Siemens SITRANS TS100, SITRANS TSthermowell, SITRANS TS200, SITRANS TS300, SITRANS TS500 Compact Operating Instructions

...
Page 1
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
SITRANS

Temperature sensors TS100/TS200/TS300/TS500/TSinse rt/TSthermowell

Compact Operating Instructions
01/2018
A5E03920348
Introduction
1
Safety notes
2
Description
3
Installing
4
Connecting
5
Commissioning
6
Service and maintenance
7
Technical data
8
Dimension drawings
9
Appendix
A
-AE
Page 2
Siemens AG Division Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY
Document order number: A5E03920348
Ⓟ
Copyright © Siemens AG 2018. All rights reserved
Legal information
Warning notice system
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
Qualified Personnel
personnel qualified
Proper use of Siemens products
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
Disclaimer of Liability
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
The product/system described in this documentation may be operated only by task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Note the following:
documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
for the specific
03/2018 Subject to change
Page 3
Table of contents
1 Introduction ............................................................................................................................................. 7
2 Safety notes .......................................................................................................................................... 11
3 Description ............................................................................................................................................ 17
4 Installing ............................................................................................................................................... 23
1.1 Purpose of this documentation ................................................................................................. 7
1.2 Scope of this documentation .................................................................................................... 7
1.3 Document history ...................................................................................................................... 8
1.4 Checking the consignment ....................................................................................................... 8
1.5 Security information .................................................................................................................. 9
1.6 Transportation and storage ....................................................................................................... 9
1.7 Notes on warranty ................................................................................................................... 10
2.1 Preconditions for use .............................................................................................................. 11
2.1.1 Laws and directives ................................................................................................................ 11
2.1.2 Conformity with European directives ...................................................................................... 12
2.2 Improper device modifications ................................................................................................ 12
2.3 Requirements for special applications .................................................................................... 13
2.4 Use in hazardous areas .......................................................................................................... 13
2.4.1 Qualified personnel for hazardous area applications ............................................................. 13
2.5 Use in flameproof enclosures "d" and protection in enclosures "tb" ....................................... 14
2.5.1 For SITRANS TS500 .............................................................................................................. 15
2.5.2 For SITRANS TSinsert/TS100/TS200/TS500 ........................................................................ 16
3.1 Overview ................................................................................................................................. 17
3.2 Application .............................................................................................................................. 18
3.3 Functional principles ............................................................................................................... 18
3.4 Nameplate structure ................................................................................................................ 18
3.5 Temperature transmitter for SITRANS TS500 ........................................................................ 19
3.6 Measuring inserts for SITRANS TS500 .................................................................................. 20
3.7 Connection heads for SITRANS TS500 ................................................................................. 21
4.1 Basic safety notes ................................................................................................................... 23
4.1.1 Installation and location requirements .................................................................................... 24
4.1.2 Proper mounting ..................................................................................................................... 25
4.2 Install ....................................................................................................................................... 27
4.3 Install SITRANS TS300 Clamp-on .......................................................................................... 29
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
3
Page 4
Table of contents
5 Connecting ........................................................................................................................................... 31
6 Commissioning ..................................................................................................................................... 39
7 Service and maintenance ...................................................................................................................... 41
8 Technical data ...................................................................................................................................... 45
9 Dimension drawings .............................................................................................................................. 65
4.4 Disassembly ........................................................................................................................... 30
5.1 Basic safety notes .................................................................................................................. 31
5.1.1 For SITRANS TSinsert ........................................................................................................... 34
5.1.2 For SITRANS TSinsert/TS100/TS200/TS500 ........................................................................ 34
5.1.3 For SITRANS TS100/TS200 .................................................................................................. 34
5.1.4 For SITRANS TS500 ............................................................................................................. 35
5.2 Electrical connection .............................................................................................................. 35
5.3 Electrical connection of resistance thermometers ................................................................. 36
5.4 Electrical connection of thermocouples ................................................................................. 37
5.5 Electrical connection of connectors ....................................................................................... 37
6.1 Basic safety notes .................................................................................................................. 39
6.2 Commissioning....................................................................................................................... 40
7.1 Cleaning ................................................................................................................................. 43
7.2 Return procedure ................................................................................................................... 43
7.3 Disposal ................................................................................................................................. 44
8.1 Rated conditions .................................................................................................................... 45
8.1.1 Maximum permissible ambient temperatures in the connection area of the sensor ............. 45
8.1.1.1 General limitations for compression fittings ........................................................................... 45
8.1.1.2 SITRANS TS100 .................................................................................................................... 46
8.1.1.3 SITRANS TS500 .................................................................................................................... 47
8.1.2 Maximum permitted sample temperatures within the process .............................................. 54
8.1.3 Measuring range .................................................................................................................... 56
8.2 Construction ........................................................................................................................... 56
8.3 Electrical data ......................................................................................................................... 57
8.4 Measuring tolerances for resistance thermometers ............................................................... 58
8.5 Measuring accuracy for thermocouples ................................................................................. 59
8.6 Certificates and approvals ..................................................................................................... 60
8.6.1 SITRANS TSInsert/TS100/TS200/TS500 .............................................................................. 60
8.6.2 SITRANS TS500 .................................................................................................................... 62
9.1 Overview ................................................................................................................................ 65
9.2 SITRANS TS100 .................................................................................................................... 69
9.3 SITRANS TS200 .................................................................................................................... 70
9.4 SITRANS TS300 .................................................................................................................... 71
9.5 SITRANS TS500 .................................................................................................................... 75
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
4 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 5
Table of contents
A Appendix............................................................................................................................................. 107
Index................................................................................................................................................... 109
9.5.1 SITRANS TS500, types 2 and 2N .......................................................................................... 75
9.5.2 SITRANS TS500, types 2G and 2F ........................................................................................ 76
9.5.3 SITRANS TS500, type 3 ......................................................................................................... 77
9.5.4 SITRANS TS500, types 3G and 3F ........................................................................................ 78
9.5.5 SITRANS TS500, types 4 and 4F ........................................................................................... 79
9.5.6 SITRANS TS500, type ST, threaded tapered well (7MC65..) ................................................ 81
9.5.7 SITRANS TS500, type SST, threaded tapered well (7MC55..) .............................................. 82
9.5.8 SITRANS TS500, type SS, threaded straight well (7MC65..)................................................. 84
9.5.9 SITRANS TS500, type SS, threaded straight well (7MC55..)................................................. 85
9.5.10 SITRANS TS500, type SR, threaded reduced well (7MC65..) ............................................... 86
9.5.11 SITRANS TS500, type SR, threaded reduced well (7MC55..) ............................................... 87
9.5.12 SITRANS TS500, type FT, flanged tapered well (7MC65..) ................................................... 88
9.5.13 SITRANS TS500, type FST, flanged tapered well (7MC55..)................................................. 89
9.5.14 SITRANS TS500, type FS, flanged straight well (7MC65..) ................................................... 91
9.5.15 SITRANS TS500, type FS, flanged straight well (7MC55..) ................................................... 92
9.5.16 SITRANS TS500, type FR, flanged reduced well (7MC65..) .................................................. 93
9.5.17 SITRANS TS500, type FR, flanged reduced well (7MC55..) .................................................. 94
9.5.18 SITRANS TS500, type SWT, socket tapered well (7MC65..) ................................................. 95
9.5.19 SITRANS TS500, type SWST, socket tapered well (7MC55..) .............................................. 96
9.5.20 SITRANS TS500, type SWS, socket straight well (7MC65..) ................................................. 98
9.5.21 SITRANS TS500, type SWS, socket straight well (7MC55..) ................................................. 99
9.5.22 SITRANS TS500, type SWR, socket reduced well (7MC65..).............................................. 100
9.5.23 SITRANS TS500, type SWR, socket reduced well (7MC55..).............................................. 101
9.5.24 SITRANS TS500 for installation in existing protective tubes ................................................ 102
9.5.25 SITRANS TS500, type GP, general purpose, no well .......................................................... 104
9.6 SITRANS TSinsert - measuring inserts for SITRANS TS500............................................... 105
A.1 Certificates ............................................................................................................................ 107
A.2 Technical support .................................................................................................................. 107
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
5
Page 6
Table of contents
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
6 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 7
1
1.1

Purpose of this documentation

See also
1.2

Scope of this documentation

Article nr.
Product
7MC72..
SITRANS TS200
7MC80..
SITRANS TS300
7MC75..
SITRANS TS500 (European portfolio)
7MC65..
SITRANS TS500 (North American portfolio)
7MC55..
SITRANS TS500 (Asian portfolio)
7MC.01..
TSinsert
7MT..
TSthermowell
These instructions contain all information required to commission and use the device. Read the instructions carefully prior to installation and commissioning. In order to use the device correctly, first review its principle of operation.
The instructions are aimed at persons mechanically installing the device, connecting it electronically, configuring the parameters and commissioning it, as well as service and maintenance engineers.
The temperature sensor has a modular design. If you integrate a transmitter or a display, read the instructions of the transmitter and/or the display.
Instructions and manuals (http://www.siemens.com/processinstrumentation/documentation)
7MC71.. SITRANS TS100
"7MC../7MT.." stands for:
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
7
Page 8
Introduction
1.3
Document history
Edition
Remark
01/2018
TSthermowell added
1.4

Checking the consignment

WARNING
Using a damaged or incomplete device

1.3 Document history

The following table shows major changes in the documentation compared to the previous edition.
The most important changes in the documentation when compared with the respective previous edition are given in the following table.
10/2016 Technical data for rated conditions changed
1. Check the packaging and the delivered items for visible damages.
2. Report any claims for damages immediately to the shipping company.
3. Retain damaged parts for clarification.
4. Check the scope of delivery by comparing your order to the shipping documents for correctness and completeness.
Risk of explosion in hazardous areas.
• Do not use damaged or incomplete devices.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
8 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 9
Introduction
1.5
Security information
1.6

Transportation and storage

NOTICE
Insufficient protection during storage

1.5 Security information

Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines, and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit: https://www.siemens.com/industrialsecurity
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under https://www.siemens.com/industrialsecurity.
To guarantee sufficient protection during transport and storage, observe the following:
● Keep the original packaging for subsequent transportation.
● Devices/replacement parts should be returned in their original packaging.
● If the original packaging is no longer available, ensure that all shipments are properly
packaged to provide sufficient protection during transport. Siemens cannot assume liability for any costs associated with transportation damages.
The packaging only provides limited protection against moisture and infiltration.
• Provide additional packaging as necessary.
Special conditions for storage and transportation of the device are listed in Technical data (Page 45).
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
9
Page 10
Introduction
1.7
Notes on warranty
See also

1.7 Notes on warranty

The contents of this manual shall not become part of or modify any prior or existing agreement, commitment or legal relationship. The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty.
The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.
Contacts (http://www.siemens.com/processinstrumentation/contacts)
SITRANS T product information (http://www.siemens.com/sitranst)
Instructions and manuals (http://www.siemens.com/processinstrumentation/documentation)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
10 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 11
2
2.1

Preconditions for use

Symbol
Description
Pay attention to the operat
2.1.1

Laws and directives

SITRANS TSthermowell
This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety.
Observe the information and symbols on the device. Do not remove any information or symbols from the device. Always keep the information and symbols in a completely legible state.
ing instructions
Observe the safety rules, provisions and laws applicable in your country during connection, assembly and operation. These include, for example:
● National Electrical Code (NEC - NFPA 70) (USA)
● Canadian Electrical Code (CEC) (Canada)
Further provisions for hazardous area applications are for example:
● IEC 60079-14 (international)
● EN 60079-14 (EU)
The thermowell is affected by the static, dynamic and chemical load from the process parameters including static and dynamic load, flow induced vortexes. This has influence on the shape of the thermometer, stem diameter and insertion length.
Observe the test certification, provisions and laws applicable in your country during connection, assembly and operation. These include:
● ASME PTC 19.3
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
● DIN 43772 Annex 1-2
● AD-directive
● VDI/VDE 3511-5
11
Page 12
Safety notes
2.1.2

Conformity with European directives

Electromagnetic compatibi i 2014/30/EU
Directive of the European Parliament and of the Council on the approximation of the laws of the Member States relating to elec­tromagnetic compatibility and repealing Directive 89/336/EEC.
Atmosphère explosible ATEX 2014/34/EU
Directive of the European Pa approximation of the laws of the Member States concerning equipment and protective systems intended for use in pote ly explosive atmospheres.
See also
2.2
Improper device modifications
WARNING
Improper device modifications

