Siemens SITRANS LR Quick Start Manual

Radar Transmitters
SITRANS Probe LR
Quick Start Manual 12/2012
SITRANS
SITRANS Probe LR Quick Start Manual
This manual outlines the essential features and functions of SITRANS Probe LR. We strongly advise you to acquire the detailed version of the manual so you can use your instrument to its fullest potential. The complete manual can be downloaded from the Siemens website at: www.siemens.com/level.
Questions about the contents of this manual can be directed to:
Siemens Milltronics Process Instruments 1954 Technology Drive, P.O. Box 4225 Peterborough, Ontario, Canada, K9J 7B1 Email: techpubs.smpi@siemens.com
The printed manual is available from your local Siemens representative.
Copyright Siemens Milltronics
Process Instruments 2013.
Disclaimer of Liability
All Rights Reserved
We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments. Siemens Milltronics Process Instruments will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions.
While we have verified the contents of this manual for agreement with the instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement.
Technical data subject to change.
mmmmm
MILLTRONICS is a registered trademark of Siemens Milltronics Process Instruments
Safety Guidelines
Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed.
WARNING: relates to a caution symbol on the product, and means that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage.
WARNING in death, serious injury, and/or considerable material damage.
1
: means that failure to observe the necessary precautions can result
1
Note: means important information about the product or that part of the operating manual.
1.
This symbol is used when there is no corresponding caution symbol on the product.
A5E32106153 SITRANS Probe LR – QUICK START MANUAL Page EN-1
SITRANS Probe LR
process temperature
–40 to +80 °C (–40 to +176 °F)
ambient temperature (surrounding enclosure volume) –40 to +80 °C (–40 to +176 °F)
process device tag
nameplate location
customer-supplied flange
locking collar
2
over threaded connection;
secured by three 2 mm Allen set-screws
hand programmer
WARNING: Changes or modifications not expressly approved by Siemens could void the user’s authority to operate the equipment.
mmmmm
Notes:
English
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.
SITRANS Probe LR is to be used only in the manner outlined in this manual, otherwise protection provided by the equipment may be impaired
This product is intended for use in industrial areas. Operation of this equipment in a residential area may cause interference to several frequency based communications..
SITRANS Probe LR is a 2-wire loop-powered, continuous level measuring instrument that utilizes advanced pulse radar technology at 5.8 GHz (6.3 GHz in North America). The instrument consists of an electronic component coupled to the antenna and process connection.
1
Communication is via HART
, and signals are processed using Sonic Intelligence®.
Specifications
For a complete listing, see the full manual for SITRANS Probe LR (Part#: 7ML19985HR0x). For Approvals information, please refer to the device nameplate.
2
Ambient/Operating Temperature
Note: Process temperature and pressure capabilities are dependent upon information on
the process device tag. The reference drawing listed on the tag can be downloaded from the Siemens website. Go to the SITRANS Probe LR product page at: https://pia.khe.siemens.com/index.asp?Nr=11158
1.
HART®is a registered trademark of the HART Communication Foundation.
2.
When the locking collar is secured, it prevents the enclosure rotating on the threaded connection.
Page EN-2 SITRANS Probe LR – QUICK START MANUAL A5E32106153
.
Power
Nominal 24 V DC at max. 550 Ohm
Maximum 30 V DC
4 to 20 mA
Approvals
General CSA
Radio Europe (R&TTE), FCC, Industry Canada
Hazardous Intrinsically Safe (Europe) ATEX II 1 G EEx ia IIC T4
Non-incendive (US) FM
, FM, CE, C-TICK
US/C
(US/Canada) FM/CSA
1
: (barrier required) Class I, Div. 1, Groups A, B, C, D Class II, Div. 1, Groups E, F, G Class III T4
(Australia) ANZEx Ex ia IIC T4
(Tamb = –40 to + 80 °C) IP67, IP68
(International) IECEx TSA 04.0020X Ex ia IIC T4 (Brazil) INMETRO: DNV 12.0068 X
Ex ia IIC T4 Ga IP66/IP67/IP68
-40 ºC
T a +80 ºC
DNV #OCP 0017 ABNT NBR IEC 60079-0:2008 e ABNT NBR IEC 60079-11:2009
2
:
mmmmm
Class I, Div. 2, Groups A, B, C, D T5
Marine Lloyd’s Register of Shipping ABS Type Approval
Note: The use of approved watertight conduit hubs/glands is required for Type 4X /
NEMA 4X, Type 6 / NEMA 6, IP67, IP68 (outdoor applications).
Note: EN61000-4-3 (CE EMC) testing was conducted on the SITRANS Probe LR while
mounted in a metallic vessel.
Mechanical
Process Connections:
threaded connection 1.5” NPT, BSP, or G (BS EN ISO 228-1)
•Antenna:
polypropylene rod hermetically sealed construction
1.
See
Wiring Drawing: Intrinsically Safe (FM )
or
Wiring Drawing: Intrinsically Safe (CSA)
2.
See
Wiring Drawing: Non-incendive (FM)
on page 2 of Appendix A, for drawing number 23651611,
on page 3 of Appendix A, for drawing number 23651621.
on page 1 of Appendix A, for drawing number 23650537.
A5E32106153 SITRANS Probe LR – QUICK START MANUAL Page EN-3
Process
preferred undesirable
Coni
Fl at
Flat Parabolic Conical
min. 300 mm (1 ft) for every 3 m (10 ft) of vessel height
beam angle
28
o
Locate the antenna away from the side wall, to avoid interference from indirect echoes.
Avoid interference from objects such as ladders or pipes, which can cause false echoes.
Avoid interference from the fill path.
Temperature (at process connection): 40 to +80 °C (40 to +176 °F)
Pressure (vessel): maximum 3 bar, gauge (43.5 psi, gauge)
mmmmm
Installation
English
WARNINGS:
• This product can only function properly and safely if it is correctly transported, stored, installed, set up, operated, and maintained.
• Never attempt to loosen, remove, or disassemble process connection or instrument housing while vessel contents are under pressure.
