amount Min:
Max:
Default:
-1 s
+1 s
+0 s
10-8© Siemens AG 2010 All Rights Reserved
Parameter table
Table 10-1 List of SICLOCK TC100 parameters
Access1)
/ no.
Parameter Eintry Value range / default
Time / Extended /Atomic Time TAI
TAI time Time and date
0.09.03
Offset from UTC to TAI Offset Min:
0.09.01
TAI events Enable
0.09.11
Synchronization
Synchronization status Status Min:
0.09.09
Synchronization / Extended
Protected synchronization
0.09.12
Microsteps Ignore / cancel Min:
0.09.13
Monitoring Monitor synchronization status Min:
0.09.14
Max:
Default:
Min:
(Record messages from the TAI domains in the Event log)
Synchronized at least once Min:
Last synchronization
Current time difference Min:
Drift correction Min:
Input jitter Min:
Ignore / clear alarm Min:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
-32768 s
+32767 s
+0 s
Yes
No
No
Non-synchronized (quartz)
Radio clock 2
Non-synchronized (quartz)
Yes
No
No
-2147483.648 s
+2147483.647 s
+0.000 s
-2147483.648 ppm
+2147483.647 ppm
+0.000 ppm
0.000 ms
4294967.295 ms
0.000 ms
Yes
No
No
Yes
No
No
Off
Alarm
Off
10-8
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Table 10-1 List of SICLOCK TC100 parameters
Parameter table
Access1)
/ no.
Parameter Eintry Value range / default
Redundanz
Redundancy Priority Min:
0.09.10
Network settings / Ethernet 1
IP adapter 1 IP address Min:
0.05.01
Network adapter 1 Hardware address Min:
0.05.05
Line status adapter 1 Link Min:
0.09.13
Advanced Settings Adapter 1
0.05.09
SIMATIC mode
Ethernet 1 Mode Min:
0.15.01
Max:
Default:
Timeout Min:
Max:
Default:
Max:
Default:
Subnet mask Min:
Max:
Default:
Gateway Min:
Max:
Default:
Max:
Default:
Max:
Default:
Linespeed Min:
Max:
Default:
Duplex Min:
Max:
Default:
Monitor link status Min:
Max:
Default:
Max:
Default:
Send condition Min:
Max:
Default:
Destination address Min:
Max:
Default:
Master
Slave
Master
10 mins
720 mins
30 mins
0.0.0.0
255.255.255.255
192.168.1.10
0.0.0.0
255.255.255.255
255.255.255.0
0.0.0.0
255.255.255.255
0.0.0.0
00.00.00.00.00.00
FF.FF.FF.FF.FF.FF
00.00.00.00.00.00
---
down
---
---
100 Mb/s
---
---
Half duplex
---
Off
Alarm
Off
Off
S5-compatible, every 10 s
Off
---
Only when synchronized
---
00.00.00.00.00.00
FF.FF.FF.FF.FF.FF
FF.FF.FF.FF.FF.FF
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
10-8
Parameter table
Table 10-1 List of SICLOCK TC100 parameters
Access1)
/ no.
NTP server
NTP server Operation Min:
0.16.01
Multicast[4] Mode Min:
0.16.02
NTP client
NTP client Operation Min:
0.18.01
NTP server list[4] IP address Min:
0.18.02
Active server IP address Min:
0.18.03
Monitoring Monitoring the server Min:
0.18.04
Inputs / Input 1
Status Signal Min:
0.20.02
Monitoring Monitor input Min:
0.20.01
Framing Baud rate Min:
0.20.03
Parameter Eintry Value range / default
On
Max:
Default:
Max:
Default:
Multicast address Min:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Timeout Min:
Max:
Default:
Max:
Default:
Only when synchronized
On
Off
60 s with local time
Off
0.0.0.0
255.255.255.255
0.0.0.0
Off
On
Off
0.0.0.0
255.255.255.255
0.0.0.0
0.0.0.0
255.255.255.255
0.0.0.0
Off
Alarm
Off
No signal
Telegram (disturbed)
No signal
Off
Alarm
Alarm
5 mins
1440 mins
30 mins
0 Bd
4294967295 Bd
0 Bd
10-8
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Table 10-1 List of SICLOCK TC100 parameters
Parameter table
Access1)
/ no.
Display
Display Language Min:
0.10.01
System
Authorization for standard protection
2.06.01
Reset Factory settings Min:
0.6.04
Environment
Status Temperature Min:
0.24.02
Time / Extended
Temperature Monitoring Min:
0.24.01
Battery Switch off Min:
0.25.01
Versions
Firmware version A2B number Min:
0.08.01
Parameter Eintry Value range / default
Data bits Min:
Max:
Default:
Parity Min:
Max:
Default:
Stop bits Min:
Max:
Default:
Max:
Default:
Time Min:
Max:
Default:
Authorization Min:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Max:
Default:
Version number Min:
Max:
Default:
0
8
0
None
Odd
None
0
2
0
German
English
German
Local time
Atomic time TAI
Local time
0
4294967295
2222
Yes
No
No
-10°C
+125°C
+25°C
No monitoring
Alarm
No monitoring
No
Yes
No
0
4294967295
0
0.0.0
65535.65535.65535
0.0.0
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
10-8
Parameter table
Table 10-1 List of SICLOCK TC100 parameters
Access1)
/ no.
0.28.03
0.08.04
0.08.02
0.08.03
Parameter Eintry Value range / default
Firmware base
(A2B00061430)
Firmware base
(U300)
Processor version A2B number Min:
Hardware version A2B number Min:
A2B number Min:
Max:
Default:
Version number Min:
Max:
Default:
A2B number Min:
Max:
Default:
Version number Min:
Max:
Default:
Max:
Default:
Version number Min:
Max:
Default:
Max:
Default:
Release Min:
Max:
Default:
Serial number
0
4294967295
0
0.0.0
65535.65535.65535
0.0.0
0
4294967295
0
0.0.0
65535.65535.65535
0.0.0
0
4294967295
0
0.0.0
65535.65535.65535
0.0.0
0
4294967295
0
0
65535
0
1) The access icons indicate the possibility of accessing with the highest authorization level.
Note
If the Configuration Tool is not authorized or is used with lower authorization rights, then not all the parameters will be displayed. This restriction concerns, e.g., settings under "System".
Furthermore, the access rights change with the authorization level.
Get more information
List of icons (Chapter C)
Authorization (Chapter 7.2.2)
10-
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Service and maintenance 11

