Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Summary 11. May 2007
1 Summary
This User manual describes the products listed in the following table and covers
handling and configuration of the controls for readers ranging from endusers to heating
engineers.
Type reference
(ASN)
RVS43.143 A Basic unit boiler
RVS63.243 B Basic unit boiler
RVS63.283 B Basic unit boiler
AVS75.390 B Extension module
AVS37.294 B Operator unit
AVS37.390 A Operator unit basic
QAA75.610 B Room unit, wired
QAA75.611 B Room unit with backlight, wired
QAA78.610 B Room unit, wireless
QAA55.110 A Room unit basic
AVS16.290 A Power section
AVS71.390 A Radio module
AVS14.390 A Radio repeater
AVS13.399 A Wireless outside sensor
The following products are described in separate pieces of documentation:
QAC34 Outside sensor NTC 1 kΩ
QAD36 Strap-on temperature sensor NTC 10 kΩ
QAZ36 Immersion temperature sensor NTC 10 kΩ
Series Name
9/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Summary 11. May 2007
Operation with room
unit
1.1 Type summary
Wired RF
Operation with operator
unit “basic”
(optionally with additional
room unit)
Operation with operator
unit “clear-text”
(optionally with additional room
unit)
B
A
D
T
B
A
E1
EB
C
T
2359Z66
B
A
D
B
A
B
F
E1
E
C
2359Z67
A
A Basic unit RVS…
B Power section AVS16…
C Room unit QAA75… / 78…
D Outside sensor AVS13…
E Operator unit AVS37.294 (clear-text)
E1 Operator unit AVS37.390 (basic)
F Radio module AVS71…
A
10/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Summary 11. May 2007
2 Safety notes
2.1 Product liability
• The products may only be used in building services plant and applications as
described in this document
• When using the products, all requirements specified in chapters "Handling" and
"Technical data" must be satisfied
• The local regulations (for installation, etc.) must be complied with
• Do not open the units. If not observed, warranty becomes void.
11/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Safety notes 11. May 2007
3 Mounting and installation
3.1 Regulations
Electrical installation
Planning
Mounting location
• Prior to installing the units, power must be turned off
• The connections for mains and low-voltage are separated
• For wiring, the requirements of safety class II must be satisfied. Sensor and power
cables must not be run in the same cable duct
3.2 Basic units RVS…
• Air circulation around the controller must be ensured, allowing the unit to emit the
heat produced by it.
A clearance of at least 10 mm must be provided for the unit's cooling slots at the top
and bottom of the housing.
That space should not be accessible and no objects should be placed there. If the
controller is enclosed in another (insulating) casing, a clearance of up to 100 mm
must be observed around the cooling slots
• The controller is designed conforming to the directives for safety class II devices
mounted in compliance with these regulations
• Power to the controller may only be supplied when completely fitted. If this is not
observed, there is a risk of electric shock hazard near the terminals and through the
cooling slots
• The controller must not be exposed to dripping water.
• Permissible ambient temperature when mounted and when ready to operate: 0...50 °C
• Power cables must be clearly segregated from low-voltage cables (sensors)
observing a distance of at least 100 mm
• Boiler
• Control panel
• Housing for wall mounting
12/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Mounting method
Screwed On DIN rail
Dimensions and drilling plan
BL1B1
A2
A1
2359Z09
L
B1
A: Mounting / B: Removal
Note:
To mount the controller on a DIN rail, a mounting clip
is required!
