Siemens RVS43.143, RVS63.243, RVS63.283, AVS75.390, AVS37.294 User Guide

...
2
Albatros Boiler controllers
RVS43.. RVS63.. AVS75..
AVS37.. QAA75.. QAA78..
User manual
Edition 2.0 Controller series B CE1U2354en
11. May 2007
QAA55..
Building Technologies
HVAC Products
2/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products 11. May 2007
Table of contents
1 Summary ......................................................................................................... 9
1.1 Type summary............................................................................................... 10
2 Safety notes................................................................................................... 11
2.1 Product liability ..............................................................................................11
3 Mounting and installation............................................................................... 12
3.1 Regulations.................................................................................................... 12
3.2 Basic units RVS… ......................................................................................... 12
Planning......................................................................................................... 12
Mounting method........................................................................................... 13
Dimensions and drilling plan.......................................................................... 13
3.2.1 Connection terminals of RVS43.143 .............................................................14
3.2.2 Connection terminals of RVS63.243 .............................................................14
3.2.3 Connection terminals of RVS63.283 .............................................................15
Terminal markings ......................................................................................... 16
3.3 Extension module AVS75.390....................................................................... 18
Dimensions and drilling plan.......................................................................... 18
3.3.1 Connection terminals of AVS75.390.............................................................. 18
Terminal markings ......................................................................................... 19
Assignment of terminals ................................................................................ 19
3.4 Operator unit AVS37.294 ..............................................................................20
Mounting method........................................................................................... 20
Connections................................................................................................... 20
Dimensions.................................................................................................... 20
3.5 Operator unit AVS37.390 ..............................................................................21
Connections................................................................................................... 21
Dimensions.................................................................................................... 21
3.6 Room unit QAA55… ...................................................................................... 22
Planning......................................................................................................... 22
Mounting method........................................................................................... 22
Connections................................................................................................... 22
Dimensions and drilling plan.......................................................................... 22
3.7 Room unit QAA75… ...................................................................................... 23
Planning......................................................................................................... 23
Mounting method........................................................................................... 23
Connections................................................................................................... 23
Dimensions and drilling plan.......................................................................... 24
3.8 Wireless components .................................................................................... 25
3.8.1 Radio module AVS71.390 ............................................................................. 25
Planning......................................................................................................... 25
Mounting method........................................................................................... 25
Connection ....................................................................................................25
Radio connection........................................................................................... 25
Dimensions and drilling plan.......................................................................... 25
3.8.2 Room unit QAA78.610................................................................................... 26
3/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Summary 11. May 2007
Planning .........................................................................................................26
Mounting with base........................................................................................26
Connection / power supply.............................................................................27
Radio connection ...........................................................................................27
Dimensions and drilling plan ..........................................................................28
3.8.3 Wireless outside sensor AVS13.399..............................................................29
Mounting method ...........................................................................................29
Radio connection ...........................................................................................30
Dimensions and drilling plan ..........................................................................30
3.8.4 Radio repeater AVS14.390 ............................................................................31
Mounting method ...........................................................................................31
Connections ...................................................................................................31
Radio connection ...........................................................................................31
Dimensions and drilling plan ..........................................................................31
3.8.5 Checking the wireless components ...............................................................32
3.9 Power supply AVS16.290 ..............................................................................32
Mounting notes ..............................................................................................32
Mounting method ...........................................................................................32
Connections ...................................................................................................32
4 Commissioning ..............................................................................................34
4.1 Basic units......................................................................................................34
5 Handling.........................................................................................................35
5.1 QAA75.. / QAA78… / AVS37.. .......................................................................35
5.1.1 Operation .......................................................................................................35
Operating elements........................................................................................35
Display choices ..............................................................................................36
Selecting heating mode .................................................................................36
Selecting DHW heating mode........................................................................37
Adjusting the room temperature setpoint .......................................................37
Occupancy button ..........................................................................................37
Displaying information....................................................................................37
5.1.2 Programming .................................................................................................40
Setting principle .............................................................................................40
Example: “Setting the time of day“.................................................................40
5.1.3 User levels .....................................................................................................41
Setting structure “Enduser“ ............................................................................42
Setting structure ”Heating engineer“ ..............................................................42
5.1.4 Overview of settings.......................................................................................43
5.1.5 AVS37.390Operation .....................................................................................62
Operating elements........................................................................................62
Display choices ..............................................................................................62
Selecting the operating mode ........................................................................62
Adjusting the room temperature setpoint .......................................................63