2.2 Improper device modifications

In critical applications, a thermowell stress calculation is recommended:
● ASME PTC 19.3-TW2016
● Dittrich/Klotter-method engineering service
The CE marking on the device symbolizes the conformity with the following European directives:
l-
ty EMC
rliament and the Council on the
The applicable directives can be found in the EC conformity declaration of the specific device.
ntial-
Certificates (Page 107)
Risk to personnel, system and environment can result from modifications to the device, particularly in hazardous areas.
• Only carry out modifications that are described in the instructions for the device. Failure to observe this requirement cancels the manufacturer's warranty and the product approvals.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
12 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 13
Safety notes
2.3
Requirements for special applications
Note Operation under special ambient conditions
We highly recommend that you contact your Siemens representative or our application department before you operate the device under special ambient conditions as can be encountered in nuclear power plants or when the device is used for research and developm
2.4

Use in hazardous areas

2.4.1

Qualified personnel for hazardous area applications

Qualified personnel for hazardous area applications
WARNING
Use in hazardous area

2.3 Requirements for special applications

Due to the large number of possible applications, each detail of the described device versions for each possible scenario during commissioning, operation, maintenance or operation in systems cannot be considered in the instructions. If you need additional information not covered by these instructions, contact your local Siemens office or company representative.
ent purposes.
Persons who install, connect, commission, operate, and service the device in a hazardous area must have the following specific qualifications:
● They are authorized, trained or instructed in operating and maintaining devices and systems according to the safety regulations for electrical circuits, high pressures, aggressive, and hazardous media.
● They are authorized, trained, or instructed in carrying out work on electrical circuits for hazardous systems.
● They are trained or instructed in maintenance and use of appropriate safety equipment according to the pertinent safety regulations.
Risk of explosion.
• Only use equipment that is approved for use in the intended hazardous area and labelled accordingly.
• Don't use devices that have been operated outside the conditions secified for hazardous areas. If you have used the device outside the conditions for hazardous areas permanently make all Ex markings unrecognizable on the nameplate.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
13
Page 14
Safety notes
See also
WARNING
Loss of safety of device with type of protection "Intrinsic safety Ex i"
2.5
Use in flameproof enclosures "d" and protection in enclosures "tb"
WARNING
Impermissible repair of explosion protected devices
WARNING
Electrostatic charge

2.5 Use in flameproof enclosures "d" and protection in enclosures "tb"

Technical data (Page 45)
If the device has already been operated in non-intrinsically safe circuits or the electrical specifications have not been observed, the safety of the device is no longer ensured for use in hazardous areas. There is a risk of explosion.
• Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe circuit.
• Observe the specifications for the electrical data on the certificate and/or in Technical data (Page 45).
Risk of explosion in hazardous areas
• Repair must be carried out by Siemens authorized personnel only.
Risk of explosion in hazardous areas if electrostatic charges develop, for example, when cleaning plastic surfaces with a dry cloth.
• Prevent electrostatic charging in hazardous areas.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
14 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 15
Safety notes
2.5.1

For SITRANS TS500

2.5 Use in flameproof enclosures "d" and protection in enclosures "tb"
● The enclosures types AG0, AH0, AU0, AV0 and SITRANS TF of the temperature sensors, series TS500 have to be connected by means of suitable cable entry fittings or conduit systems, which meet the requirements of IEC/EN 60079-1, sections 13.1 and
13.2, and for which a separate examination certificate has been issued.
● Cable entry fittings (conduit threads) and sealing plugs of simple design must not be used in the transmitter and receiver enclosures.
● Any openings in the transmitter and receiver enclosures that are not used must be closed as specified in IEC/EN 60079-1, section 11.9.
● The connecting lead of enclosures types AG0, AH0, AU0, AV0 and SITRANS TF of the temperature sensors, series TS500, must be installed to provide for permanent wiring and adequate protection against damage.
● If the temperature at entry fittings should exceed 60 °C, the connecting cables used have to be of the temperature-resistant type.
● If connection is made in the potentially explosive area, the connecting cable (unconnected cable end) of the enclosure types AG0, AH0, AU0, AV0 and TF of the temperature sensors, series TS500, must be connected in an enclosure that meets the requirements of an approved type of protection as specified in IEC/EN 60079-0, section
1.
● All models are to be mounted within Thermowells suitably rated for the application they are used.
● If a SITRANS TS500 with XP type of protection is combined with a thermowell, consider the ASME PTC19.3 and a minimum wall thickness of 1 mm.
● To separate zone 1 from zone 2 in a hazardous area, consider a wall thickness of ≥ 1 mm with austenitic steel. In addition, consider the existing process conditions. If a thermowell installed correctly and tight at Zone 0, the sensor that is screwed in this thermowell needs at least zone 1 approval.
● Suitably rated Thermowells are to have thread engagement of 5 full turns wrench tight.
● Notes to this effect must accompany each device in an adequate form.
● Components attached or installed (terminal compartments, bushings, cable entry fittings,
connectors) must be of a technical standard that complies with the specifications on the Certificate of Conformity as a minimum, and a separate examination certificate must have been issued for them.
● Use the device to measure temperature in accordance with the technical data for maximum permitted ambient temperatures in the connection area of the sensor. See chapter Gas hazardous area: Ex d / XP (Page 52) and Dust hazardous area: Ex i / IS / Ex tb / DIP (Page 53).
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
15
Page 16
Safety notes
2.5.2

For SITRANS TSinsert/TS100/TS200/TS500

NOTICE
Ambient temperature too high
2.5 Use in flameproof enclosures "d" and protection in enclosures "tb"
Damage to cable sheath.
• At an ambient temperature ≥ 60 °C (140 °F), use heat-resistant cables suitable for an ambient temperature at least 20 °C (36 °F) higher.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
16 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 17
3
3.1

Overview

SITRANS TS product family
①
general use, compact design with connecting cable
②
general use, compact design
③
general use, modular design with connection head (European portfolio/ Chinese portfolio)
④
SITRANS TSinsert measuring insert for use in the SITRANS TS500 series
⑤
general use, modular design with connection head (North American portfolio/ Chinese portfolio)
SITRANS TS100 7MC71..
SITRANS TS200 7MC72..
SITRANS TS500 7MC75../7MC55..
SITRANS TS500 7MC65../7MC55..
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
17
Page 18
Description
Elementary sensors
3.2
Application
3.3

Functional principles

3.4

Nameplate structure

Positioning of nameplate
Note SITRANS TS100/TS200 nameplate
Before commissioning, make sure the nameplate is securely fas sensor in a visible location.
Device
Positioning of the nameplate
outer periphery of the ANSI adapter.
SITRANS TS100 7MC71..
On the sensor cable

3.2 Application

Resistance thermometers or thermocouples can be used for temperature measurement.
The temperature sensors of the SITRANS TS product family are used for measuring temperatures in industrial plants.
Depending on the specifications, sensors can be combined with different connection heads, extension tubes, and process connections. This makes the sensors suitable for a variety of process engineering applications, in the following sectors:
● Petrochemical industry
● Pharmaceuticals industry
● Biotechnology
● Food production
Two different measuring principles are used for measuring temperatures.
● With resistance thermometers, the temperature is measured as a change in resistance. Resistance thermometers, also called Resistance Temperature Devices (RTD), contain sensor elements, like the Pt100 sensor elements in accordance with IEC 60751.
● With thermocouples, the temperature is the change in voltage (Seebeck effect). The thermocouples are in accordance with IEC 584/DIN EN 60584.
tened to the temperature
SITRANS TSinsert 7MC701. On the bottom of the connecting plate or at the
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
18 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 19
Description
Device
Positioning of the nameplate
SITRANS TS200 7MC72..
On the connector or on the sensor
Example of nameplate
①
②
code)
③
Additional information on the type
④
Valid standard for the device
⑤
Serial number
⑥
CE marking
⑦
Place of manufacture
⑧
Consult the operating instructions.
⑨
tection/electrical data
⑩
3.5
Temperature transmitter for SITRANS TS500
Transmitter
Features
Sensor

3.5 Temperature transmitter for SITRANS TS500

SITRANS TS500 7MC.5.. On the connection head
Product name
Order number (machine-readable product
Type-specific information Explosion pro-
Manufacturer´s specifications
The following head-mounted transmitters can be combined with the temperature sensors SITRANS TS500:
1)
TH100
TH200
• Base device
• Output 4 ... 20 mA
• Can be configured using simple software
: 12.5 mW
• P
o
• Universal device
• Output 4 ... 20 mA
• Can be configured using simple software
: 37 mW
• P
o
only
1)
or 2)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
19
Page 20
Description
Transmitter
Features
Sensor
1)
Resistance thermometers
2)
Thermocouple
Note SITRANS TS500 IEC Ex
If the contained SITRANS TH transmitter is not IEC Ex compliant, the TS500 nameplate has ATEX marking only.
3.6
Measuring inserts for SITRANS TS500

3.6 Measuring inserts for SITRANS TS500

TH300
TH400
• Universal
• Output 4 ... 20 mA / HART
• Diagnostic functions
: 37 mW
• P
o
• Output: PROFIBUS PA or FOUNDATION Fieldbus
• Sensor redundancy
• Diagnostics
: 12 mW
• P
o
1)
or 2)
1)
or 2)
Measuring inserts for SITRANS TS500 temperature sensors are available in three variants:
● Variant 1:
DIN mounting disk for accommodating a transmitter or ceramic socket.
● Variant 2:
Fixed connection of the ends of the mineral insulated cable with a DIN ceramic socket.
● Variant 3:
Measuring insert in a spring-loaded adapter (ANSI).
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
20 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 21
Description
3.7
Connection heads for SITRANS TS500

3.7 Connection heads for SITRANS TS500

The transmitters can be mounted in connection heads of type B and bigger. The following mounting types are possible:
● Measuring insert mounting
– Standard type with compact design
– Measuring insert (sensor) and transmitter form one unit
Figure 3-1 Measuring insert mounting of transmitter
● Hinged cover mounting
– Standard type for connection heads of type BC0: B head with high hinged cover
– Separate maintenance of the measuring insert and the transmitter is possible.
Figure 3-2 Hinged cover mounting of transmitter
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
21
Page 22
Description
3.7 Connection heads for SITRANS TS500
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
22 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 23
4
4.1

Basic safety notes

WARNING
Exceeded maximum permissible operating pressure
WARNING
Unsuitable connecting parts
See also
CAUTION
Gasket between extension and protective tube
WARNING
Incorrect mounting at Zone 0
Risk of injury or poisoning.
The maximum permissible operating pressure depends on the device version, pressure limit and temperature rating. The device can be damaged if the operating pressure is exceeded. Hot, toxic and corrosive process media could be released.
Ensure that maximum permissible operating pressure of the device is not exceeded. Refer to the information on the nameplate and/or in Technical data (Page 45).
Risk of injury or poisoning.
In case of improper mounting, hot, toxic, and corrosive process media could be released at the connections.
• Ensure that connecting parts (such as flange gaskets and bolts) are suitable for connection and process media.
Technical data (Page 45)
• Use gasket between device extension and protective tube only once.
Risk of explosion in hazardous areas.
• Ensure sufficient tightness at the process connection.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
• Observe the standard IEC/EN 60079-14.
23
Page 24
Installing
CAUTION
Hot surfaces resulting from hot process media
CAUTION
External stresses and loads
4.1.1

Installation and location requirements

CAUTION
High vibration area
CAUTION
Direct sunlight
4.1 Basic safety notes
Risk of burns resulting from surface temperatures above 65 °C (149 °F).
• Take appropriate protective measures, for example contact protection.
• Make sure that protective measures do not cause the maximum permissible ambient
temperature to be exceeded. Refer to the information in Technical data (Page 45).
Damage to device by severe external stresses and loads (e.g. thermal expansion or pipe tension). Process media can be released.
• Prevent severe external stresses and loads from acting on the device.
Especially with the stainless steel housing version of TS500, use short extensions or external supports when used in a high vibration area.
When TS100/200 sensors are installed in a high vibrating area, use also external supports to fix the probe stem: the unsupported length must not exceed 150 mm and the free end must not exceed 100 mm.
Device damage.
The device can overheat or materials become brittle due to UV exposure.
• Protect the device from direct sunlight.
• Make sure that the maximum permissible ambient temperature is not exceeded. Refer
to the information in Technical data (Page 45).
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
24 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 25
Installing
CAUTION
Process load
4.1.2

