Siemens SXL-EX Datasheet

Page 1
s
E
FireSafety&SecurityProducts
SXL-EX Fire Control Panel
Conventional Zone Fire Alarm Control Panel
• Four (4) zones ─ expandable to eight (8) zones
• Series 3 and 11 compatible detectors and
accessories
• Microprocessor-based control
• Factory programmed
• Two (2) Style Y notification appliance circuits
(NACs)
• 3 Amps notification and auxiliary power
• 24 and 60-hour battery backup
• Eight (8) ‘Form C’ relay-output option
• 220/240 VAC, 50 Hz power-supply option
• Remote serial-annunciator option
• Sprinkler supervisory service
• Non-silenceable bell service
• Alarm verification by zone
• One-person test feature
• Zone / output bypass feature
• Subsequent Alarm and Trouble commands with
24-hour reminders
• Alarm, Trouble and Supervisory last-event records
• UL 864 9th Edition Listed & ULC Listed;
CSFM Approved
ARCHITECT AND ENGINEER SPECIFICATIONS
─ field configurable
System Overview
Model SXL-EX from Siemens ─ Fire Safety is a microprocessor-based fire-alarm control panel (FACP) supplied with four (4) conventional zones, and is expandable to eight (8) conventional zones. Model SXL-EX also contains features, such as: field programmability; power-limited circuits, one-person person test; remote annunciation, and sufficient power to meet ADA requirements for signaling.
Model SXL-EX is designed to meet the varied fire­alarm needs for small office buildings, apartment buildings, department stores, hotels, strip malls or anywhere a cost-efficient, general-purpose FACP is required.
* AsterisksshowninthesecondcolumndenoteModelsDI‐3C;
‐11CandPE‐11TC,respectively,inCanada
P
s Industry, Inc.
Building Technologies Division
Additionally, the SXL-EX can be used to supply remote bell power for larger systems such as the MXL FACP.
Initiating Circuits
Model SXL-EX has four (4) conventional, Style B (Class B) zones, which are typically compatible with the ionization detector (Model DI-3*); the photoelectric detector (Model PE-11*) and the photo-thermal detector (Model PE-11T*); Siemens Fire Safety thermal, flame and beam detectors, and the MS Series of manual stations. (Please refer to the detector­compatibility list in the wiring diagram for specific compatibility questions).
SXL-EX
7906
Page 2
System Overview – (continued)
Any combination of 30 compatible smoke detectors can be combined on a given zone. Any number of thermal detectors, manual stations or other compatible direct shorting devices may be connected to each zone. All of these initiating devices can be mixed on the same zone, providing the total power requirement of the zone does not exceed 9mA supervisory current. Model SXL-EX has the additional capacity to support detector accessories such as: relays, remote alarm lamps and audible bases.
Initiating zones can be programmed for many functions. Alarm verification allows detector application in sensitive areas manual stations code. Manual station operation shall not be delayed on verified zones. Generic zone function allows the NACs in Model SXL-EX to follow the action of a master fire-alarm panel in the facility.
Initiating zones can also be bypassed as required for example during construction on the premises. The system is expanded through the (4) four-zone expander (Model SZE-4X), which has an additional four (4) initiating circuits, in addition to relays and open-collector outputs.
─ mixed on the zone, as allowed by
Notification Appliance Circuits
Model SXL-EX has two (2) Style Y (Class B) NACs, each rated at 1.5 Amps. The total power output of the panel, between the two (2) notification circuits and the auxiliary output, is limited to 3 Amps, which is sufficient to provide power for many applications requiring appliances designed to ADA specifications. The SXL-EX notification circuits are power limited to reduce installation costs without the addition of any hardware.
NACs can be programmed for various codes. These include: temporal / march time, simplified zone code, and number of rounds. They can also be inhibited during test and programming functions.
The two (2) circuits can be individually programmed as non-silenceable. This steady operation can be used for strobes that must continue operation after audible devices are silenced.