B2
Dimensions in mm
2359Z11
Total height required
RVS63…
RVS43…
2359Z10
x
2358M01
LBHL1B1
280.7 120.7 51.7 270 110
180.7 120.7 51.7 170 110
Dimension X:
Connectors with tongues minimum 70 mm
Connector without tongues minimum 60 mm
13/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
3.2.1 Connection terminals of RVS43.143
U TSRQPN L
QX1 N
Y2 N
Y1
Q2 N
Q3 N
SK2
SK14 S3
T2
T1
N L1
S3
L1
050110A
000020RVS43.143/109
S05011000002 0
1PRVS13.143/109
N L
2354Z08
M
BX2MBX1MB1MH1MB9MB3- - MB2- G+
n n p n kh f bba
b
CL-
CL+
CL-
G+
CL-
CL+
CL+
MB
DB
X50
X60
X30
BSB
LPB
3.2.2 Connection terminals of RVS63.243
QX4
ZUUUTSR Q PN L
QX4
FX4
EX2
QX3 N
QX2 N - - - - - - - QX1 N
061107B
000020RVS63.243/10 9
S061107000020
1PRVS63.243/109
Y2 N
Y1
Q2 N
Q3 N
SK2
SK1 4 S3
T2
T1
N L1
S3
L1
N L
2354Z06
M
UX M BX4 M BX3 M H3 - - M BX2 M BX1 M B1 M H1 M B9 M B3 - - M B2 - G+
n n n n n n p n k h f b b b a
b
CL-
CL+
CL-
CL+
CL-
CL+
MB
DB
X50
X60
X30
BSB
G+
CL-
CL+
14/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
LPB
3.2.3 Connection terminals of RVS63.283
ZUUTSU TSR Q PN L
QX4
QX4
FX4
EX2
QX3 N
QX2 N
Y6 N
Y5
Q6 N
QX1 N
Y2 N
Y1
Q2 N
Q3 N
SK2
SK1 4 S3
T2
061107B
000020RVS63.283/10 9
S061107000020
1PRVS63.283/109
T1
N L1
S3
L1
N L
2354Z07
M
UX M BX4 M BX3 M H2 M B12 M BX2 M BX1 M B1 M H1 M B9 M B3 - - M B2 - G+
n n n n p n n p n k h f b b b a
b
CL-
CL+
CL-
CL+
CL-
CL+
G+
CL-
CL+
MB
DB
X50
X60
X30
BSB
LPB
15/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Terminal markings
Mains voltage
Use Space Connector type
L Live AC 230 V basic unit N L AGP4S.05A/109
Protective earth
N Neutral conductor
L1 Live AC 230 V burner
S3 Output burner fault
L1 Live burner P AGP8S.07A/109
Protective earth
N Neutral conductor
T1 Phase 1st burner stage
T2 1st burner stage on
S3 Input burner fault
4
Input 1st burner stage hours run
SK1 Safety loop Q AGP8S.02E/109
SK2 Safety loop
N Neutral conductor R AGP8S.03A/109
Protective earth
Q3 DHW charging pump / diverting valve
N Neutral conductor S AGP8S.03B/109
Protective earth
Q2 1st heating circuit pump
Y1 1st heating circuit mixing valve opening T AGP8S.04B/109
N Neutral conductor
Protective earth
Y2 1st heating circuit mixing valve closing
N Neutral conductor U AGP8S.03C/109
Protective earth
QX1 1st multifunctional output
N Nullleiter S
Protective earth
Q6 2nd heating circuit pump
AGP8S.03B/109
Y5 2nd heating circuit mixing valve opening T AGP8S.04B/109
N Neutral conductor
Protective earth
Y6 2nd heating circuit mixing valve closing
N Neutral conductor U AGP8S.03C/109
Protective earth
QX2 2nd multifunctional output
N Neutral conductor U AGP8S.03C/109
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Low-voltage
BSB Service tool OCI700
LPB
Use Space Connector type
- -
Local Process Bus
- system
X60 Radio module AVS71.390
X50 Extension module AVS75.390
X30 Operator unit / boiler control panel
DB LPB data
MB LPB ground
CL+ BSB data
- -
-
-
AVS82.490/109
AVS82.491/109
AGP4S.02H/109
AGP4S.02A/109
CL- BSB ground b
CL+ Room unit 2 data
AGP4S.02A/109
CL- Room unit 2 ground b
CL+ Room unit 1 data
AGP4S.02A/109
CL- Room unit 1 ground b AGP4S.03D/109
G+ Room unit power supply 12 V
B2 Boiler sensor
AGP4S.02B/109
M Ground f
B3 DHW sensor top
AGP4S.02C/109
M Ground h
B9 Outside sensor
AGP4S.02D/109
M Ground k
H1 Digital / DC 0...10 V input
AGP4S.02F/109
M Ground n
B1 Flow temperature sensor HK1
AGP4S.02G/109
M Ground p
BX1 Multifunctional sensor input 1
AGP4S.02F/109
M Ground n
BX2 Multifunctional sensor input 2
AGP4S.02F/109
M Ground n
B12 Flow temperature sensor HK2
AGP4S.02G/109
M Ground p
H3 Digital / DC 0...10 V input
AGP4S.02F/109
M Ground n
BX3 Multifunctional sensor input 3
AGP4S.02F/109
M Ground n
BX4 Multifunctional sensor input 4
AGP4S.02F/109
M Ground n
UX DC 0…10 V output n AGP4S.02F/109
M Ground
17/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
3
2
Dimensions and drilling plan
Connections
3.3 Extension module AVS75.390
For planning, mounting location and mounting method, refer to the information given for
the basic modules.
L
Dimensions in mm
BL1B1
2358M01
AVS75.390
The AVS75.390 extension module must be connected to terminal
using the
LBHL1B1
108.7 120.9 51.7 98 110
X50 of the basic unit
AVS83.490/109 connecting cable. The connectors are coded.