11.1 Battery

The device has an integrated battery which supplies a clock module and the archive buffer during phases without the power supply.
The battery can be switched off when put into storage, which lengthens its service life and availability.
After a minimum operating period of 30 minutes after Power Up, SICLOCK
TC100 checks once is then switched on automatically, and a message is output.
whether the battery is switched off. If necessary, the battery
Service life of a switched-off battery
Service life of a switched-on battery in storage: Approx. 6 years
Notice
If the supply voltage is switched off while the battery is switched off, the SICLOCK TC100 loses the hardware time and the archives.
Note
The battery may only be replaced by the Siemens factory.
Please contact Product Support.
See also Battery (Chapter 9.3.6).
in storage: > 12 years

11.2 Restoring factory defaults

Restoring individual parameters
Reading / writing parameters, setting to factory defaults (Chapter 7.3.4)
Restoring parameters
You use the parameter /System/Reset (0.06.04) factory defaults. This does not reset parameters such as network addresses, authorizations etc.
SICLOCK
®
TC100 Operating Instructions
to reset the parameters to the
11-© Siemens AG 2010 All Rights Reserved
Service and maintenance

11.3 Software update

Please contact Product Support for information and software updates for your SICLOCK TC100.
See also Preface.
11-9
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Messages 12

The messages are classified under four different types of event:
System (capacity for approx. 1,500 entries)
Application (capacity for approx. 4,500 entries)
Information (capacity for approx. 21,500 entries)
Warning (capacity for approx. 3,000 entries)
Messages for which an outgoing event is triggered are termed persistent indica­tions. Persistent indications are, e.g., alarms.
Note
Each type of event is managed in its own buffer in the device. If a buffer is full, the next message of this type overwrites the oldest message in the buffer.
The size of the information buffer is sufficient for approx. 45 days. This in an ave­rage value based on experience. However, the message volume can vary accor­ding to the operating conditions and plant configuration.
For further information, see Archive (Chapter 7.4).
Table 12-1 Overview of messages, with event type and brief description
Recording a synchronization input
Information The recording of a synchronization input is pending because a threshold value has
been exceeded.
The battery has been switched off
Application A user has used the Configuration Tool to switch off the battery in readiness for
storage.
See also Battery (Chapter 9.3.6).
Battery has been switched on automatically
Application After a minimum period of operation, the battery was switched on automatically.
See also Battery (Chapter 9.3.6).
Bootloader has been updated
System and Information
Bootloader has NOT been updated
System and Information
The bootloader has been successfully installed.
The bootloader could not be installed.
SICLOCK
®
TC100 Operating Instructions
12-9© Siemens AG 2010 All Rights Reserved
Messages
Table 12-1 Overview of messages, with event type and brief description
Default processor loaded
Warning The default processor was loaded during the start.
Input 1: DCF77 OK
Information After a disturbance, the correct DCF reception has been detected again.
Input 1: DCF77 signal disturbed
Information During stable reception, a disturbance was detected in the DCF77 signal.
Input 1: GPS OK
Information After a disturbance, the correct GPS reception has been detected again.
Input 1: GPS signal disturbed
Information During stable reception, a disturbance was detected in the GPS signal.
Input 1: Signal timeout
Application
(alarm)
With monitoring activated, no signal was received within the parameterized timeout.
Check the status display, see Radio clocks via terminals (Chapter 9.1.1). If "no signal" is shown in the status, check the wiring.
Input 1: Telegram OK
Information A serial format has been detected (for the first time since failure).
