Siemens SITRANS P Series,SITRANS P DS III Series Operating Instructions Manual

Pressure transmitter
SITRANS P, DS III series
Compact Operating Instructions
08/2011
SITRANS
English..................................................................................................................................................................4
Български ..........................................................................................................................................................50
Češt
ina ...............................................................................................................................................................99
S
uomi ...............................................................................................................................................................145
S
lovenčina........................................................................................................................................................190
S
lovenščina ......................................................................................................................................................237
© Siemens Ⓟ2011 A5E03434645-01, 08/2011
3
SITRANS Pressure transmitter SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
Compact Operating Instructions
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE indicates that an unintended result or situation can occur if the relevant information is not taken into account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.
© Siemens Ⓟ2011
4 A5E03434645-01, 08/2011
Introduction
Purpose of this documentation
These instructions are a brief summary of important features, functions and safety information, and contain all information required for safe use of the device. It is your responsibility to read the instructions carefully prior to installation and commissioning. In order to use the device correctly, first review its principle of operation.
The instructions are aimed at persons who mechanically assemble the device, connect it electrically, and start it up. To achieve optimum usage of the device, read the detailed version of the manual on the electronic data medium.
See also Instructions and Manuals (http://www.siemens.com/processinstrume
ntation/documentation)
History
This history establishes the correlation between the current documentation and the valid firmware of the device. The documentation of this edition is applicable for the following firmware:
Edition Firmware identifier nameplate System integration Installation path for PDM 08/2011 HART:
FW: 11.03.03, FW: 11.03.04, FW: 11.03.05, FW: 11.03.06
PA/FF: FW: 0300.01.08
PDM 6.01); Dev. Rev.3 DD Rev.2
SITRANS P DSIII.2
1)
up to SP05 Hotfix 5
Purpose
Overview Depending on the version, a transmitter measures corrosive, non-corrosive and hazardous gases, vapors and liquids. You can use the transmitter for the following types of measurement:
● Gauge pressure
● Absolute pressure
● Differential pressure With appropriate parameter settings and the necessary add-on parts (e.g. flow orifices and remote seals), the pressure
transmitter can also be used for the following measurements:
● Level
● Volume
● Mass
● Volume of flow
● Mass flow rate The output signal is always a load-independent direct current between 4 and 20 mA. You can install the "intrinsically-safe" or "explosion-proof" version of the transmitter in hazardous areas. The devices have an
EC type examination certificate and comply with the appropriate harmonized European CENELEC directives. Transmitters with remote seals of different shapes can be delivered for special applications. For example, measuring high-
viscosity substances is a special application. Operate the device in accordance with the specifications in Section Technical specifications (Page 35). F
or additional information, please refer to the operating instructions for the device.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
5
Checking the consignment
1. Check the packaging and the device for visible damage caused by inappropriate handling during shipping.
2. Report any claims for damages immediately to the shipping company.
3. Retain damaged parts for clarification.
4. Check the scope of delivery by comparing the shipping documents with your order for correctness and completeness.
WARNING
Using a damaged or incomplete device Danger of explosion in hazardous areas.
● Do not use any damaged or incomplete devices.
Nameplate layout
Nameplate with general information The nameplate bearing the Order No. and other important information, such as design details and technical data, is on the
side of the enclosure.
Filling Silikonöl
Mat.: Connec. Diaphr.
V :DC1 0.5-45 V (not intr.s ave ) outp.:4-20 mA
H
Measuring span Ove rrange limits
Type of protection IP 65
Fab. Nr. N1LN1 1-0047 11
Tr ansmit ter for pressur e
1.4404 2.481 9
7MF4033-1EB1 0-1DA1
: 0.6 3 - 63 bar :-1-100 bar
Made in Fr ance
0032
PED:SEP
SITRANS P
D-76181 Karlsr uhe
Order number (machine-readable product code) Serial number
Figure 1 Example of a nameplate
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
6 A5E03434645-01, 08/2011
Nameplate with approval information On the opposite side is the nameplate with approval information. This nameplate shows e.g. the hardware and firmware
versions. Certificate information is also listed if the transmitter is an ex-version.