Relays and Outputs
Model SXL-EX has ‘Form C’ relays for general alarm and trouble commands, rated at 1 Amp, 30VDC. The
optional (4) four-zone expander module (Model SZE-4X) has an additional four (4) general purpose, programmable relays at 2 Amps, 30VDC / 120VAC. All remote operations in the fire-alarm system are controlled from Model SZE-4X or the relay module (SRC-8) Model SXL-EX enclosure.
─ each of which is situated within the actual
Visual and Audible Indicators
Model SXL-EX has visible LED annunciation by zone for alarm and trouble prompts.
s Industry, Inc.
Building Technologies Division
─ with or without
Additionally, there is a system alarm light-emitting diode (LED) and a system trouble LED. Supervisory zones utilize the zone trouble LED flashing in sync with a system supervisory LED to indicate an abnormal system event.
LEDs for AC power bypass and test / program mode are clustered with the system alarm, trouble and supervisory LEDs. A (7) seven-segment display and programming functions system trouble event. Trouble conditions are also annunciated by a piezo-electric sounder housed inside Model SXL-EX.
Remote annunciation is accomplished through a serial connection with Model LED-3 or Model LED-4, (8) eight­zone LED annunciators. Models LED-3 and LED-4 display alarm, supervisory and trouble conditions for eight (8) zones. A total of two (2) modules can be attached to each system. Model LED-3 comes with a black enclosure, while Model LED-4 uses a white enclosure.
─ used during testing
─ reports a code for each
Auxiliary Power
Model SXL-EX contains a 1/2 Amp auxiliary power circuit that is used to drive remote devices. The total power for Model SXL-EX, between the auxiliary output and the two (2) NACs, is 3 Amps.
Power Supply / Battery Charger
The power supply accepts a 120VAC, 60 Hz. Input or, optionally, a 220 / 240VAC, 50 Hz. Input. On loss of AC power, the system switches to battery operation, indicating a loss of power by flashing the AC power LED on the display. Battery capacities of 24 and 60 hours are available.
Manual Controls
Model SXL-EX has four (4) switches for acknowledging alarm, supervisory and trouble conditions; silencing NACs; resetting the system, and for the drill function. These switches are also used when programming the control unit.
Field Programmability and Test Functions
The following functions of Model SXL-EX are field programmable, and are generally not programmed in the unit, since the each unit is shipped ‘as received’ from the factory. Field programming is accomplished through the display, and does not require the use of a computer or any proprietary tools.
Initiating Circuits:
─ Alarm Verification by Zone; Zone Bypass; Supervisory Zone,
or Generic Zone [when Model SXL-EX is used to provide remote NACs]
Note: The default mode is an alarm-causing zone.
Notification Appliance Circuits:
─ Non-silenceable, Simple Zone Coding, March Time,
Temporal, Silence Inhibit, Cutoff Timers and Reminders
Note: The default mode is a steady signal.
Page 3
System Overview – (continued)
Details for Ordering
Outputs:
─ Bypass Outputs / Relays
System Programming:
─ Zone to Output Matrix and Password Maintenance
System-test features include: one-person test feature, a lamp test, search and clear of the alarm, trouble and supervisory history buffer.
Specifications
The fire-alarm control panel (FACP) shall be a Siemens Fire Safety SXL-EX; shall utilize conventional zones and shall be microprocessor based and fully field programmable. The base panel shall include four (4) initiating zones, relays for general alarm and trouble and two (2) power-limited notification circuits capable of a total of 3 Amps of power.
The system shall be expandable via an expander module (model SZE-4X), which contains an additional four (4) conventional zones; four (4) general-purpose relays and four (4) general-purpose, open-collector outputs.
The fire-alarm system shall have the following features: subsequent alarm and trouble prompts; one person test feature; brown out protection, and 24 or 60 hour battery backup. Model SXL-EX also has the following selectable features: supervisory zones; alarm verification by zone; non-latching zones; alarm,
trouble and supervisory history, NAC coding, alarm / trouble 24-hour reminder, and zone / output bypass.
Any initiating-device circuit shall have the capability of being mapped to any optional output, via the system­programming function.
The FACP shall be requirements of NFPA 72 for local fire alarm control for automatic or manual service, and for sprinkler supervisory and waterflow service.
