Siemens Series 2300 Installation Instructions Manual

Series 2300 Room Units for TALON® Controllers
Product Description
These room units measure temperature in the occupied space in which they are installed. Models with display allow users to view the measured temperature value. A version with temperature setpoint adjustment is also offered.
These devices are intended for use with appropriate signal input on a TALON Controller. The effective sensing and setpoint range is 55°F to 95°F (13°C to 35°C).
These room units can be mounted on electrical boxes, stud-type mounting brackets, or drywall. Obtain the necessary mounting hardware and follow the appropriate mounting procedures for the type of installation required.
Installation Instructions
Document No. 129-479
November 13, 2012
Expected Installation Time
20 minutes
Required Tools
Sizes 1 and 2 Phillips screwdrivers
Small and medium flat-blade screwdrivers
1/16-inch hex key
Medium-duty electric drill
3/16-inch (4.8 mm) drill bit
One-inch (25 mm) hole saw
Small level
Tape measure
Marker or pencil
Product Numbers
QAA2312.xWxN QAA2330.xWxx QAA23SS.xWxN QAA23SS.xWxx
Accessories
AQA2200-INTL Room Unit Back Plate (10-pack) AQA2200-2X4 Room Unit Back Plate (Single)
NOTE: If installing the Back Plate, discard the
metric screws provided with the Back Plate and utilize the Room Unit mounting screws.
Caution Notations
CAUTION
Equipment damage or loss of data may occur if you do not follow a procedure as specified.
Prerequisites
Review these instructions before beginning.
Installed: appropriate field wiring within the
maximum wiring run length for the individual equipment controller. The maximum recommended length is 100 feet (30 m).
All wiring must comply with National Electric Code (NEC) and local regulations.
Figure 1. QAA23xx.EWTN, and QAA23xx.FWTN
Room Units.
Item Number 129-479, Rev. HA
Document No. 129-479 Installation Instructions November 13, 2012
Mounting Information
Always mount the room unit vertically. Locate the room unit:
according to design specifications and local regulations.
where the air circulates around it freely (not in recessed areas or behind doors).
allowing a minimum of 4 inches (10 cm) free space above and below for proper airflow, the front cover removal tool, and the computer communication cable.
away from drafts caused by doors, windows, outside walls, air registers, pipes, return air plenums, etc.
away from heat sources such as strong lights, fireplaces, direct sunlight, etc.
on an inside wall (preferably), about 5 feet (1.5 m) above the finished floor.
Drywall Mounting (No Rough-in), Typical
Base Plate Mounting and Wiring
1. Mark the center (cable) hole and the mounting hole locations, using the room unit base plate as a template. See Figure 2.
2. Drill two 3/16-inch (4.8 mm) mounting holes and mount the two plastic wall anchors flush to below the wall surface for stable mounting of the device.
3. Cut a 1-inch (25 mm) center hole with a hole saw.
4. Pull about three inches (75 mm) of the cable through the hole in the base plate.
5. Mount the room unit base plate on the wall, noting the UP arrow:
NOTE: If required, position the Back Plate
behind the Room Unit Base, aligning the top and bottom mounting holes, prior to mounting to the wall:
d. Cut the cable, leaving about three inches
(75 mm) on the room unit side of the drywall. Ensure that pin Number 1 connects to the same wire at each end of the cable.
Figure 2. Drywall Mounting (No Rough-in), Typical.
7. Terminate the wires to the termination blocks on the room unit's base plate. (See
Figure 5.)
8. Feed the extra cable back through the hole.
Sensor Set-up
R64 Resistor
(°F/°C Selector)
Jumper
5V
10V
Voltage/Current Selector Switch
V
I
SEN0589R1
a. Install the two mounting screws provided,
but do not tighten.
b. Level the room unit base plate for
appearance.
c. Tighten the two mounting screws to the
room unit base plate.
Page 2 of 6 Siemens Industry, Inc.
Figure 3. Circuit Board
(Located inside Room Unit Cover.
Loading...
+ 4 hidden pages