V :DC 10. 5 - 4 5 V outp.: 4 - 20mA
H
II 1/2 G Ex d IIC T4/T6
PTB 99 ATEX 116 0
FW : 1 3.0 1.02 HW : 01.02.03
T = -40 ... 85/60 °C
a
Observ e EC-Type Examination Certicate !
SITRANS P
D-76181 Karlsr uhe
,,*([G,,&77
):[[\\]] +:[[\\]]
&RPSDWLELOLW\PDUN 3URGXFWYHUVLRQFRQQHFWLRQERDUG 6HULDOQXPEHU ):YHUVLRQ 'RFXPHQW5HYLVLRQ 'HYLFHW\SH
Characteristics for hazardous area Group (gas, dust) Category for operating area Maximum surface temperature (temperature class) Type of protection
Figure 2 Example of a nameplate
Transportation and storage
To guarantee sufficient protection during transport and storage, observe the following:
● Keep the original packaging for subsequent transportation.
● Devices/replacement parts should be returned in their original packaging.
● If the original packaging is no longer available, ensure that all shipments are properly packaged to provide sufficient protection during transport. Siemens cannot assume liability for any costs associated with transportation damages.
CAUTION
Insufficient protection during storage The packaging only provides limited protection against moisture and infiltration.
● Provide additional packaging as necessary.
Special conditions for storage and transportation of the device are listed in "Technical data" (Page 35).
Notes on warranty
The contents of this manual shall not become part of or modify any prior or existing agreement, commitment or legal relationship. The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty.
The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
7
Safety instructions
Precondition for use
This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety.
Observe the information and symbols on the device. Do not remove any information or symbols from the device. Always keep the information and symbols in a completely legible state.
Warning symbols on the device
Symbol Explanation
Consult operating instructions
Laws and directives
Observe the test certification, provisions and laws applicable in your country during connection, assembly and operation. These include, for example:
● National Electrical Code (NEC - NFPA 70) (USA)
● Canadian Electrical Code (CEC) (Canada) Further provisions for hazardous area applications are for example:
● IEC 60079-14 (international)
● EN 60079-14 (EC)
Conformity with European directives
The CE mark on the device is a sign of conformity with the following European directives:
Electromagnetic Compatibility EMC 2004/108/EC
Directive of the European Parliament and of the Council on the approximation of the laws of the Member States relating to electromagnetic compatibility and repealing Directive 89/336/EEC.
Atmosphère explosible ATEX 94/9/EC
Directive of the European Parliament and the Council on the approximation of the laws of the Member States concerning equipment and protective systems intended for use in potentially explosive atmospheres.
Pressure Equipment Directive PED 97/23/EC
Directive of the European Parliament and of the Council on the approximation of the laws of the Member States concerning pressure equipment.
The standards applied can be found in the EC declaration of conformity for the device.
Improper device modifications
WARNING
Improper device modifications Danger to personnel, system and environment can result from modifications to the device, particularly in hazardous areas.
● Only carry out modifications that are described in the instructions for the device. Failure to observe this requirement cancels the manufacturer's warranty and the product approvals.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
8 A5E03434645-01, 08/2011
Requirements for special applications
Due to the large number of possible applications, each detail of the described device versions for each possible scenario during commissioning, operation, maintenance or operation in systems cannot be considered in the instructions. If you need additional information not covered by these instructions, contact your local Siemens office or company representative.
Note Operation under special ambient conditions We highly recommend that you contact your Siemens representative or our application department before you operate the
device under special ambient conditions as can be encountered in nuclear power plants or when the device is used for research and development purposes.
Use in hazardous areas
Qualified personnel for hazardous area applications Persons who install, assemble, commission, operate and service the device in a hazardous area must have the following
specific qualifications:
● They are authorized, trained or instructed in operating and maintaining devices and systems according to the safety regulations for electrical circuits, high pressures and aggressive as well as hazardous media.
● They are authorized, trained, or instructed in carrying out work on electrical circuits for hazardous systems.
● They are trained or instructed in maintenance and use of appropriate safety equipment according to the pertinent safety regulations.
WARNING
Unsuitable device for the hazardous area Danger of explosion.
● Only use equipment that is approved for use in the intended hazardous area and labelled accordingly.