Proper mounting

DANGER
Protective tube ruptures
WARNING
Electrostatic charge
Note Penetration of water into the plastic head type BM0
Device failure.
•
4.1 Basic safety notes
The thermowell is affected by the static, dynamic and chemical load from the process parameters, e.g. static and dynamic load, flow induced vortexes. This has influence to the shape of the thermometer, stem diameter and insertion length.
Ensure that the applicable and relevant directives and standards are respected, e.g. ASME PTC 19.3, DIN43772 Annex 1-2, AD-directive, VDI/VDE 3511-5.
In critical applications, a thermowell stress calculation according ASME PTC 19.3-TW2016 or Dittrich/Klotter-method is recommended as an engineering service.
Protective tubes that are not suitable for the process or application in question can rupture and result in serious damage to property and personal injuries.
• Make sure that the protective tube is suitable for the respective mounting method and application. If necessary, check the selection and order data of your protective tube.
Danger of explosion in hazardous areas if electrostatic charges develop, for example, in strong airflows in close proximity to belt conveyors.
• Avoid electrostatic charge at the plastic head type BM0 when defining the installation site.
To reach IP54 with a plastic head type BM0, make sure that the mounting angle is in the
range of -14 to 194° (208°, see image below).
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
25
Page 26
Installing
CAUTION
Loss of IP protection
NOTICE
Incorrect mounting
4.1 Basic safety notes
Figure 4-1 Mounting angle of plastic head type BM0
Do not unscrew the device housing from the mounted parts with NPT threaded connection.
The device can be damaged, destroyed, or its functionality impaired through improper mounting.
• Before installing, ensure there is no visible damage to the device.
• Make sure that process connectors are clean, and suitable gaskets and glands are
used.
• Mount the device using suitable tools. Refer to the information in Technical data (Page 45) for installation torque requirements.
• Avoid temperature or mechanical shocks during mounting.
• Avoid excessive force or damaging of the on-site mechanical connections.
• Do not deform or adapt the thermowells.
• The use of additive seal or sealant (not in scope of delivery) is recommended between
sensor and thermowell.
• Thermowells from carbon steel are protected against corrosion. Clean the thermowell before mounting to avoid poisoning of the sensor and mounting problems.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
26 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 27
Installing
Note Loss of degree of protection
Damage to device if the enclosure is open or not properly closed. The degree of protection specified on the nameplate is no longer guaranteed.
4.2
Install
Condition
Procedure

4.2 Install

Prior to mounting, make sure that the device is appropriately applied for the process connection, media compatibility, temperature resistance and measuring range. See chapter Technical data (Page 45).
1. Prevent faults caused by heat dissipation in non-representative placings by observing the following rules:
2. Select an optimal immersion depth. Estimate the immersion depth using the formulas in Table 8-16 Estimation of immersion depth (Page 57).
If the flow rate allows, sensor placing between 1/3 and 1/2 of the pipe diameter is recommended.
3. If the process load on the thermowell allows the exposition, select a measurement location with a high flow rate.
4. Ensure sufficient thermal insulation of the external components of the thermometer.
5. Ensure that external parts have as small surfaces as possible.
6. Select the optimum mounting position for the process in question.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
27
Page 28
Installing
①
At a right angle to the flow
②
In a bend upstream
③
In an angle upstream
See also
4.2 Install
7. With small pipe diameters, mount the sensors upstream at an angle ③ or upstream in a
②.
bend
Figure 4-2 Possible mounting positions of the sensor
8. Use required torque values between device extension and protective tube as in Table 8­14 Torque values between device extension and protective tube (Page 56).
– If customer adjustments are necessary (M24 connections only), use required torque
values between device head and extension as in Table 8-15 Torque values between device head and extension (Page 56).
– For SITRANS TS500 barstock version (only European portfolio 7MC752..) without
flange (type 4), use required torque values to complete the mounting of the device extension to the protective tube as in Table 8-14 Torque values between device extension and protective tube (Page 56).
Construction (Page 56)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
28 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 29
Installing
4.3
Install SITRANS TS300 Clamp-on
Note Measurement position
Install on circular pipes only. Avoid installation next to angled pipes, near slide valves, valves, pum

4.3 Install SITRANS TS300 Clamp-on

ps, etc.
1. Define the measurement position.
2. Apply heat sink compound to the metallic part of the temperature sensor.
3. For standard version: halved pipe collar allows for quick and easy mounting on the pipe
using two mounting screws. For bracket version: mount on pipe using one mounting screw.
– If the pipe is not fully occupied by medium during installation, mount the temperature
sensor on the underside of the pipe.
4. Firmly tighten the mounting screws (4 Nm torque).
5. Mount the vibration protection and hand-tighten.
– You can remove the measuring insert only after you have released the RTD recessed
grip screw(s).
– Do not twist the housing.
– Use RTD recessed grip screw for installation, only.
– Do not apply force to the transmitter housing (e. g. during opening/closing of lid).
– Because the locking plugs are fitted with internal gaskets, they are only suited for
ambient temperatures to 100 °C (212 °F).
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
29
Page 30
Installing
4.4
Disassembly
WARNING
Incorrect disassembly

4.4 Disassembly

The following risks may result from incorrect disassembly:
- Injury through electric shock
- Risk through emerging media when connected to the process
- Risk of explosion in hazardous area
In order to disassemble correctly, observe the following:
• Before starting work, make sure that you have switched off all physical variables such as pressure, temperature, electricity etc. or that they have a harmless value.
• If the device contains hazardous media, it must be emptied prior to disassembly. Make sure that no environmentally hazardous media are released.
• Secure the remaining connections so that no damage can result if the process is started unintentionally.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
30 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 31
5
5.1

Basic safety notes

WARNING
Unsuitable cables, cable glands and/or plugs
See also
WARNING
Incorrect selection of type of protection
WARNING
Improper power supply
Risk of explosion in hazardous areas.
• Use only cable glands/plugs that comply with the requirements for the relevant type of
protection.
• Tighten the cable glands in accordance with the torques specified in Construction
(Page 56).
• Close unused cable inlets for the electrical connections.
• When replacing cable, glands use only cable glands of the same type.
• After installation, check that the cables are seated firmly.
Technical data (Page 45)
Risk of explosion in areas subject to explosion hazard.
This device is approved for several types of protection.
1. Decide in favor of one type of protection.
2. Connect the device in accordance with the selected type of protection.
3. In order to avoid incorrect use at a later point, make the types of protection that are not
used permanently unrecognizable on the nameplate.
Risk of explosion in hazardous areas as result of incorrect power supply, e.g. using direct current instead of alternating current.
• Connect the device in accordance with the specified power supply and signal circuits.
The relevant specifications can be found in the certificates, in Electrical data (Page 57) or on the nameplate.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
31
Page 32
Connecting
WARNING
Lack of equipotential bonding
Exception
WARNING
Unprotected cable ends
WARNING
Loss of degree of protection
WARNING
Lemo plug in hazardous areas
WARNING
Improper laying of shielded cables
5.1 Basic safety notes
Risk of explosion through compensating currents or ignition currents through lack of equipotential bonding.
• Ensure that the device is potentially equalized.
: It may be permissible to omit connection of the equipotential bonding for devices
with type of protection "Intrinsic safety Ex i".
Risk of explosion through unprotected cable ends in hazardous areas.
• Protect unused cable ends in accordance with IEC/EN 60079-14.
When connecting the SITRANS TS100 or TS200 with type protection "Intrinsically safe", ensure the following:
• Adhere to the requirements for electrical connection seperation.
• Use IP54 rated enclosure.
For Lemo plug version (7MC7xxx-xxxx2-xxx) make sure the cable ends are in an environment free from dust, water, or shock.
Risk of explosion through compensating currents between hazardous area and the non-hazardous area.
• Shielded cables that cross into hazardous areas should be grounded only at one end.
• If grounding is required at both ends, use an equipotential bonding conductor.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
32 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 33
Connecting
WARNING
Connecting device in energized state
Exceptions
Note Electromagnetic compatibility (EMC)
You can use this device in industrial environments, households and small businesses.
For metal housings there is an increased electromagnetic compatibility compared to high frequency radiation. This protection can be increased by grounding the housing, see Electrical connection
Note Improvement of interference immunity
•
•
•
•
•
5.1 Basic safety notes
Risk of explosion in hazardous areas.
• Connect devices in hazardous areas only in a de-energized state.
:
• Devices having the type of protection "Intrinsic safety Ex i" may also be connected in
energized state in hazardous areas.
• Exceptions for type of protection "Non-sparking nA" (Zone 2) are regulated in the
relevant certificate.
-
(Page 35).
Lay signal cables separate from cables with voltages > 60 V. Use cables with twisted wires. Keep device and cables at a distance from strong electromagnetic fields. Take account of the conditions for communication specified in the Technical data
(Page 45).
Use shielded cables to guarantee the full specification according to HART/PA/FF.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
33
Page 34
Connecting
5.1.1

For SITRANS TSinsert

WARNING
Flying leads
greater than 500 V.
5.1.2

For SITRANS TSinsert/TS100/TS200/TS500

NOTICE
Ambient temperature too high
5.1.3

For SITRANS TS100/TS200

WARNING
Use of plug connectors in explosive dust atmosphere
5.1 Basic safety notes
Risk of explosion in hazardous areas due to loss of Intrinsic Safety protection.
• Shorten the ends of flying leads to the appropriate length.
• Keep a minimal clearance of 2 mm between the wires of different circuits, or any circuit
and the grounded enclosure.
- or ­Use heat shrinking tubes TFE-R 1/8": wall thickness ≥ 0.2 mm, di-electrical strength
Damage to cable sheath.
• At an ambient temperature ≥ 60 °C (140 °F), use heat-resistant cables suitable for an ambient temperature at least 20 °C (36 °F) higher.
Danger of explosion.
Temperature sensors of the SITRANS TS100 and SITRANS TS200 series must not be used together with plug connectors in atmospheres with combustible dust.
• Do not use plug connectors in areas with combustible dust.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
34 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 35
Connecting
5.1.4

For SITRANS TS500

NOTICE
Condensation in the device
5.2
Electrical connection
Condition
Procedure
See also

5.2 Electrical connection

Damage to device through formation of condensation if the temperature difference between transportation or storage and the mounting location exceeds 20 °C (36 °F).
• Before taking the device into operation let the device adapt for several hours in the new
environment.
● Temperature transmitter is installed.
1. Release the fixing screws on the enclosure cover and remove the enclosure cover.
2. Insert the connecting cable through the cable gland.
3. Connect the wires to the relevant connecting terminals. Observe the terminal assignment.
– Electrical connection of resistance thermometers (Page 36)
– Electrical connection of thermocouples (Page 37)
– Electrical connection of connectors (Page 37)
Electrical data (Page 57)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
35
Page 36
Connecting
5.3
Electrical connection of resistance thermometers
1 x RTD
2 x RTD
2-wire connection
2-wire connection
3-wire connection
3-wire connection
4-wire connection
4-wire connection

5.3 Electrical connection of resistance thermometers

Abbreviation of color: RD = red; WH = white; YE = yellow; BK = black
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
36 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 37
Connecting
5.4
Electrical connection of thermocouples
1 thermocouple
2 thermocouples
Thermocouples
Cable colors
Type + -
J
Black
White
K
Green
White
N
Pink
White
E
Violet
White
T
Brown
White
Note 2 thermocouples
On the terminal block is an additional mark to differentiate between sensor 1 and sensor 2.
5.5

Electrical connection of connectors

5.4 Electrical connection of thermocouples

M12 x 1 connection with SITRANS TH100 transmitter
Lemo 1S coupling for SITRANS TS100/TS200
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
37
Page 38
Connecting
5.5 Electrical connection of connectors
M12 connector for single sensors for SITRANS TS100/TS200/TS500
M12 connector for single sensors SITRANS TS300
M12 connector for double sensors SITRANS TS100
HAN7 D connector for SITRANS TS500
LCD and transmitter connection
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
38 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 39
6
6.1

Basic safety notes

WARNING
Improper commissioning in hazardous areas
WARNING
Hot surfaces
WARNING
Loss of explosion protection
WARNING
Opening device in energized state
Exception
Device failure or risk of explosion in hazardous areas.
• Do not commission the device until it has been mounted completely and connected in
accordance with the information in Technical data (Page 45).
• Before commissioning take the effect on other devices in the system into account.
Risk of burns resulting from hot surfaces.
• Take corresponding protective measures, for example by wearing protective gloves.
Danger of explosion in hazardous areas if the device is open or not properly closed.
Risk of explosion in hazardous areas
• Only open the device in a de-energized state.
• Check prior to commissioning that the cover, cover locks, and cable inlets are
assembled in accordance with the directives.
: Devices having the type of protection "Intrinsic safety Ex i" may also be opened
in energized state in hazardous areas.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
39
Page 40
Commissioning
Note Loss of degree of protection
Damage to device if the enclosure is open or not properly closed. The degree of protection specified on the nameplate is no longer guaranteed.
6.2
Commissioning
Requirements
Procedure