• This product is designated as a Pressure Accessory per Directive 97 / 23 / EC, and is not
intended for use as a safety device.
• Materials of construction are chosen based on their chemical compatibility (or inertness) for general purposes. For exposure to specific environments, check with chemical compatibility charts before installing.
• The user is responsible for the selection of bolting and gasket materials which will fall within the limits of the flange and its intended use, and which are suitable for the service conditions.
• Improper installation may result in loss of process pressure.
Mounting location
Recommendations
Ensure ambient temperature is within –40 to +80 °C (–40 to +176 °F).
Provide easy access for viewing the display and programming via the hand programmer.
Ensure the environment is suitable to the housing rating and materials of construction.
Precautions
Avoid proximity to high voltage or current wiring, high voltage or current contacts, and to variable frequency motor speed controllers.
Avoid interference to the emission cone from obstructions or from the fill path.
Avoid central locations on vessels.
Page EN-4 SITRANS Probe LR – QUICK START MANUAL A5E32106153
Mounting instructions
minimum 100 mm (4")
minimum
10 mm (0.4")
To provide optimum signal conditions on a manhole cover, locate the antenna off-center relative to the cover, typically 100 mm (4”) from the side of the manhole.
Use the 100 mm (4") shield on nozzles that are 100 mm (4") in length, or shorter.
Use the 250 mm (10") shield on nozzles that are 250 mm (10") in length, or shorter.
Mounting on a nozzle Mounting on a manhole cover
Before inserting SITRANS Probe LR into its mounting connection, check to ensure the threads are matching to avoid damaging them.
Simply screw SITRANS Probe LR into the process connection, and hand tighten.
For pressure applications, it will be necessary to use PTFE tape (or other appropriate thread-sealing compound) and tighten the process connection beyond hand-tight. The maximum torque is 40 N-m (30 ft-lbs).
To rotate the enclosure, use a 2 mm Allen key to loosen the three set-screws that secure the locking collar. Once the enclosure is positioned as desired, tighten the set-screws.
mmmmm
Wiring
Power1
WARNINGS:
DC terminals shall be supplied from an SELV 1 source in accordance with IEC­1010-1 Annex H.
All field wiring must have insulation suitable for rated voltages.
1.
Safety Extra Low Voltage
A5E32106153 SITRANS Probe LR – QUICK START MANUAL Page EN-5
mmmmm
locking collar
terminal block
lid screw (1 of 2)
Unscrew the two lid screws to release the hinged lid and access the terminal block.
strain relief (or NPT cable entry)
Connecting SITRANS Probe LR
Notes:
For detailed wiring instructions, please refer to the full Instruction Manual.
Use shielded, twisted pair cable (wire gauge AWG14 to AWG22).
English
Separate cables and conduits wiring practices, or electrical codes.
The non-metallic enclosure does not provide a continuous ground path between conduit connections: use grounding type bushings and jumpers.
1
may be required to conform to standard instrumentation
1
1. If you want to rotate the instrument on the process connection, use the 2 mm Allen key provided to loosen the 3 Allen set-screws securing the locking collar. Position
the unit, and retighten the screws.
Note: Do not rotate the enclosure after programming and vessel calibration,
otherwise an error may occur, caused by a polarity shift of the transmit pulse.
2. Strip the cable jacket for approximately 70 mm (2.75") from the end of the cable, and thread the wires through the strain relief
1.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.
2.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof applications.
Page EN-6 SITRANS Probe LR – QUICK START MANUAL A5E32106153
2
.
3. Connect the wires to the terminals: the polarity is identified
m
m
Normal operation Failsafe operation
1
3
4
5
1
3
4
5
2
6
6
on the terminal block.
4. Tighten the gland to form a good seal. Close the lid and tighten screws: please do not overtighten screws. (Recommended torque is 1.1 to 1.7 N-m (10 to 15 in-lb) of torque)
RUN Mode and PROGRAM Mode
SITRANS Probe LR has two modes of operation: RUN and PROGRAM. After you complete the installation procedures and power up SITRANS Probe LR, it starts in
RUN mode and detects the material level. It returns the distance (in meters) to the material level referenced from Empty (process empty level). This is the default start-up display mode.
RUN Mode Display
Use the hand programmer to control the display.
mmmmm
1 – Primary Reading (displays level, distance, or volume, in either units or percent) 2 – Secondary Reading (displays Parameter number for Auxiliary Reading) 3 – Echo status indicator: Reliable Echo or Unreliable Echo 4 – Units or Percent 5 – Active bar graph represents material level 6 – Auxiliary Reading (depending on the parameter selected, it displays milliAmp value,
distance, or echo confidence, with units where applicable)
If the echo confidence drops below the echo confidence threshold, the failsafe timer starts running. When the timer expires, the letters LOE (Loss of Echo) alternate with the reading every two seconds, and the Reliable Echo indicator is replaced by the Unreliable indicator. When a valid reading is received, the level reading display returns to normal operation.
A5E32106153 SITRANS Probe LR – QUICK START MANUAL Page EN-7
mmmmm
1
2
3
6
1 – Primary Reading (displays parameter value) 2 – Secondary Reading (displays parameter number) 3 – Programming indicator 6 – Auxiliary Reading (displays parameter names for P001 to
P010, if a language is selected. It displays the index value for indexed parameters, such as P054)
display
hand-held programmer
max. 600 mm
(2 ft)
Key Programming Mode
to
Values
Decimal point
Negative value
CLEAR value TOGGLE between Units and % on parameter
value End PROGRAM session and enable RUN mode
Update echo quality parameters
Parameter scroll-up
Parameter scroll-down
DISPLAY opens parameter fields
ENTER the displayed value
For direct access to SITRANS Probe LR, point the programmer at the SITRANS Probe LR display and press the keys. (For detailed instructions, see the next page.)
PROGRAM Mode Display
English
Programming
Note: Do not use the handheld programmer at the same time as SIMATIC PDM, or erratic
operation may result.
Set parameters to suit your specific application.
•Activate PROGRAM mode at any time, to change parameter values and set operating conditions.
For local programming, use the Siemens hand programmer.
For programming from a distance, use either a PC running SIMATIC handheld communicator.