See also Technical specifications (Page 35)
WARNING
Loss of safety of device with type of protection "Intrinsic safety Ex i" If the device has already been operated in non-intrinsically safe circuits or the electrical specifications have not been
observed, the safety of the device is no longer ensured for use in hazardous areas. There is a danger of explosion.
● Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe circuit.
● Observe the specifications for the electrical data in the certificate and in Technical data (Page 35).
WARNING
Use of incorrect device parts in potentially explosive environments Devices and their associated device parts are either approved for different types of protection or they do not have
explosion protection. There is a danger of explosion if device parts (such as covers) are used for devices with explosion protection that are not expressly suited for this type of protection. If you do not adhere to these guidelines, the test certificates and the manufacturer warranty will become null and void.
● Use only device parts that have been approved for the respective type of protection in the potentially explosive environment. Covers that are not suited for the "explosion-proof" type of protection are identified as such by a notice label attached to the inside of the cover with "Not Ex d Not SIL".
● Do not swap device parts unless the manufacturer specifically ensures compatibility of these parts.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
9
WARNING
Risk of explosion due to electrostatic charge To prevent the build-up of an electrostatic charge in a hazardous area, the key cover must be closed during operation and
the screws tightened. The key cover may be opened temporarily at any time for the purposes of operating the transmitter, even during plant
operation; the screws should then be tightened again.
Installing/mounting
Basic safety instructions
WARNING
Wetted parts unsuitable for the process media Danger of injury or damage to device. Hot, toxic and corrosive media could be released if the process medium is unsuitable for the wetted parts.
● Ensure that the material of the device parts wetted by the process medium is suitable for the medium. Refer to the
information in "Technical data" (Page 35).
WARNING
Incorrect material for the diaphragm in Zone 0 Danger of explosion in the hazardous area. In the case of operation with intrinsically safe supply units of category "ib" or
devices of the flameproof enclosure version "Ex d" and simultaneous use in Zone 0, transmitter explosion protection depends on the tightness of the diaphragm.
● Ensure that the material used for the diaphragm is suitable for the process medium. Refer to the information in the
section "Technical specifications (Page 35)".
WARNING
Unsuitable connecting parts Danger of injury or poisoning. In case of improper mounting hot, toxic and corrosive process media could be released at the connections.
● Ensure that connecting parts (such as flange gaskets and bolts) are suitable for connection and process media.
Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you
are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
10 A5E03434645-01, 08/2011
WARNING
Exceeded maximum permissible operating pressure Danger of injury or poisoning. The maximum permissible operating pressure depends on the device version. The device can be damaged if the operating
pressure is exceeded. Hot, toxic and corrosive process media could be released.
● Make sure that the device is suitable for the maximum permissible operating pressure of your system. Refer to the information on the nameplate and/or in "Rated operating conditions" (Page 35).
WARNING
Exceeded maximum ambient or process media temperature Danger of explosion in areas subject to explosion hazard. Device damage.
● Make sure that the maximum permissible ambient and process media temperatures of the device are not exceeded. Refer to the information in Chapter Technical specifications (Page 35).
WARNING
Open cable inlet or incorrect cable gland Danger of explosion in hazardous areas.
● Close the cable inlets for the electrical connections. Only use cable glands or plugs which are approved for the relevant type of protection.
WARNING
Incorrect conduit system Danger of explosion in hazardous areas as result of open cable inlet or incorrect conduit system.
● In the case of a conduit system, mount a spark barrier at a defined distance from the device input. Observe national regulations and the requirements stated in the relevant approvals.
See also Technical specifications (Page 35)
WARNING
Incorrect mounting at Zone 0 Danger of explosion in areas subject to explosion hazard.
● Ensure sufficient tightness at the process connection.
● Observe the standard IEC/EN 60079-26.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
11
WARNING
Danger with "flameproof enclosure" protection Danger of explosion in hazardous areas. An explosion may be caused by hot gas escaping from the flameproof enclosure
if there is too little space between it and the fixed parts.
● Ensure that there is a space of at least 40 mm between the flameproof joint and the fixed parts.
Flameproof joint
WARNING
Loss of explosion protection Danger of explosion in hazardous areas if the device is open or not properly closed.
● Close the device as described in Chapter "Connecting the device (Page 21)".
CAUTION
Hot surfaces resulting from hot process media Danger of burns resulting from surface temperatures above 70 °C (155 °F).