6.2 Commissioning

Verify that the following commissioning conditions are satisfied:
● You have connected the sensors correctly. For further details, see:
– Electrical connection of resistance thermometers (Page 36)
– Electrical connection of thermocouples (Page 37)
● Verify that the electrical connections are firmly tightened to the suitable torque.
● The following applies in particular with device versions with explosion protection:
– Verify whether the cable glands are appropriate for the process and are correctly
tightened.
– The electrical data must match the specified Ex-relevant values.
● All seals must be present, placed correctly and undamaged.
1. Close the connection head. Fully screw on the cover for device versions with flameproof enclosures.
2. Connect the sensor integrated in the process to the power supply.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
40 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 41
7
WARNING
Impermissible repair of explosion protected devices
WARNING
Humid environment
Recalibration
Note Recalibration intervals
Define the recalibration intervals for the specific process or plant. With constant operating temperatures and a low load, the reference values are as fo
•
•
Risk of explosion in hazardous areas
• Repair must be carried out by Siemens authorized personnel only.
Risk of electric shock.
• Avoid working on the device when it is energized.
• If working on an energized device is necessary, ensure that the environment is dry.
• Make sure when carrying out cleaning and maintenance work that no moisture
penetrates the inside of the device.
Temperature sensors are essentially maintenance-free. However, we recommend recalibration under the following conditions:
● Processes with strong vibrations or changes in temperature.
● Food, pharma, biotechnology applications (annually), TS300 only.
● Processes that demand high measuring accuracy and safety.
llows:
< 2 years at temperatures up to 400 °C < 5 years at temperatures up to 200 °C
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
41
Page 42
Service and maintenance
Recalibration of SITRANS TS300
Description
Recalibration procedure
measurement.
perform calibration.
from the pipe collar.
shape of the RTD unit only.
depth = 8 mm (0.31").
(176 °F) when using a temperature transmitter].
internal reference sensor only.
turer when heating the calibrator.
inserting it in the calibrator sleeve.
indicated by the nameplate.
the RTD temperature and adjust if necessary.
1
Take into account any line resistance.
unit.
Clamp-on version Do not disconnect the pipe sleeve from the pipe - leave
the measuring position unchanged for reproducible
It is not necessary to disconnect the power supply to
Loosen recessed grip screw(s) to remove the RTD con­nector or housing and unscrew the measuring insert
Block calibrators Use calibrator sleeves that have been adapted to the
Insert must have a borehole of ∅6.00 mm (0.24") H7,
Do not exceed 100 °C (212 °F) at locking plug [80 °C
Use block calibrator with dual-zone-technology with
Ohmic measurement
Observe the adjustment time specified by the manufac-
1 Apply heat sink compound to the RTD unit before
2 Check the electrical connector (cable end) as
3 After inserting the RTD unit, wait about 5 minutes
for the temperature to settle.
4 Compare the temperature of the calibrator with
2 Apply heat sink compound to the RTD plug-in
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
42 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 43
Service and maintenance
7.1
Cleaning
Cleaning the enclosure
WARNING
Electrostatic charge
7.2

Return procedure

Required forms

7.1 Cleaning

● Clean the outside of the enclosure with the inscriptions and the display window using a
cloth moistened with water or a mild detergent.
● Do not use any aggressive cleansing agents or solvents, e.g. acetone. Plastic parts or the
painted surface could be damaged. The inscriptions could become unreadable.
Risk of explosion in hazardous areas if electrostatic charges develop, for example, when cleaning plastic surfaces with a dry cloth.
• Prevent electrostatic charging in hazardous areas.
Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the outside of the packaging.
● Delivery note
● Return goods delivery note
(http://www.siemens.com/processinstrumentation/returngoodsnote)
with the following information:
– Product (item description)
– Number of returned devices/replacement parts
– Reason for returning the item(s)
● Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination)
With this declaration you warrant "that the device/replacement part has been carefully cleaned and is free of residues. The device/replacement part does not pose a hazard for humans and the environment."
If the returned device/replacement part has come into contact with poisonous, corrosive, flammable or water-contaminating substances, you must thoroughly clean and decontaminate the device/replacement part before returning it in order to ensure that all hollow areas are free from hazardous substances. Check the item after it has been cleaned.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
Any devices/replacement parts returned without a decontamination declaration will be cleaned at your expense before further processing.
43
Page 44
Service and maintenance
7.3
Disposal
Devices d disposed of in the municipal waste disposal services according to the Directive 2012/19/EC on waste electronic and electrical equipment (WEEE).
Devices can be returned to the suppli proved disposal service for eco regulations valid in your country.
Further information about devices containing batteries can be found at: Information about battery / product retu (https://support.industry.siemens.com/cs/document/109479891/)

7.3 Disposal

escribed in this manual should be recycled. They may not be
er within the EC, or to a locally ap-
-friendly recycling. Observe the specific
rn (WEEE)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
44 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 45
8
8.1

Rated conditions

Storage
Storage temperature
-40 ... +80 °C (-40 ... +176 °F)
SITRANS TSinsert/SITRANS TS100/TS200/TS500
SITRANS TS300
-20 °C
SITRANS TSinsert/SITRANS TS100/TS200/TS500
-40 °C
AU0 (option G and U) in Non-SIL-applications
Caution Ambient temperature of electronic and cable glands assembled to SITRANS TS500
accordingly. Check the operating instructions of your used electronic and cable gland for more
information.
Note
not rated to -50 °C but -40 °C.
See also
8.1.1

Maximum permissible ambient temperatures in the connection area of the sensor

8.1.1.1
General limitations for compression fittings
Degree of protection in accordance with EN 60529 See nameplate.
Degree of protection is archived, when the device is correct­ly installed. See chapter Installing (Page 23).
SITRANS TS500 type 7MC75.. with head type AG0 and
If electronic and cable glands are assembled, their minimum permitted ambient temperature must also be rated up to the minimum ambient temperature shown in the table above, otherwise the minimum ambient temperature of the complete SITRANS TS500 is derated
Siemens temperature transmitters SITRANS TH as well as HAN 7D and M12 (option codes G12 and G13) connectors are
-50 °C
Nameplate structure (Page 18)
Due to the PTFE sealing, standard compression fittings are limited to a maximum temperature of 200 °C.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
45
Page 46
Technical data
8.1.1.2
SITRANS TS100
Note Application SITRANS TS100
SITRANS
he temperature classes T4 and T6. Pay attention to the temperature resistance of the connection cables. See temperature too high
8.1 Rated conditions
TS100 temperature sensors are only approved for t
Ambient
(Page 34).
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
46 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 47
Technical data
8.1.1.3
SITRANS TS500
Gas
Dust
SITRANS TS500
in "Intrinsic safety Ex i"
- or ­in "Non-sparking nA"
in flameproof enclosure (Ex d)
is part of a "Intrinsic safety Ex i"
- or ­in non-intrinsically safe circuits
(Ex tb)
relevant temperature class in the
Table 8-6 Type 2N (Page 52).
Notice!
Table 8-10 Type 2N (Page 54).
8.1 Rated conditions
Without electronic (only enclosure with terminal base)
With temperature transmitters SITRANS TH or third party trans­mitters
Refer to your TS500 head and
Table 8-3 Gas Ex i/nA (Page 50), Table 8-4 Gas Ex i/nA (Page 51), Table 8-5 Type 2N (Page 51) and
T
= (T1 - ∆T2G) ≤ T2
a_max
= see relevant certificate of
T
1
the temperature transmitters. ∆T2G and T
Table 8-3 Gas Ex i/nA (Page 50), Table 8-4 Gas Ex i/nA (Page 51), Table 8-5 Type 2N (Page 51) and Table 8-6 Type 2N (Page 52).
= see
2
Refer to your TS500 head without electronic in the Table 8-7 Gas Ex d (Page 52) and Table 8-8 Type 2N (Page 53).
Refer to your TS500 head with electronic in Table 8-7 Gas Ex d (Page 52) and Table 8-8 Type 2N (Page 53).
When installing third party transmitter, keep in mind the max. permitted power consump­tion of 3 W.
Refer to your TS500 head without electronic in the Table 8-9 Dust Ex i/tb (Page 53) and Table 8-10 Type 2N (Page 54).
Refer to your TS500 head with electronic" in Table 8-9 Dust Ex i/tb (Page 53) and Table 8-10 Type 2N (Page 54).
When installing third party transmitter, keep in mind the max. permitted power consump­tion of 1 W. Assumed max. surface temperature of the TS500 enclosure is 85 °C.
If the max. permissible ambient temperature of third party transmitters is lower then 85 °C calculate as follow:
= T1 - ∆T1D - ∆T2D
T
a_max
T1 = see relevant certificate of the temperature transmitters.
∆T1D = 22K (max. permitted power consumption of 1 W)
∆T2D = See Table 8-9 Dust Ex i/tb (Page 53) and
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
47
Page 48
Technical data
Gas
Dust
SITRANS TS500
in "Intrinsic safety Ex i"
- or ­in "Non-sparking nA"
in flameproof enclosure (Ex d)
is part of a "Intrinsic safety Ex i"
- or ­in non-intrinsically safe circuits
(Ex tb)
T T T3 = Max. permissible ambient temperature SITRANS TH100/200/300 and display DVM-LCD
See also
8.1 Rated conditions
With temperature transmitters SITRANS TH100/200/300 and Display DVM­LCD (A5E33119275 respectively 7MF4997-1BS)
T
= T3 ≤ T2
a_max
= see
T
3
Table 8-1 Gas hazardous area Zone 1 / 21 / Div. 1 (Page 49).
T2 = see Table 8-3 Gas Ex i/nA (Page 50), Table 8-4 Gas Ex i/nA (Page 51),
Refer to your TS500 head with electronic in the Table 8-7 Gas Ex d (Page 52) and Table 8-8 Type 2N (Page 53).
T T
ous area Zone 21 / Div. 1 (Page 49).
Table 8-5 Type 2N (Page 51) and Table 8-6 Type 2N (Page 52).
= Max. permissible ambient temperature of temperature transmitter according certificate
1
= Max. permissible ambient temperature for the respective connection head without transmitter
2
SITRANS TH100/200/300 and display DVM-LCD (Page 49)
Certificates (Page 107)
Gas hazardous area: Ex i / IS / Ex nA/ec / NI (Page 50)
= T3
a_max
= see Table 8-2 Dust hazard-
3
Gas hazardous area: Ex d / XP (Page 52)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
48 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 49
Technical data
SITRANS TH100/200/300 and display DVM-LCD
Gas hazardous area Zone 1 / 21 / Div. 1
Permitted electrical supply parameters
T3 = Permissible ambient temperature
Assembly of DVM-LCD A5E33119275 (HW: 05)
Assembly of DVM-LCD 7MF4997-1BS (HW: 03)
Pi = 750 mW
Pi = 610 mW
Pi = 530 mW
Dust hazardous area Zone 21 / Div. 1
Permitted electrical supply parameters
T3 = Permissible ambient temperature
Assembly of DVM-LCD A5E33119275 (HW: 05)
Assembly of DVM-LCD 7MF4997-1BS (HW: 03)
Pi = 750 mW
Pi = 610 mW
Pi = 530 mW
See also
8.1 Rated conditions
You can find the values of ∆T2G in the tables Table 8-3 Gas Ex i/nA (Page 50), Table 8-4 Gas Ex i/nA (Page 51), Table 8-5 Type 2N (Page 51) and Table 8-6 Type 2N (Page 52) and ∆T2D in the table Table 8-9 Dust Ex i/tb (Page 53) and Table 8-10 Type 2N (Page 54).
Table 8- 1
Ui = 30 V
= 100 mA
I
i
Ui = 27 V Ii = 90 mA
Ui = 25,2 V
= 84 mA
I
i
Table 8- 2
Ui = 30 V
= 100 mA
I
i
T4: -40 °C ≤ T3 ≤ +75 °C - ∆T2G T6: -40 °C ≤ T
T4: -40 °C ≤ T3 ≤ +85 °C - ∆T2G T6: -40 °C ≤ T3 ≤ +50 °C - ∆T2G
T4: -40 °C ≤ T3 ≤ +85 °C - ∆T2G T6: -40 °C ≤ T
T85 °C: -40 °C ≤ T3 ≤ +53°C - ∆T2D T85 °C: -40 °C ≤ T3 ≤ +45°C - ∆T2D
≤ +45 °C - ∆T2G
3
≤ +52 °C - ∆T2G
3
T4: -40 °C ≤ T
≤ +67 °C - ∆T2G
3
T4: -40 °C ≤ T3 ≤ 80 °C - ∆T2G
T4: -40 °C ≤ T
≤ +85 °C - ∆T2G
3
Ui = 27 V Ii = 90 mA
Ui = 25,2 V Ii = 84 mA
Gas hazardous area: Ex i / IS / Ex nA/ec / NI (Page 50)
Dust hazardous area: Ex i / IS / Ex tb / DIP (Page 53)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
T85 °C: -40 °C ≤ T3 ≤ +63 °C - ∆T2D T85 °C: -40 °C ≤ T3 ≤ +60 °C - ∆T2D
T85 °C: -40 °C ≤ T3 ≤ +63 °C - ∆T2D T85 °C: -40 °C ≤ T3 ≤ +63 °C - ∆T2D
49
Page 50
Technical data
Gas hazardous area: Ex i / IS / Ex nA/ec / NI
without
transmitter
Head type
AU0
AV0, SITRANS TF
BA0: BB0; BC0; BD0; AA0, AB0,
AC0, KJ0, BS0,
AG0
T
max
head
120 °C
85 °C
100 °C
Temperature class
T4
T6
T4
T6
T4
T6
Medium temperature (°C)
Tempera­ture in­crease by medium ΔT2G (K)
Extension length "X" (mm)
T2 in °C
T2 in °C
T2 in °C
T2 in °C
T2 in °C
T2 in °C
440 °C
12
80
108
68
73
68
88
68
6
150
114
74
79
74
94
74
3
300
117
77
82
77
97
77
290 °C
22
40
98
58
63
58
78
58
11
80
109
69
74
69
89
69
5
150
115
75
80
75
95
75
2
300
118
78
83
78
98
78
200 °C
16
40
104
64
69
64
84
64
8
80
112
72
77
72
92
72
4
150
116
76
81
76
96
76
2
300
118
78
83
78
98
78
130 °C
9
40
111
71
76
71
91
71
5
80
115
75
80
75
95
75
3
150
117
77
82
77
97
77
1
300
119
79
84
79
99
79
80 °C
5
40
120
80
85
80
100
80
3
80
120
80
85
80
100
80
1
150
120
80
85
80
100
80
0
300
120
80
85
80
100
80
8.1 Rated conditions
The maximum ambient temperatures T2 for the respective connection head
given by the medium is already considered there.
Table 8- 3 Gas Ex i/nA
23 40 97 57 62 57 77 57
can be obtained from the cells in the following tables. The temperature increase
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
50 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 51
Technical data
Head type
BT0, AH0
BMO
BP0
T
max
head
80 °C
80 °C
100 °C
Temperature class
T6
T6
T4
T6
Medium tem­perature (°C)
Tempera­ture in­crease by medium ΔT2G (K)
Extension length "X" (mm)
T2 in °C
T2 in °C
T2 in °C
T2 in °C
440 °C
12
23*
80
68
57
77
57
6
11*
150
74
69
89
69
3
300
77
77
97
77
290 °C
22
40
58
58
78
58
11
80
69
69
89
69
2
300
78
78
98
78
200 °C
16
40
64
64
84
64
8
80
72
72
92
72
4
150
76
76
96
76
2
300
78
78
98
78
130 °C
9
40
71
71
91
71
5
80
75
75
95
75
3
150
77
77
97
77
1
300
79
79
99
79
80 °C
5
40
80
80
100
80
3
80
80
80
100
80
1
150
80
80
100
80
0
300
80
80
100
80
* Value for head type BP0 and BMO
Head type
AU0
AV0, SITRANS TF
T
max
head
120 °C
85 °C
Temperature class
T4
T6
T4
T6
Medium tempera­ture (°C)
Temperature increase by me­dium ΔT2G (K)
T2 in °C
T2 in °C
T2 in °C
T2 in °C
100 °C
7
120
73
78
73
80 °C
8.1 Rated conditions
Table 8- 4 Gas Ex i/nA
23 43* 40 57 37 57 37
5 150 75 75 95 75
Table 8- 5 Type 2N
5 120 80 85 80
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
51
Page 52
Technical data
Head type
BA0: BB0; BC0; BD0; AA0, AB0,
AC0, KJ0, BS0, AG0
BMO, BT0,
AH0
BP0
T
max
head
100 °C
80 °C
100 °C
Temperature class
T4
T6
T6
T4
T6
Medium tem­perature (°C)
Temperature increase by medium ΔT2G (K)
T2 in °C
T2 in °C
T2 in °C
T2 in °C
T2 in °C
100 °C
100 73 73 100 73
80 °C 5 100
80
80
100
80
Gas hazardous area: Ex d / XP
with or without
transmitter
Head type
AH0, AV0,
SITRANS TF
AG0, UG0
AU0, UU0
T
max
head
85 °C
100 °C
120 °C
Temperature class
T6
T4
T3
T4
Max. permitted power consumption
of electronic (W)
0 ... 31)
With or without
electronic
0
Without elec-
tronic
1 ... 31)
With electronic
0
Without elec-
tronic
1 ... 31)
With electronic
Medium tem­perature (°C)
Extension length "X" (mm)
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
440 °C
40 43
76
53
96
48
80
55
88
65
108
60
150 ... 300
61
94
71
114
66
290 °C 40
54
87
64
107
59
80 ... 300
61
94
71
114
66
200 °C 40
58
91
68
111
63
80 ... 300
63
96
73
116
68
130 °C
40 ... 300
61
94
71
114
66
80 °C
40 ... 300
67
100
77
120
72
1)
electronic are incorporated.
8.1 Rated conditions
Table 8- 6 Type 2N
7
The maximum ambient temperatures Ta for the respective connection head
given by the medium is already considered there.
Table 8- 7 Gas Ex d
can be obtained from the cells in the following tables. The temperature increase
For the determination of ambient temperatures, maximum enclosure temperature of 85 °C was taken as a basis when
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
52 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 53
Technical data
Head type
AH0, AV0,
SITRANS TF
AG0, UG0
AU0, UU0
T
max
head
85 °C
100 °C
120 °C
Temperature class
T6
T4
T3
T4
Max. permitted power
consumption of elec-
tronic (W)
0 ... 31)
With or without
electronic
0
Without electronic
1 ... 31)
With electronic
0
Without electronic
1 ... 31)
With electronic
Medium tempera­ture (°C)
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
100 °C 60
100
70
120
65
80 °C
1)
electronic are incorporated.
Dust hazardous area: Ex i / IS / Ex tb / DIP
with or without
transmitter
Head type
AH0, AV0, SITRANS TF
AG0, UG0
AU0, UU0
T
max
head
85 °C
100 °C
120 °C
Max. permitted power consumption of
electronic (W)
0
Without
electronic
11)
With elec-
tronic
0
Without
electronic
11)
With elec-
tronic
0
Without
electronic
11)
With elec-
tronic
Medium tempera­ture (°C)
Temper-
ature increase by Medi-
um ΔT2D
(K)
Extension length "X"
(mm)
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
440 °C
36
40 49
--
64
--
84
--
18
80
67
45
82
45
102
45
8
150
77
55
92
55
112
55
4
300
81
59
96
59
116
59
250 °C
22
40
63
--
78
--
98
--
11
80
74
52
89
52
109
52
5
150
80
58
95
58
115
58
1
300
84
62
99
62
119
62
8.1 Rated conditions
Table 8- 8 Type 2N
67 100 77 120 72
For the determination of ambient temperatures, maximum enclosure temperature of 85 °C was taken as a basis when
The maximum ambient temperatures Ta for the respective connection head
given by the medium is already considered there.
Table 8- 9 Dust Ex i/tb
can be obtained from the cells in the following tables. The temperature increase
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
53
Page 54
Technical data
Head type
AH0, AV0, SITRANS TF
AG0, UG0
AU0, UU0
T
max
head
85 °C
100 °C
120 °C
Max. permitted power consumption of
electronic (W)
0
Without
electronic
11)
With elec-
tronic
0
Without
electronic
11)
With elec-
tronic
0
Without
electronic
11)
With elec-
tronic
Medium tempera­ture (°C)
Temper-
ature increase by Medi-
um ΔT2D
(K)
Extension length "X"
(mm)
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
120 °C
5
80
80
58
95
58
120
58 3 150
82
60
97
60
120
60
0
300
85
63
100
63
120
63
1)
Assembled temperature transmitter e.g. SITRANS TH without Display DVM-LCD
Head type
AH0, AV0, SITRANS TF
AG0, UG0
AU0, UU0
T
max
head
T85 °C
100 °C
120 °C
Max. permitted power con-
sumption of electronic (W)
0
Without elec-
tronic
11)
With elec-
tronic
0
Without elec-
tronic
11)
With elec-
tronic
0
Without elec-
tronic
11)
With elec-
tronic
Medium temperature (°C)
Tempera­ture in­crease by Medium ΔT2D (K)
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
T
a_max
in °C
100 °C
80 °C
8
85
63
100
63
120
63
1)
Assembled temperature transmitter for example SITRANS TH
8.1.2

