Siemens AVS75.39 Series, AVS75 Series, RVS43.345, Albatros2, AVS75.390 User Manual

...
Page 1
Infrastructure & Cities

Albatros2

Boiler controller

User Manual

RVS43.345

AVS75..

Page 2

Siemens Switzerland Ltd. Infrastructure & Cities Sector Building Technologies Division Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24 www.siemens.com/sbt

2 / 239

© 2007-2013 Siemens Switzerland Ltd. Subject to change

Page 3

Contents

1 Summary 5
1.1 Type summary 6
1.1.1 Topology 6
1.1.2 I he communication choices in detail 1
2 Safety notes 8
2.1 Notes on product liability 8
3 Mounting and installation 8
3.1 Regulations 8
3.2 Basic units RVS43.345 8
3.2.1 Connection terminals RVS43.345 10
3.3
3 3 1
Extension module AVS75.370 13
14
3.4 Extension module AVS75.39x 14
3.4.1 Connection terminals AVS75.390 17
3.4.2 Connection terminals AVS75.391 19
4 Commissioning 21
4.1 Basic unit RVS43.345 21
5 Overview of settings 22
6 The settings in detail 51
6.1 Time programs 51
6.2 Holidays 51
6.3 Heating circuits 52
6.4 Cooling circuit 70
6.5 DHW 79
6.6 Consumer circuits and swimming pool circuit 84
6.7 Swimming pool 86
6.8 Primary controller/system pump 88
6.9 Boiler 91
6.10 Cascade 103
6.11 Supplementary source 108
6.12 Solar 113
6.13 Solid fuel boiler 120
6.14 Buffer storage tank 124
6.15 DHW storage tank 133
6.16 Instantaneous DHW heater 146
6.17 Configuration 149
6.18 LPB 183
6.19 Fault 187
6.20 Maintenance/special operation 188
6.21 Configuring the extension modules 192
6.22 Input/output test 197
Page 4
6.23 State . 198
6.24 Diagnostics cascade .203
6.25 Diagnostics Heat source .204
6.26 Diagnostics consumers .205
6.27 Pump and valve kick .206
6.28 List of displays .208
6.28.1 Error codes .208
6.28.2 .210
6.28.3 Special operation code .210
7 Plant diagrams . 211
7.1 Basic diagrams .212
7.1.1 Basic diagram RVS43.345 .212
7.2 Source variants .213
7.3 Extra functions in general .214
7.4 Auxiliary functions with mixer group or extension module AVS75.3XX 220
8 Technical data .225
8.1 Basic unit RVS43.345 .225
8.2 Extension module AVS75.370 .227
8.3 Extension module AVS75.39x .229
8.4 Sensor characteristics .230
8.4.1 NTC 1 k .230
8.4.2 NTC 10 k .231
8.4.3 Pt1000 .231
Index .232
Page 5

1 Summary

The present User Manual describes the products listed in the following table and covers handling and configuration of the controls for readers ranging from end users to heating engineers.

Product No. (ASN) Series Description
RVS43.345 В Basic unit boiler
AVS75.370 В Extension module
AVS75.39x В Extension module

The following products are described in separate pieces of documentation:

QAC34 Outdoor air temperature sensor NTC 1 kΩ
QAD36 Clamp-on temperature sensor NTC 10 kΩ
QAZ36 Immersion temperature sensor NTC 10 kΩ
AVS37.x94 Operating unit with text display
AVS37.390 Operator unit basic
QAA75.611 Room unit, for wiring, with backlit display
QAA78.610 Room unit, wireless
QAA55.110 Room unit basic, wired
QAA58.110 Room unit basic, RF.
AVS16.290 Power section
AVS71.390 Radio module
AVS14.390 Radio repeater
AVS13.399 Wireless outside sensor
Page 6

1.1 Type summary

1.1.1 Topology

Page 7

1.1.2 The communication choices in detail

* Only with OZW672

  • PSTN Public switched telephone network WIAN
    • Wireless I AN
  • GSM Global System for Mobile Communications

Key

Page 8

2 Safety notes

2.1 Notes on product liability

  • The products may only be used in building services plant and applications as described above
  • Comply with all requirements specified in Section "Mounting and installation" when using the products.
  • Comply with all local regulations (for installation, etc.).
  • Do not open the units. If not observed, warranty becomes void.

3 Mounting and installation

3.1 Regulations

Electrical installation

  • Prior to installing the controller, the power supply must be turned off
  • The connections for mains and low voltage are separated
  • For wiring, the requirements of safety class II must be satisfied.
  • Sensor and power cables must not be run in the same cable duct
  • One and the same sensor cannot be connected to several inputs

3.2 Basic units RVS43.345

Engineering

  • Air circulation around the controller must be ensured, allowing the unit to emit the heat produced by it.
  • A clearance of at least 10 mm must be provided for the controller's cooling slots at the top and bottom of the housing. That space should not be accessible and no objects must be placed there. If the controller is enclosed in another (insulating) casing, a clearance of up to 100 mm must be observed around the cooling slots
  • The controller is designed conforming to the directives for safety class II mounted in compliance with these regulations.
  • Power to the controller may be supplied only when completely installed. If this is not observed, there is a risk of electric shock hazard near the terminals and through the cooling slots.
  • The controller must not be exposed to dripping water.
  • Permissible ambient temperature when mounted and when ready to operate: 0...50 °C.
  • Power cables must be clearly separated from low-voltage cables (sensors) observing a distance of at least 100 mm
Mounting location

  • BoilerControl panel
  • Housing for wall mounting
Page 9

Note: To mount the controller on a DIN rail, a

mounting clip is required!

x:

L В Н L1 B1
RVS43.345 180.7 120.7 51.7 170 110

Total height required

Connectors with min. 70 mm tongues Connectors without tongues, min. 60 mm

Page 10

PCB diagram

Terminal markings RVS43.345

Page 11

Mains voltage

Use Socket Connector type
L Live AC 230 V basic unit N∔L AGP4S.05A/109
÷ Protective earth
Ν Neutral conductor
L1 Input Phase AC 230 V burner
S3 Output burner fault
L1 Output Phase burner В AGP8S.07A/109
Ļ Protective earth
Ν Neutral conductor
T1 Phase Burner 1st stage
T2 Burner 1st stage ON
S3 Input burner fault
EX1 Multifunctional input AC230V EX1
SK1 Safety loop Q AGP8S.02E/109
SK2 Safety loop
Ν Neutral conductor R AGP8S.03A/109
Ļ Protective earth
QX3 DHW charging pump/diverting valve/
multifunctional output
Ν Neutral conductor S AGP8S.03B/109
Ļ Protective earth
Q2 / QX5 1. Heating circuit pump/
5th multifunctional output
Y1 / QX4 1. Heating circuit mixing valve opening/ Т AGP8S.04B/109
4. multifunctional output
Ν Neutral conductor
Ť Protective earth
Y2 / QX2 1. heating circuit mixing valve closing/
2. multifunctional output
FX1 Phase 1st multifunctional output В AGP8S.03G/109
QX1 Inverted signal from QX1
QX1 1. Multifunctional output /
2nd hurner stage
Page 12

Low-voltage

Use Socket Connector type
BSB Service tool OCI700 - -
LPB Service tool OCI700 - -
X60 RF module AVS71.390 - -
X50 Extension module AVS75.390 / - AVS82.490/109
AVS75.391
X30 Operator unit / boiler control panel - AVS82.491/109
DB LPB data AGP4S.02H/109
MB LPB ground
CL+ Room unit 2 data AGP4S.02A/109
CL- Room unit 2 ground b
CL+ Room unit 1 data AGP4S.02A/109
CL- Room unit 1 ground b
G+ Room unit 1 power supply 12 V AGP4S.03D/109
GX1 Power supply 5 V/12 V for active AGP4S.03H/109
sensors
H3 Digital / DC 010 V input AGP4S.02F/109
Μ Ground n
B2 Boiler sensor AGP4S.02B/109
Μ Ground f
B3 DHW sensor top AGP4S.02C/109
Μ Ground h
B9 Outside sensor AGP4S.02D/109
Μ Ground k
H1 Digital / DC 010 V input AGP4S.02F/109
Μ Ground n
B1 / BX3 Flow temperature sensor HC1/ AGP4S.02S/109
Multifunctional sensor input 3
Μ Ground р
BX1 Multifunctional sensor input 1 AGP4S.02F/109
М Ground n
BX2 Multifunctional sensor input 2 AGP4S.02F/109
Μ Ground n
Page 13

3.3 Extension module AVS75.370

  • i
  • Engineering, mounting location and mounting method as per specification for the basic module.

Electrical connections The AVS75.370 extension module is connected to terminal X50 of the basic unit using the AVS83.490/109 connecting cable. The connectors are coded. Additional modules are connected from socket X50 of the first module to socket X50 of the next module.

Up to 3 extension modules can be connected to the basic module.

Page 14
Mains voltage connections

Diagram for AVS75.370

Terminal markings AVS75.370

Page 15

Terminal markings AVS75.370

Mains voltage

Use Socket Connector type
L Mains connection Phase AC 230 V N∔L AGP4S.03E/109
burner
÷ Main connection protective ground wire
Ν Main connection Neutral conductor
QX21 Multifunctional output QX21 Т AGP8S.04B/109
Ν Neutral conductor
Ť Protective earth
QX22 Multifunctional output QX22
Ν Neutral conductor S AGP8S.03B/109
Ť Protective earth
QX23 Multifunctional output QX23
L Live conductor AC 230 V С AGP8S.03K/109
FX23 Power supply QX23
EX21 Function input EX21
Low-voltage
Use Socket Connector type
Connection to basic unit or extension module X50 AVS82.490/109
Connection to basic unit or extension module X50 AVS82.490/109
Terminal for firmware updated X61 -
CL+ Room unit 1 Data AGP4S.02A/109
CL- Room unit 1 ground b AGP4S.03D/109
G+ Room unit 1 voltage 12 V
UX21 Output UX21 (DC 010 V/PWM output) е AGP4S.03G/109
М Ground
UX22 Output UX22 (DC 010 V/PWM output)
BX21 Sensor input BX21 е AGP4S.03G/109
Μ Ground
BX22 Sensor input BX22
GX21 Power supply 5 V/12 V for active g AGP4S.04D/109
sensors
H21 Digital/DC 010 V input H21
H22 Digital/DC 010 V input H22
М Ground
No function WX21

Assignment of terminals

With parameters

  • "Function extension module 1" Operating line 7300
  • "Function extension module 2" Operating line 7375
  • "Function extension module 3" Operating line 7450

are used to define usage of the respective module.