Model SLX-EX shall meet NFPA 72 requirements for central-station service when connected to Model 5128 or Model 5129 digital fire communicator.
The system can alternately be expanded through the expander module (Model SZE-8AX), which has an additional four (4) Class A (Style D) initiating circuits. Model SZE-8AX also converts the four (4) initiating circuits and the two (2) notification circuits on the main SXL-EX to Style D (Class A) and Style Z (Class A), respectively.
UL / ULC Listed, and meet the
Model Number
(Black Enclosure)
SXL-EX-RED Planning Bill (Red Enclosure)
SXL-EX-DF Planning Bill (Dead Front, Black Enclosure)
(International, Black Enclosure)
Part
Number
500-695884 EN-SX Enclosure SXL-EX Planning Bill
500-696000 SXL-XLCON
500-696011 EN-SX Enclosure (Red) 600-696000 SXL-XLCON
500-695885 EN-SX Enclosure 500-696000 SXL-XLCON 500-695889 DF-SX Dead Front
500-695885 EN-SX Enclosure SXL-EX-INT
500-696010
Description
SXL-EX-INT Board, Transformer & Hardware
SXL Optional Modules
Model Number
SZE-4X 500-696006 SXL 4-Zone Expander (with outputs)
SZE-8AX 500-696007 SXL 8-Class “A” Zone Module
SRC-8 500-692972 SXL 8-Relay Module RPR-1 500-694998 Remote Polarized 24VDC Relay
SLT-1 500-093285 SXL Leased Line / Municipal Tie Module
MM-SX 500-696008 Meter Module for SXL-EX
LED-3 500-693062 LED-3 Annunciator
Part
Number
Description
(with SXL, MXL and System 3 FACPs)
SXL Control Equipment Components
SXL-XCON 500-696000 SXL-EX Board, Transformer & Hardware
SXL-XCON-INT
EN-SX 500-695884 SXL-EX Enclosure, Black
EN-SXR 500-696011 SXL-EX Enclosure, Red
DF-SX 500-695889 SXL-EX Dead Front Kit. Black Only
FT-SX 500-695890 SXL-EX Semi-Flush Trim Kit FT-SXR 500-696104 SXL-EX Semi-Flush Trim, Red SXL-AK 500-696358 SXL-EX / ENS-S Adapter Kit
SXL-MAIN 500-695992 SXL-X Main PCB Assembly Pkg.
500-696010
SXL-EX-INT Board, Transformer & Hardware
SXL Batteries & Power Supplies
BT-33 175-387141 6AH Battery Set
BT-34 175-387140 10AH Battery Set
BP-61 175-387194 15AH Battery Set
PAD-3 599-699189 P/S NAC EXT (6 Amps) PAD-3R 599-699190 P/S NAC EXT, Red
PAD-3-MB 500-699080 Main Board Only for PAD-3
EN-PAD 310-099073 Black Enclosure for PAD-3
EN-PADR 310-099150 Red Enclosure for PAD-3
PAD-3-UK 500-648449 PAD-3-UK Upgrade Kit
SXL Upgrade Kits
SXL-EX-UK 500-363009 SXL-EX-UK F/W Upgrade Kit
SLT-1-UK 500-699052 SLT-1F/W Upgrade Kit
LED-UK 500-696205 LED-3/4 Upgrade Kit
Digital Fire Communicators
5128C 500-693213 4-Channel Slave Communicator
5129 500-693214 4-Channel Communicator [in enclosure]
5230K 500-693215 Programmer / Annunciator [5128 / 5129]
TIK-5128 500-693218 (1) Dual-Pack-RJ331X Block & Cord
Note: Model BP-61 requires a separate enclosure (i.e. − BB-55)
s Industry, Inc.
Building Technologies Division
Page 4
Dimensional Data
s Industry, Inc.