● Take appropriate protective measures, for example contact protection.
● Make sure that protective measures do not cause the maximum permissible ambient temperature to be exceeded.
Refer to the information in Chapter Technical specifications (Page 35).
CAUTION
External stresses and loads Damage to device by severe external stresses and loads (e.g. thermal expansion or pipe tension). Process media can be
released.
● Prevent severe external stresses and loads from acting on the device.
Installation location requirements
WARNING
Insufficient air supply The device may overheat if there is an insufficient supply of air.
● Install the device so that there is sufficient air supply in the room.
● Observe the maximum permissible ambient temperature. Refer to the information in the section "Technical
specifications (Page 35)".
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
12 A5E03434645-01, 08/2011
CAUTION
Aggressive atmospheres Damage to device through penetration of aggressive vapors.
● Ensure that the device is suitable for the application.
CAUTION Direct sunlight
Increased measuring errors.
● Protect the device from direct sunlight.
Make sure that the maximum ambient temperature is not exceeded. Refer to the information in the section Technical specifications (Page 35).
Proper mounting
CAUTION Incorrect assembly
The device can be damaged or destroyed or its functionality impaired through incorrect assembly.
● Make sure before installing the device that there is no visible damage.
● Check that the process connections are clean and the right seals and cable glands have been used.
● Assemble the device using suitable tools, observing the torques specified in the technical specifications.
NOTICE Loss of degree of protection
Damage to device if the enclosure is open or not properly closed. The degree of protection specified on the nameplate or in "Technical data" (Page 35) is no longer guaranteed.
● Make sure that the device is securely closed.
See also Connecting the device (Page 21)
Disassembly
WARNING
Incorrect disassembly The following dangers may result through incorrect disassembly:
- Injury through electric shock
- Danger through emerging media when connected to the process
- Danger of explosion in hazardous area
In order to disassemble correctly, observe the following:
● Before starting work, make sure that you have switched off all physical variables such as pressure, temperature, electricity etc. or that they have a harmless value.
● If the device contains dangerous media, it must be emptied prior to disassembly. Make sure that no environmentally hazardous media are released.
● Secure the remaining connections so that no damage can result if the process is started unintentionally.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
13
Installation (except level)
Instructions for installation (except level)
Conditions
NOTICE Compare the desired operating data with the data on the nameplate.
Please also refer to the information on the remote seal if this is fitted.
Note Protect the transmitter against:
● Direct heat radiation
● Rapid temperature fluctuations
● Heavy contamination
● Mechanical damage
● Direct sunlight
The installation location is to be as follows:
● Easily accessible
● As close as possible to the measuring point
● Vibration-free
● Within the permitted ambient temperature values
Installation configuration The transmitter may in principle be configured above or below the pressure tapping point. The recommended configuration
depends on the aggregate state of the medium. Installation configuration for gases Install the transmitter above the pressure tapping point. Lay the pressure tubing with a constant gradient to the pressure tapping point, so that any condensation produced can drain
in the main line and thereby avoid corruption of the measured values. Installation configuration for vapor and liquid Install the transmitter below the pressure tapping point. Lay the pressure tubing with a constant gradient to the pressure tapping point so that any gas pockets can escape in the
main line.
Installation (except level)
NOTICE Damage to measuring cell
When installing the process connection of the pressure transmitter, do not rotate the housing. Rotating the housing may damage the measuring cell.
To avoid damage to the device, tighten the threaded nuts of the measuring cell using a wrench.
Procedure Attach the transmitter to the process connection with an appropriate tool.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
14 A5E03434645-01, 08/2011
See also Introduction to commissioning (Page 24)
Fastening
Fastening without the mounting bracket You can fasten the transmitter directly on the process connection.
Fastening with the mounting bracket You can fasten the mounting bracket as follows:
● On a wall or a mounting frame using two screws
● On a vertical or horizontal mounting tube (Ø 50 to 60 mm) using a tube bracket Fasten the transmitter mounting bracket using the two screws provided.
Figure 3 Fastening the transmitter on the mounting bracket
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
15
Figure 4 An example of fastening the transmitter on the mounting bracket in the case of differential pressure and
horizontal differential pressure lines
Figure 5 An example of fastening on the mounting bracket in the case of differential pressure and vertical differential
pressure lines
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
16 A5E03434645-01, 08/2011
"Level" installation
Instructions for level installation
Requirements
NOTICE Compare the desired operating data with the data on the nameplate.