Hand programmer.
1
PDM or a HART
1.
SIMATIC® is a registered trademark of Siemens AG.
Page EN-8 SITRANS Probe LR – QUICK START MANUAL A5E32106153
Security: (P000: Lock)
Parameter Value
Parameter Number
PROGRAM Icon
current value
Value Description
Value stored in P069 * Lock off: programming permitted other Lock activated: no changes permitted
* Factory setting for P069 is 1954: after a new value is entered and accepted, it becomes the default setting.
Activating SITRANS Probe LR
Power up the instrument. SITRANS Probe LR starts in RUN mode.
Notes:
Keep infrared devices such as laptops, cell phones, and PDAs, away from SITRANS Probe LR to prevent inadvertent operation.
The following instructions apply when using the Hand Programmer.
Do not use the Hand Programmer at the same time as SIMATIC PDM, or erratic operation may result.
You do not need to key in initial zeros when entering a parameter number: for example, for P005, key in 5.
Accessing a parameter
mmmmm
1. Press PROGRAM then DISPLAY , to activate PROGRAM mode.
2. Either use the ARROW keys to scroll to a different parameter, or:
3. Press DISPLAY
to open the Parameter Number
field. (The current parameter value remains visible.)
4. Key in the desired parameter number followed by ENTER .
For example: press
.
5. The LCD displays the new parameter number and value.
A5E32106153 SITRANS Probe LR – QUICK START MANUAL Page EN-9
mmmmm
ENGLISH DEUTSCH FRANÇAIS ESPAÑOL
P000 LOCK VERRIEGELG VERROUIL BLOQUEO P001 OPERATION BETRIEB FONCTIONMT FUNCIONAM. P003 MEAS RESP REAKTIONSZ TEMPS REP. TIEMPO R. P004 ANTENNA ANTENNE ANTENNE ANTENA P005 UNITS EINHEIT UNITES UNIDADES P006 EMPTY MESSBER. VIDE VAC IO P007 SPAN MESSSPANNE PLAGE RANGO
P010 LANGUAGE SPRACHE LANGUE IDIOMA
Value
0*
Numeric/None
1
English
2
German
3
French
4
Spanish
Changing a Parameter Value
Notes:
• Security must be disabled to enable programming: set P000 to the Unlocked Value stored in P069. (A remote master can still change configuration, if P799 is set to allow this.)
• Invalid entries will be rejected or limited.
English
• CLEAR can be used to clear the field.
1. Key in the new value.
2. Press ENTER to set the value.
Parameter Reset to Factory Default
1. Scroll to the parameter or enter its address.
2. Press CLEAR
then ENTER . The value returns to the default setting.
Master Reset (P999)
Returns all parameters except P000, P069, and P838 to default settings. (The learned TVT curve is not lost.)
1. Press PROGRAM , then DISPLAY to activate PROGRAM mode.
2. Press DISPLAY to open parameter fields.
3. Key in 999.
4. Press CLEAR then ENTER , to Clear All and initiate reset. The LCD displays C.ALL.
5. Reset complete. (Reset takes several seconds to complete.)
Quick Setup: steps 1 to 9
Note: Factory settings are marked by an asterisk (*) in the tables.
1. Select language (P010: Language)
Page EN-10 SITRANS Probe LR – QUICK START MANUAL A5E32106153
2. Set P001: Operation (measurement mode)
Level
(P001 = 1)
Space
(P001 = 2)
Distance
(P001 = 3)
Distance
Space
Level
P007
P006
100% (20 mA)
(20 mA) 100%
0% (4 mA)
(4 mA) 0%
100% (20 mA)
(4 mA) 0%
Empty
Span
Span
Empty
Span
Empty
mA Output with Level, Space, and Distance operation
reference point
Notes:
• Setting P001 resets Span (P007), unless Span has previously been set to a different value.
• Changing P001 may reset Output Function (P201): this applies to HART only.
Level returns distance to material level referenced from Empty (process empty level). The
1*
Val ue
reading is returned in volumetric units if parameters 050 to 055 are set to enable this. Space returns distance to material level referenced from Span (process full level).
2 3
Distance returns distance to material level from reference point.
mmmmm
3. Set P003: Measurement Response
1* slow 0.1m/minute
Value
2 medium 1m/minute 3 fast 10m/minute
Set P003 to a measurement response speed just faster than the maximum filling or emptying rate (whichever is greater).
(P004 - view only)
Value 240 *
rod antenna
A5E32106153 SITRANS Probe LR – QUICK START MANUAL Page EN-11
4. Select measurement units (P005)
1*
meters
2
centimeters
Val ue
3 4 5
millimeters feet inches
mmmmm
P007
P006
(100% Level)
(0% Level)
Level
Empty
Span
reference point
Space
Distance
5. Set process empty level (P006: Empty)
Note:
Setting P006 resets Span, if it has not previously been set to a different value.
English
Val ue
Range 0.0000 to 20.00 m (65.6 ft)
Default 20.00 m (65.6 ft) max. range
Empty can be set to any distance: not necessarily the bottom of the tank.
6. Set measurement range (P007: Span)
Range 0.0000 to 20.00 m (65.6 ft)
Value
Default
19.56 m (64.1 ft) (See note on next page.)
Span can be set at any distance above Empty level.
Notes:
The default setting for Span is based on Operation (P001) and Empty (P006). Span is set to Empty minus 110% of Blanking distance that case, Span is set to Empty distance.
Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the transducer face.
1
, unless Operation is set to distance (P001=3). In
7. Minimize false reflections: Set P838 (Auto False-Echo Suppression
Distance)
Val ue
Range:
0.0000 to 20.00 m (65.6 ft)
* 1.000 m (3.28 ft)
Using P837 and P838 (perform this function at low tank levels)
8. Enable False Echo Suppression: set P837 (Auto False Echo Suppression.
Val ue
0 1* 2
Off Use "learned" TVT "Learn"
1
Notes:
• P837 and P838 should be used together to adjust the TVT (Time Varying Threshold) curve.
• Use this function only if there is at least 2 m (6.5 ft) from the reference point to the material.