Maximum permitted sample temperatures within the process

Note Permissible ambient temperature at sensor
The maximum permissible ambient temperature at the sensor simultaneously corresponds to the highest permissible sample temperature.
The minimum permissible sample temperatures are up to of the temperature sensor.
8.1 Rated conditions
10 40 75 53 90 53 120 53
Table 8- 10 Type 2N
10 75 53 100 53 120 53
-200 °C depending on the version
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
54 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 55
Technical data
See also
Resistance thermometers
1 x RTD TF/3 mm/6 mm 2 x RTD TF/3 mm/6 mm 1 x RTD WW/3 mm/6 mm 2 x RTD WW/3 mm/6 mm
Max. permissible sample temperature (°C)
Certified transmitter in Zone 0 with type of protection "Intrinsically safe"
Certified transmitter in Zone 1, 2 with type of protection "Intrinsically safe"
P0: 0 … ≤37 mW 1)
P0: ≥37 … ≤100 mW
P0: 0 … ≤37 mW 1)
P0: ≥37 … ≤100 mW
T1 = 450 °C -10K
348
340
436
428
T2 = 300 °C -10K
228
220
286
278
T3 = 200 °C - 5K
152
144
191
183
T6 = 85 °C - 5K
60
52
76
68
1)
For example SITRANS TH
Thermocouples
1 x TC type J, K, N /3 mm 2 x TC type J, K, N /3 mm 1 x TC type J, K, N /6 mm 2 x TC type J, K, N /6 mm
Max. permissible sample temperature (°C)
Certified transmitter in Zone 0 with type of protection "Intrinsically safe"
Certified transmitter in Zone 1, 2 with type of protection "Intrinsically safe"
P0: 0 … 100 mW
T1 = 450 °C -10K
351
439
T2 = 300 °C -10K
231
289
T3 = 200 °C -5K
155
194
T4 = 135 °C -5K
103
129
T6 = 85 °C -5K
63
79
8.1 Rated conditions
Maximum permitted sample temperatures within the process (Page 54)
Table 8- 11 RTD temperature sensor (Rth max=120 K/W)
T4 = 135 °C - 5K 100 92 126 118
Table 8- 12 Thermocouple temperature sensor (Rth max=15 K/W)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
55
Page 56
Technical data
8.1.3

Measuring range

Note Measuring ranges
The application or possible operating temperatures depend on the configurat temperature sensor.
8.2
Construction
Torques for M20 accessories
Plastic head
Metal head
Cable diameter
Plastic cable gland
5.0 Nm
5.0 Nm
6 ... 12 mm
Metal cable gland
N/A
5.0 Nm
5 ... 14 mm
Adapter M20 to NPT½
5.0 Nm
5.0 Nm
N/A
Connection type
Torque value
M14 thread
25 Nm
M18 thread
40 Nm
G½ thread; M20 threads
50 Nm
wrench
Head type
Torque value
Metal head
20 Nm
Plastic heads
5 Nm

8.2 Construction

The measuring range refers to the temperature limits in which the thermometer can be used practically for measuring purposes. Depending on the loads at the place of use and the required accuracies, the actual measuring range may decrease.
ion of the
Table 8- 13 Torque values for M20 accessories
SITRANS TS500 with head types A requires a minimum thickness of the wrench flat of 5 mm. The maximal wrench size is SW24.
Table 8- 14 Torque values between device extension and protective tube
½ inch NPT Hand-tight and one to two complete turns with a
Table 8- 15 Torque values between device head and extension
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
56 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 57
Technical data
Medium
Immersion depth (calculation)1)
Water
Immersion depth ≥ TSL1) + (5 x ∅
protective tube
)
1)
TSL = Temperature Sensitive Length
8.3
Electrical data
Devices for general use
Measured current
I
Measuring
(Pt 1000)
0.1 ... 0.3 mA
Devices in explosion-protected version
Equipment protection by means of intrinsic safety
Li = 15 µH/m
Equipment protection by means of non incendive
peak values
U
max
= 32 V 1)
1)
Maximum safety voltage
Equipment protection by means of Explosionproofed / Dust-Ignition proofed
P = 25/37/50/100 mW
Effective internal capacitance and internal inductance
DVM-LCD
SITRANS TH100
∑
Ci
16 nF
13 nF
29 nF
Li
3 µH
106 µH
109 µH