Please also refer to the information on the remote seal if this is fitted.
Note Protect the transmitter from:
● Direct heat
● Rapid temperature changes
● Severe soiling
● Mechanical damage
● Direct sunlight
Note Select the height of the mounting flange such that the pressure transmitter is always mounted below the lowest fill height to
be measured.
The installation location is to be as follows:
● Easily accessible
● The measuring point must be as close as possible
● Vibration-free
● Within the permitted ambient temperature values
Installation for level
Note Seals are required for the installation. The seals must be compatible with the medium to be measured. Seals are not included in the delivery.
Procedure To install the transmitter for level, proceed as follows:
1. Attach the seal to the container's mating flange. Ensure that the seal is centrically positioned and that it does not restrict the movement of the flange's seal diaphragm in
any way as otherwise the tightness of the process connection is not guaranteed.
2. Screw on the transmitter's flange.
3. Observe the installation position.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
17
Connection of the negative pressure line
Measurement in an open container A line is not required when taking measurements in an open container since the negative chamber is connected with the
atmosphere. Ensure that no dirt enters the open connection ports, for example by using connection screws with a 7MF4997-1CP bleed
valve.
+
)XOOVFDOHYDOXH
6WDUWRIVFDOHYDOXH
K
2
K
8
Measurement assembly on an open container
Formula: Start of scale value: p
MA
= ρ · g · hU
Full scale value: p
ME
= ρ · g · hO
hU Lower filling height ΔpMA Start of scale value h
O
Upper filling height ΔpME Full scale value
p Pressure ρ Density of the measured medium in the
container
g Acceleration due to gravity
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
18 A5E03434645-01, 08/2011
Measurement in a closed container When taking measurements in a closed container without or with little condensate formation, the negative pressure line is
not filled. Lay the line in such a way that pockets of condensate do not form. Install a condensation container if required.
)XOOVFDOHYDOXH
6WDUWRIVFDOHYDOXH
0D[LPXPOHYHO
6WDWLF SUHVVXUH
K
2
K
8
*DVILOOHGORZ SUHVVXUHOLQH
7UDQVPLWWHU UHIHUHQFHOLQH
Measurement assembly on a closed container (no or little condensate separation)
Formula: Start-of-scale value: Δp
MA
= ρ · g · hU
Full scale value: Δp
ME
= ρ · g · hO
hU Lower filling height ΔpMA Start of scale value h
O
Upper filling height ΔpME Full scale value
p Pressure ρ Density of the measured medium in the
container
g Acceleration due to gravity
When taking measurements in a closed container with strong condensate formation, you must fill the negative pressure line (mostly with the condensate of the measured medium) and install a condensate pot. You can cut off the device using the dual pneumatic block 7MF9001-2.
'
-
K
2
K
8
)XOOVFDOHYDOXH
6WDUWRIVFDOHYDOXH
0D[LPXPOHYHO
6WDWLF SUHVVXUH
&RQVWDQW FRPSDULVRQ OHYHO
/LTXLGILOOHG ORZSUHVVXUHOLQH
7UDQVPLWWHU UHIHUHQFHOLQH
K
Y
Measurement assembly on a closed container (strong condensate formation)
Formula: Start-of-scale value:
Δp
MA
= g · (hU · ρ- hV · ρ')
Full scale value: Δp
MA
= g · (hO · ρ- hV · ρ')
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
19
hU Lower filling height ΔpMA Start of scale value h
O
Upper filling height ΔpME Full scale value
h
V
Gland distance ρ Density of the measured medium in the
container
p Pressure ρ ' Density of fluid in the negative pressure line
corresponds to the prevailing temperature there
g Acceleration due to gravity
The process connection on the negative side is a female thread 1/4-18 NPT or an oval flange. Lay the line for the negative pressure using a seamless steel tube 12 mm x 1.5 mm.
Connecting
Basic safety instructions
WARNING
Unsuitable cables and/or cable glands Danger of explosion in hazardous areas if you connect cables and/or cable glands which do not match one another or do
not comply with the technical requirements.