Adjusting the nominal DHW setpoint .............................................................63
Displaying information....................................................................................63
Setting principle .............................................................................................64
Example: “Setting the time of day“.................................................................64
5.1.6 User levels .....................................................................................................65
5.1.7 Overview of settings.......................................................................................66
4/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Summary 11. May 2007
5.2 QAA55... ........................................................................................................ 67
5.2.1 Operation....................................................................................................... 67
Operating elements ....................................................................................... 67
Display choices.............................................................................................. 67
5.2.2 Programming ................................................................................................. 67
6 The settings in detail...................................................................................... 68
6.1 Time of day and date..................................................................................... 68
6.2 Operator section ............................................................................................ 68
Operation and display.................................................................................... 68
Heating circuit assignment ............................................................................69
Room sensor ................................................................................................. 70
Device data.................................................................................................... 70
6.3 Radio ............................................................................................................. 70
Binding........................................................................................................... 70
Device list radio ............................................................................................. 71
6.4 Time programs ..............................................................................................71
Switching points............................................................................................. 71
Standard program.......................................................................................... 72
6.5 Holidays......................................................................................................... 72
6.6 Heating circuits .............................................................................................. 72
Operating mode............................................................................................. 72
Setpoints........................................................................................................ 72
Heating curve ................................................................................................73
ECO functions ...............................................................................................74
Flow temperature setpoint limitations ............................................................ 75
Room influence.............................................................................................. 75
Room temp limitation..................................................................................... 76
Boost heating................................................................................................. 77
Quick setback ................................................................................................ 77
Optimum start / stop control ..........................................................................78
Increase of Reduced setpoint........................................................................ 79
Overtemperature protection pump heating circuit .........................................79
Mixing valve control ....................................................................................... 79
Floor curing function ...................................................................................... 80
Excess heat draw .......................................................................................... 81
Buffer storage tank / primary controller .........................................................81
Speed-controlled pump .................................................................................81
Remote .......................................................................................................... 82
6.7 DHW .............................................................................................................. 82
Setpoints........................................................................................................ 82
Priority ...........................................................................................................82
Legionella function......................................................................................... 83
Circulating pump............................................................................................ 83
6.8 Pump H1/H2/H3 ............................................................................................84
Pump H1/H2/H3 ............................................................................................84
6.9 Swimming pool ..............................................................................................84
Setpoints........................................................................................................ 84
Priority ...........................................................................................................84
Plant hydraulics ............................................................................................. 85
6.10 Primary controller / system pump .................................................................. 85
5/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Summary 11. May 2007
Primary controller / system pump ..................................................................85
6.11 Boiler..............................................................................................................85
Operating mode .............................................................................................85
Setpoints ........................................................................................................85
Minimum limitation of the return temperature ................................................86
Output data ....................................................................................................86
2 x 1 cascade.................................................................................................86
6.12 Cascade.........................................................................................................87
Control ...........................................................................................................87
Boiler sequence .............................................................................................87
Minimum limitation of the return temperature ................................................88
6.13 Solar...............................................................................................................89
Charging controller (dT) .................................................................................89
Priority............................................................................................................89
Start function..................................................................................................90
Frost protection for the collector ....................................................................91
Overtemperature protection for the collector .................................................91
Medium’s evaporation temperature ...............................................................91
Speed control.................................................................................................92
Yield measurement ........................................................................................92
6.14 Solid fuel boiler ..............................................................................................92
Operating mode .............................................................................................92
Setpoints ........................................................................................................92
Boiler / burner control.....................................................................................92
6.15 Buffer storage tank.........................................................................................93
Automatic locks..............................................................................................93
Overtemperature protection ...........................................................................93
Recooling .......................................................................................................93
Plant hydraulics..............................................................................................94
Return diversion.............................................................................................94
Partial charging ..............................................................................................95
Full charging ..................................................................................................95