Building Technologies Division
SXL‐EX[withDeadfrontEnclosure]
Page 5
SXL-EX Main Board Connection Diagram
Fuse Replacement Electrical Ratings
Model
Number
F1 105-217858 AC Input, 8 Amps F2 105-224090 Batteries, 15 Amps F3 105-280300 AUX Port, 0.75 Amps
Notes:
7. All field wiring must be in accordance with NFPA 70, Article 760.
8. Make no wiring connections while the system is powered.
9. Alarm Relay contacts are shown de-energized, and Trouble Relay contacts are shown energized. Suitable for resistive load only.
10. Auxiliary output rate 0.5 Amps @ +24VDC, filtered. Maximum line impedance of 5 ohms.
11. Combined current output for NAC1, NAC2 and auxiliary outputs is limited to 3.0 Amps.
12. Equipment connected to these terminals must be located within the same room.
13. Refer to the SXL-EX Operation, Installation and
Maintenance Manual (IOM): P/N 315-095997, for further
.
details
Part
Number
Description
Alarm / Trouble Relay
244 mmHg., 41 kPa @ 20°C
11.6 (ref std.: Air = 1)
1. No T-tapping allowed.
2. Connect standby batteries only to Terminals B+ and B-. The batteries may be installed in either the bottom of the cabinet, or in a UL Listed battery enclosure.
3. In all cases, the Siemens Fire Safety model number is the compatibility identifier, including the control panel, module(s), and all compatible initiating devices.
4. When using the SLT-1 module, not suitable for remote station protected premises service where separate transmission circuits are required for alarm, trouble and supervisory signals.
5. All power-limited wiring requires separation from non­power-limited wiring. Refer to the SXL-EX Power Limited Wiring Instructions: P/N 315-095994.
s Industry, Inc.
Building Technologies Division
Page 6
Compatibility Detectors Electrical Ratings
Detector
DI-3 / 3H 30 DB-3S 315-081943 DI-A3 / A3H 30 DB-3S 315-081943 DI-B3 / B3H 30 AD-31 315-093234
DT-3P-135 30 DB-3S 315-084401
DT-11 30
PB-119A 1 PB-1191B 315-095424
PE-3 / 3T
PE-11 / 11T
Quantity per Loop
30
30
Base
DB-11
DB-3S with
DB-ADPT
DB-3S
AD-3ILP
DB-11
DB-3S with
DB-ADPT
Installation Instructions
Part Number
315-095429 315-095429
315-090875 315-093234
315-094198 315-094198
Initiating Device Circuit
Voltage:
Supervisory Current:
Alarm Current:
Maximum line impedance of 25 ohms per IDC zoneAll IDC zones are supervised and power limited, per
NFPA 70, Article 760
Each IDC zone must use at least 18 AWG, 300V
insulation, color-coded wire for low-voltage circuits where local codes require conduit. Where local codes permit, use limited-energy shielded cable rated at 300V.
Each IDC zone will support one (1) initiating device
in alarm mode. The IDC zone compatibility is an unlimited number of shorting-type devices.
For smoke-detector compatibility, see: Compatible Detectors’ chart.
16.4 − 26.4VDC 9mA, max.
120mA, max.
Electrical Ratings
Notification Appliance Circuits (NACs)
Voltage:
Supervisory Current:
Alarm Current:
Each NAC is rated at 1.5 Amps, +24VDC. Maximum line impedance, 3.0 ohms per circuit All NACs are supervised.
Each NAC must use at least 14 AWG, 300V
insulation, color-coded wire.
All NACs are power limited per NFPA 70, Article
-
24VDC
1.5mA, max.
1.5A, max.
Model SZE-4X ‘Form C’ Relay
2.0 Amps @ 30 VDC, Resistive Only
0.5 Amps @ 30 VAC, Resistive Only
Open Collector
50mA, max. @ 26.4 VDC, max.
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.
s Industry, Inc.
Building Technologies Division
Fire Safety 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600 FAX: (908) 547-6877
URL: www.SBT.Siemens.com/FIS
(SII‐FS)
Printed in U.S.A.
Fire Safety 2 Kenview Boulevard Brampton, Ontario L6T 5E4 / Canada Tel: (905) 799-9937
FAX: (905) 799-9858
October 2010
Supersedes sheet dated 5/02
(Rev. 1)
Loading...