● Only use cables and cable glands complying with the requirements specified in the section Technical specifications (Page 35).
● Tighten the cable glands in accordance with the specified torques.
● When replacing cable glands use only cable glands of the same type.
● After installation check that the cables are seated firmly.
WARNING
Hazardous contact voltage in versions with 4-conductor extension Danger of electrocution in case of incorrect connection.
● For the electrical connection, please refer to the information in the section "Technical specifications (Page 35)".
WARNING
Improper power supply Danger of explosion in hazardous areas as result of incorrect power supply, e.g. using direct current instead of alternating
current.
● Connect the device in accordance with the specified power supply and signal circuits. The relevant specifications can be found in the certificates, in Chapter "Technical specifications (Page 35)" or on the nameplate.
WARNING
Unsafe extra-low voltage Danger of explosion in hazardous areas due to voltage flashover.
● Connect the device to an extra-low voltage with safe isolation (SELV).
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
20 A5E03434645-01, 08/2011
WARNING
Lack of equipotential bonding Danger of explosion through compensating currents or ignition currents through lack of equipotential bonding.
● Ensure that the device is potentially equalized. Exception: It may be permissible to omit connection of the equipotential bonding for devices with type of protection
"Intrinsic safety Ex i".
WARNING
Unprotected cable ends Danger of explosion through unprotected cable ends in hazardous areas.
● Protect unused cable ends in accordance with IEC/EN 60079-14.
WARNING
Improper laying of shielded cables Danger of explosion through compensating currents between hazardous area and the non-hazardous area.
● Only ground shielded cables that run into the hazardous area at one end.
● If grounding is required at both ends, use an equipotential bonding conductor
WARNING
Connecting device in energized state Danger of explosion in hazardous areas.
● Connect devices in hazardous areas only in a de-energized state. Exceptions:
● Circuits of limited energy may also be connected in the energized state in hazardous areas.
● Exceptions for type of protection "Non-sparking nA" (Zone 2) are regulated in the relevant certificate
WARNING
Incorrect selection of type of protection Danger of explosion in areas subject to explosion hazard. This device is approved for several types of protection.
1. Decide in favor of one type of protection.
2. Connect the device in accordance with the selected type of protection.
3. In order to avoid incorrect use at a later point, make the types of protection that are not used permanently unrecognizable on the nameplate.
CAUTION Ambient temperature too high
Damage to cable sheath.
● At an ambient temperature ≥ 60 °C (140 °F), use heat-resistant cables suitable for an ambient temperature at least 20 °C (68 °F) higher.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
21
CAUTION Incorrect measured values with incorrect grounding
The device must not be grounded via the "+" connection. It may otherwise malfunction and be permanently damaged.
● If necessary, ground the device using the "-" connection.
Note Electromagnetic compatibility (EMC) You can use this device in industrial environments, households and small businesses. For metal housings there is an increased electromagnetic compatibility compared to high-frequency radiation. This
protection can be increased by grounding the housing, see section "Connecting the device (Page 21)".
Note Improvement of interference immunity
● Lay signal cables separate from cables with voltages > 60 V.
● Use cables with twisted wires.
● Keep device and cables in distance to strong electromagnetic fields.
● Use shielded cables to guarantee the full specification according to HART.
● Connect a load resistor of at least 230 Ω in series in the signal circuit in order to guarantee fault-free HART communication. When power supply isolators are used for HART transmitters, e.g. SITRANS I, a load resistor is already installed in the device.
Connecting the device
Opening the device
1. Unscrew the cover of the electrical cable compartment. An identification text "FIELD TERMINAL" is provided at the side of the housing.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
22 A5E03434645-01, 08/2011
Connecting the device
1. Lead the connecting cable through the cable gland .
2. Connect the device to the plant with the protective conductor connection
.
3. Connect the wires to the connecting terminals
"+" and "-".
Ensure the correct polarity! If necessary, ground the device using the "-" connection by connecting the "-" connection to the ground terminal .
4. If necessary, connect the shield to the screw of the ground terminal
. This is electrically connected with the external
protective conductor connection.