6.16 DHW storage tank..........................................................................................96
Charging control.............................................................................................96
Overtemperature protection ...........................................................................96
Recooling .......................................................................................................96
Electric immersion heater ..............................................................................96
Plant hydraulics..............................................................................................98
Speed-controlled pump..................................................................................98
6.17 Instantaneous DHW heater............................................................................98
Setpoints ........................................................................................................98
Mixing valve control .......................................................................................98
6.18 Configuration..................................................................................................99
Heating circuits 1 and 2 .................................................................................99
DHW sensor B3 .............................................................................................99
DHW controlling element Q3 .........................................................................99
Separate circuit ..............................................................................................99
Boiler............................................................................................................100
Solar.............................................................................................................103
Output relay QX ...........................................................................................104
Input sensor BX ...........................................................................................107
Input H1/H3..................................................................................................107
Input EX2 .....................................................................................................110
6/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Summary 11. May 2007
Mixing valve groups basic unit..................................................................... 111
Extension module ........................................................................................ 112
QX extension module .................................................................................. 113
BX extension module................................................................................... 114
H2 extension module................................................................................... 114
10V output UX ............................................................................................. 114
Types of sensors/readjustments.................................................................. 115
Building and room model............................................................................. 115
Frost protection for the plant........................................................................ 115
External requirements .................................................................................116
sensor state ................................................................................................. 116
Parameter reset........................................................................................... 116
Plant diagram ..............................................................................................117
Device data.................................................................................................. 119
6.19 LPB system .................................................................................................120
Address / power supply ............................................................................... 120
Central functions.......................................................................................... 120
Clock............................................................................................................ 121
6.20 Errors........................................................................................................... 122
6.21 Maintenance / service.................................................................................. 122
Maintenance functions................................................................................. 122
Chimney sweep ........................................................................................... 123
Economy mode............................................................................................ 123
Manual operation......................................................................................... 123
Simulations .................................................................................................. 124
Telephone customer service .......................................................................124
6.22 Input / output test......................................................................................... 125
6.23 State ............................................................................................................ 125
Messages .................................................................................................... 125
6.24 Diagnostics of heat source .......................................................................... 128
6.25 Diagnostics consumers ...............................................................................128
6.26 List of displays ............................................................................................. 129
6.26.1 Error code.................................................................................................... 129
6.26.2 Maintenance code .......................................................................................130
6.26.3 Special operation code ................................................................................ 130
7 Plant diagrams............................................................................................. 131
7.1 Basic diagrams ............................................................................................ 131
7.1.1 Basic diagram RVS43.143 ..........................................................................131
7.1.2 Basic diagram RVS63.243 ..........................................................................132
7.1.3 Basic diagram RVS63.283 ..........................................................................132
7.2 Versions of heat sources ............................................................................. 133
7.3 Extra functions in general ............................................................................ 134
Solar ............................................................................................................ 134
Boiler ...........................................................................................................136
Storage tank temperature............................................................................ 137
Heating circuit.............................................................................................. 137
Heat converter ............................................................................................. 138
Swimming pool ............................................................................................138
Pressureless header.................................................................................... 138
7/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Summary 11. May 2007
Extra functions .............................................................................................139
7.4 Extra functions with AVS75.390...................................................................140
Legend mains voltage..................................................................................142
Legend low-voltage......................................................................................143
8 Technical data..............................................................................................144
8.1 Basic units RVS…........................................................................................144
8.2 Extension module AVS75.390 .....................................................................145
8.3 Operator unit and room units AVS37... / QAA7x… / QAA55.. .....................146
8.4 Power supply AVS16.290 ............................................................................147
8.5 Radio module AVS71.390............................................................................147
8.6 Wireless outside sensor AVS13.399............................................................148
8.7 Radio repeater AVS14.390 ..........................................................................149
8.8 Sensor characteristics..................................................................................150
8.8.1 NTC 1 k........................................................................................................150
8.8.2 NTC 10 k......................................................................................................151
8.8.3 PT1000 ........................................................................................................151
9 Revision history............................................................................................155
8/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Summary 11. May 2007
1 Summary
This User manual describes the products listed in the following table and covers handling and configuration of the controls for readers ranging from endusers to heating engineers.
