Siemens SINAMICS PM230 Getting Started Manual

s
SINAMICS PM230 (IP20) Power Module
Getting Started Guide
-1-
Warning
This equipment contains dangerous voltages and controls potentially dangerous rotating mechanical parts. The terminals can carry hazardous voltages even after the inverter has been switched off. After disconnecting the line supply, wait at least 5 minutes until the drive unit has discharged itself. Only then, carry out any installation work. Read the instructions in the associated manuals under:
http://support.automation.siemens.com. Non-compliance or failure to follow the
instructions can result in loss of life, severe personal injury or serious damage to property. Only suitable qualified personnel should work on this equipment. Qualified persons are defined as persons who are authorized to commission, ground and label systems and circuits in accordance with established safety practices and standards. The successful and safe operation of this equipment is dependent upon its proper handling, installation, operation and maintenance.
Warnung
Das vorliegende Gerät führt gefährliche Spannungen und steuert rotierende mechanische Teile, die gegebenenfalls gefährlich sind. Die Klemmen können auch dann gefährliche Spannungen führen, wenn der Umrichter außer Betrieb ist. Warten Sie nach dem Unterbrechen der Netzversorgung mindestens 5 Minuten, bis sich das Gerät entladen hat. Führen Sie erst dann Montagearbeiten aus. Beachten Sie die Hinweise in den zugehörigen Betriebsanleitungen unter:
http://support.automation.siemens.com. Bei Missachtung oder Nichtbefolgen der
Hinweise können Tod, schwere Körperverletzungen oder erheblicher Sachschaden eintreten. Inbetriebsetzung und Betrieb dieses Geräts dürfen nur von qualifiziertem Personal vorgenommen werden. Qualifiziertes Personal sind Personen, welche die Berechtigung haben, Systeme und Stromkreise gemäß den Standards der Sicherheitstechnik in Betrieb zu nehmen, zu erden und zu kennzeichnen. Der einwandfreie und sichere Betrieb des Gerätes setzt sachgemäßen Transport, ordnungsgemäße Installation, Bedienung und Instandhaltung voraus.
Attention
L' appareil présente des tensions dangereuses et contrôle des pièces mécaniques rotation potentiellement dangereuses. Les bornes peuvent présenter des tensions dangereuses, même lorsque le variateur est à l'arrêt. Après coupure de la tension du réseau, il convient d'attendre au moins 5 minutes pour permettre la décharge de l'appareil. Procéder à une intervention seulement après écoulement de ce délai. Respecter les consignes figurant dans les instructions de service correspondantes et disponibles sous le lien suivant : http://support.automation.siemens.com. Le non-respect des consignes peut entraîner la mort, des blessures graves ou des dégâts matériels importants. La mise en service et l'utilisation de cette machine ne doivent être effectuées que par des personnes qualifiées. Par personnes qualifiées on entend des personnes autorisées à mettre en service, mettre à la terre et repérer les systèmes et les circuits électriques dans le respect des règles de l'art en matière de sécurité. L'exploitation sûre et sans défaut de l'appareil suppose un transport, un entreposage, une installation, une conduite et une maintenance dans les règles de l'art.
Avvertenza
Questo apparecchio conduce tensioni pericolose ed aziona parti meccaniche rotanti potenzialmente pericolose. I morsetti possono condurre tensioni pericolose anche quando il convertitore è stato spento. Dopo avere interrotto l’alimentazione di rete, attendere almeno 5 minuti finché l’apparecchio non si è scaricato. Solo allora si possono eseguire interventi sull’apparecchio. Leggere le istruzioni riportate nei rispettivi manuali all’indirizzo:
http://support.automation.siemens.com. In caso di non osservanza o di mancata
applicazione delle istruzioni sussiste la possibilità di morte, gravi lesioni fisiche o ingenti danni materiali. Solo personale qualificato può essere addetto alla messa in servizio e al funzionamento di questo apparecchio. Per personale qualificato si intendono persone autorizzate a mettere in servizio, mettere a terra e contrassegnare sistemi e circuiti elettrici in conformità agli standard della tecnica di sicurezza. Il funzionamento corretto e sicuro dell'apparecchio presuppone un trasporto, un’installazione, un utilizzo e una manutenzione appropriati.
Advertencia
El presente equipo está sometido a tensiones peligrosas y controla piezas mecánicas rotación que también pueden ser peligrosas. Los bornes o terminales de conexión pueden estar también bajo tensión eléctrica peligrosa incluso aunque el convertidor o variador no esté funcionando. Tras desconectar la alimentación de red, espere al menos 5 minutos para que el equipo pueda descargarse. Sólo entonces proceda a realizar los trabajos de montaje. Respete las indicaciones que se especifican en las instrucciones de servicio asociadas, y que pueden consultarse en: http://support.automation.siemens.com. Si no se observan las advertencias o no se siguen las indicaciones de las instrucciones, existe peligro de muerte, graves lesiones corporales o considerables daños materiales La puesta en marcha y el funcionamiento de este equipo debe encomendarse exclusivamente a personal cualificado. Personal cualificado son personas autorizadas para poner en servicio, conectar a tierra e identificar sistemas y circuitos eléctricos conforme a las normas en materia de seguridad. El funcionamiento correcto y seguro del equipo presupone un transporte, instalación, montaje y puesta en marcha adecuados, así como un manejo y un mantenimiento rigurosos.