HART PROFIBUS PA / Foundation™ Fieldbus FF
˖

Feed separator with integrated load
Safety catch
Auxiliary power
Protective conductor connection/ equipotential bonding terminal
Cable entry for auxiliary power/analog output
Process connection
Connecting terminals
Ground terminal
Test connector for direct current measuring device or connection for external display
PROFIBUS PA / Foundation™ Fieldbus FF
Electrical connection, power supply
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
23
Closing the device
1. Screw the covers ④⑦ back on as far as they will go.
2. Secure each cover with the cover catch
③⑥.
3. Close the key cover
.
4. Tighten the screws in the key cover.
5. Check the tightness of the blanking plugs
and cable gland in accordance with the degree of protection.
8
Key cover Blanking plug Cable gland Safety catch (front) Safety catch (back) Cover (front), optionally with inspection window Cover (rear) for electrical terminal compartment Safety catch for stainless steel enclosure
Figure 6 View of the transmitter: Left: Back right: Front view
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
24 A5E03434645-01, 08/2011
Commissioning
Basic safety instructions
DANGER
Toxic gases and liquids Danger of poisoning when the device is vented. If toxic process media are measured, toxic gases and liquids can be released when the device is vented.
● Before venting ensure that there are no toxic gases and liquids in the device. Take the appropriate safety measures.
WARNING
Improper commissioning in hazardous areas Device failure or danger of explosion in hazardous areas.
● Do not commission the device until it has been mounted completely and connected in accordance with the information in Chapter "Technical specifications (Page 35)".
● Before commissioning take the effect on other devices in the system into account.
WARNING
Opening device in energized state Danger of explosion in areas subject to explosion hazard.
● Only open the device in a de-energized state.
● Check prior to commissioning that the cover, cover locks, and cable inlets are assembled in accordance with the directives.
Exception: Devices having the type of protection "Intrinsic safety Ex i" may also be opened in energized state in hazardous areas.
NOTICE Hot surfaces
Hot process medium and high ambient temperatures lead to hot surfaces which can cause burns.
● Take corresponding protective measures, for example wear protective gloves.
Introduction to commissioning
Following commissioning, the transmitter is immediately ready for use. To obtain stable measured values, the transmitter needs to be allowed to warm up for five minutes or so after the power
supply is switched on. The operating data must correspond to the values specified on the nameplate. If you switch on the auxiliary power, the
transmitter will operate. The following commissioning cases are typical examples. Configurations different from those listed here may be meaningful
depending on the system configuration.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
25
gauge pressure, absolute pressure from the differential pressure series and absolute pressure from the gauge pressure series
Commissioning for gases
Usual arrangement Special arrangement


Measuring gases above the pressure tapping point Measuring gases below the pressure tapping point
Pressure transmitter
Pressure line
Shut-off module
Shut-off valve
Shut-off valve to process
Shut-off valve (optional)
Condensate vessel (optional)
Shut-off valve for test connection or for bleed screw
Drain valve
Condition All valves are closed.
Procedure To commission the transmitter for gases, proceed as follows:
1. Open the shut-off valve for the test connection
.
2. Via the test connection of the shut-off fitting
, apply the pressure corresponding to the start of scale value to the
pressure transmitter
.
3. Check the start of scale value.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
26 A5E03434645-01, 08/2011
4. If the start of scale value differs from the value desired, correct it.
5. Close the shut-off valve for the test connection .
6. Open the shut-off valve
at the pressure tapping point.
7. Open the shut-off valve for the process
.
Commissioning with steam or liquid

Pressure transmitter Shut-off fitting Shut-off valve to process Shut-off valve for test connection or for bleed screw Pressure line Shut-off valve Blow-out valve Compensation vessel (steam only)
Figure 7 Measuring steam
Requirement All valves are closed.
Procedure To commission the transmitter for steam or liquid, proceed as follows:
1. Open the shut-off valve for the test connection .
2. Via the test connection of the shut-off module
, apply the pressure corresponding to the start of scale value to the
pressure transmitter
.
3. Check the start of scale value.
4. If the start of scale value differs from the value desired, correct it.
5. Close the shut-off valve for the test connection
.
6. Open the shut-off valve
at the pressure tapping point.