• Set P837 and P838 during start up, if possible.
• If the vessel contains an agitator, the agitator should be running.
1.
Default setting for Blanking is 0.3 m (1 ft) plus shield length.
Page EN-12 SITRANS Probe LR – QUICK START MANUAL A5E32106153
If SITRANS Probe LR displays an incorrect full level, or if the reading fluctuates between a false high level and a correct level, use P838 and P837 together to prevent false echo detection. They elevate the TVT in this region and de-sensitize the receiver from any ‘base noise’ caused by internal antenna reflections, nozzle echoes, or other vessel false echoes
P838 sets the distance within which SITRANS Probe LR will learn a new echo profile. P837 instructs the Probe LR to learn the echo profile at that moment, and use the learned profile instead of the default TVT curve.
a. Perform this function when the vessel is empty or nearly empty. b. First rotate the instrument for best signal (lowest false echo amplitude). c. Determine the distance from the reference point to the material level, and subtract 0.5 m
(1.6 ft). d. Select P838 and key in [distance to liquid level minus 0.5 m/1.6 ft ], and press ENTER . e. Select P837, then press 2 (Learn) and ENTER . P837 will automatically revert to 1 (use
Learned TVT) after a few seconds.
9. Return to RUN
Press PROGRAM to return to RUN mode: setup is complete.
SITRANS Probe LR Communications: HART
1
.
mmmmm
Note: See
mA Output with Level, Space, and Distance operation
on page 11 for an
illustration of the mA output with different modes of operation.
You will need the full manual (Part#: 7ML19985HR0x) to acquire the list of applicable
parameters.
The HART Electronic Device Description (EDD) may be obtained from the HART
Communication Foundation at www.hartcomm.org
.
We recommend that you use SIMATIC Process Device Manager (PDM) to program your
instrument.
Maintenance
SITRANS Probe LR requires no maintenance or cleaning under normal operating conditions. If cleaning becomes necessary under severe operating conditions:
1. Note the antenna material and the process medium, and select a cleaning solution that
will not react adversely with either.
2. Remove the instrument from service and wipe the antenna clean using a cloth and
suitable cleaning solution.
Unit Repair and Excluded Liability
For detailed information, please see the inside back cover.
1.
For more details on Auto False Echo Suppression, please see the full manual.
A5E32106153 SITRANS Probe LR – QUICK START MANUAL Page EN-13
mmmmm
Instructions specific to hazardous area installations
(Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6)
The following instructions apply to equipment covered by certificate number SIRA 03ATEX2142X:
English
1. For use and assembly, refer to the main instructions.
2. The equipment is certified for use as Category 1G equipment.
3. The equipment may be used with flammable gases and vapors with apparatus group IIC
and temperature class T4.
4. The equipment is certified for use in an ambient temperature range of –40 C to +80 C.
5. The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6. Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and EN 60079-
17 in Europe).
7. Repair of this equipment shall be carried out by suitably trained personnel in accordance
with the applicable code of practice (e.g. EN 60079-19 within Europe).
8. Components to be incorporated into or used as replacements in the equipment shall be
fitted by suitably trained personnel in accordance with the manufacturer’s
documentation.
9. It is the responsibility of the user to ensure that manual override is possible in order to
shut down the equipment and protective systems incorporated within automatic
processes which deviate from the intended operating conditions, provided that this does
not compromise safety.
10. The ‘X’ suffix to the certificate number relates to the following special conditions for safe
use:
Parts of the enclosure may be non-conducting and may generate an ignition­capable level of electrostatic charge under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charge on non-conducting surfaces.
Page EN-14 SITRANS Probe LR – QUICK START MANUAL A5E32106153
11. If the equipment is likely to come into contact with aggressive substances, then it is the
responsibility of the user to take suitable precautions that prevent it from being adversely
affected, thus ensuring that the type of protection is not compromised.
Aggressive substances:e.g. acidic liquids or gases that may attack metals, or
solvents that may affect polymeric materials.
Suitable precautions: e.g. regular checks as part of routine inspections or
establishing from the material’s data sheet that it is resistant to specific chemicals.
12. Equipment Marking:
The equipment marking contains at least the information on the product label, shown on the inside front cover of this manual.
mmmmm
A5E32106153 SITRANS Probe LR – QUICK START MANUAL Page EN-15
mmmmm
Notes
English
Page EN-16 SITRANS Probe LR – QUICK START MANUAL A5E32106153
SITRANS Probe LR Kvikstart manual
Denne manual opridser de væsentligste karakteristika og funktioner af SITRANS Probe LR. Vi anbefaler dig kraftigt at anskaffe den detaljerede version af denne manual, så du kan anvende apparatet fuldt ud. Den komplette manual kan downloades fra Siemens' websted: www.siemens.com/level
Spørgsmål vedrørende indholdet af denne manual kan rettes til:
Siemens Milltronics Process Instruments
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Canada, K9J 7B1
E-mail: techpubs.smpi@siemens.com
Copyright Siemens Milltronics
Process Instruments 2013.
Alle rettigheder forbeholdes
. Den trykte manual kan fås hos din Siemens repræsentant.
Ansvarsfragåelse
Dansk
mmmmm
Vi opfordrer brugerne til at anskaffe de autoriserede, indbundne manualer eller at læse de elektroniske versioner, der er udarbejdet og skrevet af Siemens Milltronics Process Instruments. Siemens Milltronics Process Instruments påtager sig intet ansvar for indholdet af delvise eller fuldstændige gengivelser af indbundne eller elektroniske versioner.
MILLTRONICS er et registreret varemærke, der tilhører Siemens Milltronics Process Instruments
Sikkerhedsvejledning
De anførte advarsler skal overholdes for at sikre egen og andres sikkerhed samt for at beskytte produktet og det tilhørende udstyr. Disse advarsler ledsages af en tydeliggørelse af graden af forsigtighed, der bør overholdes.
ADVARSEL: vedrører et advarselssymbol på produktet og betyder, at en manglende overholdelse af de nødvendige forholdsregler kan føre til død, alvorlig personskade og/eller omfattende materielle skader.