Type reference (ASN)
RVS43.143 A Basic unit boiler RVS63.243 B Basic unit boiler RVS63.283 B Basic unit boiler AVS75.390 B Extension module AVS37.294 B Operator unit AVS37.390 A Operator unit basic QAA75.610 B Room unit, wired QAA75.611 B Room unit with backlight, wired QAA78.610 B Room unit, wireless QAA55.110 A Room unit basic AVS16.290 A Power section AVS71.390 A Radio module AVS14.390 A Radio repeater AVS13.399 A Wireless outside sensor
The following products are described in separate pieces of documentation:
QAC34 Outside sensor NTC 1 k QAD36 Strap-on temperature sensor NTC 10 k QAZ36 Immersion temperature sensor NTC 10 k
Series Name
9/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Summary 11. May 2007
Operation with room unit
1.1 Type summary
Wired RF
Operation with operator unit “basic”
(optionally with additional
room unit)
Operation with operator unit “clear-text”
(optionally with additional room
unit)
B
A
D
T
B
A
E1
EB
C
T
2359Z66
B
A
D
B
A
B
F
E1
E
C
2359Z67
A
A Basic unit RVS… B Power section AVS16… C Room unit QAA75… / 78… D Outside sensor AVS13… E Operator unit AVS37.294 (clear-text) E1 Operator unit AVS37.390 (basic) F Radio module AVS71…
A
10/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Summary 11. May 2007
2 Safety notes
2.1 Product liability
The products may only be used in building services plant and applications as described in this document
When using the products, all requirements specified in chapters "Handling" and "Technical data" must be satisfied
The local regulations (for installation, etc.) must be complied with
Do not open the units. If not observed, warranty becomes void.
11/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Safety notes 11. May 2007
3 Mounting and installation
3.1 Regulations
Electrical installation
Planning
Mounting location
Prior to installing the units, power must be turned off
The connections for mains and low-voltage are separated
For wiring, the requirements of safety class II must be satisfied. Sensor and power
cables must not be run in the same cable duct
3.2 Basic units RVS…
Air circulation around the controller must be ensured, allowing the unit to emit the heat produced by it. A clearance of at least 10 mm must be provided for the unit's cooling slots at the top and bottom of the housing. That space should not be accessible and no objects should be placed there. If the controller is enclosed in another (insulating) casing, a clearance of up to 100 mm must be observed around the cooling slots
The controller is designed conforming to the directives for safety class II devices mounted in compliance with these regulations
Power to the controller may only be supplied when completely fitted. If this is not observed, there is a risk of electric shock hazard near the terminals and through the cooling slots
The controller must not be exposed to dripping water.
Permissible ambient temperature when mounted and when ready to operate: 0...50 °C
Power cables must be clearly segregated from low-voltage cables (sensors)
observing a distance of at least 100 mm
Boiler
Control panel
Housing for wall mounting
12/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Mounting method
Screwed On DIN rail
Dimensions and drilling plan
BL1B1
A2
A1
2359Z09
L
B1
A: Mounting / B: Removal
Note: To mount the controller on a DIN rail, a mounting clip is required!
B2
Dimensions in mm
2359Z11
Total height required
RVS63… RVS43…
2359Z10
x
2358M01
L B H L1 B1
280.7 120.7 51.7 270 110
180.7 120.7 51.7 170 110
Dimension X: Connectors with tongues minimum 70 mm Connector without tongues minimum 60 mm
13/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
3.2.1 Connection terminals of RVS43.143
U TSR Q P N L
QX1 N
Y2 N
Y1
Q2 N
Q3 N
SK2
SK1 4 S3
T2
T1
N L1
S3
L1
050110A 000020RVS43.143/109
S05011000002 0
1PRVS13.143/109
N L
2354Z08
M
BX2 M BX1 M B1 M H1 M B9 M B3 - - M B2 - G+
n n p n k h f b b a
b
CL-
CL+
CL-
G+
CL-
CL+
CL+
MB
DB
X50
X60
X30
BSB
LPB