8.3 Electrical data

Table 8- 16 Estimation of immersion depth
Air Immersion depth ≥ TSL1) + (10 to 15 x ∅
I
(Pt 100) 0.3 ... 1.0 mA
Measuring
For connecting to circuits with the following peak values
protective tube
Ui ≤ 30 V
≤ 100 mA
I
i
P
= Po (transmitter)
i
= 700 pF/m
C
i
)
For connecting to circuits with the following
For connecting to circuits with the following peak values
Un = 30 V
U
= 45 V
max
(U
= 35 V for USA/Canada)
max
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
57
Page 58
Technical data
8.4
Measuring tolerances for resistance thermometers
Tolerance classes
Tolerance class
Precision
∆t
±1.8x0.30 °F +0.0050x|t[°F]-32|
±1.8x0.15 °F +0.0020x|t[°F]-32|
±1.8x0.10 °F +0.0017x|t[°F]-32|
Tolerances
Action
Tolerance
Precision
Range
Class B
Basic accuracy
-50 ... +400 °C (-58 ... +752 °F)
Class A
Increased accuracy
-30 ... +300 °C (-22 ... +572 °F)
Class AA (1/3 B)
High accuracy
0 ... +150 °C (+32 ... +302 °F)
Class B
Basic accuracy
-50 ... +400 °C (-58 ... +752 °F)
Class A
Increased accuracy
-30 ... +300 °C (-22 ... +572 °F)
Class AA (1/3 B)
High accuracy
0 ... +150 °C (+32 ... +302 °F)
Class B
Basic accuracy
-196 ... +600 °C (-320 ... +1112 °F)
Class A
Increased accuracy
-100 ... +450 °C (-148 ... +842 °F)
Class AA (1/3 B)
Increased accuracy
-50 ... +250 °C (-58 ... +482 °F)

8.4 Measuring tolerances for resistance thermometers

The tolerance classes of the resistance thermometers are defined as follows in accordance with IEC 60751:
Class B Basic accuracy ±(0.30 °C +0.0050|t[°C]|)
Class A Increased accuracy ±(0.15 °C +0.0020|t[°C]|)
Class AA (1/3 B) High accuracy ±(0.10 °C +0.0017|t[°C]|)
The following tables provide an overview of the validity ranges of these tolerances. When you use a thermometer above the specified limits, the values of the next lower accuracy class apply.
Basic version
With increased vibra-
tion resistance
With extended measur-
ing range
If an RTD will be subjected in a higher temperature as specified in the class, the sensor will be declassified to the referring accuracy class. For enduring operation near 400 °C we recommend the use of an extended measuring range RTD, instead of basic and increased vibration versions.
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
58 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 59
Technical data
8.5
Measuring accuracy for thermocouples
Tolerance classes
Catalog versions
Type
Basic accuracy, Class 2
Increased accuracy, Class 1
(631 °F ... 2012 °F ±0.0075x|t[°F]-32|)
(707 °F ... 1832 °F ±0.004x|t[°F]-32|)
(631 °F ... 1832 °F ±0.0075x|t[°F]-32|)
(707 °F ... 1832 °F ±0.004x|t[°F]-32|)
(631 °F ... 1382 °F ±0.0075x|t[°F]-32|)
(707 °F ... 1382 °F ±0.004x|t[°F]-32|)
Further base thermocouples
Type
Basic accuracy, Class 2
Increased accuracy, Class 1
(271 °F ... 662 °F ±0.0075x|t[°F]-32|)
(257 °F ... 662 °F ±0.004x|t[°F]-32|)
(631 °F ... 1652 °F ±0.0075x|t[°F]-32|)
(707 °F ... 1472 °F ±0.004x|t[°F]-32|)
Further noble thermocouples
Type
Basic accuracy, Class 2
Increased accuracy, Class 1
(1112 °F ... 2912 °F ±0.0025x|t[°F]-32|)
(2012 °F ... 2912 °F ±1,8+0,003x(t[°F]-2012)

8.5 Measuring accuracy for thermocouples

The tolerance classes of the thermocouples are defined in the following table in accordance with IEC 584/DIN EN 60584:
N -40 °C ... +333 °C ±2.5 °C
(-40 °F ... +631 °F ±4.5 °F)
333 °C ... 1100 °C ±0.0075x|t[°C]|
K -40 °C ... +333 °C ±2.5°C
(-40 °F... +631 °F ±4.5 °F)
333 °C ... 1000 °C ±0.0075x|t[°C]|
J -40 °C ... +333 °C ±2.5 °C
(-40 °F ... +631 °F ±4.5 °F)
333 °C ... 750 °C ±0.0075x|t[°C]|
T -40 °C ... +133 °C ±1 °C
(-40 °F ... +271 °F ±1.8 °F)
133 °C ... 350 °C ±0.0075x|t[°C]|
E -40 °C ... +333 °C ±2.5°C
(-40 °F... +631 °F ±4.5 °F)
333 °C ... 900 °C ±0.0075x|t[°C]|
-40 °C ... +375 °C ±1.5 °C
(-40 °F ... +707 °F ±2.7 °F)
375 °C ... 1000 °C ±0.004x|t[°C]|
-40 °C ... +375 °C ±1.5 °C
(-40 °F... +707 °F ±2.7 °F)
375 °C ... 1000 °C ±0.004x|t[°C]|
-40 °C ... +375 °C ±1.5 °C
(-40 °F ... +707 °F ±2.7 °F)
375 °C ... 750 °C ±0.004x|t[°C]|
-40 °C ... +125 °C ±0.5 °C
(-40 °F ... +257 °F ±0.9 °F)
125 °C ... 350 °C ±0.004x|t[°C]|
-40 °C ... +375 °C ±1.5 °C (-40 °F... +707 °F ±2.7 °F)
375 °C ... 800 °C ±0.004x|t[°C]|
R,S 0 °C ... 600 °C ±1.5 °C
(32 °F ... +1112 °F ±2.7 °F)
600 °C ... 1600 °C ±0.0025x|t[°C]|
B 600 °C ... 1700 °C ±0.0025x|t[°C]|
(1112 °F ... 3092 °F ±0.0025x|t[°F]-32|)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
0 °C ... 1100 °C ±1 °C
(32 °F ... +2012 °F ±1.8 °F)
1100 °C ... 1600 °C ±[1 + 0.003 x(t -1100)] °C
-
59
Page 60
Technical data
8.6
Certificates and approvals
8.6.1

SITRANS TSInsert/TS100/TS200/TS500

SITRANS TSInsert/TS100/TS200/TS500
"Intrinsic safety" type of protection
PTB 09 ATEX 2014 X
IECEx PTB 11.0010 X
IEC 60079-26 Ed 3 2014
GB 12476.4-2010

8.6 Certificates and approvals

ATEX/IECEx
EN 60079-0:2012/A11:2013 EN 60079-11:2012 EN 60079-15:2010 EN 60079-7:2015 EN 60079-26:2015
IEC 60079-0 Ed 6 2011 IEC 60079-11 Ed 6 2011 IEC 60079-15 Ed 4 2010 IEC 60079-7 Ed 5 2015
NEPSI
GYJ14.1005X GB 3836.1-2010
GB 3836.4-2010 GB 3836.20-2010 GB 3836.8-2003 IEC 61241-0:2004
II 1 D Ex ia IIIC T 200 °C Da II 1 G Ex ia IIC T6 / T4 ... T1 Ga II 3 G Ex ic IIC T6 / T4 ... T1 Gc
Ex iaD 20 T200 Ex ibD 21 T200 Ex ia IIC T1/T2/T3/T4/T6 Ga Ex ib IIC T1/T2/T3/T4/T6 Gb Ex ic IIC T1/T2/T3/T4/T6 Gc
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
60 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 61
Technical data
SITRANS TSInsert/TS100/TS200/TS500
IEC 60079-26-2006
CAN/CSA-C22.2 No. 60529:2005
8.6 Certificates and approvals
EACEx
RU C-DE.AA87.B.00006 IEC 60079-0-2011
IEC 60079-1-2011 IEC 60079-11-2010 IEC 60079-15-2010 IEC 60079-31-2010
cCSAus
70037146 FM Class 3600:2011
FM Class 3611:2004 FM Class 3615:2006 FM Class 3616:2013 FM Class 3810:2005 ANSI/ISA 60079-0:2009 ANSI/ISA 60079-1:2013 ANSI/ISA 60079-31:2013 ANSI/NEMA 250:1991 ANSI/IEC 60529:2004
CSA C22.2 No. 0.4:2013 CSA C22.2 No. 0.5:2012 CSA C22.2 No. 14 CSA C22.2 No. 25:2014 CSA C22.2 No. 30:2005 CSA C22.2 No. 94 CSA C22.2 No. 142:1993 CSA C22.2 No. 157:2002 CSA C22.2 No. 213:1999 CAN/CSA-C22.2 No. 60079-0:2011 CAN/CSA-C22.2 No. 60079-1:2011 CAN/CSA-C22.2 No. 60079-31:2012
Ex ia IIIC T200 °C Da X 0Ex ia IIC T6/T4 …T1 Ga X 2Ex ic IIC T6/T4 … T1 Gc X
Class I, Division 1, Groups A, B, C, D T6/T4 … T1 Class I, Division 2, Groups A, B, C, D T6/T4 … T1 Class II Division 1 Groups E, F, G T6/T4 … T1 Class II Division 2 Groups F, G T6/T4 … T1 Class III Ex ia IIC T6/T4 … T1 Ga Ex ia IIIC T200 °C Da AEx ia IIC T6/T4 … T1 Ga AEx ia IIIC T200 °C Da Ex ic IIC T6/T4 … T1 Gc Class I, Zone 2, AEx ic IIC T6/T4 … T1 Gc
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
61
Page 62
Technical data
8.6.2

SITRANS TS500

SITRANS TS500
of protection
PTB 10 ATEX 1005 X
IECEx PTB 10.0018 X
IEC 60079-31 Ed. 2 2013
GB 12476.1-2000
8.6 Certificates and approvals
"Explosionproofed" and "dust-ignition proofed" type
ATEX/IECEx
EN 60079-0:2012/A11:2013 EN 60079-1:2014 EN 60079-26:2015 EN 60079-31:2014
IEC 60079-0 Ed. 6 2011 IEC 60079-1 Ed. 7 2014 IEC 60079-26 Ed. 3 2014
NEPSI
GYJ14.1004X GB 3836.1-2010
GB 3836.2-2010 GB 3836.20-2010
EACEx
RU C-DE.AA87.B.00006 IEC 60079-0-2011
IEC 60079-1-2011 IEC 60079-11-2010 IEC 60079-15-2010 IEC 60079-31-2010 IEC 60079-26-2006
II 1/2 G Ex d IIC T6, T4, T3 Ga/Gb II 1/2 D Ex tb IIIC T85 °C, 100 °C or 150 °C
Ex d IIC T3/T4/T6 Ga/Gb DIP A20/21 TA85 °C/100 °C/150 °C IP65
Ga/Gb Ex d IIC, T6, T4, T3 X Ex tb IIIC T85 °C,T100 °C,T150 °C Da/Db X
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
62 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 63
Technical data
SITRANS TS500
CAN/CSA-C22.2 No. 61010-1
CAN/CSA-C22.2 No. 61010-1
8.6 Certificates and approvals
cCSAus
70037146 FM Class 3600:2011
FM Class 3611:2004 FM Class 3615:2006 FM Class 3616:2013 FM Class 3810:2005 ANSI/ISA 60079-0:2009 ANSI/ISA 60079-1:2013 ANSI/ISA 60079-31:2013 ANSI/NEMA 250:1991 ANSI/IEC 60529:2004
CSA C22.2 No. 0.4:2013 CSA C22.2 No. 0.5:2012 CSA C22.2 No. 14 CSA C22.2 No. 25:2014 CSA C22.2 No. 30:2005 CSA C22.2 No. 94 CSA C22.2 No. 142:1993 CSA C22.2 No. 157:2002 CSA C22.2 No. 213:1999 CAN/CSA-C22.2 No. 60079-0:2011 CAN/CSA-C22.2 No. 60079-1:2011 CAN/CSA-C22.2 No. 60079-31:2012 CAN/CSA-C22.2 No. 60529:2005
Class I, Division 1, Groups A, B, C, D T6, T4 … T1 Class I, Division 1, Groups B, C, D T6, T4 … T1 (type code
7MC65..-.....-.(G;U)..)
Class I, Division 2, Groups A, B, C, D T6, T4 … T1 Class II Division 1 Groups E, F, G T6, T4 … T1 Class II Division 2 Groups F, G T6, T4 … T1 Class III Ex d IIC T6, T4,T3 Ga/Gb Ex tb IIIC T85 °C, T100 °C, T150 °C Da/Db AEx tb IIIC T85 °C, T100 °C, T150 °C Da/Db
cFMus
FM17US0010X (USA) FM17CA0005X (Canada) FM Class 3600:2011
FM Class 3611:2004 FM Class 3615:2006 FM Class 3616:2013 FM Class 3810:2005 ANSI/ISA 60079-0:2009 ANSI/ISA 60079-1:2013 ANSI/ISA 60079-31:2013 ANSI/NEMA 250:1991 ANSI/IEC 60529:2004
CSA C22.2 No. 0.4:2013 CSA C22.2 No. 0.5:2012 CSA C22.2 No. 14 CSA C22.2 No. 25:2014 CSA C22.2 No. 30:2005 CSA C22.2 No. 94 CSA C22.2 No. 142:1993 CSA C22.2 No. 157:2002 CSA C22.2 No. 213:1999 CAN/CSA-C22.2 No. 60079-0:2011 CAN/CSA-C22.2 No. 60079-1:2011 CAN/CSA-C22.2 No. 60079-31:2012 CAN/CSA-C22.2 No. 60529:2005
Class I Division 1, Groups A, B, C, D; T* Ta = -40 °C to +Tx°C Class II, III, Division 1, Groups E, F, G; T* Ta = -40 °C to +Tx°C Class I, II, III, Division 2, Group A, B, C, D, F, G; T* Ta = -40°C to
+Tx °C Class I, Zone 1, AEx d IIC T* Gb Ta = -40 °C to +Tx °C (FMus only) Class I, Zone 1, Ex d IIC T* Gb Ta = -40 °C to +Tx °C (cFM only) Zone 21 AEx tb IIIC T* Db Ta = -40 °C to +Tx °C (FMus only) Ex tb IIIC T* Db Ta = -40°C to +Tx °C (cFM only) Type 4X, IP66/67
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
63
Page 64
Technical data
8.6 Certificates and approvals
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
64 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 65
9
9.1