ADVARSEL forholdsregler kan føre til død, alvorlig personskade og/eller omfattende materielle skader.
1
: betyder, at en manglende overholdelse af de nødvendige
1
Skønt vi har kontrolleret, at indholdet af denne manual stemmer overens med de beskrevne instrumenter, kan der stadig forekomme variationer. Vi kan derfor ikke garantere en fuldstændig overensstemmelse. Indholdet af denne manual revideres jævnligt, og eventuelle rettelser inkluderes i de efterfølgende udgaver. Vi modtager gerne forslag til forbedringer.
Retten til ændringer af de tekniske data forbeholdes.
Bemærk: betyder vigtige oplysninger om produktet eller denne del af brugsvejledningen.
1
Dette symbol anvendes, når der ikke er noget tilsvarende advarselssymbol på produktet.
A5E32106153 SITRANS Probe LR – KVIKSTART MANUAL Side DA-1
SITRANS Probe LR
procestemperatur –40 til +80 °C (–40 til +176 °F)
omgivende temperatur (omkring huset) –40 til +80 °C (–40 til +176 °F)
mærkeskilt
navneskiltets placering
brugerleveret flange
låsekrave
2
over
gevindtilslutningen, fastgøres vha.
tre 2 mm unbrako-stopskruer
håndholdt programmeringsenhed
ADVARSEL: Ændringer eller modifikationer, der ikke er udtrykkeligt godkendt af Siemens, kan ophæve brugerens ret til at benytte udstyret.
Bemærkninger:
Dette udstyr er blevet testet og fundet at overholde grænserne for en klasse A digital anordning i henhold til Afsnit 15 i FCC Reglerne. Disse grænser er beregnet til at yde en rimelig beskyttelse mod skadelige interferenser, når anordningen anvendes i kommercielle omgivelser. Dette udstyr frembringer, bruger og kan udstråle radiofrekvent energi, og kan, såfremt det ikke installeres og bruges i overensstemmelse med instruktionsbogen, forårsage interferens, der er skadelig for radiokommunikation. Brugen af dette udstyr i et beboelsesområde vil sandsynligvis forårsage skadelig interferens, som brugeren i givet fald vil være nødsaget til at udbedre for egen regning.
SITRANS Probe LR bør kun anvendes som beskrevet i denne manual, da den beskyttelse, udstyret yder, ellers kan forringes.
mmmmm
Dansk
Dette produkt er beregnet til anvendelse i industriområder. Brugen af dette udstyr i et beboelsesområde kan forårsage interferens med forskellige frekvensbaserede kommunikationer.
SITRANS Probe LR er et kontinuert niveaumålingsinstrument med totråds­strømfødningssløjfe, der benytter avanceret pulsradarteknologi ved 5,8 GHz (6,3 GHz i Nordamerika). Dette instrument består af en elektronisk komponent, der er forbundet til antennen og procestilslutningen.
1
Kommunikationen foregår via HART
, og signalerne behandles ved hjælp af Sonic
Intelligence®.
Tekniske data
For en fuldstændig liste, jf. den komplette manual for SITRANS Probe LR (Del nr.: 7ML19985HR0x). For oplysninger om godkendelser henvises der til apparatets navneskilt.
Omgivende temperatur/Driftstemperatur
Bemærk: De tilladelige procestemperaturer og –tryk afhænger af oplysningerne på
mærkeskiltet. Referencetegningen, der er angivet på dette skilt, kan downloades fra Siemens' website. Gå til SITRANS Probe LR's produktside: https://pia.khe.siemens.com/index.asp?Nr=11158
.
2
1 2
Side DA-2 SITRANS Probe LR – KVIKSTART MANUAL A5E32106153
HART®er et registreret varemærke, der tilhører HART Communication Foundation. Når låsekraven er fastgjort, forhindrer det huset i at dreje omkring gevindtilslutningen.
Strømforsyning
Nominel 24 V dc ved max. 550 Ohm:
• Max. 30 V dc
4 til 20 mA
Godkendelser
Alment: CSA
Radio: Europa (R&TTE), FCC, Industry Canada
Risikoområder Egensikker (Europa) ATEX II 1 G EEx ia IIC T4
Ikke-antændingsfarlig
, FM, CE, C-TICK
US/C
1
(US/Canada) FM/CSA
: (barriere påkrævet) Klasse I, Div. 1, Grupper A, B, C, D Klasse II, Div. 1, Grupper E, F, G Klasse III T4
(Australien) ANZEx Ex ia IIC T4
(Tomg = -40 til + 80 °C) IP67, IP68
(Internationalt) IECEx TSA 04.0020X Ex ia IIC T4
(Brasilien) INMETRO: DNV 12.0068 X
Ex ia IIC T4 Ga IP66/IP67/IP68
-40 ºC T a +80 ºC DNV #OCP 0017 ABNT NBR IEC 60079-0:2008 e ABNT NBR IEC 60079-11:2009
2
(US) FM
:
Dansk
mmmmm
Klasse I, Div. 2, Grupper A, B, C, D T5
Maritimt Lloyd's Skibsregister
ABS typegodkendelse
Bemærk: Brugen af godkendte vandtætte kabelrørsmuffer/afslutninger er påkrævet for
type 4X / NEMA 4X, type 6 / NEMA 6, IP67 (udendørs applikationer).
Bemærk: Afprøvningen af SITRANS Probe LR ifølge EN 61000-4-3 (CE EMC) blev udført
med apparatet monteret i en metallisk beholder.
Mekanik
• Procestilslutninger: gevindtilslutning 1,5" NPT, BSP eller G (BS EN ISO 228-1)
•Antenne: polypropylenstav hermetisk forseglet konstruktion
1
Se referencetegning nr. 23651611 referencetegning nr. 23651621
2
Se referencetegning nr. 23650537
A5E32106153 SITRANS Probe LR – KVIKSTART MANUAL Side DA-3
Wiring Drawing: Intrinsically Safe (FM )
Wiring Drawing: Intrinsically Safe (CSA)
Wiring Drawing: Non-incendive (FM)
på side 2 i Appendiks A eller
på side 3 i Appendiks A.
på side 1 i Appendiks A.