Page 16
34 Extension module AVS75 39x

i

For planning, mounting location and mounting method, refer to the information given for the basic modules.

Terminals

plan

The AVS75.39x extension module is connected to terminal X50 of the basic unit using the AVS83.490/109 connecting cable. The connectors are coded. Additional modules are connected using connector X30 on the first module to connector X50 for the next module.

Up to 3 extension modules can be connected to the basic module

Page 17

Mains voltage connections Diagram AVS75.390

Terminal markings AVS75.390

Page 18
Terminal markings AVS75.390

Mains voltage

Use Socket Connector type
L Live AC 230 V basic unit NĻL AGP4S.03E/109
Ť Protective earth
Ν Neutral conductor
QX21 Assignment according to function Т AGP8S.04B/109
Ν Neutral conductor
Ť Protective earth
QX22 Assignment according to function
Ν Neutral conductor S AGP8S.03B/109
Ť Protective earth
QX23 Assignment according to function
Low-voltage
Use Socket Connector type
X30 Connection for additional extension module - AVS82.490/109
X50 Connection to basic unit or first extension module AVS82.490/109
BX21 Assignment according to function AGP4S.02F/109
Μ Ground n
BX22 Assignment according to function AGP4S.02F/109
Μ Ground n
H2 Digital/DC 010 V input AGP4S.02F/109
Μ Ground n
Page 19

Mains voltage connections

Diagram AVS75.391

Page 20
Terminal markings AVS75.391

Mains voltage

Use Socket Connector type
L Live AC 230 V basic unit N∔L AGP4S.03E/109
÷ Protective earth
Ν Neutral conductor
QX21 Assignment according to function Т AGP8S.04B/109
Ν Neutral conductor
÷ Protective earth
QX22 Assignment according to function
Ν Neutral conductor S AGP8S.03B/109
÷ Protective earth
QX23 Assignment according to function
L Live conductor AC 230 V С AGP8S.03K/109
FX23 Power supply QX23
EX21 EX21
Low-voltage
Use Socket Connector type
X30 Connection for additional extension module - AVS82.490/109
X50 Connection to basic unit or first extension module AVS82.490/109
BX21 Assignment according to function AGP4S.02F/109
М Ground n
BX22 Assignment according to function AGP4S.02F/109
М Ground n
H2 Digital/DC 010 V input AGP4S.02F/109
М Ground n

Assignment of terminals

With parameters

  • "Function extension module 1" Operating line 7300
  • "Function extension module 2" Operating line 7375
  • "Function extension module 3" Operating line 7450

are used to define usage of the respective module.

Page 21

4 Commissioning

Prerequisites
  • To commission the units, the following working steps must be carried out:
  • Prerequisite is the correct mounting and correct electrical installation and, in the case of wireless products, correctly working radio connections to all required auxiliary units
  • Make all plant-specific settings. Pay special attention to menu "Configuration". For that purpose, the relevant operating level is to be selected as follows:
    • Press the OK button on the room unit to switch to programming.
    • Press the Info button for at least 3 seconds and select operating level "Commissioning" with the setting knob. Then, press the OK button.
  • Make the function check as described below
  • Reset the attenuated outside temperature (Menu "Diagnostics of consumers", operating line "Outside temp attenuated" (8703))
Functional check To facilitate commissioning and fault tracing, the controller can be used to make input and output tests. With these tests, the controller's inputs and outputs can be checked. For testing, switch to menu "Input / output test" and work through all available setting lines.
Operating state The current operating state can be checked on menu "State".
Diagnostics For detailed diagnostics of the plant, check menus "Diagnostics heat generation" and "Diagnostics consumers".

4.1 Basic unit RVS43.345

Page 22
5 Overview of settings

The table displays all available settings. However, certain operating lines may be hidden, depending on the type of unit.

