Siemens RWD62U Technical Instructions

RWD62U
Universal Controller
Technical Instructions
Document No. 155-737
January 14, 2005
Description
Features
The Universal controller is intended for heating, air conditioning, ventilation and refrigeration in comfort control applications. RWD62U main loop control applications are designed for temperature, static pressure, humidity, air pressure, fluid pressure, refrigeration, air quality and air fluid velocity control. The controller contains pre­programmed applications.
Auxiliary control functions include:
Day/night setpoints
Remote setpoint control
Limiter control
Cascade control
Maximum priority
Setpoint compensation
Summer/winter operation
Control parameters are adjusted for maximum comfort control via three buttons on the face of the device, or with a laptop computer and Siemens Building Technologies program software.
NOTE: For complete supporting technical documentation, including training
presentations, see www.us.sbt.siemens.com/hvp/components.
Stand-alone electronic temperature controller with P or P+I response
24 Vac operating voltage
Control application selectable via Application Number
Active input scale can be selectable
Limit and direction of the output scale can be freely assigned
Two universal inputs for Siemens 1000 ohm nickel (Ni 1000), 1000 ohm platinum
(Pt 1000) temperature sensors and 0 Vdc to 10 Vdc signals
Unit can be set as °F, °C, % or no specified unit
Two modulating 0 to 10 Vdc signal outputs, direct or reverse action
One digital input for day/night changeover
Entering or changing of all data via operating buttons on the controller, possible
without additional tools
Computer connection for downloading canned applications via the software tool
Product Number
RWD62U
Siemens Building Technologies, Inc.
Technical Instructions RWD62U Universal Controller Document Number 155-737 January 14, 2005
Warning/Caution Notations
CAUTION:
Equipment damage may occur if you do not follow a procedure as specified.
Specifications
Operating voltage 24 Vac +
20%
Frequency 50/60 Hz
Power Supply
Power consumption 2.5 VA
LCD Actual and nominal values Four digits
Setpoint adjustment range -58°F to 302°F (-50°C to 150°C)
Display Resolution (does not relate to controller accuracy)
Siemens Ni 1000 ohm 1°F (0.5°C) Pt 1000 ohm 1°F (0.5°C) Active sensor Depends on setting range
Environmental Conditions Storage and transport
Temperature -13°F to 158°F (-25°C to 70°C) Humidity <95% rh
Operation Temperature 32°F to 122°F (0°C to 50°C) Humidity <95% rh
Regulatory Approvals Conforms to requirements
UL UL listed to 916 Energy Management Equipment
Terminals Screw terminals, min./max. conductors Minimum: 24 AWG (1)
Maximum: 16 AWG (2), or 14 AWG (1)
Weight RWD62U Controller 10.4 oz (295 grams)
With packaging 12.24 oz (347 grams)
Analog Inputs X1, X2 Siemens Ni 1000 ohm @ 32°F
Controller measuring range -58°F to 302°F (50°C to 150°C)
Maximum cable length for 14 AWG Maximum 984 ft (300 m) (0°C) Pt 1000 ohm at 32°F (0°C) Controller measuring range -4°F to 356°F (-20°C to 180°C)
Maximum cable length for 14 AWG Maximum 984 ft (300 m)
Analog voltages (For measured variable in °F, °C, % or without unit)
Range 0 to 10 Vdc corresponding to
adjustable range from –100 to
8000 (°C, °F, % or no unit)
Maximum cable length for 14 AWG Maximum 984 ft (300 m)
Remote setpoint X2 Range 0 to 1000 ohm corresponding to
adjustable range from –100 to
8000 (°C, °F, % or no unit)
Maximum cable length for 14 AWG Maximum 984 ft (300 m)
Digital input D1 Polling voltage for control commands (D…M) 15 Vdc
Current consumption <15 mA
Analog outputs Y1, Y2 Range 0 to 10 Vdc
Maximum current +1 mA
Accessories
ARG62.21 Protective enclosure for wall mounting.
SEH62.1U Program Clock
SEM62.2U 24/120 Vac Transformer
125-3481 RWD Controller Programming Tool (CD)
RWDTKU Tool Kit
Page 2 Siemens Building Technologies, Inc.
RWD62U Universal Controller Technical Instructions Document Number 155-737 January 14, 2005
Function Summary
Controller Stand-alone controller with two 0 to 10 Vdc outputs with independent adjustment on each sequence for direct acting and/or reverse acting. Adjustable parameters, including proportional band and integral action time.