Proces
foretrukket uønskeligt
Coni
Fl at
Flad Parab olsk Konisk
min. 300 mm (1 fod) for hver 3 m (10 fod) højde af beholderen
stråle-
vinkel
28
o
Anbring antennen i en vis afstand fra sidevæggene for at undgå indirekte ekko.
Undgå interferens fra genstande såsom stiger eller rør, der kan forårsage falsk ekko.
Undgå interferens fra påfyldningssystemet.
• Temperatur (ved procestilslutningen): -40 til +80 °C (-40 til +176 °F)
• Tryk (beholder): højst 3 bar gauge (43,5 psi gauge)
Installation
ADVARSLER:
• Dette produkt kan kun fungere korrekt og sikkert, såfremt det transporteres, opbevares, installeres, indstilles, bruges og vedligeholdes rigtigt.
• Forsøg aldrig at løsne, afmontere eller adskille procestilslutningen eller instrumenthuset, mens indholdet er under tryk.
• Dette produkt betegnes som trykbærende udstyr i henhold til direktivet 97 / 23 / EF og er ikke
• Konstruktionsmaterialerne er valgt på basis af deres kemiske kompatibilitet (eller
mmmmm
Dansk
inerti) ved almindelig brug. Hvis de skal udsættes for særlige omgivelser, bør foreneligheden kontrolleres i tabeller over kemiske kompatibiliteter inden installationen.
• Brugeren er ansvarlig for at vælge sammenboltnings- og pakningsmaterialer, der ligger inden for flangens begrænsninger og dens påtænkte anvendelse, og som passer til anvendelsesforholdene.
• Ukorrekt installation kan medføre et tab af procestryk.
beregnet til brug som sikkerhedsanordning.
Montagested
Anbefalinger
Sørg for, at den omgivende temperatur ligger inden for intervallet fra –40 til +80 °C (–40 til +176
Sørg for en lettilgængelig adgang for aflæsning af displayet og programmering ved hjælp af den håndholdte programmeringsenhed.
Sørg for, at omgivelserne svarer til instrumenthusets klassificering og konstruktionsmaterialer.
Forholdsregler
Undgå nærhed til højspændings- eller stærkstrømsledninger, højspændings- eller stærkstrømskontakter samt motorhastighedsregulatorer med variabel frekvens.
Undgå interferens med emissionskeglen fra forhindringer eller påfyldningssystemet.
Undgå centrale placeringer på beholderne.
°F).
Side DA-4 SITRANS Probe LR – KVIKSTART MANUAL A5E32106153
Montageanvisning
minimum 100 mm (4")
minimum
10 mm (0,4")
For at opnå optimale signalforhold på et mandehulsdæksel skal antennen anbringes excentrisk i forhold til dækslet, typisk 100 mm (4") fra mandehullets side.
Brug 100 mm (4") afskærmningen på mundstykker, der er 100 mm (4") lange eller derunder.
Brug 250 mm (10") afskærmningen på mundstykker, der er 250 mm (10") lange eller derunder.
Montering på et mundstykke Montering på et mandehulsdæksel
Inden SITRANS Probe LR indføres i montagetilslutningen, skal det kontrolleres, at gevindene passer sammen, for at undgå at beskadige dem.
SITRANS Probe LR skrues blot på procestilslutningen og strammes med håndkraft.
For anvendelser under tryk er det nødvendigt at bruge PTFE-tape (eller et andet passende middel til tætning af gevind) og at stramme procestilslutningen mere end med håndkraft. Det maksmimale stramningsmoment er 40 N.m. (30 ft-lbs.)
For at dreje instrumenthuset løsnes de tre stopskruer, der holder låsekraven, ved hjælp af en 2 mm unbrakonøgle. Når instrumenthuset sidder i den ønskede stilling, strammes stopskruerne.
Elektrisk installation
Strømforsyning1
ADVARSLER:
1
DC–klemmerne skal forsynes fra en SELV IEC-1010-1 Bilag H.
kilde i henhold til
Dansk
mmmmm
Alle elinstallationer på stedet skal være forsynet med en passende isolering i forhold til de nominelle spændinger.
1
Safety Extra Low Voltage (Sikkerhed ekstralav spænding)
A5E32106153 SITRANS Probe LR – KVIKSTART MANUAL Side DA-5
Tilslutning af SITRANS Probe LR
låsekrave
klemrække
skrue på låget (1 af 2)
Løsn de to skruer for at åbne det hængslede låg og få adgang til klemrækken.
trækaflastning (eller indføring af NPT kabel)
1
Bemærkninger:
For detaljerede anvisninger for elinstallationen henvises der til den komplette instruktionsbog.
Brug afskærmet parsnoet kabel (trådtykkelse AWG14 til AWG22).
1
Forskellige kabler og kabelrør
kan være nødvendige for at overholde
standardmetoderne for elinstallation af instrumentering eller de elektriske normer.
Det ikke-metalliske instrumenthus giver ikke en kontinuert jordingsvej mellem kabelrørenes tilslutninger: brug gennemføringer og ledningsbroer af jordingstypen.
Tilslutning af SITRANS Probe LR (fortsat)
mmmmm
Dansk
1. For at dreje instrumentet omkring procestilslutningen skal de 3 unbrako-stopskruer, der holder låsekraven, løsnes ved hjælp af den medfølgende 2 mm unbrakonøgle. Placer enheden som ønsket og stram skruerne igen.
Bemærk: Undgå at dreje instrumenthuset efter programmering og kalibrering af
beholderen, da der herved kan opstå fejl som følge af en polaritetsforskydning af sendeimpulsen.
2. Afisoler kablet på ca. 70 mm (2,75") fra enden af kablet og før ledningerne gennem trækaflastningen2.
1
Hvis kablerne føres gennem kabelrør, brug kun muffer af en passende størrelse, der er godkendt til vandtætte applikationer.
2
Hvis kablerne føres gennem kabelrør, brug kun muffer af en passende størrelse, der er godkendt til vandtætte applikationer.