Kev

  • E = End user I = Commissioning E = Engineer line = Operating line
a
g line - alue
atinç leve tion
ber lser Jefau lin. lax. Init
Time pro na hei ating circuit 1 2 2
500 E Preselection Mo - Su -
Mo - Su | Mo - Fr | Sa - Su | Mo | Tu | We | Th | Fr | Sa |Su
501 E 1st phase on 6:00 00:00 24:00 hh:mm
502 E 1st phase off 22:00 00:00 24:00 hh:mm
503 E 2nd phase on 24:00 00:00 24:00 hh:mm
504 E 2nd phase off 24:00 00:00 24:00 hh:mm
505 E 3rd phase on 24:00 00:00 24:00 hh:mm
506 E 3rd phase off 24:00 00:00 24:00 hh:mm
516 E Default values No -
Time pro na he ating circuit 2
520 F Preselection Mo - Su _
Mo - Su | Mo - Fr | Sa - Su | Mo | Tu | We | Th | Fr | Sa |Su
521 E 1st phase on 6:00 00:00 24:00 hh:mm
522 E 1st phase off 22:00 00:00 24:00 hh:mm
523 E 2nd phase on 24:00 00:00 24:00 hh:mm
524 E 2nd phase off 24:00 00:00 24:00 hh:mm
525 E 3rd phase on 24:00 00:00 24:00 hh:mm
526 E 3rd phase off 24:00 00:00 24:00 hh:mm
536 E Default values No -
Time pro gram 3/HC3 1 1 1
540 Ē Preselection
Mo - Su | Mo - Fr | Sa - Su | Mo | Tu | We | Th | Fr | Sa |Su
Mo - Su -
541 Е 1st phase on 6:00 00:00 24:00 hh:mm
542 E 1st phase off 22:00 00:00 24:00 hh:mm
543 E 2nd phase on 24:00 00:00 24:00 hh:mm
544 E 2nd phase off 24:00 00:00 24:00 hh:mm
545 E 3rd phase on 24:00 00:00 24:00 hh:mm
546 E 3rd phase off 24:00 00:00 24:00 hh:mm
556 E Default values
No¦Yes
No -
Time pro ogram 4/DHW 1
560 E Preselection
Mo - Su | Mo - Fr | Sa - Su | Mo | Tu | We | Th | Fr | Sa |Su
Mo - Su -
561 E 1st phase on 6:00 00:00 24:00 hh:mm
562 E 1st phase off 22:00 00:00 24:00 hh:mm
563 Е 2nd phase on 24:00 00:00 24:00 hh:mm
564 E 2nd phase off 24:00 00:00 24:00 hh:mm
565 E 3rd phase on 24:00 00:00 24:00 hh:mm
566 E 3rd phase off 24:00 00:00 24:00 hh:mm
576 E Default values
No¦Yes
No -
Page 23
пе Ð
il g a valu
atir e | tion nlt
ber lser n n befa lin. lax. lnit
Time pr n oram л с 2 2
600 Preselection Mo Su
000 Mo - Su ! Mo - Fr ! Sa - Su ! Mo ! Tu ! We ! Th ! Fr ! Sa !Su 1010 - Su -
601 Е 1st phase on 6:00 00:00 24:00 hh:mm
602 Е 1st phase off 22:00 00:00 24:00 hh:mm
603 E 2nd phase on 24:00 00:00 24:00 hh:mm
604 E 2nd phase off 24:00 00:00 24:00 hh:mm
605 E 3rd phase on 24:00 00:00 24:00 hh:mm
606 F 3rd phase off 24.00 00.00 24.00 hh:mm
616 F No 00.00 21.00 _
No¦Yes
Holidays s heat ing circuit 1
641 E Preselection
Period 1 Period 8
1 8 -
642 E Start 01.01 31.12 tt.MM
643 Е End 01.01 31.12 tt.MM
648 E Frost prote ection -
Holidaye s haat ing circuit 2
651 E Preselection 1 8 -
050 - Period 1 Period 8 01.01 24.40 44 8 4 8 4
652 E Start 01.01 31.12
653 E 01.01 31.12 tt.MM
658 E Operating level
Frost protection | Reduced
Frost prote ction -
Holidays s heat ing circuit 3 1 1
661 E Preselection
Period 1 Period 8
1 8 -
662 E Start 01.01 31.12 tt.MM
663 E End 01.01 31.12 tt.MM
668 E Operating level
Frost protection | Reduced
Frost prote ection -
Heating circui t 1
710 E Comfort setpoint 20.0 Line 712 Line 716 °C
712 Е Reduced setpoint 16 Line 714 Line 710 °C
714 Е Frost protection setpoint 10.0 4 Line 712 °C
716 F Comfort setpoint max 35.0 Line 710 35 °C
720 E Heating curve slope 1.50 0.10 4.00 -
721 F Heating curve displacement 0.0 -4.5 4.5 °C
726 F Heating curve adaption Off 1 -
730 F Summer/winter heating limit 18 /8 30 °C
732 F 24-hour heating limit -3 /-10 10 °C
733 0 Ext'n 24-hour heating limit Yes , 10 -
740 0 o Lino 741 °C
740 0
00
741 00
742 Flow temp setpoint room stat CO
750 /1 99 %
0/
150 20 /1 100 %0
760 1 /0.5 4 °C
//0 ∣⊢ Boost neating 3 |/ U 20 -U
Page 24
Dperating line Jser level unction Default value Min. Max. Lnit
780 F Quick setback Down to r educe d set point 2 -
790 F Optimum start control max 0 0 360 min
791 F Optimum stop control max 0 0 360 min
794 F Heat up gradient 60 0 600 Min/K
800 F Reduced setp increase start - / -30 10 °C
801 F Reduced setp increase end -15 -30 Line 800 °C
810 F Frost prot plant HC pump
Off ¦ On
On -
820 F Overtemp prot pump circuit On -
830 F Mixing valve boost 5 0 50 °C
832 F Actuator type
2-position | 3-position
3-position -
833 F Switching differential 2-pos 2 0 20 °C
834 F Actuator running time 120 30 873 s
835 0 Mixing valve Xp 24 1 100 °C
836 0 Mixing valve Tn 90 10 873 s
850 I Floor curing function
Off | Functional heating | Curing heating |
Functional/curing heating | Curing/functional heating |
Manually
Off -
851 I Floor curing setp manually 25 0 95 °C
856 Ι Floor curing day current 0 0 32 -
857 Ι Floor curing days completed 0 0 32 -
861 F Excess heat draw
Off ¦ Heating mode ¦ Always
Always -
870 F With buffer
No¦Yes
Yes -
872 F With prim contr/system pump
No¦Yes
Yes -
880 F Pump speed reduction
Operating level | Characteristic
Character ristic -
882 F Pump speed min 40 0 Line 883 %
883 F Pump speed max 100 L ine 882 100 %
888 0 Curve readj at 50% speed 33 0 100 %
890 0 Flow setp readj speed ctrl
No¦Yes
Yes -
900 F Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
Protection n mode 9 -
Cooling circui t 1 I
901 E Operating mode
Off | Automatic
Automatic ; -
902 E Comfort setpoint 24.0 15 40 °C
907 E Release
24h/day | Time progr HC | Time program 5
24h / day -
908 | Flow temp setp at OT 25°C 20 8 35 °C
909 I Flow temp setp at OT 35°C 16 8 35 °C
912 1 Cooling limit at OT 20 - / 8 355 °C
913 F Lock time at end of heating 24 - / 8 100 h
918 F Summer comp start at OT 26 20 35 °C
919 F Summer comp end at OT 35 20 35 °C
920 F Summer comp setp increase 4 -/1 10 O°|
Page 25
Operating line User level Function Default value Min. Max. Unit
923 F Flow temp setp min OT 25°C 18 8 35 °C
924 F Flow temp setp min OT 35°C 18 8 35 °C
928 F Room influence 80 / 1 10 %
932 F Room temp limitation 0.5 /05 4
937 F Off , 0.0 1 -
938 F Mixing valve decrease 0 0 20 °C
939 F Actuator type
2-position | 3-position
3-position -
940 F Switching differential 2-pos 2 0 20 °C
941 F Actuator running time 120 30 873 s
942 0 12 1 100 0°C
943 0 90 10 873 s
945 F Mixing valve in heating mode
Control ! Open
Controls -
946 F Lock time dewpoint monitor 60 / 10 600 min
947 F Flow temp setp incr hydro 10 / 1 10 °C
948 F Flow setp incr start at r.h. 60 0 100 %
950 1 Flow temp diff dewpoint 2 100 °C.
962 F With buffer
No! Yes
No -
963 F With prim contr/system pump No -
969 I Optg mode changeover
None ¦ Off ¦ Automatic
Off -
Heating circui it 2
1010 E Comfort setpoint 20.0 Line 1012 Line 1016 °C
1012 Е Reduced setpoint 16 Line 1014 Line 1010 °C
1014 Е Frost protection setpoint 10.0 4 Line 1012 °C
1016 F Comfort setpoint max 35.0 Line 1010 35 °C
1020 E Heating curve slope 1.50 0.10 4.00 -
1021 F Heating curve displacement 0.0 -4.5 4.5 °C
1026 F Off -
1030 F Summer/winter beating limit 18 /8 30 °C
1030 24 hour boating limit 3 / 10 10 °C
1032 0 Ext'n 24-hour heating limit Yes -
1040 1 Flow temp setpoint min 8 8 l ine 1041 °C
1040 1 Flow temp setpoint max 80 Line 1040 95 ا
1041 F Flow temp setpoint max 65 l ine 1041 ا
1042 Swi on ratio room stat 00 / 1 0/2
1044 20 100 70
0/_
1050 1 / 0 5 100 /0
°C
1000 2 /0.5 4 °C
1070 E 20
1000 Off | To Reduced setpoint | To frost Prot setpoint 260 min
1090 U 0 300 min
1091 U 0 360
1094 Heat up gradient 60 U 600
1100 Reduced setp increase start /-30 10 С.
1101 |F Reduced setp increase end |-15 -30 Line 1100 J
Page 26
Operating line User level Function Default value Min. Max. Unit
1110 F Frost prot plant HC pump
Off ¦ On
On -
1120 F Overtemp prot pump circuit On -
1130 F Mixing valve boost 5 0 50 °C
1132 F Actuator type
2-position | 3-position
3-positior ו -
1133 F Switching differential 2-pos 2 0 20 °C
1134 F Actuator running time 120 30 873 S
1135 0 Mixing valve Xp 24 1 100 °C
1136 0 Mixing valve Tn 90 10 873 S
1150 F Floor curing function
Off | Functional heating | Curing heating |
Functional/curing heating | Curing/functional heating |
Manually
Off -
1151 F Floor curing setp manually 25 0 95
1156 1 Floor curing day current 0 0 32 -
1157 1 Floor curing days completed 0 0 32 -
1161 F Excess heat draw
Off | Heating mode | Always
Always
1170 F With buffer
No¦Yes
Yes -
1172 F With prim contr/system pump
No ¦ Yes
Yes -
1180 F Pump speed reduction
Operating level ¦ Characteristic
Characte ristic -
1182 F Pump speed min 40 0 Line 1183 %
1183 F Pump speed max 100 Line 118 32 100 %
1188 0 Curve readj at 50% speed 33 0 100 %
1190 0 Flow setp readj speed ctrl
No ¦ Yes
Yes -
1200 F Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
Protection n mode -
Heating circu it 3
1300 E Operating mode
Protection | Automatic | Reduced | Comfort
Automatio -
1310 E Comfort setpoint 20.0 Line 1312 Line 1316