Mounting hole for mounting frame
Panel template and mounting
holes for PT housing
Panel template and mounting
holes for PT housing
Mounting hole for mounting frame
Mounting hole for mounting frame
Cool air
Bottom
Side Side
Top
Heated air
PM + CU + OP
Power Module (PM)
Width
Height
Cool air
Bottom
Side Side
Top
Heated air
PM + CU + OP Width
Height
Drill Patterns and Dimensions for PM230 IP20 Power Modules Drill Patterns and Dimensions for PM230 IP20 Push-Through (PT) Power Modules
Push-Through mounting frame
It is recommended that the optional mounting frame is used to install the Push-through Power Module in a cabinet. This optional mounting frame is designed, in conjunction with, the supplied seal to easily maintain an IP54 rating of the enclosure (the seal is delivered with the Power Module). If the Power Module is mounted without using the optional mounting frame, it is the user's responsibility to ensure the correct IP protection rating is reached.
Dimensions (mm) Distances (mm)3) Frame Size
Height Width Depth 2) a b c top bottom
FSA filtered /unfiltered 196 73 165 186 62.3 6 80 100
FSB filtered /unfiltered 292 100 165 281 80 6 80 100
FSC filtered /unfiltered 355 140 165 343 120 6 80 100
FSD unfiltered 4191) 275 204 325 235 11 300 300
FSD filtered 5121) 275 204 419 235 11 300 300
FSE unfiltered 4991) 275 204 405 235 11 300 300
FSE filtered 6351) 275 204 541 235 11 300 300
FSF unfiltered 6341) 350 316 598 300 11 350 350
FSF filtered 9341) 350 316 899 300 11 350 350
Fixing: FSA/FSB: Screws M4, 2.5 Nm (22 lbf.in)
FSC: Screws M5, 2.5 Nm (22 lbf.in)
FSD/FSE: Screws M6, 6 Nm (53 lbf.in) FSF: Screws M8, 13 Nm (115 lbf.in)
1)
plus 123 mm using a screen termination kit
2)
plus 58 mm using a CU230, plus 40 mm using a CU240, plus another 10 mm or 25 mm using a BOP-2 or an IOP as Operator Panel (OP)
3)
The Power Modules can be mounted side-by-side. Due to tolerance reasons, we recommend a lateral distance of about 1 mm
Dimensions (mm) Frame Size
Height Width Depth 2) D1 D2 a b c d e
FSA filtered /unfiltered 238 125.9 170.8 117.7 53.1 103 106 88 198 27
FSB filtered /unfiltered 345 153.9 170.8 117.7 53.1 147.5 134 116 304 34.5
FSC filtered /unfiltered 410.5 200 170.8 117.7 53.1 123 174 156 365 30.5
Fixing: FSA/FSB/FSC: Screws M5, 6 Nm
1)
plus 123 mm using a screen termination kit
2)
plus 58 mm using a CU230, plus 40 mm using a CU240, plus another 10 mm or 25 mm using a BOP-2 or an IOP as Operator Panel (OP). The Power Modules require a distance of 80 mm above and 100 mm below. They can be mounted side-by-side. Due to tolerance reasons, we recommend a lateral distance of about 1 mm
D1 D2
PM230 IP20 Push-Through mounting sequence
Mounting Frame
Cabinet
Seal
Mounting Frame
SINAMICS PM230 (IP20) Power Module
Getting Started Guide
Fitting CU to PM
Mains and Motor terminals FSA ... FSC Screening methods
Access to motor and mains terminals FSD ... FSF
Motor and mains terminals FSD ... FSF
Maximum cable lengths
Components for United States / Canadian installations (UL/cUL)
Star and Delta connection
Using Maximum cable
length
EMI Level
Screened cables, filtered units (class A) 25 m Second Environment, C2*
Screened cables, filtered units (class A) 50 m Second Environment, C3*
Screened cables, unfiltered units, 50 m EMI Standard not fullfilled
Unscreened cables, filtered or unfiltered units 100 m EMI Standard not fullfilled
Inside the terminal box of Siemens motors is a diagram showing both methods of connections:
Star connection (Y)
Delta connection (∆)
The motor rating plate provides information for each method of connection.
The Power Modules are fitted with two-part-connectors. The removable part of the connector can be unplugged from the Power Module by pressing the release catch. The connectors are not interchangeable.