Overview

Versions
Description
Versions
Description
Versions
Description
or head
The following tables contain brief descriptions of the temperature sensors as well as references to the corresponding dimensional drawings.
Table 9- 1 Overview of SITRANS TS100 dimensional drawings
Basic version
Mineral-insulated cable
Table 9- 2 Overview of SITRANS TS200 dimensional drawings
Basic sensor, flying leads, LEMO 1S coupling, M12, thermocouple coupling, mini connection head
Table 9- 3 Overview of SITRANS TS300 dimensional drawings
• Temperature sensors in cable design, for universal use, plastic-insulated version, for unfavorable space conditions.
• SITRANS TS100 (Page 69)
• Temperature sensors in cable design, for universal use, mineral-insulated
version, for unfavorable space conditions.
• SITRANS TS100 (Page 69)
• Temperature sensors in cable design, for universal use, mineral-insulated
version, for unfavorable space conditions.
• SITRANS TS200 (Page 70)
Modular design with a wide range of process connections for hygienic appli­cations
Clamp-on design with collar, strap, or hook mounting, integrated transmitter
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
• Temperature sensors for pipe and vessels in a hygienic application.
• Design according EHEDG
• SITRANS TS300 (Page 71)
• Clamp-on temperature sensor particulary for satured steam sterilization.
• SITRANS TS300 (Page 71)
65
Page 66
Dimension drawings
Versions
Description
Temperature sensors for vessels and pipelines, threaded process connection,
Temperature sensors for vessels and pipelines, threaded process connection,
9.1 Overview
Table 9- 4 Overview of SITRANS TS500 dimensional drawings
Type 2, pipe version without process connection
Type 2N, pipe version with screw-in nipple
Type 2G, pipe version with screw-in nipple and extension
Type 2F, pipe version with flange and extension
Type 3, fast pipe version without pro­cess connection
Type 3G, fast pipe version with screw­in nipple and extension
Type 3F, fast pipe version with flange and extension
Types 4 and 4F, full material version, with extension
Type ST, threaded tapered well (7MC65..)
Type SST, threaded tapered well (7MC55..)
• Temperature sensors for containers and pipelines, pipe version for low to medium stress, without process connection, without extension, for plugging-in or use with sliding compression joints
• SITRANS TS500, types 2 and 2N (Page 75)
• Temperature sensors for containers and pipelines, pipe version for low to
medium stress, protective tube type 2N similar to DIN 43772, for screwing-in, without extension, for process temperatures up to 100 °C (212°F)
• SITRANS TS500, types 2 and 2N (Page 75)
• Temperature sensors for containers and pipelines, pipe version for low to
medium stress, protective tube in accordance with DIN 43772, type 2G, for screwing-in, with extension
• SITRANS TS500, types 2G and 2F (Page 76)
• Temperature sensors for containers and pipelines, pipe version for low to
medium stress, protective tube in accordance with DIN 43772, type 2F, with flange, with extension
• SITRANS TS500, types 2G and 2F (Page 76)
• Temperature sensors for containers and pipelines, pipe version for low to
medium stress, without process connection, without extension, for plugging-in or use with sliding compression joints
• SITRANS TS500, type 3 (Page 77)
• Temperature sensors for containers and pipelines, pipe version for low to
medium stress, protective tube in accordance with DIN 43772, type 3G, for screwing-in, without process connection, with extension
• SITRANS TS500, types 3G and 3F (Page 78)
• Temperature sensors for containers and pipelines, pipe version for low to
medium stress, protective tube in accordance with DIN 43772, type 3F, with flange, with extension
• SITRANS TS500, types 3G and 3F (Page 78)
• Temperature sensors for containers and pipelines, full material version for
medium to very high stress, protective tube in accordance with DIN 43772, type 4, for welding-in, with extension
• Protective tube type 4F, with flange, with extension
• SITRANS TS500, types 4 and 4F (Page 79)
•
tapered thermowell
• SITRANS TS500, type ST, threaded tapered well (7MC65..) (Page 81)
•
tapered thermowell
• SITRANS TS500, type SST, threaded tapered well (7MC55..) (Page 82)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
66 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 67
Dimension drawings
Versions
Description
Temperature sensors for vessels and pipelines, threaded process connection,
Temperature sensors for vessels and pipelines, threaded process connection,
Temperature sensors for vessels and pipelines, threaded process connection,
Temperature sensors for vessels and pipelines, threaded process connection,
Temperature sensors for vessels and pipelines, threaded process connection,
Temperature sensors for vessels and pipelines, threaded process connection,
Temperature sensors for vessels and pipelines, threaded process connection,
Temperature sensors for vessels and pipelines, threaded process connection,
Temperature sensors for vessels and pipelines, threaded process connection,
9.1 Overview
Type SS, threaded straight well (7MC65..)
Type SS, threaded straight well (7MC55..)
Type SR, threaded reduced well (7MC65..)
Type SR, threaded reduced well (7MC55..)
Type FT, flanged tapered well (7MC65..)
Type FST, flanged tapered well (7MC55..)
Type FS, flanged straight well (7MC65..)
Type FS, flanged straight well (7MC55..)
Type FR, flanged reduced well (7MC65..)
Type FR, flanged reduced well (7MC55..)
Type SWT, socket tapered well (7MC65..)
Type SWT, socket tapered well (7MC55..)
Type SWS, socket straight well (7MC65..)
•
straight thermowell
• SITRANS TS500, type SS, threaded straight well (7MC65..) (Page 84)
• Temperature sensors for vessels and pipelines, threaded process connection,
straight thermowell
• SITRANS TS500, type SS, threaded straight well (7MC55..) (Page 85)
•
straight thermowell
• SITRANS TS500, type SR, threaded reduced well (7MC65..) (Page 86)
•
straight thermowell
• SITRANS TS500, type SR, threaded reduced well (7MC55..) (Page 87)
•
straight thermowell
• SITRANS TS500, type FT, flanged tapered well (7MC65..) (Page 88)
•
straight thermowell
• SITRANS TS500, type FST, flanged tapered well (7MC55..) (Page 89)
•
straight thermowell
• SITRANS TS500, type FS, flanged straight well (7MC65..) (Page 91)
•
straight thermowell
• SITRANS TS500, type FS, flanged straight well (7MC55..) (Page 92)
•
straight thermowell
• SITRANS TS500, type FR, flanged reduced well (7MC65..) (Page 93)
•
straight thermowell
• SITRANS TS500, type FR, flanged reduced well (7MC55..) (Page 94)
• Temperature sensors for vessels and pipelines, socket well process connec-
tion, tapered thermowell
• SITRANS TS500, type SWT, socket tapered well (7MC65..) (Page 95)
• Temperature sensors for vessels and pipelines, socket well process connec-
tion, tapered thermowell
• SITRANS TS500, type SWST, socket tapered well (7MC55..) (Page 96)
• Temperature sensors for vessels and pipelines, socket well process connec-
tion, tapered thermowell
• SITRANS TS500, type SWS, socket straight well (7MC65..) (Page 98)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
67
Page 68
Dimension drawings
Versions
Description
Temperature sensors for vessels and pipelines, threaded process connection,
Versions
Description
9.1 Overview
Type SWS, socket straight well (7MC55..)
Type SWR, socket reduced well (7MC65..)
Type SWR, socket reduced well (7MC55..)
SITRANS TS500 for installation in existing protective tubes
Type GP, general purpose, no well
• Temperature sensors for vessels and pipelines, socket well process connec- tion, tapered thermowell
• SITRANS TS500, type SWS, socket straight well (7MC55..) (Page 99)
• Temperature sensors for vessels and pipelines, socket well process connec-
tion, tapered thermowell
• SITRANS TS500, type SWR, socket reduced well (7MC65..) (Page 100)
• Temperature sensors for vessels and pipelines, socket well process connec-
tion, tapered thermowell
• SITRANS TS500, type SWR, socket reduced well (7MC55..) (Page 101)
• Temperature sensors for containers and pipelines, temperature sensors for
installation in existing protective sleeves, suitable for sleeves in accordance with DIN 43772 and ASME B40.9-2001, with extension of European or Amer­ican design
• SITRANS TS500 for installation in existing protective tubes (Page 102)
•
no thermowell
• SITRANS TS500, type GP, general purpose, no well (Page 104)
Table 9- 5 Overview of SITRANS TSinsert dimensional drawings: measuring inserts for retrofitting and upgrading
European design
American design
• Measuring inserts for temperature sensors, replaceable, mineral-insulated version, European design (DIN ceramic base), spring approx. 8 mm (0.31 inch)
• SITRANS TSinsert - measuring inserts for SITRANS TS500 (Page 105)
• Measuring inserts for temperature sensors, replaceable, mineral-insulated
version, American design, spring approx. 25 mm (0.98 inch)
• SITRANS TSinsert - measuring inserts for SITRANS TS500 (Page 105)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
68 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 69
Dimension drawings
9.2
SITRANS TS100
①
TS100 mineral-insulated version
∅d
External diameter of measuring insert (6 (0.24))
B
Length of measuring insert
LC
Cable length
NBL
Non bendable length
TSL
Temperature sensitive length
U
Mounting length

9.2 SITRANS TS100

Figure 9-1 Dimensional drawings SITRANS TS100 - dimensions in mm (inch)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
69
Page 70
Dimension drawings
9.3
SITRANS TS200
B
Length of measuring insert
U
Mounting length
H
Height of head
①
Basic sensor
U = B
②
Flying Leads
U = B + 10 (0.39)
③
Coupling LEMO 1S
U = B - 10 (0.39)
④
M12 connector
U = B - 10 (0.39)
⑤
Thermocouple coupling
U = B - 5 (0.20)
⑥
Miniature connection head
U = B - 20 (0.79)

9.3 SITRANS TS200

Figure 9-2 Dimensional drawings SITRANS TS200 - dimensions in mm (inch)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
70 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 71
Dimension drawings
9.4
SITRANS TS300
SITRANS TS300 Modular:
B
Length of measuring insert
H
Height of head
∅d
External diameter of measuring insert
N
Nominal length
options)
tions)

9.4 SITRANS TS300

∅D External diameter of process connection U Mounting length (see process connection
∅D3 Internal diameter of protective tube X Extension (see process connection op-
Figure 9-3 Dimensions in mm (inch)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
71
Page 72
Dimension drawings
Process connection options:
tapered coupling with groove union nut aseptic design per DIN 11864-1
tapered coupling with groove union nut per DIN 11851
tri-clamp connection clamp connection per DIN 32676 or ISO 2852
thermowell with welding ball 30 x 40 mm
G1A dead-zone free (coni­cal metal taper)
Varivent connection
NEUMO connection
connection per INGOLD DN 25 with coupling nut
neck tube according to DIN 43772
model 2
similar model 3 reduced tip
9.4 SITRANS TS300
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
72 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 73
Dimension drawings
SITRANS TS300 Clamp-on:
①
circular connector M12 x 1
⑥
cable connection M16 x 1,5 cable ∅4, 5-10
②
M12 x 1
⑦
③
housing
⑧
④
ble
⑨
⑤
∅3-6, 5
⑩
pipe ∅
A B C
4-17.2 (0.16 -
0.68)
18-38 (0.71 - 1.5)
30
40
70
38.1-57 (1.5 -
2.24)
9.4 SITRANS TS300
transmitter with circular connector
stainless steel connection head
electrical connection ± 170° rotata-
cable connection M12 x 1,5 cable
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
clamping shoe for pipe ≥ ∅10 - ∼∅300
example ∅21 (0.83)
clamping bracket for pipe ∅4-17, 2
clamping block for pipe ∅4-57
20 30 35
40 50 85
73
Page 74
Dimension drawings
9.4 SITRANS TS300
Figure 9-4 Dimensions in mm (inch)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
74 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 75
Dimension drawings
9.5
SITRANS TS500
9.5.1