1312 E Reduced setpoint 16 Line 1314 Line 1310
1314 E Frost protection setpoint 10.0 4 Line 1312
1316 F Comfort setpoint max 35.0 Line 1310 35
1320 E Heating curve slope 1.50 0.10 4.00 -
1321 F Heating curve displacement 0.0 -4.5 4.5 °C
1326 F Heating curve adaption
Off | On
Off -
1330 E Summer/winter heating limit 18 /8 30
1332 F 24-hour heating limit -3 / - 10 10
1333 0 Ext'n 24-hour heating limit
No ¦ Yes
Yes -
1340 F Flow temp setpoint min 8 8 Line 1341 °C
1341 F Flow temp setpoint max 80 Line 1340 95 °C
1342 E Flow temp setpoint room stat 65 Line 1340 Line 1341 °C
1344 0 Swi-on ratio room stat / 1 99 %
1350 F Room influence 20 |/ 1 100 %
Page 27
0
line _ alue
ating eve u og lit va
pera ser efau . c ax. it
0
1260
2 Σ 5
°C
1360 Room temp limitation 1 /0.5 4 °С
1370 J
Devue te m
20 С
С
1380 F QUICK SETDACK Down to re eaucea set point -
1390 F Optimum start control max 0 0 360 min
1391 F Optimum stop control max 0 0 360 min
1394 F Heat up gradient 60 0 600 Min/K
1400 F Reduced setp increase start / -30 10 °C
1401 F Reduced setp increase end -15 -30 Line 1400 °C
1410 F Frost prot plant HC pump On -
Off ¦ On
1420 F Overtemp prot pump circuit
Off ¦ On
On -
1430 F Mixing valve boost 5 0 50 °C
1432 F Actuator type
2-position | 3-position
3-position -
1433 F Switching differential 2-pos 2 0 20 °C
1434 F Actuator running time 120 30 873 s
1435 0 Mixing valve Xp 24 1 100 °C
1436 0 Mixing valve Tn 90 10 873 s
1450 I Floor curing function Off - -
Off | Functional heating | Curing heating |
Functional/curing heating | Curing/functional heating |
Manually
1451 I Floor curing setp manually 25 0 95 °C
1456 I Floor curing day current 0 0 32 -
1457 I Floor curing days completed 0 0 32 -
1461 F Excess heat draw
Off | Heating mode | Always
Always
1470 F With buffer
No¦Yes
Yes -
1472 F With prim contr/system pump Yes -
1480 F Pump speed reduction Character istic -
1482 F Pump speed min 40 0 Line 1483 %
1483 F Pump speed max 100 Line 1482 100 %
1488 0 Curve readj at 50% speed 33 0 100 %
1490 0 Flow setp readj speed ctrl Yes I -
1500 F Optg mode changeover Protection mode -
Domest ic hot water 1 1
1601 0 Optg mode selection Eco None -
None | Instantaneous water heater | DHW storage tank |
1610 F 55 l ine 1612 B7 1614 OEM ംറ
1612 F Reduced setpoint 40 8 Line 1610 °C
1614 0 Nominal setopint may 65 8 80 °C
1620 I Release Time prog rams HCs _
| 24h/day | Time programs HCs | Time program 4/DHW pine piog -
1630 I Charging priority
Absolute | Shifting | None | MC shifting, PC absolute
MC shiftin g, PC absolute -
1640 F Legionella function Fixed wee kday -
Page 28
Operating line User level Function Default value Min. Max. Unit
Off | Periodically | Fixed weekday
1641 F Legionella funct periodically 3 1 7 Days
1642 F Legionella funct weekday
Monday | Tuesday | Wednesday | Thursday | Friday |
Saturday | Sunday
Monday
1644 F Legionella funct time / 00:00 23:50 hh:mm
1645 F Legionella funct setpoint 65 55 95 °C
1646 F Legionella funct duration 30 / 10 360 min
1647 F Legionella funct circ pump
Off¦On
On -
1648 F Legio funct circ temp diff / O 20 °C
1660 F Circulating pump release
Time program 3/HC3 | DHW release | Time program
4/DHW | Time program 5
DHW relea ISE -
1661 F Circulating pump cycling
Off ¦ On
On -
1663 F Circulation setpoint 45 8 80 °C
1680 F Optg mode changeover
None ¦ Off ¦ On
Off -
Consum er cir cuit 1
1859 I Flow temp setp cons request 70 8 120 °C
1860 F Frost prot plant VK pump
Off ¦ On
On -
1874 0 DHW charging priority
No¦Yes
Yes -
1875 F Excess heat draw
Off ¦ On
On -
1878 F With buffer
No¦Yes
Yes -
1880 F With prim contr/system pump
No¦Yes
Yes -
Consum er cir cuit 2 -1
1909 I Flow temp setp cons request 70 8 120 °C
1910 F Frost prot plant VK pump
Off ¦ On
On -
1924 0 DHW charging priority
No¦Yes
Yes -
1925 F Excess heat draw
Off ¦ On
On -
1928 F With buffer
No¦Yes
Yes -
1930 F With prim contr/system pump
No¦Yes
Yes -
Swimmi ng po ol circuit
1959 I Flow temp setpoint 70 8 120 °C
1960 F Frost prot plant pool pump
Off ¦ On
Off -
1974 0 DHW charging priority
No¦Yes
Yes -
1975 F Excess heat draw
Off ¦ On
On -
1978 F With buffer
No¦Yes
Yes -
1980 F With prim contr/system pump
No¦Yes
Yes -
Page 29
Operating line User level Function Default value Min. Max. Unit
Swimmi ng po ol I. 1 1
2055 F Setpoint solar heating 26 8 80 °C
2056 F Setpoint source heating 22 8 80 °C
2065 F Charging priority solar
Priority 1 | Priority 2 | Priority 3
priority 3 -
2070 0 Swimming pool temp max 32 8 95 °C
2080 F With solar integration
No | Yes
Yes -
Primary contr /system pump 1
2110 0 Flow temp setpoint min 8 8 95 °C
2111 0 Flow temp setpoint max 80 8 95 °C
2112 0 Flow temp setp cooling min 8 8 20 °C
2120 F Frost prot plant syst pump
Off ¦ On
On -
2130 0 Mixing valve boost 2 0 50 °C
2131 0 Mixing valve decrease 0 0 20 °C
2132 0 Actuator type
2-position | 3-position
3-position -
2133 0 Switching differential 2-pos 2 0 20 °C
2134 0 Actuator running time 120 30 873 s
2135 0 Mixing valve Xp 24 1 100 °C
2136 0 Mixing valve Tn 90 10 873 s
2145 0 DHW charging priority
No ¦ Yes
Yes -
2150 I Primary contr/system pump
Before buffer ¦ After buffer
After buffer ſ -
Boiler
2200 0 Operating mode
Continuous operation | Automatic | Auto, extended running
time
Automatic -
2203 F Release below outside temp /-50 50 °C
2204 F Release above outside temp /-50 50 °C
2205 F With Economy mode
Off | On DHW | On
Off 1 -
2208 F Full charging buffer Off -
2210 F Setpoint min 40 BZ 2211 OEM Setpoint
manual control
°C
2211 0 Setpoint min OEM 40 8 95 °C
2212 F Setpoint max 80 Setp man contr BZ 2213 OEM °C
2213 0 Setpoint max OEM 85 8 120 °C
2220 0 Release integral stage2/mod 50 0 500 °C min
2221 0 Reset integral stage2/mod 10 0 500 °C min
2232 0 Damper actuator run time 60 7.5 480 s
2233 0 Modulating Xp 20 1 200 °C
2234 0 Modulating Tn 150 10 873 S
2235 0 Modulating Tv 4.5 0 30 S
2240 0 Switching differential boiler 8 0 20 °C
2241 0 Burner running time min 4 0 20 min
2250 0 Pump overrun time 5 0 20 min
2260 0 Prot boil startup consumers
Off | On
On -
Page 30
Operating line Function Default value Min. Max. Unit
2261 O Prot boil startup boil pump
Off¦On
On -
2262 O Optimum start control
Off ¦ On
Off -
2270 F Return setpoint min 8 8 95
2271 O Return setpoint min OEM 8 8 95 °C
2272 O Return influence consumers
Off | On
On -
2282 O Actuator running time 120 30 873 s
2283 O Mixing valve Xp 24 1 100 °C
2284 O Mixing valve Tn 90 10 873 s
2285 O Mixing valve Tv 10 0 60 s
2290 O Switching diff bypass pump 6 0 20 °C
2291 O Control bypass pump
Parallel burner operation | Return temp
Return te mperature -
2300 O Frost prot plant boiler pump Off -
2310 O Limit thermostat function On -
2316 O Temp differential max - 0 80 °C
2317 O Temp differential nominal 10 0 80 °C
2320 O Pump modulation
None | Demand | Boiler setpoint | Temp differential
nominal | Burner output
Burner output -
2322 F Pump speed min 40 0 100 %
2323 F Pump speed max 100 0 100 %
2330 F Output nominal 50 0 1000 kW
2331 F Output basic stage 30 0 1000 kW
Cascade
3510 O Lead strategy
Late on, early off | Late on, late off | Early on, late off
Late on, I ate off -
3511 O Output band min 40 0 100 %
3512 O Output band max 90 0 100 %
3530 O Release integral source seq 50 0 500 °C min
3531 O Reset integral source seq 20 0 500 °C min
3532 F Restart lock 300 0 1800 s
3533 F Switch on delay 5 0 120 min
3534 O Forced time basic stage 0 0 1200 s
3540 F Auto source seq ch'over 500 / 10 990 h
3541 F Auto source seq exclusion
None | First | Last | First and last
None -
3544 F Leading source
Heat source 1 | Heat source 2 | | Heat source 16
Heat sour rce 1 -
3550 O Prot startup cascade pump Off -
3560 F Return setpoint min 8 8 95 °C
3561 O Return setpoint min OEM 8 8 95 °C
3562 O Return influence consumers On -
3570 F Actuator running time 120 30 873 s
3571 O Mixing valve Xp 24 1 100 °C
3572 O Mixing valve Tn 90 10 873 s
3590 O Temp differential min 4 /0 20 °C
Page 31
Operating line User level Function Default value Min. Max. Unit
Supplet 0 0 10 ° C
3090 0 10
3691 |/1 100 %
3692 F Locked | Substitute | Complement | Instantly Substitute ; -
3694 F OT limit with DHW charging
Ignore | Note
Note
3700 F Release below outside temp -50 50 °C
3701 F Release above outside temp -50 50 °C
3702 F With Economy mode
Off | On DHW | On
Off -
3703 F Full charging buffer
Off ¦ On
Off -
3705 F Overrun time 5 0 120 min
3710 F Setpoint min /0 80 °C
3720 F Switching integral 50 0 500 °C*min
3722 F Switching diff off 15 0 20 °C
3723 F Locking time 5 0 120 min