Input 1: Telegram cannot be decoded
Information The serial format cannot be decoded.
Firmware has been updated
System and
A firmware update has been performed, and the firmware has been updated.
Information
Firmware has NOT been updated
System and
A firmware update has been performed, and the firmware could not be updated.
Information
Flash file system has been formatted
System The file system has been formatted.
Protected synchronization
Application
(alarm)
The protected synchronization was activated, a discontinuity was detected during the external synchronization.
The message indicates an external synchronization error. See also Synchronization (Chapter 9.3.2).
Internal error, please contact Support.
System The message text specifies the exact error, and this is important, e.g. for Support
(Hotline).
Processor has been updated
System and
A processor update has been performed, and the processor has been updated.
Information
12-9
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Table 12-1 Overview of messages, with event type and brief description
Processor has not been updated
System and
A processor update has been performed, but the processor could not be updated.
Information
Hardware time set
Information The SICLOCK TC100 internal real-time clock has been set.
No usable NTP server
Information No preferred server was found.
No hardware time
Application A valid time could be read out of the hardware.
Critical temperature exceeded
Application The critical module temperature has been exceeded.
See also Temperature (Chapter 9.3.5).
Link down EHT1
Application The link status monitoring has found the status "Link down".
The triggering of an archive entry or alarm can be set with the following parameter:
/Network Settings/Ethernet 1/Extended Settings Adapter 1/Monitor Link Status (0.05.09)
Messages
Microstep mode ignored
Application A microstep mode has been circumvented once by the user.
See also Synchronization (Chapter 9.3.2).
NTP server selected
Information A new NTP server has been selected.
NTP server unreachable
Information The server is no longer available.
A parameter has been reset to the factory setting via the HMI
Information A parameter has been reset to the factory setting via the HMI. The parameter number is
stated in the message text.
A parameter has been written via the HMI
Information A parameter has been written via the HMI. The parameter number is stated in the
message text.
Sector in the parameter memory cleaned up
System The data in the parameter memory has been cleaned up automatically.
Stabilized synchronization
Information New stabilizer data are present, and are shown in the message.
Synchronization inconsistent
Information The consistency check of an external synchronization was negative. The external
synchronization and the negatively tested offset are displayed.
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
12-9
Messages
Table 12-1 Overview of messages, with event type and brief description
Synchronization density
Information States the number of synchronization inputs per interval.
The message is triggered cyclically, and serves to evaluate the quality of reception.
Synchronization status
Information The message is triggered cyclically (e.g. every 12 h) to document the current external
synchronization in the archive.
Synchronization status (change)
Information The synchronization status has changed.
System start
System The system has been started. The message is triggered during the system start.
TFTP file requested
Information A file has been requested via TFTP.
(E.g. firmware update, Web-data update etc.)
TFTP file received
Information A file has been imported via TFTP.
(E.g. firmware update, Web-data update etc.)
TFTP file transferred
Information A file has been transferred from the device via TFTP.
(E.g. firmware update, Web-data update etc.)
Time initialized from hardware
Application An initial synchronization has been performed from the clock module.
Time set via HMI
Application Time domain(s) has/have been changed via HMI
12-9
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions

Technical data 13

Table 13-1 SICLOCK TC100, technical data
Dimensions 180.0 x 88.9 x 47.0 (W x H x D in mm)
Weight approx. 750 g
Supply voltage 24 VDC (-15% to +20%) at X1
Power supply continuous current 0.7 A max.
Transient voltage interruption 3 ms (at 20.4 to 28.8 V) max.
Power consumption 15 W max.
Power loss typically 7.5 W
External fuse 1 A slow-action
Degree of protection IP 20
Mounting type 35 mm standard mounting rail
EN 50022-35 mounting rail (15 mm high) or SIMATIC DIN rail
Safety
Product standard EN 61131-2 (environment)
Test voltage Circuits with nominal voltage Ue <50 V relative to other circuits or
ground, test voltage 500 VDC:
Protection class Protection class III according to EN 60536
Electrical safety EN 60950-1
Time of day characteristics
Accuracy in relation to
< 50 µs
GPS signal
Accuracy in relation to
< 1000 µs
DCF77 signal
Accuracy in case of loss of
< 50x10
-9
GPS signal
Accuracy in case of loss of
< 1x10
-6
DCF77 signal
Accuracy in case of power
< 4x10
-6
failure
Time-of-day correction by
< 50 µs/s
microsteps
Jitter in GPS operation < 200 ns/s
Reserve power See battery
Operating Instructions SICLOCK
®
TC100
13-9© Siemens AG 2010 All Rights Reserved
Technical data
Table 13-1 SICLOCK TC100, technical data
Battery
Service life in operation > 12 years
Service life when switched off
> 12 years
during storage
Service life when switched on
< 6 years, see Battery (Chapter 11.1)
during storage
Electromagnetic compatibility (EMC)
Radiated interference EN 55022 class A, FCC class A
Interference immunity EN 55024
Environmental characteristics
In operation EN 60721-3-3 (stationary use in weather-proof locations) class 3K3,
During storage/transport EN 60721-3-2 class 2K4
Climatic conditions
Temperature in operation 0°C to 55°C
Temperature during
-40°C to +70°C
storage/transport
Temperature gradient 10°C/h max. in operation, 20°C/h in storage, no condensation
Relative humidity
- Operation
- Storage / transport
Tested according to IEC 60068-2-78, IEC 60068-2-30
10% to 95% at 25°C (no condensation)
10% to 95% at 25°C (no condensation)
Atmospheric pressure 1080 to 795 hPa (corresponds to an elevation of -1000 to 2000 m)
Mech. environmental conditions
During operation EN 60721-3-3, class 3M3
During storage / transport EN 60721-3-2, class 2M2
Interfaces (see also Connection (Chapter 6))
Ethernet connection 1x Ethernet port, 10/100 Mbit/s, autonegotiation
8-pin terminal strip (see also Terminal assignment (Chapter 15.1))
Radio clock input
(short-circuit proof)
Rated current 20 mA to 40 mA, supply voltage 48 V for connecting to SICLOCK GPS1000, SICLOCK GPSDEC or SICLOCK DCFRS
The radio clock input is galvanically separated from the rest of the electronics.
1 relay output NC contact for
0.06 A, 48 VDC max.
WARNING signal
1 relay output NC contact for
0.06 A, 48 VDC max.
ALARM signal
13-9
© Siemens AG 2010 All Rights Reserved
SICLOCK
®
TC100 Operating Instructions
Technical data
Table 13-1 SICLOCK TC100, technical data
Status displays on the device
Display Two-line, alphanumeric LCD display with background lighting and
temperature-compensated contrast control
LED 1x orange LED for Ethernet port link-up
1x green LED for Ethernet port activity
1x green LED for radio clock status
1x green LED for POWER
1x green LED for SYNC status
1x red LED for FAULT status
Operator controls on the device
Buttons 1x MODE button
© Siemens AG 2010 All Rights Reserved SICLOCK
®
TC100 Operating Instructions
13-9
Loading...