Side DA-6 SITRANS Probe LR – KVIKSTART MANUAL A5E32106153
3. Forbind ledningerne med klemmerne: polariteten er angivet
m
m
Normal drift Fejlsikker drift
1
3
4
5
1
3
4
5
2
6
6
på klemrækken.
4. Stram kabelafslutningen for at opnå en god tætning. Luk låget og stram skruerne: pas på ikke at stramme skruerne for meget. (Det anbefalede moment er fra 1,1 til 1,7 N.m (10 til 15 in-lb).
RUN Mode og PROGRAM Mode
SITRANS Probe LR har to driftstilstande: RUN og PROGRAM. Når du er færdig med installationsproceduren og tænder SITRANS Probe LR, starter den i
RUN mode og måler afstanden til materialniveauet. Den opgiver afstanden til materialniveauet (i meter) i forhold til Tom (proces tom niveau). Dette er standardtilstanden ved opstart.
Display i RUN Mode
Brug den håndholdte programmeringsenhed til at betjene displayet.
1 – Primær visning (viser niveau, afstand eller volumen i enheder eller procenter) 2 – Sekundær visning (viser parameternummeret svarende til den ekstra visning) 3 – Ekkostatusindikator: Pålideligt ekko eller Upålideligt ekko 4 – Enheder eller procenter 5 – Det dynamiske søjlediagram angiver materialniveauet 6 – Ekstra visning (afhængigt af den valgte parameter vises milliAmp-værdien, afstanden
eller ekkokonfidensen, med enheder som påkrævet)
Hvis ekkokonfidensen falder til under ekkokonfidensgrænsen, går timeren for fejlsikker drift i gang. Når timeren udløber, vises bogstaverne LOE (Loss of Echo – Tab af ekko) skiftevis med målingen hvert andet sekund, og indikatoren Pålideligt ekko erstattes af Upålideligt ekko. Når der modtages en gyldig måling, vender niveauvisningen tilbage til normal drift.
Dansk
mmmmm
A5E32106153 SITRANS Probe LR – KVIKSTART MANUAL Side DA-7
Display i PROGRAM Mode
1
2
3
6
1– Primær visning (viser parameterværdien) 2– Sekundær visning (viser parameternummeret) 3– Programmeringsindikator 6– Ekstra visning (viser parameternavne for P001 til P010,
såfremt et sprog er valgt. Viser indeksværdien for indekserede parametre, såsom P054)
display
håndholdt programmeringsenhed
max. 600 mm
(2 fod)
Ta st Programmeringsmode
til
Værdier
Decimalpunktum
Negativ værdi
SLET værdi SKIFT mellem Enheder og % for
parameterværdien Afslut PROGRAM sessionen og slå RUN mode
til Opdatér ekkokvalitetsparametrene
Gennemløb parametrene opad
Gennemløb parametrene nedad
DISPLAY åbner parameterfelterne
ENTER indlæser den viste værdi
For at få direkte adgang til SITRANS Probe LR skal du rette programmeringsenheden mod displayet på SITRANS Probe LR og trykke på tasterne. (Se detaljerede anvisninger på næste side).
Programmering
Bemærk: Brug aldrig den håndholdte programmeringsenhed samtidig med SIMATIC PDM,
da dette kan føre til uberegnelige ændringer.
Indstil parametrene, så de passer til din specifikke applikation.
PROGRAM mode kan aktiveres når som helst for at ændre parameterværdierne og
mmmmm
Dansk
indstille driftsbetingelserne.
Brug Siemens håndholdte programmeringsenhed til lokal programmering.
1
Til fjernprogrammering bruges enten en PC, der kører SIMATIC
PDM, eller en HART
håndholdt kommunikationsenhed.
Håndholdt programmeringsenhed
1
SIMATIC®er et registreret varemærke, der tilhører Siemens AG.
Side DA-8 SITRANS Probe LR – KVIKSTART MANUAL A5E32106153
Sikkerhed: (P000: Lås)
Paramet ervær di
Paramet ernum mer
PROGRAM ikonet
aktuel værdi
Værdi Beskrivelse
Værdi gemt i P069 * Lås slået fra: programmering tilladt andet Lås aktiveret: ingen ændringer tilladt
* Fabriksindstillingen for P069 er 1954: når en ny værdi indlæses og accepteres, bliver den standardindstillingen.
Aktivering af SITRANS Probe LR
Tænd for instrumentet. SITRANS Probe LR starter i RUN mode.
Bemærkninger:
Hold infrarøde apparater, såsom bærbare computere, bærbare telefoner og PDA'er væk fra SITRANS Probe LR for at undgå utilsigtede ændringer.
Følgende anvisninger gælder ved brug af den håndholdte programmeringsenhed.
Brug aldrig den håndholdte programmeringsenhed samtidig med SIMATIC PDM, da dette kan føre til uberegnelige ændringer.
Du behøver ikke indtaste de indledende nuller ved indlæsning af parameternumre: for P005 indtastes for eksempel 5.
Dansk
mmmmm
Adgang til en parameter
1. Tryk på PROGRAM og derefter på DISPLAY , for at aktivere PROGRAM mode.
2. Brug enten PILE tasterne for at scrolle hen til en parameter, eller:
3. Tryk DISPLAY feltet. (Den aktuelle parameterværdi forbliver synlig).
4. Indtast det ønskede parameternummer efterfulgt af ENTER
For eksempel: tryk på
5. LCD-skærmen viser det nye parameternummer og parameterens værdi.
for at åbne Parameternummer-
A5E32106153 SITRANS Probe LR – KVIKSTART MANUAL Side DA-9
Ændring af en parameterværdi
ENGLISH DEUTSCH FRANÇAIS ESPAÑOL
P000 LOCK VERRIEGELG VERROUIL BLOQUEO P001 OPERATION BETRIEB FONCTIONMT FUNCIONAM. P003 MEAS RESP REAKTIONSZ TEMPS REP. TIEMPO R. P004 ANTENNA ANTENNE ANTENNE ANTENA P005 UNITS EINHEIT UNITES UNIDADES P006 EMPTY MESSBER. VIDE VAC IO P007 SPAN MESSSPANNE PLAGE RANGO
P010 LANGUAGE SPRACHE LANGUE IDIOMA
Værdi
0*
Numerisk/Intet
1
English
2
Deutsch
3
Français
4
Español
Bemærkninger:
• Sikkerhedsfunktionen skal være slået fra for at tillade programmering: indstil P000 til værdien Ulåst, der er gemt i P069. (En master kan stadig ændre konfigurationen på afstand, såfremt P799 er indstillet, så dette er tilladt).