3725 F Control sensor Common flow temp · -
3750 F Source type
Other | Solid fuel boiler | Heat pump | Oil/gas boiler
Other -
3755 F Delay lockout position 1 1 40 min
Solar
3810 F Temp diff on 8 0 40 °C
3811 F Temp diff off 4 0 40 °C
3812 F Charg temp min DHW st tank 20 /8 95 °C
3813 0 Temp diff on buffer / 0 40 °C
3814 0 Temp diff off buffer / 0 40 °C
3815 F Charging temp min buffer 20 /8 95 °C
3816 0 Temp diff on swi pool / 0 40 °C
3817 0 Temp diff off swi pool / 0 40 °C
3818 F Charging temp min swi pool 20 / 8 95 °C
3822 F Charging prio storage tank
None | DHW storage tank | Buffer storage tank
DHW stor age tank -
3825 F Charging time relative prio / 2 60 min
3826 F Waiting time relative prio 5 1 40 min
3827 F Waiting time parallel op / 0 40 min
3828 F Delay secondary pump 60 0 600 s
3830 F Collector start function / 5 60 min
3831 F Min run time collector pump 20 5 120 s
3832 0 Collector start function on 07:00 00:00 23:50 hh:mm
3833 0 Collector start function off 19:00 00:00 23:50 hh:mm
3834 F Collector start funct grad / 1 20 min/°C
3835 F Min collector temp start fct 5 10 100
3840 F Collector frost protection /-20 5 °C
3850 F Collector overtemp prot /30 350 °C
3860 F Evaporation heat carrier /60 350 °C
3862 F To own co ollector pumps -
3870 F Pump speed min 40 0 Line 3871 %
1. ····· •
Page 32
ω
g lin alue
ratin leve tion nit
Oper User Defa Min. Max Unit
3871 F Pump speed max 100 Line 3870 100 %
3880 F Antifreeze
None ¦ Ethylene glycol ¦ Propylene glycol ¦ Ethyl and
None -
2004 - 20 4 100 0/
3881 30 1 100 %
3004 Pullip capacity 10 1500
5000 None | With input H1 | With input H3 | With input H31
Module 1 | With input H31 Module 2 | With input H31
Module 3 | With input H32 Module 1 | With input H32
Module 2 | With input H32 Module 3 | With input H33
None
3887 F Pulse unit yield
None ¦ kWh ¦ Liter
None -
3888 F Pulse value yield numer 10 1 1000 -
3889 F Pulse value yield denom 10 1 1000 -
3891 F Flow measurement yield
None | With input H1 | With input H31 Module 1 | With
input H31 Module 2 | With input H31 Module 3 | With
input H31 Module 1 | With input H31 Module 2 | With
input H31 Module 3 | With input H32 Module 1 | With
input H32 Module 2 | With input H32 Module 3 | With
input H3
None -
3896 F Readj solar flow sensor 0 -20 20 °C
3897 F Readj solar return sensor 0 -20 20 °C
Solid fue el boil er
4102 F Locks other heat sources
Off ¦ On
On -
4103 F Charg prio DHW stor tank
Off¦On
Off -
4110 F Setpoint min 40 8 120 °C
4114 F Temp differential min 4 0 40 °C
4130 F Temp diff on 4 1 40 °C
4134 F Connection DHW stor tank
With B3 ¦ With B31 ¦ With B3 and B31
With B3 -
4135 F Boiler temp setp DHW charg
Storage tank temp | Storage tank setpoint | Boiler temp
setpoint min
Storage tar nk temperature -
4136 F DHW charging with Q3
No | Yes
Yes -
4137 F Connection buffer
With B4 ¦ With B42/B41 ¦ With B4 and B42/B41
With B4 -
4138 F Boil temp setp buffer charg
Storage tank temp | Storage tank setpoint | Boiler temp
setpoint min
Storage tar nk temperature -
4140 F Pump overrun time 20 0 120 min
4141 0 Excess heat discharge 90 60 140 °C
4153 F Return setpoint min 8 8 95 °C
4154 0 Return setpoint min OEM 8 8 95 °C
4158 F Flow influence return ctrl
Off | On
Off -
4163 Actuator rupping time 100 30 072
- 0 120 30 013 S
4164 0 Mixing valve Xp 24 1 100 °C
Page 33
(D)
g line - alue
atinç leve u lit va
Dpera Jser Defau , ui Мах. , Pit
4170 0 Frost prot plant boiler pump Off 2 -
4190 F Residual heat fct dur max 5 60 min
4192 F Residual heat fct trigg
Once / Several times
Once -
4201 F Pump speed min 40 0 Line 4202 %
4202 F Pump speed max 100 Line 4201 100 %
Buffer s storage e tank İ
4720 F Auto generation lock
None ¦ With B4 ¦ With B4 and B42/B41
With B4 -
4721 0 Auto heat gen lock SD 2 0 20 °C
4722 F Temp diff buffer/HC -5 -20 20 °C
4723 0 Temp diff buffer/CC 0 -20 20 °C
4724 0 Min st tank temp heat mode / 8 95 °C
4726 0 Max st tank temp cool mode 25 / 10 40 °C
4728 F Rel temp diff buffer/HC 0 -50 50 %
4739 F Stratification protection
Off | Always | With solid fuel boiler
Off -
4740 0 Strat prot temp diff max 5 0 20 °C
4743 0 Strat prot anticipation time 60 0 240 S
4744 0 Strat protection Tn 120 10 200 S
4746 0 DHW prot combi st tank Off -
4749 F Min charging setpoint solar 8 8 94 °C
4750 F Charging temp max 80 8 95 °C
4751 0 Storage tank temp max 90 8 95 °C
4755 F Recooling temp 70 8 95 °C
4756 F Recooling DHW/HCs Off -
4757 F Recooling collector
Off | Summer | Always
Off -
4783 F With solar integration
No¦Yes
No -
4790 F Temp diff on return div 10 0 40 °C
4791 F Temp diff off return div 5 0 40 °C
4795 F Compar temp return div
B4 | B41 | B42
B42 -
4796 F Optg action return diversion
Temp decrease ¦ Temp increase
Temper ature boost -
4800 F Partial charging setpoint /8 95 °C
4810 F Full charging Off | Current heat request | Buffer setpoint Buffer s etpoint -
4811 F Full charge temperature min. 8 8 80 °C
4813 F Full charging
With B4 ¦ With B42/B41
With B4 2/B41 -
DHW s torage tank
5010 0 Charging
Once/day | Several times/day
Several times/day
5020 F Flow setpoint boost 16 0 30 °C
5021 F Transfer boost 8 0 30 °C
Page 34
Operating line User level Function Default value Min. Max. Unit
5022 F Type of charging
Recharging | Full charging | Full charging legio | Full charg
1st time day | Full charg 1st time legio
Full charge 9 -
5024 0 Switching diff 5 0 20 °C
5030 0 Charging time limitation 150 / 10 600 min
5040 0 Discharging protection
Off | Always | Automatically
Automatica ally -
5050 F Charging temp max 80 8 BZ 5051 OEM °C
5051 0 Storage tank temp max 90 8 95 °C
5055 F Recooling temp 70 8 95 °C
5056 F Recooling heat gen/HCs
Off ¦ On
Off -
5057 F Recooling collector
Off | Summer | Always
Off -
5060 F El imm heater optg mode
Substitute | Summer | Always
Substitute -
5061 F El immersion heater release
24h/day | DHW release | Time program 4/DHW
DHW relea ISE -
5062 F El immersion heater control
External thermostat ¦ DHW sensor
DHW sens or -
5063 F El immersion heater control For Eco mode
On ¦ Off
On -
5070 0 Automatic push
Off¦On
On -
5071 0 Charging prio time push 0 0 120 min
5085 F Excess heat draw
Off | On
On -
5090 F With buffer
No¦Yes
No -
5092 F With prim contr/system pump
No¦Yes
No -
5093 F With solar integration
No¦Yes
Yes -
5101 F Pump speed min 40 0 100 %
5102 F Pump speed max 100 0 100 %
5120 0 Mixing valve boost 0 0 50 °C
5124 F Actuator running time 120 30 873 S
5125 0 Mixing valve Xp 24 1 100 °C
5126 0 Mixing valve Tn 90 10 873 S
5130 F Transfer strategy
Off | Always | DHW release
Always -
5131 F Comparison temp transfer
With B3 | With B31 | With B3 and B31
With B3 -
5140 F Intermediate circuit boost 2 0 10 °C
5142 0 Flow setp compensation delay 30 0 60 S
5143 0 Flow setp compensation Xp 24 1 100 °C
5144 0 Flow setp compensation Tn 120 10 873 S
5145 0 Flow setp compensation Tv 0 0 60 S
5146 F No -
5148 F Min start temp diff Q33 -5 -20 20 J ° C
5149 F Start delay Q33 10 0 255 S
5160 F Off | With charging | With charging and duration vvith charg ing and duration -
Page 35
perating line ser level unction efault value Ē ax. nit
0
5165
F Off Σ 2 -
5166 F Restrat temp min 8 8 95 °C
5167 F Restrat temp diff min 8 0 40
Instanta neous s water heater 0 10 U
5406 F Min setp diff to tank temp 4 0 20 °C
5420 F Flow setpoint boost 6 0 30 °C
5429 0 Switching diff 1 0 20 °C
5455 F Setp readi cons 40°C 0 -20 20 °C
5456 F Setp readi cons 60°C 0 -20 20 °C
5460 F Setpoint keep hot 50 10 60 °C
5461 F Readi setp keep hot 40°C 4 -20 20 °C
5462 F Readi setp keep hot 60°C 4 -20 20 °C
5464 F Keep hot release
None | 24h/day | DHW release | Time program 3/HC3 |
Time program 4/DHW | Time program 5
24h / day -
5470 F Keep hot time wo heating 2 0 1440 min
5471 F Keep hot time with heating 0 0 30 min
5472 F Pump overrun time keep hot 0 0 255 min
5473 F Pump overrun time keep hot 20 0 59 S
5476 F Keep hot periodically 1 1 255 Min.
5477 F Min keep hot time 0 0 255 S
5478 F Keep hot in heating mode
Off | On
Off -
5489 F Overrun via inst WH
No¦Yes
No -
Configu ration
5710 I Heating circuit 1
Off | On
On -
5711 I Cooling circuit 1
Off | 4-pipe system | 2-pipe system
Off -
5712 I Use of mixing valve 1 None | Heating | Cooling | Heating and Cooling Heating an d cooling
5715 I Heating circuit 2
Off | On
Off -
5721 I Heating circuit 3
Off¦On
Off
5730 I DHW sensor B3
Sensor | Thermostat
Sensor -
5731 I DHW ctrl elem Q3
None | Charging pump | Diverting valve
charging p ump -
5734 F Basic position DHW div valve
Last demand | Heating circuit | DHW
Heating cir cuit.