3.2.2 Connection terminals of RVS63.243
QX4
Z U U UTSR Q PN L
QX4
FX4
EX2
QX3 N
QX2 N - - - - - - - QX1 N
061107B 000020RVS63.243/10 9
S061107000020
1PRVS63.243/109
Y2 N
Y1
Q2 N
Q3 N
SK2
SK1 4 S3
T2
T1
N L1
S3
L1
N L
2354Z06
M
UX M BX4 M BX3 M H3 - - M BX2 M BX1 M B1 M H1 M B9 M B3 - - M B2 - G+
n n n n n n p n k h f b b b a
b
CL-
CL+
CL-
CL+
CL-
CL+
MB
DB
X50
X60
X30
BSB
G+
CL-
CL+
14/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
LPB
3.2.3 Connection terminals of RVS63.283
Z U U T SU TS R Q P N L
QX4
QX4
FX4
EX2
QX3 N
QX2 N
Y6 N
Y5
Q6 N
QX1 N
Y2 N
Y1
Q2 N
Q3 N
SK2
SK1 4 S3
T2
061107B 000020RVS63.283/10 9
S061107000020
1PRVS63.283/109
T1
N L1
S3
L1
N L
2354Z07
M
UX M BX4 M BX3 M H2 M B12 M BX2 M BX1 M B1 M H1 M B9 M B3 - - M B2 - G+
n n n n p n n p n k h f b b b a
b
CL-
CL+
CL-
CL+
CL-
CL+
G+
CL-
CL+
MB
DB
X50
X60
X30
BSB
LPB
15/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Terminal markings
Mains voltage
Use Space Connector type
L Live AC 230 V basic unit N L AGP4S.05A/109
Protective earth
N Neutral conductor
L1 Live AC 230 V burner
S3 Output burner fault
L1 Live burner P AGP8S.07A/109
Protective earth N Neutral conductor T1 Phase 1st burner stage T2 1st burner stage on S3 Input burner fault 4
Input 1st burner stage hours run SK1 Safety loop Q AGP8S.02E/109 SK2 Safety loop N Neutral conductor R AGP8S.03A/109
Protective earth Q3 DHW charging pump / diverting valve N Neutral conductor S AGP8S.03B/109
Protective earth Q2 1st heating circuit pump Y1 1st heating circuit mixing valve opening T AGP8S.04B/109 N Neutral conductor
Protective earth Y2 1st heating circuit mixing valve closing N Neutral conductor U AGP8S.03C/109
Protective earth QX1 1st multifunctional output N Nullleiter S
Protective earth Q6 2nd heating circuit pump
AGP8S.03B/109
Y5 2nd heating circuit mixing valve opening T AGP8S.04B/109 N Neutral conductor
Protective earth Y6 2nd heating circuit mixing valve closing N Neutral conductor U AGP8S.03C/109
Protective earth QX2 2nd multifunctional output N Neutral conductor U AGP8S.03C/109
Protective earth QX3 3rd multifunctional output
EX2 Multifunctional input Z AGP8S.04C/109 FX4 (T6) QX4 (T7) QX4 (T8)
Phase 4th Multifunctional output
(phase 2nd burner stage)
4th Multifunctional output off
(2nd burner stage off)
4th Multifunctional output on
(2nd burner stage on)
16/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Low-voltage
BSB Service tool OCI700 LPB
Use Space Connector type
- -
Local Process Bus
- ­system X60 Radio module AVS71.390 X50 Extension module AVS75.390
X30 Operator unit / boiler control panel
DB LPB data MB LPB ground
CL+ BSB data
- -
-
-
AVS82.490/109 AVS82.491/109
AGP4S.02H/109
AGP4S.02A/109 CL- BSB ground b
CL+ Room unit 2 data
AGP4S.02A/109 CL- Room unit 2 ground b
CL+ Room unit 1 data
AGP4S.02A/109 CL- Room unit 1 ground b AGP4S.03D/109
G+ Room unit power supply 12 V
B2 Boiler sensor
AGP4S.02B/109 M Ground f
B3 DHW sensor top
AGP4S.02C/109 M Ground h
B9 Outside sensor
AGP4S.02D/109 M Ground k
H1 Digital / DC 0...10 V input
AGP4S.02F/109 M Ground n
B1 Flow temperature sensor HK1
AGP4S.02G/109 M Ground p
BX1 Multifunctional sensor input 1
AGP4S.02F/109 M Ground n
BX2 Multifunctional sensor input 2
AGP4S.02F/109 M Ground n
B12 Flow temperature sensor HK2
AGP4S.02G/109 M Ground p
H3 Digital / DC 0...10 V input
AGP4S.02F/109 M Ground n
BX3 Multifunctional sensor input 3
AGP4S.02F/109 M Ground n
BX4 Multifunctional sensor input 4
AGP4S.02F/109 M Ground n
UX DC 0…10 V output n AGP4S.02F/109 M Ground
17/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
3
2
Dimensions and drilling plan
Connections
3.3 Extension module AVS75.390
For planning, mounting location and mounting method, refer to the information given for the basic modules.
L
Dimensions in mm
BL1B1
2358M01
AVS75.390
The AVS75.390 extension module must be connected to terminal
using the
L B H L1 B1
108.7 120.9 51.7 98 110
X50 of the basic unit
AVS83.490/109 connecting cable. The connectors are coded.