Auxiliary selectable function
Universal input X2 for one of the following auxiliary functions:
P+I limiter function (Absolute and Relative)
Remote setpoint
Cascade control
Setpoint compensation
Winter/summer operation
Maximum priority
Digital input D1 for setpoint changeover day/night
Equipment Combinations
The following Siemens devices can be connected to RWD62U Universal Controllers. Other combinations with units from third-party manufacturers are possible, if the input and output specifications match the RWD62U.
Table 1.
Description Document Number
Sensor with Siemens Ni 1000 temperature sensing element QAA25U Room temperature sensor with setpoint adjuster
GIB Series 310 lb-in Non Spring Return Actuators GBB Series 177 lb-in Non Spring Return Actuators
GEB Series 132 in-lb Non Spring Return Actuators 155-318P25
GCA Series 142 in-lb Spring Return Actuators
GMA Series 62 in-lb Spring Return Actuators 155-315P25
SKD Valve Actuator with proportional input 155-180P25
SKB/SKC Valve Actuator with proportional input 155-163P25
SQX Valve Actuator with proportional input 155-182P25
SQS Valve Actuator with proportional input 155-190P25
SSC Valve Actuator with proportional input 155-313P25
SSB Valve Actuator with proportional input 155-192P25
Electric Rack and Pinion proportional actuator 155-541P25
1/2 to 2-inch two-way globe valves 155-184P25
1/2 to 2-inch three-way globe valves 155-185P25
2-1/2 to 6-inch two-way flange valves 155-159P25
2-1/2 to 6-inch three-way flange valves 155-160P25
MT Series 1/2 to 1-1/2-inch two-way globe valves 155-196P25
MT Series 1/2 to 1-1/2-inch three-way globe valves 155-197P25
MZ Series 1/2 to 1-inch two-way globe valves 155-198P25
MZ Series 1/2 to I-inch three-way ball valves 155-199P25
Differential Pressure Sensor 155-719
155-330
155-176P25 155-177P25
155-173P25 155-174P25 155-175P25
Siemens Building Technologies, Inc. Page 3
Technical Instructions RWD62U Universal Controller Document Number 155-737 January 14, 2005
Software Tool
An optional, user-friendly, Windows® 95 (or later) based software tool for controller application selection and parameter adjustment is available. It provides you with a printout of the controller settings. This tool allows controller programming prior to installation.
Functions
Controller Type
Main Functions
The RWD62U is a stand-alone universal controller, which performs both primary and auxiliary control functions. The respective mode is defined by entering the corresponding configuration and setting parameters via the push buttons on the controller or the software tool.
The RWD62U controller can be programmed as follows:
One sequence: Y1 or Y2 Reverse or direct acting
Two sequences: Y1 and Y2 Reverse and direct acting or
Y1 and Y2 Reverse and reverse acting or Y1 and Y2 Direct and direct acting
NOTE: Direct Acting – As air temperature increases, the control output increases.
Reverse Acting – As air temperature increases, the control output decreases.
= TEMPERATURE SENSOR
= AIR DAMPER ACTUATOR
+
= HEATING COIL
-
= COOLING COIL
+
-
= HEATING OR COOLING COIL (TWO-PIPE)
= FAN OR PUMP
= TIME CLOCK
= REMOTE SET POINT UNIT
= OUTSIDE AIR SENSOR
TH0599R3
Figure 1. Frequently Used Symbols in Application Drawings.
Output
Voltage
TH0786R1
Figure 2. One Sequence Heat, Direct
Acting or Reverse Acting
(Application 10 to 19).
Y1
Output
Voltage
TH0788R1
Figure 4. One Direct Acting Heat and One Direct Acting Cool or One Reverse Acting
Heat and One Direct Acting Cool
Setpoint
Y1
Setpoint
Setpoint
Setpoint
Sequence
Y1
Setpoint
Temp.
Temp.
Y2
Output
Voltage
TH0787R1
Figure 3. Two Sequence Heat, Two Direct Acting or Two Reverse Acting Sequences
Y2
Temp
(Application 20 to 29
Setpoint
Y1
Output
Voltage
TH0789R1
Setpoint
).
Temp.
Figure 5. One Direct Acting Cool or One
Reverse Acting Cool Sequence
(Application 40 to 49).
(Application 30 to 39).
Page 4 Siemens Building Technologies, Inc.