5736 I DHW separate circuit
Off | On
Off -
5750 I Consumer circuit 1
Heating ¦ 4-pipe system cooling ¦
2-pipe system cooling
Heating -
5751 I Consumer circuit 2
Heating ¦ 4-pipe system cooling ¦
2-pipe system cooling
Heating -
5770 I Source type
1-stage ¦ 2-stage ¦ Modulating 3-position ¦ Modulating UX ¦
Without boiler sensor
1-stage -
5772 0 Burner prerun time / 0 255 s
Page 36
erating line er level r ction fault value - × It
ð n
N
e M M Ъ.
5840 I Solar controlling element
Charging pump | Diverting valve
Charging p ump
5841 I External solar exchanger
Jointly | DHW storage tank | Buffer storage tank
Jointly
5890 1 Relay output QX1
None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Bypass pump Q12 ¦ Alarm output K10 ¦ 2nd pump spee
Q23 ¦ Heat circuit pump HC3 Q20 ¦ Cons circuit pump Y
fuel boiler pump Q10 ¦ Time program 5 K13 ¦ Buffer retu
Solar ctrl elem swi pool K18 ¦ Collector pump 2 Q16 ¦ S
K30 ¦ Cascade pump Q25 ¦ St tank transfer pump Q11 ¦
request K27 ¦ Refrigeration request K28 ¦ Air dehumidifi
Heat circuit pump HC2 Q6 ¦ DHW ctrl elem Q3 ¦ Suppl
Collector pump
d HC1 Q21 ¦ 2i
/K2 Q18 ¦ Syst
urn valve Y15 ¦
wimming pool j
DHW mixing p
ier K29 ¦ Diverti
source control l
0 Q5 | Cons circuit pur
nd pump speed HC2 0
em pump Q14 | Heat
Solar pump ext exch
pump Q19 | Flue gas
pump Q35 | DHW inte
ng valve cooling Y21
K32 | Excess heat dis
np VK1 Q15¦ Boiler
Q22 ¦ 2nd pump spe
gen shutoff valve Y4
K9 ¦ Solar ctrl elem I
relay K17 ¦ Assisted
rm circ pump Q33 ¦ I
¦ Heat circuit pump I
charge K11
pump Q1 |
ed HC3
I | Solid
buffer K8 |
firing fan
Heat
HC1 Q2 |
5891 I Relay output QX2
Ditto 5890
None -
5892 Ι Relay output QX3
Ditto 5890
DHW contr olling element Q3 3 -
5894 I Relay output QX4
Ditto 5890
None -
5895 I Relay output QX5
Ditto 5890
None -
5930 I Sensor input BX1
None | DHW sensor B31 | Collector sensor B6 | Return
sensor B41 | Flue gas temp sensor B8 | Common flow s
B36 | Buffer sensor B42 | Common return sensor B73 |
Collector sensor 2 B61 | Solar flow sensor B63 | Solar r
Return sensor B7 | DHW circulation sensor B39 | Buffer sensor B4 | Buf
n flow sensor B10 | Solid fuel boiler sensor B22 | DHW charging sensor
B73 | Cascade return sensor B70 | Swimming pool sensor B13 |
Solar return concert B64 | Solid fuel beil set core B72
5931 I Sensor input BX2
Ditto 5930
None -
5932 I Sensor input BX3
Ditto 5930
None
5950 I Function input H1
Optg mode change HCs+DHW ¦ Optg mode changeove
HC1 ¦ Optg mode changeover HC2 ¦ Optg mode chang
Consumer request VK1 ¦ Consumer request VK2 ¦ Rele
pool solar ¦ Operating level DHW ¦ Operating level HC1
HC1 ¦ Room thermostat HC2 ¦ Room thermostat HC3 ¦
Flow temp setp incr hygro ¦ Boiler return thermostat ¦ St
measurement Hz ¦ Consumer request VK1 10V ¦ Consu
humidity 10V ¦ Room temp 10V ¦ Flow measurement 100
er DHW ¦ Optg
eover HC3 ¦ He
ease swi pool so
¦ Operating lev
Circulating pun
tatus info suppl
umer request V
DV ¦ Temp meas
mode changeover HC
eat generation lock | E
purce heat | Excess h
rel HC2 | Operating le
np thermostat | Pulse
source | Charg prio E
K2 10V | Pressure me
surement 10V
Es | Optg mode chan
Fror/alarm message
eat discharge | Rele
wel HC3 | Room the
count | Dewpoint mo
DHW sol fuel boil | Fl
easurement 10V | Re
geover
¦
ase swi
rmostat
onitor ¦
ow
el room
5951 I Contact type H1
NC ¦ NO
Make conta act (NO) -
5953 1 Input value 1 H1 0 0 1000 -
5954 1 Function value 1 H1 0 -100 500 -
5955 1 Input value 2 H1 10 0 1000 -
5956 1 Function value 2 H1 100 -100 500 -
5957 I Temperature sensor H1
None | Solar flow sensor B63 | Solar return sensor B64
None -
5960 I Function input H3
Ditto 5950
Optg mode change HCs+DF łW -
5961 I Contact type H3 Make conta act (NO) -
5963 I Input value 1 H3 0 0 1000 -
5964 I Function value 1 H3 0 -100 500 -
5965 Ι Input value 2 H3 10 0 1000 -
5966 I Function value 2 H3 100 -100 500 -
5967 I Temperature sensor H3
None ! Solar flow sensor B63 ! Solar return sensor B64
None -
Page 37
line alue
erating er leve ction ault ve j
Ope Use - Б
- Щ
Def Min May Unit
5980 F Function input EX1
None ¦ Counter 1st burner stage ¦ Heat gen lock ¦
Error/alarm message ¦ Excess heat discharge
Counter 1s t burner stage -
5981 F Cont type input EX1
NC ¦ NO
Make conta act (NO) -
5986 F SLT error message input L1
Off ¦ Always ¦ Automatically
Automatica lly -
6014 I Function mixing group 1
Multifunctional | Heating circuit 1 | Return temp controller |
Primary contr/system pump | DHW primary controller |
Instantaneous water heater | Return controller cascade |
Cooling circuit 1 | Heating circ/cooling circ 1 | Ret temp
contr sol fuel boil
Heating cire cuit 1 -
6097 F Sensor type collector
NTC ¦ Pt 1000
NTC -
6098 F Readjustm collector sensor 0 -20 20 °C
6099 F Readjustm coll sensor 2 0 -20 20 °C
6100 F Readjustm outside sensor 0 -3.0 3.0 °C
6101 F Sensor type flue gas temp
NTC | Pt 1000
NTC
6102 F Readjustm flue gas sensor 0 -20 20 °C
6110 F Time constant building 10 0 50 h
6116 0 Time constant setp compens 0 0 14 min
6117 0 Central setp compensation 10 / 1 100 °C
6118 0 Setpoint drop delay 10 / 1 200 K/min
6120 F Frost protection plant
Off | On
On -
6135 F Air dehumidifier
Off¦On
Off
6136 F Release air dehumidifier
24h/day ¦ Time progr HC ¦ Time program 5
24h / day
6137 F Air dehumidifier r.h. on 55 0 100 %
6138 F Air dehumidifier r.h. SD 5 2 50 %
6140 0 Water pressure max 3 /0.0 10.0 bar
6141 0 Water pressure min 0.8 /0.0 10.0 bar
6142 0 Water pressure critical min 0.5 / 0.0 10.0 bar
6148 F Static press supervision 1
None | With input H1 | With input H2 module 1 | With input
H2 module 2 | With input H2 module 3 | With input H21
module 1 | With input H21 module 2 | With input H21
module 3 | With input H22 module 1 | With input H22
module 2 | With input H22 module 3 | With input H3
None -
6150 0 Water pressure 2 max 3 / 0.0 10.0 bar
6151 0 Water pressure 2 min 0.8 / 0.0 10.0 bar
6152 0 Water press 2 critical min 0.5 / 0.0 10.0 bar
6154 F Static press supervision 2
None | With input H1 | With input H2 module 1 | With input
H2 module 2 | With input H2 module 3 | With input H21
module 1 | With input H21 module 2 | With input H21
module 3 | With input H22 module 1 | With input H22
module 2 | With input H22 module 3 | With input H3
None -
6180 0 Water pressure 3 max 3 / 0.0 10.0 bar
6181 0 Water pressure 3 min 0.8 / 0.0 10.0 bar
6182 0 Water press 3 critical min 0.5 / 0.0 10.0 bar
Page 38
Operating line User level Function Default value Min. Max. Unit
6184 F Static press supervision 3
None | With input H1 | With input H2 module 1 | With input
H2 module 2 | With input H2 module 3 | With input H21
module 1 | With input H21 module 2 | With input H21
module 3 | With input H22 module 1 | With input H22
module 2 | With input H22 module 3 | With input H3
None -
6200 I Save sensors
No¦Yes
No -
6204 F Save parameters No
6205 F Reset to default parameters No -
6212 1 Check no. heat source 1 - 0 199999 _
6213 1 Check no. heat source 2 - 0 199999 -
6215 1 Check no. storage tank - 0 199999 -
6217 1 Check no. heating circuits - 0 199999 -
6220 I Software version - 0 99.9 -
6222 0 Device hours run 0 0 65535 h
6270 F Excess heat discharge temp 95 20 350 °C
6271 F SD excess heat discharge 4 0 50 °C
6272 F Excess heat discharge sens
None | DHW sensor B31 | Collector sensor B6 | Return
sensor B7 | Buffer sensor B4 | Buffer sensor B41 | Flue
gas temp sensor B8 | Common flow sensor B10 | Solid
fuel boiler sensor B22 | Buffer sensor B42 | Common
return sensor B73 | Cascade return sensor B70 |
Swimming pool sensor B13 | Collector sensor 2 B61 |
Solid fuel boil ret sens B72 | Boiler sensor B2 | DHW
sensor B3
None -
6273 F Excess heat dischar dur min 0 0 42 min
6345 0 Code commissioning 0 0 99999 -
6346 0 Code engineer 0 0 99999 -
6358 F Voltage output GX1
5 Volt | 12 Volt
5 Volt -
LPB sys stem
6600 I Device address 1 0 16 -
6601 F Segment address 0 0 14
6604 F Bus power supply function
Off | Automatically
Automatica ally -
6605 F Bus power supply state
Off ¦ On
On -
6610 0 Display system messages
No¦Yes
Yes
6612 0 Alarm delay / 2 60 min
6620 F Action changeover functions
Segment | System
System -
6621 F Summer changeover
Locally¦ Centrally
Locally -
6623 F Optg mode changeover
Locally¦ Centrally
Centrally
6624 Manual source lock
Local ¦ Segment
Locally
6625 F DHW assignment
Local HCs ¦ All HCs in segment ¦ All HCs in system
All HCs in system -
Page 39
perating line lser level unction befault value lax. Init
6627 F Locally 2 2
6630 F Automatica ally
6631 F Ext source in Eco mode On