Tightening torques:
FSD 6 Nm (53 lbf.in)
FSE 6 Nm (53 lbf.in)
FSF 13 Nm (115 lbf.in)
2
1
6
9
2
3
3
10
5
8
8
1
2
5
1
7
8
4 4
Line connection Steel band Motor connection Cable strap Unshielded cable for line connection Metal back plate Shielded cable for motor connection Shielding plate Cable screen Suitable clip to fix motor cable screen securely to metal back plate
Standards
European Low Voltage Directive
Europäische Niederspannungsrichtlinie
Directive européene basse tension
Directiva europea “Baja tension”
Direttiva europea sulla bassa tensione
ISO 9001
Siemens plc operates a quality management system, which complies with the requirements of ISO 9001
Siemens plc
Industry Sector Drives Technology Motion Control Systems Varey Road Congleton, CW12 1PH United Kingdom
© Siemens AG, 2011 Subject to change without prior notice Printed in the United Kingdom
Issue: 06/2011
*Only if EMC compliant connections are used.
Typical rating label
E0605 /049 6382 0 2 001
660-725 440- 480
380- 420
1LE1 002-1 DB43- 4AA0
kW 15
A
Hz
V
690
400
Y
60
50
50
17,1
29,5
D-91056 Erlangen
3~Mot .
1/min
cos φ
eta
89,4%
89,4%
0,82
0,82
0,82
17,3 176 0
1460
A
V
30,0- 30,2
IEC/E N 6003 4
160L IMB3
IP55
73 kg
29,5
15
89,4%
1460
Bearin g DE NE
6209-2 ZC3
6209-2 ZC3
460
17,4-17,5
30,2-2 9,8
Th.Cl. 15 5(F)
Tightening torques:
FSA 0.4 Nm ... 0.5 Nm (3.5 ... 4.4 lbf.in)
FSB 0.55 Nm ... 0.6 Nm (4.7 ... 5.3 lbf.in)
FSC 1.2 Nm ... 1.5 Nm (10.6 ... 13.3 lbf.in)
CAUTION - Cable cross-section for grounding: The earth cable must be at least as big as the power cables.
In order that the system is UL/cUL-compliant, use UL/cUL-certified J-type fuses, overload circuit-breakers or intrinsically safe motor protection devices. Use class 1 75° C copper wire only. Install the inverter with any external recommended suppressor with the following features:
● Surge-protective devices; device shall be a Listed Surge-protective device (Category code VZCA and VZCA7)
● Rated nominal voltage 480/277 VAC, 50/60 Hz, 3-phase
● Clamping voltage VPR = 2000 V, IN = 3 kA min, MCOV = 550 VAC, SCCR = 65 kA
● Suitable for Type 1 or Type 2 SPD application
● Clamping shall be provided between phases and also between phase and ground.
Feature Specification
Line voltage
3 AC 380 V … 480 V ± 10% - The permissible voltage depends on the installation altitude
Output voltage 3 AC 0 V … input voltage * 0.95 (max)
Input frequency
50 Hz … 60 Hz, ± 3 Hz
Output frequency
0 Hz … 650 Hz, depending on the control mode
Power factor λ
0.9
Line impedance
Uk 1 %, no line reactor must be used
Inrush current
Less than rated input current
Pulse frequency (factory setting)
4 kHz - Can be increased up to 16 kHz (up to 8 kHz for 55 kW, 75 kW, 90 kW) in 2 kHz st eps. Increasing the pulse frequencies leads to an output current reduction.
Electromagnetic compatibility
Filtered Units are suitable for environmental classes category C2 in accordance with IEC 61800-3. For details, see the Hardware Installation Manual, Appendix A2.
Braking methods
DC braking
Protection level
IP20 built-in units
Operating temperature (LO operation)
0 °C … +40 °C (32 °F … 104 °F) without derating / up to 60 °C (140 °F) with derating
Operating temperature (HO operation)
0 °C … +50 °C (14 °F … 122 °F) without derating / up to 60 °C (140 °F) with derating
Storage temperature
-40 °C … +70 °C (-40 °F … 158 °F)
Installation altitude above sea level
Up to 1000 m (3300 ft) without derating / Up to 4000 m (13000 ft) with derating
Humidity
< 95% RH - non-condensing
Environmental requirements
Protected according to environmental class 3C2 to EN 60721-3-3 against damaging ch emical substances
Pollution
According pollution degree level 2 - Do not install the inverter in an environment which c ontains atmospheric pollutants such as dust and/or corrosive gases.
Shock and vibration
Do not drop the inverter or expose to sudden shock. Do not install the inverter in an area where it is likely to be exposed to constant vibration.
Electromagnetic radiation
Do not install the inverter near sources of electromagnetic radiation.
Short Circuit Current Rating (SCCR)
65 kA