SITRANS TS500, types 2 and 2N

①
Type 2, pipe version without process connection
②
Type 2N, pipe version with screw-in nipple
Type Bxx: 26 (1.02)
∅d
External diameter of measuring insert
K
Penetration depth
∅D
To ①: External diameter of fixing point (6 (0.24))
LE
Cable inlet
∅D
To ②: External diameter of process connection
N
Nominal length
∅D3
Internal diameter of protective tube
P
Space for process connection
E
Thread dimension of process connection
U
Mounting length
H
Height of head
X
Extension

9.5 SITRANS TS500

B Length of measuring insert H1 Type Axx: 41 (1.61)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
75
Page 76
Dimension drawings
9.5.2

SITRANS TS500, types 2G and 2F

①
Type 2G, pipe version with screw-in nipple and extension
②
Type 2F, pipe version with flange and extension
Type Bxx: 26 (1.02)
∅d
External diameter of measuring insert (6 (0.24))
K
Penetration depth
∅D
External diameter of process connection
LE
Cable inlet
∅D3
Internal diameter of protective tube
N
Nominal length
E
Thread dimension of process connection
U
Mounting length
H
Height of head
X
Extension
9.5 SITRANS TS500
Figure 9-5 Dimensional drawings SITRANS TS500, types 2 and 2N - dimensions in mm (inch)
B Length of measuring insert H1 Type Axx: 41 (1.61)
Figure 9-6 Dimensional drawings SITRANS TS500, types 2G and 2F - dimensions in mm (inch)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
76 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 77
Dimension drawings
9.5.3

SITRANS TS500, type 3

①
Type 3, fast pipe version without process connection
B
Length of measuring insert (European)
H
Height of head
(6 (0.24))
Type Bxx: 26 (1.02)
∅D
External diameter of fixing point
LE
Cable inlet
∅D1
Internal diameter of tip
N
Nominal length
∅D2
External diameter of tip
P
Space for process connection
∅D3
Internal diameter of protective tube
9.5 SITRANS TS500
∅d External diameter of measuring insert
Figure 9-7 Dimensional drawing SITRANS TS500, type 3 - dimensions in mm (inch)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
H1 Type Axx: 41 (1.61)
77
Page 78
Dimension drawings
9.5.4

SITRANS TS500, types 3G and 3F

①
Type 3G, fast pipe version with screw-in nipple and extension
②
Type 3F, fast pipe version with flange and extension
Type Bxx: 26 (1.02)
∅d
External diameter of measuring insert (6 (0.24))
H
Height of head
∅D
External diameter of process connection
K
Penetration depth
∅D1
Internal diameter of tip
LE
Cable inlet
∅D2
External diameter of tip
N
Nominal length
∅D3
Internal diameter of protective tube
U
Mounting length
E
Thread dimension of process connection
X
Extension
9.5 SITRANS TS500
B Length of measuring insert (European) H1 Type Axx: 41 (1.61)
Figure 9-8 Dimensional drawings SITRANS TS500, types 3G and 3F
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
78 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 79
Dimension drawings
9.5.5

SITRANS TS500, types 4 and 4F

①
Type 4, full material version, with extension
②
Type 4F, full material version, with flange and extension
nection
C
Cone length = U
min
H
Height of head
Type Bxx: 26 (1.02)
∅D
External diameter of process connection
K
Penetration depth
∅D1
Internal diameter of tip
L
Length of protective sleeve
∅D2
External diameter of tip
LE
Cable inlet
∅D3
Internal diameter of protective tube
N
Nominal length
∅D4
External diameter of extension
U
Mounting length
X
Extension
9.5 SITRANS TS500
B Length of measuring insert E Thread dimension of process con-
∅d External diameter of measuring insert (6 (0.24)) H1 Type Axx: 41 (1.61)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
79
Page 80
Dimension drawings
9.5 SITRANS TS500
Figure 9-9 Dimensional drawings SITRANS TS500, types 4 and 4F - dimensions in mm (inch)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
80 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 81
Dimension drawings
9.5.6

SITRANS TS500, type ST, threaded tapered well (7MC65..)

tion
∅D
External diameter of process connection
N
Nominal length
∅D2
External diameter of tip
U1
Unsupported length
X
Extension
9.5 SITRANS TS500
∅d External diameter of measuring insert E Thread dimension of process connec-
Figure 9-10 Dimensional drawings SITRANS TS500, type ST, threaded tapered well - dimensions in
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
mm (inch)
81
Page 82
Dimension drawings
9.5.7

SITRANS TS500, type SST, threaded tapered well (7MC55..)

L
Length of thermowell
B
Length of insert
∅D1
External diameter of process connection
N
Nominal length
U
Insertion length
U1
Unsupported length
Type Bxx = 26 (1.02)
X1
Lag length
C
Cone length
F
Thermowell bottom thickness
9.5 SITRANS TS500
∅D2 External diameter of tip
X Extension H1 Head bottom thickness:
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
82 Compact Operating Instructions, 01/2018, A5E03920348-AE
Type Axx = 41 (1.61)
Page 83
Dimension drawings
9.5 SITRANS TS500
Figure 9-11 Dimensional drawings SITRANS TS500, type SST, threaded tapered well (7MC55…) -
dimensions in mm (inch)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
83
Page 84
Dimension drawings
9.5.8

SITRANS TS500, type SS, threaded straight well (7MC65..)

tion
∅D
External diameter of process connection
N
Nominal length
X
Extension
U1
Unsupported length
9.5 SITRANS TS500
∅d External diameter of measuring insert E Thread dimension of process connec-
Figure 9-12 Dimensional drawings SITRANS TS500, type SS, threaded straight well - dimensions in
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
84 Compact Operating Instructions, 01/2018, A5E03920348-AE
mm (inch)
Page 85
Dimension drawings
9.5.9

SITRANS TS500, type SS, threaded straight well (7MC55..)

L
Length of thermowell
X1
Lag length
Type Bxx = 26 (1.02)
∅D
External diameter of process connection
N
Nominal length
U
Insertion length
U1
Unsupported length
9.5 SITRANS TS500
H1 Head bottom thickness:
X Extension
Figure 9-13 Dimensional drawings SITRANS TS500, type SS, threaded straight well (7MC55…)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
B Length of measuring insert
Type Axx = 41 (1.61)
85
Page 86
Dimension drawings
9.5.10

SITRANS TS500, type SR, threaded reduced well (7MC65..)

tion
∅D
External diameter of process connection
N
Nominal length
∅D2
External diameter of tip
U1
Unsupported length
X
Extension
9.5 SITRANS TS500
∅d External diameter of measuring insert E Thread dimension of process connec-
Figure 9-14 Dimensional drawings SITRANS TS500, type SR, threaded reduced well - dimensions in
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
86 Compact Operating Instructions, 01/2018, A5E03920348-AE
mm (inch)
Page 87
Dimension drawings
9.5.11

SITRANS TS500, type SR, threaded reduced well (7MC55..)

Type Bxx = 26 (1.02)
∅D
External diameter of process connection
N
Nominal length
U
Insertion length
U1
Unsupported length
X1
Lag length
L
Length of thermowell
9.5 SITRANS TS500
H
Head bottom thickness:
1
X Extension
Figure 9-15 Dimensional drawings SITRANS TS500, type SR, threaded reduced well (7MC55…)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
B Length of measuring insert
Type Axx = 41 (1.61)
87
Page 88
Dimension drawings
9.5.12

SITRANS TS500, type FT, flanged tapered well (7MC65..)

(6 (0.24))
X
Extension
U
Mounting length
9.5 SITRANS TS500
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
88 Compact Operating Instructions, 01/2018, A5E03920348-AE
∅d External diameter of measuring insert
Figure 9-16 Dimensional drawings SITRANS TS500, type FT, flanged tapered well - dimensions in
mm (inch)
N Nominal length
Page 89
Dimension drawings
9.5.13

SITRANS TS500, type FST, flanged tapered well (7MC55..)

L
Length of thermowell
B
Length of measuring Insert
∅D1
External diameter of process connection
N
Nominal length
∅D2
External diameter of tip
U
Insertion length
Type Bxx = 26 (1.02)
9.5 SITRANS TS500
X Extension length H1 Head bottom thickness
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
Type Axx = 41 (1.61)
89
Page 90
Dimension drawings
X1
Lag lenght
C
Cone Length
9.5 SITRANS TS500
Figure 9-17 Dimensional drawings SITRANS TS500, type FST, flanged tapered well (7MC55…)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
90 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 91
Dimension drawings
9.5.14

SITRANS TS500, type FS, flanged straight well (7MC65..)

(6 (0.24))
X
Extension
U
Mounting length
9.5 SITRANS TS500
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
∅d External diameter of measuring insert
Figure 9-18 Dimensional drawings SITRANS TS500, type FS, flanged straight well - dimensions in
mm (inch)
N Nominal length
91
Page 92
Dimension drawings
9.5.15

SITRANS TS500, type FS, flanged straight well (7MC55..)

∅D
External diameter of measuring insert
N
Nominal length
X
Extension
U
Mounting length
X1
Lag length
B
Lenght of measuring insert
H1
Head bottom thickness
9.5 SITRANS TS500
Figure 9-19 Dimensional drawings SITRANS TS500, type FS, flanged straight well (7MC55…)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
92 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 93
Dimension drawings
9.5.16

SITRANS TS500, type FR, flanged reduced well (7MC65..)

(6 (0.24))
X
Extension
U
Mounting length
9.5 SITRANS TS500
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
∅d External diameter of measuring insert
Figure 9-20 Dimensional drawings SITRANS TS500, type FR, flanged reduced well - dimensions in
mm (inch)
N Nominal length
93
Page 94
Dimension drawings
9.5.17

SITRANS TS500, type FR, flanged reduced well (7MC55..)

∅D
External diameter of measuring insert
N
Nominal length
X
Extension
U
Mounting length
B
Lenght of measuring insert
H1
Head bottom thickness
9.5 SITRANS TS500
Figure 9-21 Dimensional drawings SITRANS TS500, type FR, flanged reduced well (7MC55…)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
94 Compact Operating Instructions, 01/2018, A5E03920348-AE
Page 95
Dimension drawings
9.5.18

SITRANS TS500, type SWT, socket tapered well (7MC65..)

(6 (0.24))
∅D
External diameter of process connection
U
Mounting length
∅D2
External diameter of tip
X
Extension
∅D8
Internal diameter of protective tube
9.5 SITRANS TS500
∅d External diameter of measuring insert
Figure 9-22 Dimensional drawings SITRANS TS500, type SWT, socket tapered well - dimensions in
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
N Nominal length
mm (inch)
95
Page 96
Dimension drawings
9.5.19

SITRANS TS500, type SWST, socket tapered well (7MC55..)

L
Length of thermowell
B
Length of measuring insert
∅D1
External diameter of process connection
N
Nominal length
∅D2
External diameter of tip
U
Insertion length
Type Bxx = 26 (1.02)
X1
Lag lenght
C
Cone Length
9.5 SITRANS TS500
X Extension length H1 Head bottom thickness
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
96 Compact Operating Instructions, 01/2018, A5E03920348-AE
Type Axx = 41 (1.61)
Page 97
Dimension drawings
9.5 SITRANS TS500
Figure 9-23 Dimensional drawings SITRANS TS500, type SWST, socket tapered well (7MC55…)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
97
Page 98
Dimension drawings
9.5.20

SITRANS TS500, type SWS, socket straight well (7MC65..)

(6 (0.24))
∅D
External diameter of process connection
U
Mounting length
∅D2
External diameter of tip
X
Extension
∅D8
Internal diameter of protective tube
9.5 SITRANS TS500
∅d External diameter of measuring insert
Figure 9-24 Dimensional drawings SITRANS TS500, type SWS, socket straight well - dimensions in
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
98 Compact Operating Instructions, 01/2018, A5E03920348-AE
N Nominal length
mm (inch)
Page 99
Dimension drawings
9.5.21

SITRANS TS500, type SWS, socket straight well (7MC55..)

∅D
External diameter of process connection
U
Mounting length
B
Length of measuring Insert
X
Extension
Type Bxx = 26 (1.02)
N
Nominal length
L
Length of thermowell
9.5 SITRANS TS500
H1 Head bottom thickness:
Figure 9-25 Dimensional drawings SITRANS TS500, type SWS, socket straight well (7MC55…)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell Compact Operating Instructions, 01/2018, A5E03920348-AE
X1 Lag length
Type Axx = 41 (1.61)
99
Page 100
Dimension drawings
9.5.22

SITRANS TS500, type SWR, socket reduced well (7MC65..)

(6 (0.24))
∅D
External diameter of process connection
U
Mounting length
∅D8
Internal diameter of tip
X
Extension
9.5 SITRANS TS500
∅d External diameter of measuring insert
Figure 9-26 Dimensional drawings SITRANS TS500, type SWR, socket reduced well - dimensions in
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
100 Compact Operating Instructions, 01/2018, A5E03920348-AE
N Nominal length
mm (inch)
Loading...