6632 F Note OT limit ext source No
6640 I Clock mode
Autonomously | Slave without remote setting | Slave with
remote setting | Master
Autonomo usly -
6650 F Outside temp source 0 0 239 -
Fault
6710 I Reset alarm relay No -
6740 F Flow temp 1 alarm / 10 240 min
6741 F Flow temp 2 alarm /10 240 min
6742 F Flow temp 3 alarm /10 240 min
6743 F Boiler temp alarm /10 240 min
6745 F DHW charging alarm /1 48 h
6746 F Flow temp cooling 1 alarm / 10 240 min
6800 F _ , 10
6801 F Fror code 1 _ 0 255 _
6802 - 0 200 -
6803 Fror code 2 - ٥ 255
6904 - U 200 -
6805 First code 3 - ٥ 255
0000 - U 200 -
6907 - 0 255
0007 - U 200 -
8080 - 0 255
0809 - 0 200 -
6810 - 055
6811 - 0 255 -
6812 - 0 055
6813 - 0 255 -
6814 - 0 055
6815 - 0 255 -
6816 - 0 055
6817 - 0 255 -
6818 History 10 -
6819 F Error code 10 - 0 255 -
6820 0 Reset history
No¦Yes
NO -
Service /speci al operation
7040 F Burner hours interval / 10 / 100 10000 h
7041 F Burn hrs since maintenance 0 0 10000 h
7042 F Burner start interval /60/100 65535 -
7043 F Burn starts since maint 0 0 65535 -
7044 F Maintenance interval / 1 240 months
7045 F Time since maintenance 0 0 240 months
7053 F Flue gas temp limit / 0 350 °C
Page 40
۵
glin alue
ating leve tion ult <
Oper User Defa Min. Max. Unit
7054 F
Delay flue gas message
0 0 120 min
7056 F DHW scalding risk 70 40 80 °C
7119 F Economy function
Locked | Released
Locked -
7120 Е Economy mode
Off ¦ On
Off -
7130 Е Chimney sweep function
Off | On
Off -
7140 Е Manual control
Off | On
Off -
7150 I Simulation outside temp -50.0 50 °C
7170 I Telephone customer service -
Config e extens ion module
Module 1
7300 F Function extension module 1
Primary contr/system pump | DHW primary controller | Instantaneous water heater | Return temp contr cascade | Cooling circuit 1 | Heating circ/cooling circ 1 | Solid fuel boiler
7301 F Relay output QX21 module 1
None | Circulating pump Q4 | El imm heater DHW K6 | Collector pump Q5 | Cons circuit pump VK1 Q15 | Boiler pump Q1 |
Bypass pump Q12 | Alarm output K10 | 2nd pump speed HC1 Q21 | 2nd pump speed HC2 Q22 | 2nd pump speed HC3
Q23 | Heat circuit pump HC3 Q20 | Cons circuit pump VK2 Q18 | System pump Q14 | Heat gen shutoff valve Y4 | Solid
fuel boiler pump Q10 | Time program 5 K13 | Buffer return valve Y15 | Solar pump ext exch K9 | Solar ctrl elem buffer K8 |
Solar ctrl elem swi pool K18 | Collector pump 2 Q16 | Swimming pool pump Q19 | Flue gas relay K17 | Assisted firing fan
K30 | Cascade pump Q25 | St tank transfer pump Q11 | DHW mixing pump Q35 | DHW interm circ pump Q33 | Heat
request K27 | Refrigeration request K28 | Air dehumidifier K29 | Div valve HC/CC1 Y21 | Heat circuit pump HC1 Q2 | Heat
circuit pump HC2 Q6 | DHW ctrl elem Q3 | Instant WH ctrl elem Q34 | Suppl source control K32 | Overtemperature
protection K11
7302 F Relay output QX22 module 1
Ditto 7301
7303 F Relay output QX23 module 1
Ditto 7301
7307 F Sensor input BX21 module 1
None | DHW sensor B31 | Collector sensor B6 | Return
sensor B41 | Flue gas temp sensor B8 | Common flow s
B36 | Buffer sensor B42 | Common return sensor B73 |
Collector sensor 2 B61 | Solar flow sensor B63 | Solar r
B72
sensor B7 ¦ Di
sensor B10 ¦ So
Cascade return
eturn sensor B
HW circulation sensor
olid fuel boiler sensor
n sensor B70 ¦ Swimr
64 ¦ DHW outlet sens
B39 ¦ Buffer sensor
B22 ¦ DHW chargin
ning pool sensor B1
or B38 ¦ Solid fuel b
- B4 ¦ Buffer
g sensor
3 ¦
oil ret sens
7308 F Sensor input BX22 module 1
Ditto 7307
7311 F Ditto 7307 Function input H2 module 1 None | Optg mode change HCs+DHW | Optg mode changeover DHW | Optg mode changeover HCs | Optg mode changeover HC1 | Optg mode changeover HC2 | Optg mode changeover HC3 | Heat gen lock | Error/alarm message | Consumer request VK1 | Consumer request VK2 | Release swi pool source heat | Excess heat discharge | Release swi pool solar | Operating level DHW | Operating level HC1 | Operating level HC2 | Operating level HC2 | Release swi pool solar | Operating level DHW | Operating level HC1 | Operating level HC2 | Operating level HC3 | Room thermostat HC1 | Room thermostat HC2 | Room thermostat HC3 | DHW flow switch | Circ'pump thermostat | Dewpoint monitor | Flow temp setp incr hygro | Boiler return thermostat | Status info suppl source | Charg prio DHW sol fuel boil | Consumer request VK1 10V | Consumer request VK2 10V | Pressure measurement 10V | Rel room humidity 10V | Room temp 10V | Flow measurement 10V |
7312 F Contact type H2 module 1
NC ¦ NO
NO
7314 F Voltage value 1 H2 module 1 0 0 10 V
7315 F Funct value 1 H2 module 1 0 -100 500
7316 F Voltage value 2 H2 module 1 10 0 10 V
7317 F Funct value 2 H2 module 1 100 -100 500
7318 F Temp sensor H2 module 1
None | Solar flow sensor B63 | Solar return sensor B64
None
Page 41
berating line ser level Inction sfault value c X ıit
ŏ ۳
۱
ŭ ž Ň 2
7321 F Function input H21 module 1
None | Optg mode change HCs+DHW | Optg mode ch
changeover HC1 | Optg mode changeover HC2 | Optg I
Consumer request VK1 | Consumer request VK2 | Rele
pool solar | Operating level DHW | Operating level HC1
HC1 | Room thermostat HC2 | Room thermostat HC3 | I
monitor | Flow temp setp incr hygro | Boiler return therm
Flow measurement Hz | Consumer request VK1 10V | O
room humidity 10V | Room temp 10V | Flow measurement
nangeover DHV
mode changeo
ase swi pool s
| Operating lev
DHW flow swit
nostat | Status i
Consumer requ
ent 10V | Temp
W | Optg mode chang
ver HC3 | Het gen loc
ource heat | Excess h
vel HC2 | Operating le
ch | Circ pump thermo
nfo suppl source | Ch
lest VK2 10V | Pressu
o measurement 10V
eover HCs ¦ Optg m
k ¦ Error/alarm mess
eat discharge | Rele
vel HC3 | Room the
ostat | Pulse count | I
arg prio DHW sol fu
ire measurement 10
ode
sage ¦
ase swi
rmostat
Dewpoint
el boil ¦
V ¦ Rel
7322 F Contact type H21 module 1 NO
7324 F Input value 1 H21 module 1 0 0 1000
7325 F Funct value 1 H21 module 1 0 -100 500
7326 F Input value 2 H21 module 1 10 0 1000
7327 F Funct value 2 H21 module 1 100 -100 500
7328 F Temp sensor H21 module 1
None ¦ Solar flow sensor B63 ¦ Solar return sensor B64
None -
7331 F Function input H22 module 1
Ditto 7321
1 -
7332 F Contact type H22 module 1
NC ¦ NO
NO
7334 F Input value 1 H22 module 1 0 0 1000
7335 F Funct value 1 H22 module 1 0 -100 500
7336 F Input value 2 H22 module 1 10 0 1000
7337 F Funct value 2 H22 module 1 100 -100 500
7338 F Temp sensor H22 module 1
None | Solar flow sensor B63 | Solar return sensor B64
None
7341 F Voltage out GX21 module 1
5 Volt | 12 Volt
5 Volt
7342 I Funct input EX21 module 1
None | Counter 1st burner stage | Heat gen lock | Error/
/alarm messag e ¦ Excess heat disch arge
7343 0 Cont type inp EX21 module 1
NC ¦ NO
NO
7348 F Funct output UX21 module 1
None | Boiler pump Q1 | DHW pump Q3 | DHW interm
Q6 | Heat circuit pump HC3 Q20 | Collector pump Q5 | 3
pool K18 | Collector pump 2 Q16 | Instant WH pump Q3
circ pump Q33
Solar pump ex
34 ¦ Solid fuel b
¦ Heat circuit pump H
t exch K9 ¦ Solar pum
oiler pump Q10
IC1 Q2 ¦ Heat circuit
p buffer K8 ¦ Solar p
pump HC2
ump swi
7349 F Sign logic out UX21 module1
Standard ¦ Inverted
Standard
7350 F Signal output UX21 module 1
010V | PWM
010V
7354 F Temp val 10V UX21 module1 100 5 130 °C
7355 F Funct output UX22 module 1
Ditto 7348
7356 F Sign logic out UX22 module1
Standard | Inverted
Standard
7357 F Signal output UX22 module 1
010V | PWM
010V
7361 F Temp val 10V UX22 module1 100 5 130 °C
Module 2
7375 F Function extension module 2
None | Multifunctional | Heating circuit 1 | Heating circui
Primary contr/system pump | DHW primary controller | I
circuit 1 | Heating circ/cooling circ 1 | Solid fuel boiler
it 2 ¦ Heating ci
nstantaneous
rcuit 3 ¦ Return temp
water heater ¦ Return
controller ¦ Solar DH
temp contr cascade
W ¦
¦Cooling
Page 42
erating line ır level tion ault value
Ope Use L L Def Min May Unit
7376 F Relay output QX21 module 2
None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Bypass pump Q12 ¦ Alarm output K10 ¦ 2nd pump spee
Q23 ¦ Heat circuit pump HC3 Q20 ¦ Cons circuit pump V
fuel boiler pump Q10 ¦ Time program 5 K13 ¦ Buffer retu
Solar ctrl elem swi pool K18 ¦ Collector pump 2 Q16 ¦ S
K30 | Cascade pump Q25 ¦ St tank transfer pump Q11 ¦
request K27 ¦ Refrigeration request K28 ¦ Air dehumidifi
circuit pump HC2 Q6 ¦ DHW ctrl elem Q3 ¦ Instant WH o
protection K11
Collector pump
d HC1 Q21 ¦ 2r
/K2 Q18 ¦ Syst
urn valve Y15 ¦
wimming pool r
DHW mixing p
er K29 ¦ Div va
ctrl elem Q34 ¦
Q5 | Cons circuit pur
nd pump speed HC2 (