3.3.1 Connection terminals of AVS75.390
S T N L
- - -
QX2
AVS75.390/109
S050110000020
M
H2 M BX22 M BX21 - -X50 - -
n n n
N
1PAVS75.390/109
QX2
N
QX21
N L
050110A 000020
1
2359Z49
2
12
1
2
= Module 1
= Module 2
X30
18/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Terminal markings
Mains voltage
Low-voltage
Assignment of terminals
Use Space Connector type
L Live AC 230 V basic unit N L AGP4S.03E/109
Protective earth N Neutral conductor QX21 Assignment according to function T AGP8S.04B/109 N Neutral conductor
Protective earth QX22 Assignment according to function N Neutral conductor S AGP8S.03B/109
Protective earth QX23 Assignment according to function
X30 Operator unit / boiler control panel X50 Basic unit
BX21 Assignment according to function M Ground n
BX22 Assignment according to function M Ground n
H2 Digital / DC 0...10 V input
Use Space Connector type
-
AVS82.491/109 AVS82.490/109
AGP4S.02F/109
AGP4S.02F/109
AGP4S.02F/109
M Ground n
Using the 2 parameters
Function extension module 1 (operating line 6020)
Function extension module 2 (operating mode 6021)
usage of the respective module will be defined.
19/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Mounting method
3.4 Operator unit AVS37.294
Installation
2358Z30
2358Z31
Removal
2358Z32
Connections
Dimensions
Panel cutout
The AVS37.294 operator unit must be connected to terminal X30 of the basic unit using the AVS82.491/109 connecting cable. The connectors are coded.
27
17
2358M03
96
144
90
42.4
(144)
0.5...3.0
0
+0.8
92
(96)
+1
138
0
2358M05
20/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Connections
Dimensions
3.5 Operator unit AVS37.390
The AVS37.390 operator unit must be connected to terminal X30 of the basic unit using the AVS82.491/109 connecting cable. The connectors are coded.
2354M01
0,5
13
A
A Control panel, front
21/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Planning
Mounting method
3.6 Room unit QAA55…
@
The room unit should be located in the main living room while giving consideration to the following points:
The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)
In the case of wall mounting, there must be sufficient clearance above the unit, enabling it to be fitted and removed
When the unit is removed from its base, power is cut off so that the unit is out of operation.
2284Z33a
2284Z34a
Connections
Dimensions and drilling plan
The controller must not be exposed to dripping water
34
562
1
Terminal Designation QAA55..
2284Z40
1 2
CL+ BSB data CL- BSB ground
2282M02
1
6
9
9
96
7
4
4,2
56
12
56
60
2359Z27
60
22/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Planning
Mounting method
3.7 Room unit QAA75…
@
The room unit should be located in the main living room while giving consideration to the following points:
The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)
In the case of wall mounting, there must be sufficient clearance above the unit, enabling it to be fitted and removed
When the unit is removed from its base, power is cut off so that the unit is out of operation.
Connections
2359Z25
2359Z20
2359Z26
2359Z24
Terminal Designation QAA75.610 QAA75.611 1 2 3
CL+ BSB data BSB data CL- BSB ground BSB ground G+ Reserved Power supply DC 12 V
2359Z21
23/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Dimensions and drilling plan
4,2
56
60
100
2359Z50
56
60
80
82
42
185
100
2359Z12
24/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Planning
Mounting method
3.8 Wireless components
The wireless components should be located such that transmission will be as interference-free as possible. The following criteria must be observed:
Not in the vicinity of electrical cables, strong magnetic fields or equipment like PCs, TV sets, microwave ovens, etc.
Not near larger metal structures or constructional elements with fine metal meshes such as special glass or special concrete
The distance to the transmitter should not exceed 30 meters or 2 floors
3.8.1 Radio module AVS71.390
The radio module extends the product range by introducing wireless communication. With this type of device, the system components, such as room units, transmit data with no need for laying cables.
Do not install the radio module inside metal casings (e.g. inside a boiler).
2359Z23
Connection
Radio connection
Dimensions and drilling plan
LED
A
Button
B
2359Z57
The prefabricated cable is to be connected to terminal X60 of the controller. Prior to connecting, the basic unit must be disconnected from power!
Establishment of the wireless connection is described in the following sections which cover the relevant radio-controlled units.