3.3.1 Connection terminals of AVS75.390
S T N L
- --
QX2
AVS75.390/109
S050110000020
M
H2 M BX22 M BX21 - -X50 - -
n n n
N
1PAVS75.390/109
QX2
N
QX21
N L
050110A
000020
1
2359Z49
2
12
1
2
= Module 1
= Module 2
X30
18/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Terminal markings
Mains voltage
Low-voltage
Assignment of terminals
Use Space Connector type
L Live AC 230 V basic unit N L AGP4S.03E/109
Protective earth
N Neutral conductor
QX21 Assignment according to function T AGP8S.04B/109
N Neutral conductor
Protective earth
QX22 Assignment according to function
N Neutral conductor S AGP8S.03B/109
Protective earth
QX23 Assignment according to function
X30 Operator unit / boiler control panel
X50 Basic unit
BX21 Assignment according to function
M Ground n
BX22 Assignment according to function
M Ground n
H2 Digital / DC 0...10 V input
Use Space Connector type
-
AVS82.491/109
AVS82.490/109
AGP4S.02F/109
AGP4S.02F/109
AGP4S.02F/109
M Ground n
Using the 2 parameters
• Function extension module 1 (operating line 6020)
• Function extension module 2 (operating mode 6021)
usage of the respective module will be defined.
19/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Mounting method
3.4 Operator unit AVS37.294
Installation
2358Z30
2358Z31
Removal
2358Z32
Connections
Dimensions
Panel cutout
The AVS37.294 operator unit must be connected to terminal X30 of the basic unit using
the AVS82.491/109 connecting cable. The connectors are coded.
27
17
2358M03
96
144
90
42.4
(144)
0.5...3.0
0
+0.8
92
(96)
+1
138
0
2358M05
20/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Connections
Dimensions
3.5 Operator unit AVS37.390
The AVS37.390 operator unit must be connected to terminal X30 of the basic unit using
the AVS82.491/109 connecting cable. The connectors are coded.
2354M01
0,5
13
A
A Control panel, front
21/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Planning
Mounting method
3.6 Room unit QAA55…
@
The room unit should be located in the main living room while giving consideration to
the following points:
• The place of installation should be chosen so that the sensor can capture the room
temperature as accurately as possible without getting adversely affected by direct
solar radiation or other heat or refrigeration sources (about 1.5 meters above the
floor)
• In the case of wall mounting, there must be sufficient clearance above the unit,
enabling it to be fitted and removed
When the unit is removed from its base, power is cut off so that the unit is out of
operation.
2284Z33a
2284Z34a
Connections
Dimensions and drilling plan
• The controller must not be exposed to dripping water
34
562
1
TerminalDesignation QAA55..
2284Z40
1
2
CL+ BSB data
CL- BSB ground
2282M02
1
6
9
9
96
7
4
4,2
56
12
56
60
2359Z27
60
22/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Planning
Mounting method
3.7 Room unit QAA75…
@
The room unit should be located in the main living room while giving consideration to
the following points:
• The place of installation should be chosen so that the sensor can capture the room
temperature as accurately as possible without getting adversely affected by direct
solar radiation or other heat or refrigeration sources (about 1.5 meters above the
floor)
• In the case of wall mounting, there must be sufficient clearance above the unit,
enabling it to be fitted and removed
When the unit is removed from its base, power is cut off so that the unit is out of
operation.
Connections
2359Z25
2359Z20
2359Z26
2359Z24
TerminalDesignationQAA75.610QAA75.611
1
2
3
CL+ BSB data BSB data
CL- BSB ground BSB ground
G+ Reserved Power supply DC 12 V
2359Z21
23/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Dimensions and drilling plan
4,2
56
60
100
2359Z50
56
60
80
82
42
185
100
2359Z12
24/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Planning
Mounting method
3.8 Wireless components
The wireless components should be located such that transmission will be as
interference-free as possible. The following criteria must be observed:
• Not in the vicinity of electrical cables, strong magnetic fields or equipment like PCs,
TV sets, microwave ovens, etc.
• Not near larger metal structures or constructional elements with fine metal meshes
such as special glass or special concrete
• The distance to the transmitter should not exceed 30 meters or 2 floors
3.8.1 Radio module AVS71.390
The radio module extends the product range by introducing wireless communication.
With this type of device, the system components, such as room units, transmit data with
no need for laying cables.
Do not install the radio module inside metal casings (e.g. inside a boiler).
2359Z23
Connection
Radio connection
Dimensions and drilling plan
LED
A
Button
B
2359Z57
The prefabricated cable is to be connected to terminal X60 of the controller.
Prior to connecting, the basic unit must be disconnected from power!
Establishment of the wireless connection is described in the following sections which
cover the relevant radio-controlled units.
