Siemens SENTRON 3WL10,SENTRON 3VA27 User Manual

Manual
SENTRON
Air Circuit Breaker and Molded Case Circuit Breaker
3WL10 and 3VA27 with communication-capability
05/2019Edition
siemens.de/SENTRON
SENTRON
Protection devices Communication 3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers
System Manual
06/2019
L1V30499596021-01
Introduction
1
Description
2
Commissioning
3
Configuration
4
Data structure
5
List of abbreviations
A
Siemens AG Smart Infrastructure Low Voltage Products Postfach 10 09 53 93009 REGENSBURG GERMANY
Document order number: 3ZW1012-0VA27-2AC1
06/2019 Subject to change
Copyright © Siemens AG 2019.
All rights reserved
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.

Table of contents

1
Title
Article number
3WL10 Air Circuit Breakers & 3VA27 Molded Case Circuit Breakers Equipment manual (https://support.industry.siemens.com/cs/ww/en/view/109753821)
3ZW1012-0WL10-0AB1
3WL10 Air Circuit Breakers / Non-Automatic Air Circuit Breakers Catalog (https://support.industry.siemens.com/cs/ww/en/view/109749565)
E86060-K8280-A101-A7
LV10 Catalog (https://support.industry.siemens.com/cs/document/109482234)
E86060-K8280-A101-A7
Circuit breaker (CB) 3WL10, fixed-mounted Operating Instructions (https://support.industry.siemens.com/cs/ww/de/view/109748199)
3ZW1012-0VA27-0AA0
Circuit breaker (CB) 3WL10, withdrawable Operating Instructions (https://support.industry.siemens.com/cs/ww/com/view/109748198)
3ZW1012-0VA27-1AA0
Circuit breaker (CB) 3VA27, fixed-mounted Operating Instructions (https://support.industry.siemens.com/cs/ww/en/view/109748313)
3ZW1012-0VA27-0AA0
Circuit breaker (CB) 3VA27, withdrawable Operating Instructions (https://support.industry.siemens.com/cs/ww/en/view/109748314)
3ZW1012-0VA27-1AA0
Circuit Breaker CB Bus module - COM / IOM Operating Instructions (https://support.industry.siemens.com/cs/document/109754881)
3ZW1012-0VW00-3CA0
Actuator module COM ACT remote control f. aux. solenoids (ST/CC) Operating Instructions (https://support.industry.siemens.com/cs/document/109754868)
3ZW1012-0VW00-7CA0
Breaker Connect module, external power supply Operating Instructions (https://support.industry.siemens.com/cs/document/109754879)
3ZW1012-0VW00-2CA0
External digital I/O module IOM300 Operating Instructions (https://support.industry.siemens.com/cs/document/109756445)
3ZW1012-0VW00-0DA0
Position signaling switch PSS - COM for guide frame Operating Instructions (https://support.industry.siemens.com/cs/document/109754872)
3ZW1012-0VW00-8AA0
Ready to close signaling switch COM RTC Operating Instructions (https://support.industry.siemens.com/cs/document/109754921)
3ZW1012-0VW00-2BA0
Metering function MF basic / advanced for ETU6xx Operating Instructions (https://support.industry.siemens.com/cs/document/109756489)
3ZW1012-0VW00-1DA0
Display DSP800 Operating Instructions (https://support.industry.siemens.com/cs/document/102393764)
3ZW1012-0VA00-8DA0
Hartmut Kiank, Wolfgang Fruth: Planning Guide for Power Distribution Plants, Publicis Publishing
ISBN: A19100-L531-B115
Schalten, Schützen, Verteilen in Niederspannungsnetzen (Switching, Protection and Distri-
bution in Low-Voltage Networks), substantially extended and revised edition 1997
ISBN 3-89578-041-3
Siemens: Residual Current Protective Devices, Low-Voltage Circuit Protection Technology Primer Siemens AG © 04 / 2009
E10003-E38-9T-B3011
Position signaling switch of the circuit breaker in the guide frame (COM PSS), not shown in the figure.
Breaker Connect module, external power supply
Module slots for communication modules or digital I/O modules
IOM040 digital I/O module
Ready-to-close signaling switch for communication (COM RTC) - only available for the version with a spring energy store
Actuation module for remote operation (COM ACT) - only available for the version with a spring energy store
Electronic trip unit (ETU)
Metering function
Note
You can assemble your own 3WL10/3VA27 circuit breaker simply and quickly in the online configurator and then generate an article number.
Online configurator for 3WL10 (https://mall.industry.siemens.com/spice/pcmplus/app/)
Online configurator for 3VA27 (https://mall.industry.siemens.com/spice/pcmplus/app/)
In the Online Configurator, impermissible combinations are automatically excluded in the article number. If you compile the article number yourself based on the following lists, you must check the exclusion criteria yourself.
You will find more information in Catalog LV10 (see Chapter Reference documents (Page 7)).
2
Feature
Value
IP address Modbus TCP
0.0.0.0
Network mask
0.0.0.0
Gateway address
0.0.0.0
Port
502
Feature
Value
Designation
COM043
Article number in conjunction with 3WL10 / 3VA27
Z option F11
Article number (as spare part)
3VW9011-0AT16
Protocol
Modbus TCP
Transmission medium
Ethernet, IEEE 802.3
Transmission rate
10/100 Mbps
Port
502
Connection technology
An RJ45 socket
Simultaneous TCP clients
Maximum 3
Storage temperature
40 °C … +70 °C
Operating temperature
25 °C … +70 °C
Feature
Value
Transmission rate
19200 bps
Address
247
Format
8E1
Feature
Value
Designation
COM042
Article number in conjunction with 3WL10 / 3VA27
Z option F12
Article number (as spare part)
3VW9011-0AT17
Protocol
Modbus RTU
Transmission medium
RS485
Transmission rate
9,600, 19,200, and 38,400 bps
Address
1 247
Format
8N2, 8E1, 8O1, 8N1
Connection technology
Clamping
Modbus terminating resistor
120 Ω integrated in COM042, can be switched on or off
Storage temperature
40 °C … +70 °C
Operating temperature
25 °C … +70 °C
Loading...
+ 40 hidden pages