2354Z11
43
25/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Planning
Mounting with base
3.8.2 Room unit QAA78.610
@
The room unit should be located in the main living room while giving consideration to the following points:
The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)
In the case of wall mounting, there must be sufficient clearance above the unit, enabling it to be fitted and removed
2359Z26
2359Z20
2359Z25
2359Z21
2359Z22
26/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Connection / power supply
Radio connection
Establishment
Testing
Mounting without base
2359Z61
The room unit is powered by three 1.5 V Alkali batteries type AA (LR06).
Make the radio connection in the vicinity of the radio module prior to mounting so that all system are within easy reach.
Prerequisite for the radio connection is that all components receive power, which means that the radio module must be correctly connected to the basic unit and the batteries must be correctly installed in the room unit.
1. Press the button on the installed radio module for at least 8 seconds until the LED on the radio module starts flashing at high frequency.
2. Press OK on the room unit to switch to programming.
3. Press the info button for at least 3 seconds and select operating level “Commissioning“ with the setting knob. Then, press OK.
4. Select operating page “Operator unit“ and press OK.
5. Select operating line “Used as“ (operating line 40) and make the appropriate selection. Then, press OK.
6. Select operating page “Radio“ and press OK.
7. Select setting line “Binding“ (line 120). Then, press OK.
8. Set the setting knob to “YES“ and press OK. Connection establishment is started.
9. The display shows the progress of connection establishment in %. This process can take 2 to 120 seconds.
10. The connection is established when “Device ready” appears and the LED on the radio module extinguishes
The test is made to check the quality of the radio link.
The test can be aborted by pressing the ESC button.
While the radio link can be opened on the controller, the test should be made at the
location where the room unit will be installed
On the room unit, as described above (points 2 through 4), select operating page “Radio“ and activate the test mode on setting line “Test mode“ (line 121).
27/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Dimensions and drilling plan
Example of a display during the test:
The digits on the left shows telegrams that have been sent, the digits on the right telegrams that have been received. The test will be ended
Operator section Testmode
after 24 telegrams. The test is considered successful when at least 50 % of the telegrams sent have been received.
If the test was not successful, some other mounting location is to be selected or the AVS14.390 radio repeater can be used.
9
185
11
39
67
4,2
2359Z140
2359Z50
100
82
42
2359Z12
56
60
80
100
28/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Mounting method
3.8.3 Wireless outside sensor AVS13.399
The radio transmitter must be installed inside the building.
The radio transmitter’s mounting location should be chosen such that batteries
can be easily changed.
Radio transmitter Outside sensor
2359Z30
2359Z33
2359Z54
2359Z32
2359Z59
2359Z31
2359Z53
Battery
AAA
AAA
Battery transit tab
2359Z55
Connections
The outside sensor is to be connected to the radio transmitter via a 2-core cable, the connections are interchangeable. The room unit is powered by 2 pieces 1.5 V Alkali batteries type AAA (LR03).
29/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007
Radio connection
Establishment
Testing
Dimensions and drilling plan
Make the radio connection in the vicinity of the radio module prior to mounting so that all system are within easy reach. Prerequisite for the radio connection is that all components receive power, which means that the radio module must be correctly connected to the basic unit and the batteries must be correctly installed in the room unit.
1. Press the button on the radio module for at least 8
LED
seconds until the LED on the radio module starts flashing at high frequency.
2. Press the button on the transmitter of the wireless
AAA
AAA
outside sensor for at least 8 seconds until that LED also starts flashing at high frequency.
3. The connection is established when the LED on the radio module extinguishes.
Button
4. Press the button on the transmitter of the wireless outside sensor briefly again until the LED extinguishes.
The test is made to check the quality of the radio link.
The test can be aborted by pressing the ESC button.
While the radio link can be opened on the controller, the test should be made at the
location where the room unit will be installed
1. Press button 3 on the transmitter of the wireless outside sensor for a maximum of 8 seconds until the LED starts flashing at low frequency.
2. When radio communication works, the LED on the radio module flashes briefly at 10-second intervals.
3. After the test, press the button on the transmitter of the wireless outside sensor again briefly until the LED extinguishes.
2359Z58
2359Z16
100
90
4,2
12
56
60
2359Z27
32
56
60
79,8
5,5
4
49,5
2524,5
Ø 14,1
91,6
49,7
3
6
5,5
1811M02
1811M01
30/156
Siemens Switzerland Ltd. User manual CE1U2354en HVAC Products Mounting and installation 11. May 2007