2354Z11
43
25/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Planning
Mounting with base
3.8.2 Room unit QAA78.610
@
The room unit should be located in the main living room while giving consideration to
the following points:
• The place of installation should be chosen so that the sensor can capture the room
temperature as accurately as possible without getting adversely affected by direct
solar radiation or other heat or refrigeration sources (about 1.5 meters above the
floor)
• In the case of wall mounting, there must be sufficient clearance above the unit,
enabling it to be fitted and removed
2359Z26
2359Z20
2359Z25
2359Z21
2359Z22
26/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Connection / power supply
Radio connection
Establishment
Testing
Mounting without base
2359Z61
The room unit is powered by three 1.5 V Alkali batteries type AA (LR06).
Make the radio connection in the vicinity of the radio module prior to mounting so that
all system are within easy reach.
Prerequisite for the radio connection is that all components receive power, which
means that the radio module must be correctly connected to the basic unit and the
batteries must be correctly installed in the room unit.
1. Press the button on the installed radio module for at least 8 seconds until the LED
on the radio module starts flashing at high frequency.
2. Press OK on the room unit to switch to programming.
3. Press the info button for at least 3 seconds and select operating level
“Commissioning“ with the setting knob. Then, press OK.
4. Select operating page “Operator unit“ and press OK.
5. Select operating line “Used as“ (operating line 40) and make the appropriate
selection. Then, press OK.
6. Select operating page “Radio“ and press OK.
7. Select setting line “Binding“ (line 120). Then, press OK.
8. Set the setting knob to “YES“ and press OK. Connection establishment is started.
9. The display shows the progress of connection establishment in %. This process can
take 2 to 120 seconds.
10. The connection is established when “Device ready” appears and the LED on the
radio module extinguishes
The test is made to check the quality of the radio link.
• The test can be aborted by pressing the ESC button.
• While the radio link can be opened on the controller, the test should be made at the
location where the room unit will be installed
On the room unit, as described above (points 2 through 4), select operating page
“Radio“ and activate the test mode on setting line “Test mode“ (line 121).
27/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Dimensions and drilling plan
Example of a display during the test:
The digits on the left shows telegrams that have
been sent, the digits on the right telegrams that
have been received. The test will be ended
Operator section
Testmode
after 24 telegrams. The test is considered
successful when at least 50 % of the telegrams
sent have been received.
If the test was not successful, some other mounting location is to be selected or the
AVS14.390 radio repeater can be used.
9
185
11
39
67
4,2
2359Z140
2359Z50
100
82
42
2359Z12
56
60
80
100
28/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Mounting method
3.8.3 Wireless outside sensor AVS13.399
• The radio transmitter must be installed inside the building.
• The radio transmitter’s mounting location should be chosen such that batteries
can be easily changed.
Radio transmitterOutside sensor
2359Z30
2359Z33
2359Z54
2359Z32
2359Z59
2359Z31
2359Z53
Battery
AAA
AAA
Battery transit
tab
2359Z55
Connections
The outside sensor is to be connected to the radio transmitter via a 2-core cable, the
connections are interchangeable.
The room unit is powered by 2 pieces 1.5 V Alkali batteries type AAA (LR03).
29/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007
Radio connection
Establishment
Testing
Dimensions and drilling plan
Make the radio connection in the vicinity of the radio module prior to mounting so that
all system are within easy reach.
Prerequisite for the radio connection is that all components receive power, which
means that the radio module must be correctly connected to the basic unit and the
batteries must be correctly installed in the room unit.
1. Press the button on the radio module for at least 8
LED
seconds until the LED on the radio module starts
flashing at high frequency.
2. Press the button on the transmitter of the wireless
AAA
AAA
outside sensor for at least 8 seconds until that LED
also starts flashing at high frequency.
3. The connection is established when the LED on the
radio module extinguishes.
Button
4. Press the button on the transmitter of the wireless outside sensor briefly again until
the LED extinguishes.
The test is made to check the quality of the radio link.
• The test can be aborted by pressing the ESC button.
• While the radio link can be opened on the controller, the test should be made at the
location where the room unit will be installed
1. Press button 3 on the transmitter of the wireless outside sensor for a maximum of 8
seconds until the LED starts flashing at low frequency.
2. When radio communication works, the LED on the radio module flashes briefly at
10-second intervals.
3. After the test, press the button on the transmitter of the wireless outside sensor
again briefly until the LED extinguishes.
2359Z58
2359Z16
100
90
4,2
12
56
60
2359Z27
32
56
60
79,8
5,5
4
49,5
2524,5
Ø 14,1
91,6
49,7
3
6
5,5
1811M02
1811M01
30/156
Siemens Switzerland Ltd. User manual CE1U2354en
HVAC Products Mounting and installation 11. May 2007