• Ugyldige værdier afvises eller begrænses.
• SLET kan bruges til at slette feltet.
1. Indtast den nye værdi.
2. Tryk ENTER for at indstille værdien.
Reset af en parameter til fabriksstandarden
1. Gennemløb parametrene, til du når den ønskede, eller indtast dens adresse.
2. Tryk SLET standardindstillingen.
mmmmm
Dansk
og derefter på ENTER . Værdien tilbagestilles til
Master Reset (P999)
Tilbagestiller alle parametre undtagen P000, P069 og P838 til standardindstillingerne. (Den indlærte TVT-kurve går ikke tabt).
1. Tryk på PROGRAM
og derefter på DISPLAY for at aktivere PROGRAM mode.
,
2. Tryk DISPLAY for at åbne parameterfelterne.
3. Indtast 999.
4. Tryk SLET og derefter på ENTER for at slette alt og starte reset. LCD-skærmen viser C.ALL.
5. Reset afsluttet. (Det tager adskillige sekunder at gennemføre et reset).
Hurtig opsætning: trin 1 til 9
Bemærk: Fabriksindstillingerne er angivet med en stjerne (*) i tabellerne.
1. Vælg sprog (P010: Sprog)
Side DA-10 SITRANS Probe LR – KVIKSTART MANUAL A5E32106153
2. Indstil P001: Drift (målingsmode)
Niveau
(P001 = 1)
To m ru m
(P001 = 2)
Afstand
(P001 = 3)
Afstand
To mr u m
Niveau
P007
P006
100% (20 mA)
(20 mA) 100%
0% (4 mA)
(4 mA) 0%
100% (20 mA)
(4 mA) 0%
To m
Spænd­vidde
Spænd­vidde
To m
Spænd­vidde
To m
mA-udgang med funktionen Niveau, Tomrum og Afstand
referencepunkt
Bemærkninger:
• Når P001 indstilles, resettes Spændvidden (P007), medmindre Spændvidden forinden er indstillet til en anden værdi.
• Ændring af P001 kan medføre reset af Outputfunktionen (P201): dette gælder kun for HART.
Niveau opgiver afstanden til materialniveauet i forhold til Tom (proces tom niveau).
1*
Visningen opgives i volumenenheder, såfremt parametrene 050 til 055 er indstillet, så dette er tilladt.
Værdi
To m ru m opgiver afstanden til materialniveauet i forhold til Spændvidde (proces fuld
2
niveau).
3
Afstand opgiver afstanden til materialniveauet i forhold til referencepunktet.
Dansk
mmmmm
3. Indstil P003: Målingsrespons
1*langsom 0,1m/minut
Værdi
2 middel 1m/minut 3 hurtig 10m/minut
Indstil P003 til en målingsresponshastighed, der lige netop er hurtigere end den maksimale fyldnings- eller tømningshastighed (den største af disse).
(P004 – kun til aflæsning)
Værdi 240 *
stavantenne
A5E32106153 SITRANS Probe LR – KVIKSTART MANUAL Side DA-11
4. Vælg måleenheder (P005)
1*
meter
2
centimeter
Værdi
3 4 5
millimeter fod tommer
5. Indstil proces tom niveauet (P006: Tom)
P007
P006
(100% Niveau)
(0% Niveau)
Niveau
To m
Spænd­vidde
referencepunkt
To mr u m
Afstand
Bemærk: P006 og P007 er forbundet
med hinanden: jf. bemærkninger vedrørende P007.
Måleområde
Værdi
Standard-
værdi
0,0000 til 20,00 m (65,6 fod)
20,00 m (65,6 fod) (max. måleområde)
Tom kan indstilles til en hvilken som helst afstand: det behøver ikke være bunden af tanken.
6. Indstil måleområdet (P007: Spændvidde)
mmmmm
Dansk
Værdi
Måleom-
råde
Standard-
værdi
0,0000 til 20,00 m (65,6 fod)
19,56 m (64,1 fod) (jf. bemærkning på næste side).
Spændvidden kan indstilles til enhver afstand over niveauet Tom.
Bemærkninger:
• Standardværdien for Spændvidde er baseret på Drift (P001) og Tom (P006). Spændvidde er indstillet til Tom minus 110% af Slukningsafstanden afstand (P001=3). I så fald er Spændvidde indstillet til afstanden Tom.
Den målte overflade må aldrig komme nærmere end 0,3 m (1 fod) fra transduceroverfladen.
7. Minimer falske refleksioner: Indstil
8.
P838 (Afstand for automatisk dæmpning af falsk ekko)
Værdi
Værdi
Måleom­råde:
0,0000 til 20,00 m (65,6 fod)
* 1,000 m (3,28 fod)
1
, medmindre Drift er indstillet til
Slå dæmpning af falsk ekko til: indstil P837 (Automatisk dæmpning af falsk ekko)
0 1* 2
Fra Brug "indlært" TVT "Indlær"
.
Ved hjælp af P837 og P838 (udfør denne funktion med lavt tankniveau)
Bemærkninger:
• P837 og P838 bør anvendes sammen for at justere TVT-kurven (Time Varying Threshold –
TidsVarierende Tærskel).
• Brug kun denne funktion, hvis der er mindst 2 m (6,5 fod) fra referencepunktet til materialet.
• Indstil så vidt muligt P837 og P838 under opstarten.
• Hvis beholderen indeholder en omrører, bør denne være i drift.
1
Standardindstillingen for Slukning er 0,3 m (1 fod) plus afskærmningens længde.
Side DA-12 SITRANS Probe LR – KVIKSTART MANUAL A5E32106153
1