7. Open the shut-off valve for the process
.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
27
Differential pressure and flow rate
Safety notes for commissioning with differential pressure and flow rate
WARNING
Incorrect or improper operation If the lock screws are missing or are not sufficiently tight, and/or if the valves are operated incorrectly or improperly, it could
lead to serious physical injuries or considerable damage to property. Measure
● Take care that the locking screw and/or the vent valve are screwed in and tightened.
● Ensure that the valves are operated correctly and properly.
WARNING
Hot mediums In the case of hot mediums, the individual operational steps should be carried out one after the other. Otherwise, it could
lead to excessive heating, thus causing damage to the valves and the transmitter.
Commissioning in gaseous environments
Usual arrangement Special arrangement


Pressure transmitter
Shut-off valves
Stabilizing valve
Drain valves
,
Differential pressure valves
Condensate vessels (optional)
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
28 A5E03434645-01, 08/2011
Differential pressure lines
Differential pressure transducer
Transmitter above the differential pressure transducer
Transmitter below the differential pressure transducer
Condition All shut-off valves are closed.
Procedure To commission the transmitter for gases, proceed as follows:
1. Open both the shut-off valves
at the pressure tapping point.
2. Open the stabilizing valve
.
3. Open the differential pressure valve (
or ).
4. Check and if required correct the zero point when the start of scale value is 0 mbar (4 mA).
5. Close the stabilizing valve
.
6. Open the other differential pressure valve (
or ).
Commissioning for liquids
Usual arrangement Special arrangement

 
Pressure transmitter
Drain valves
Stabilizing valve
Gas collector vessels (optional)
,
Differential pressure valves
Differential pressure transducer
Differential pressure lines
Vent valves
Shut-off valves
Transmitter below the differential pressure transducer
Transmitter above the differential pressure transducer
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..) A5E03434645-01, 08/2011
29
Condition All valves are closed.
Procedure
WARNING
The transmitter should not be depressurized if toxic substances are being used.
To commission the transmitter with liquids, proceed as follows:
1. Open both the shut-off valves
at the pressure tapping point.
2. Open the stabilizing valve
.
3. With transmitters below the differential pressure transducer, open both the drain valves one after the other
until the
air-free liquid emerges. In the case of a transmitter above the differential pressure transducer, open both the vent valves one after the other
until the liquid emerges.
4. Close both drain valves
or vent valves .
5. Open the differential pressure valve
and the vent valve on the positive side of the transmitter slightly, until fluid
escapes without bubbles.
6. Close the vent valve.
7. Open the vent valve on the negative side of the transmitter
slightly, until fluid escapes without bubbles.
8. Close the differential pressure valve
.
9. Open the differential pressure valve
until the liquid emerges and then close it.
10. Close the vent valve on the negative side of the transmitter
.
11. Open the differential pressure valve
by rotating it in half a turn.
12. Check and if required adjust the zero point (4 mA) if the start-of-scale value is 0 bar.
13. Close the stabilizing valve
.
14. Open the differential pressure valves (
and ) completely.
SITRANS P, DS III series (7MF4.33.. 7MF4.34.. 7MF4.35..)
30 A5E03434645-01, 08/2011
Commissioning with vapor


Pressure transmitter Drain valves Stabilizing valve Condensate pots , Differential pressure valves Differential pressure transducer/Orifice plate Differential pressure lines Insulation Shut-off valves
Figure 8 Measuring steam
Condition All valves are closed.
Procedure
CAUTION The measuring result is error-free only if the differential pressure lines have equally high condensate columns with the
same temperature. The zero calibration must be repeated if required if these conditions are fulfilled. If the shut-off valves
and the differential pressure valves are open at the same time and the stabilizing valve is opened, there is a
possibility of the transmitter
being damaged due to the streaming vapor.
To commission the transmitter for vapor, proceed as follows:
1. Open both the shut-off valves
at the pressure tapping point.
2. Open the stabilizing valve
.
3. Wait until the steam in the differential pressure lines
and in the equalizing vessels has condensed.
4. Open the differential pressure valve
and the vent valve on the positive side of the transmitter slightly, until
condensate escapes without bubbles.
5. Close the vent valve.
6. Open the vent valve on the negative side of the transmitter
slightly, until condensate escapes without bubbles.
7. Close the differential pressure valve
.
8. Open the differential pressure valve
slightly, until condensate escapes without bubbles, then close it.
Loading...
+ 254 hidden pages