Siemens SIMARIS User Manual

Totally Integrated Power
Technical Series Edition 3
Modeling of systems for Uninterrup­tible Power Supply (UPS) in SIMARIS® design for application in data centers
siemens.com/tip-cs
Technical Series Edition 3
Modeling of systems for Uninterruptible Power Supply (UPS) in SIMARIS® design for application in data centers
1. Basics
Uninterruptible power supply to the servers is of funda­mental importance for data centers in order to have those
available 24hours a day and 365days a year. To achieve this goal, the power supply must be thoroughly planned.
This includes the coordination between the components to be used, taking into account that the selection and inte­gration of UPS systems in the power supply concept is
essential in this process.
Meaning of the code elements:
AAA
The characteristic value describes the depen­dency of the UPS output supply in normal ope­ration in case of change of voltage and fre-
quency at the input AC supply.
"VFD" (Voltage and Frequency Dependent):
UPS systems with VFD classification must pro-
tect the load against power failure.
In this case, the UPS output is influenced by changes of the input AC voltage and the fre­quency, and it is not suitable for assuming additional correction functions which may arise from the application of an
autotransformer.
Characteristic values dependent on the voltage curve. A difference is made between
the following operating modes:
• Normal or bypass operation (first character)
• Energy storage operation (second character)
"S": The voltage curve is sinusoidal.
In case of linear and non-linear reference load (the exact specification can be found
in IEC62040-3), the total harmonic distortion is lower than 8%. The curve shape is defined as sinusoidal.
"X": The curve shape is only sinusoidal in case of linear load. In case of non-linear refe-
rence load, the curve shape is no longer sinusoidal, as the total harmonic distortion
exceeds the limit value of 8%.
"Y": The voltage curve is not sinusoidal, neither for linear nor for non-linear reference
loads. The limit value of 8% is exceeded in both cases.
In accordance with the IEC 62040-3 standard (DINEN62040-3; VDE0558 Part 530), UPS manufacturers
can designate their devices according to the classification
described therein. The assessment criteria are shown
hereafter as an excerpt:
Designation code: AAA BB CCC
i
e.g.: VFI SS 111 (highest classification)
BB
"VI" (Voltage Independent):
Like UPS systems with VFD, UPS systems with VI classification must protect the load against power failure, and also additionally ensure the supply in case of
• undervoltage permanently applied to the input
• overvoltage permanently applied to the
input.
The output of a UPS with VI classification depends on the frequency of the AC voltage input, and the output voltage must remain
within the prescribed limit voltage values.
"VFI" (Voltage and Frequency Dependent):
UPS systems with VFI classification are inde­pendent of (mains) supply voltage and fre­quency fluctuations, and must protect the load against negative effects of such fluctuations without discharging the energy storage
system.
CCC
Characteristic values for the dynamic behavior of the UPS output voltage:
• First numeral: in case of change of the operating mode
• Second numeral: in case of linear load step in normal or battery operation (specification for the worst case)
• Third numeral: in case of non-linear load step in normal or battery operation (specification for the worst case)
"1": required operating behavior for sensitive, critical loads.
The UPS output voltage remains within the limit values of curve 1 (see IEC62040-3)
in this section.
"2": permissible operating behavior for most of the critical loads.
The UPS output voltage remains within the limit values of curve 2 (see IEC62040-3)
in this section.
"3": permissible operating behavior for most of the general IT loads, e.g. switched-mode
power supplies.
The UPS output voltage remains within the limit values of curve 3 (see IEC62040-3)
in this section.
2
With SIMARIS design, electrical networks can be dimen­sioned with minimum input effort on the basis of real products – from the medium-voltage level down to the power consumer (which in the case of a data center means down to the rack where the ICT equipment (ICT: Informa­tion and Communication Technology) is supplied with
power). This reduces your efforts for the overall planning
of the power distribution a lot, and thus the time for selecting and dimensioning the electrical equipment –
with a high level of planning security.
When UPS systems are integrated for planning the power distribution, the functionality is structured in SIMARIS design, both
• as a load for selecting the components of the infeed
(transformers, generators, cables, busbars, switching devices)
• and as a power source to depict the effects on the
downstream network regarding the maximum short-cir­cuit currents in case of transformer infeed, as well as the minimum short-circuit currents in case of inverter opera-
tion mode.
Following the standard EN 50600-2-2, Clause 6.3.2, the
functional elements of a power distribution system must be selected in accordance with the selectivity and short­circuit withstand strength requirements in all operating
modes and during different operating phases.
To supply the connected loads, the
• supply via the UPS
• supply via a UPS bypass
must be considered. Infeed takes places either through a supply network (e.g. primary infeed for VFI operation and
secondary supply in case of internal bypass operation of
the UPS), or through an additional supply (e.g. generator).
With SIMARIS design it is possible to verify – for the down­stream network – the compliance with the electrotechnical conditions according to the standard, such as the switch-
off condition according to IEC60364-4-41 (DINVDE0100 Part410), as well as the selectivity.
3
Loading...
+ 7 hidden pages