em pump Q14 | Heat
Solar pump ext exch
pump Q19 | Flue gas
pump Q35 | DHW inte
lve HC/CC1 Y21 | He
Suppl source control
mp VK1 Q15 | Boiler
Q22 | 2nd pump spe
gen shutoff valve Y4
K9 | Solar ctrl elem I
relay K17 | Assisted
rm circ pump Q33 | I
at circuit pump HC1
K32 | Overtemperati
r pump Q1 ¦
ed HC3
I | Solid
puffer K8 |
firing fan
Heat
Q2 | Heat
ure
7377 F Relay output QX22 module 2
Ditto 7376
7378 F Relay output QX23 module 2
Ditto 7376
out QX23 module 2
7382 F Sensor input BX21 module 2
None | DHW sensor B31 | Collector sensor B6 | Return
sensor B41 | Flue gas temp sensor B8 | Common flow s
B36 | Buffer sensor B42 | Common return sensor B73 |
Collector sensor 2 B61 | Solar flow sensor B63 | Solar r
B72
sensor B7 ¦ Dł
sensor B10 ¦ So
Cascade return
eturn sensor B
HW circulation sensor
blid fuel boiler sensor
n sensor B70 ¦ Swimn
64 ¦ DHW outlet sens
B39 | Buffer sensor
B22 | DHW charging
ning pool sensor B13
or B38 | Solid fuel bo
B4 ¦ Buffer
g sensor
3 ¦
bil ret sens
7383 F Sensor input BX22 module 2
Ditto 7382
7386 F Function input H2 module 2
None | Optg mode change HCs+DHW | Optg mode changeover DHW | Optg mode changeover HCs | Optg mode changeover HC2 | Optg mode changeover HC3 | Heat gen lock | Error/alarm message | Consumer request VK1 | Consumer request VK2 | Release swi pool source heat | Excess heat discharge | Release swi pool solar | Operating level DHW | Operating level HC1 | Operating level HC2 | Operating level HC3 | Room thermostat HC1 | Room thermostat HC2 | Room thermostat HC3 | DHW flow switch | Circ'pump thermostat | Dewpoint monitor | Flow temp setp incr hygro | Boiler return thermostat | Status info suppl source | Charg prio DHW sol fuel boil | Consumer request VK1 10V | Consumer request VK2 10V | Pressure measurement 10V | Rel room humidity 10V | Room temp 10V | Flow measurement 10V | Temp measurement 10V
7387 F Contact type H2 module 2
NC ¦ NO
NO
7389 F Voltage value 1 H2 module 2 0 0 10 V
7390 F Funct value 1 H2 module 2 0 -100 500
7391 F Voltage value 2 H2 module 2 10 0 10 V
7392 F Funct value 2 H2 module 2 100 -100 500
7393 F Temp sensor H2 module 2 None 100
None | Solar flow sensor B63 | Solar return sensor B64
/396 None | Solar how sensor Bo3 | Solar return sensor Bo4 Function input H21 module 2 None | Optg mode change HCs+DHW | Optg mode changeover DHW | Optg mode changeover HC3 | Optg mode changeover HC2 | Optg mode changeover HC3 | Het gen lock | Error/alarm message | Consumer request VK1 | Consumer request VK2 | Release swi pool source heat | Excess heat discharge | Release swi pool solar | Operating level DHW | Operating level HC1 | Operating level HC2 | Operating level HC2 | Operating level HC3 | Room thermostat HC1 | Room thermostat HC3 | DHW flow switch | Circ pump thermostat | Pulse count | Dewpoint monitor | Flow temp setp incr hygro | Boiler return thermostat | Status info suppl source | Charg prio DHW sol fuel boil | Flow measurement H2 | Consumer request VK1 10V | Consumer request VK2 20V | Pressure measurement 10V | Rel
7397 F Contact type H21 module 2
NC ¦ NO
NO
7399 F Input value 1 H21 module 2 0 0 1000
7400 F Funct value 1 H21 module 2 0 -100 500
7401 F Input value 2 H21 module 2 10 0 1000
7402 F Funct value 2 H21 module 2 100 -100 500
7403 F Temp sensor H21 module 2
None ¦ Solar flow sensor B63 ¦ Solar return sensor B64
None -
7406 F Function input H22 module 2
Ditto 7396
Page 43
Operating line User level Function Default value Min. Max. Chrit
7407 F Contact type H22 module 2 NO
7409 F Input value 1 H22 module 2 0 0 1000
7410 F Funct value 1 H22 module 2 0 -100 500
7411 F Input value 2 H22 module 2 10 0 1000
7412 F Funct value 2 H22 module 2 100 -100 500
7413 F Temp sensor H22 module 2
None | Solar flow sensor B63 | Solar return sensor B64
None
7416 F Voltage out GX21 module 2
5 Volt | 12 Volt
5 Volt
7417 I Funct input EX21 module 2
None | Counter 1st burner stage | Heat gen lock | Error.
/alarm messag ge ¦ Excess heat disch narge
7418 0 Cont type inp EX21 module 2 NO
7423 F Funct output UX21 module 2
None | Boiler pump Q1 | DHW pump Q3 | DHW interm
HC2 Q6 | Heat circuit pump HC3 Q20 | Collector pump
swi pool K18 | Collector pump 2 Q16 | Instant WH pump
circ pump Q3
Q5 ¦ Solar pur
p Q34 ¦ Solid fi
3 ¦ Heat circuit pump
np ext exch K9 ¦ Sola
uel boiler pump Q10
HC1 Q2 ¦ Heat circu
r pump buffer K8 ¦ S
it pump
olar pump
7424 F Sign logic out UX21 module2
Standard | Inverted
Standard
7425 F Signal output UX21 module 2
0.10V | PWM
010V
7429 F Temp val 10V UX21 module2 100 5 130 °C
7430 F Funct output UX22 module 2
Ditto 7423
7431 F Sign logic out UX22 module2
Standard | Inverted
Standard
7432 F Signal output UX22 module 2
0.10V | PWM
010V
7436 F Temp val 10V UX22 module2 100 5 130 °C
- Module 3
7450 F Function extension module 3
None | Multifunctional | Heating circuit 1 | Heating circu
Primary contr/system pump | DHW primary controller | I
circuit 1 | Heating circ/cooling circ 1 | Solid fuel boiler
it 2 ¦ Heating c
Instantaneous
sircuit 3 ¦ Return temp
water heater ¦ Return
controller ¦ Solar DH
temp contr cascade
₩ ¦
¦Cooling
7451 F Relay output QX21 module 3
None | Circulating pump Q4 | El imm heater DHW K6 |
Bypass pump Q12 | Alarm output K10 | 2nd pump spee
Q23 | Heat circuit pump HC3 Q20 | Cons circuit pump V
fuel boiler pump Q10 | Time program 5 K13 | Buffer retu
Solar ctrl elem swi pool K18 | Collector pump 2 Q16 | S
K30 | Cascade pump Q25 | St tank transfer pump Q11 |
request K27 | Refrigeration request K28 | Air dehumidifi
circuit pump HC2 Q6 | DHW ctrl elem Q3 | Instant WH of
protection K11
Collector pum
d HC1 Q21 | 2
/K2 Q18 | Sys
urn valve Y15 |
wimming pool
DHW mixing
ier K29 | Div va
ctrl elem Q34 |
p Q5 | Cons circuit pu
2nd pump speed HC2
tem pump Q14 | Heat
| Solar pump ext exch
pump Q19 | Flue gas
pump Q35 | DHW inte
alve HC/CC1 Y21 | He
| Suppl source control
Imp VK1 Q15 ¦ Boile
Q22 ¦ 2nd pump spo
gen shutoff valve Y
K9 ¦ Solar ctrl elem
relay K17 ¦ Assisted
erm circ pump Q33 ¦
eat circuit pump HC1
K32 ¦ Overtempera
r pump Q1 |
eed HC3
4 | Solid
buffer K8 |
I firing fan
Heat
I Q2 | Heat
ture
7452 F Relay output QX22 module 3
Ditto 7451
7453 F Relay output QX23 module 3
Ditto 7451
7457 F Sensor input BX21 module 3
None | DHW sensor B31 | Collector sensor B6 | Return sensor B7 | DHW circulation sensor B39 | Buffer sensor B4 | Buffer
sensor B41 | Flue gas temp sensor B8 | Common flow sensor B10 | Solid fuel boiler sensor B22 | DHW charging sensor
B36 | Buffer sensor B42 | Common return sensor B73 | Cascade return sensor B70 | Swimming pool sensor B13 |
Collector sensor 2 B61 | Solar flow sensor B63 | Solar return sensor B64 | DHW outlet sensor B38 | Solid fuel boil ret sens
B72
7458 F Sensor input BX22 module 3
Ditto 7457
Page 44
erating line er level nction fault value ć × it
Ö ŝ De Σ Σ
Σ
ň
7461 F Function input H2 module 3
None | Optg mode change HCs+DHW | Optg mode ch
changeover HC1 | Optg mode changeover HC2 | Optg
Consumer request VK1 | Consumer request VK2 | Rele
pool solar | Operating level DHW | Operating level HC1
HC1 | Room thermostat HC2 | Room thermostat HC3 |
temp setp incr hygro | Boiler return thermostat | Status i
VK1 10V | Consumer request VK2 10V | Pressure meas
measurement 10V | Temp measurement 10V
nangeover DHV
mode changeo
ase swi pool so
Operating lev
DHW flow swite
nfo suppl source
surement 10V
V ¦ Optg mode chang
ver HC3 ¦ Heat gen lo
ource heat ¦ Excess h
vel HC2 ¦ Operating le
ch ¦ Circ'pump thermo
ce ¦ Charg prio DHW s
Rel room humidity 10
eover HCs ¦ Optg mo
ock ¦ Error/alarm mes
eat discharge ¦ Rele
vel HC3 ¦ Room the
istat ¦ Dewpoint mon
sol fuel boil ¦ Consur
DV ¦ Room temp 10\
ode
ssage ¦
ase swi
rmostat
itor ¦ Flow
ner request
/ ¦ Flow
7462 F Contact type H2 module 3
NC ¦ NO
NO
7464 F Voltage value 1 H2 module 3 0 0 10 V
7465 F Funct value 1 H2 module 3 0 -100 500
7466 F Voltage value 2 H2 module 3 10 0 10 V
7467 F Funct value 2 H2 module 3 100 -100 500
7468 F Temp sensor H2 module 3 7468 -100 500
1400 ľ None ! Solar flow sensor B63 ! Solar return sensor B64 7400
7471 F Function input H21 module 3
None | Optg mode change HCs+DHW | Optg mode ch
changeover HC1 | Optg mode changeover HC2 | Optg
Consumer request VK1 | Consumer request VK2 | Rele
pool solar | Operating level DHW | Operating level HC1
HC1 | Room thermostat HC2 | Room thermostat HC3 | I
monitor | Flow temp setp incr hygro | Boiler return therm
Flow measurement Hz | Consumer request VK1 10V | O
room humidity 10V | Room temp 10V | Flow measurement
nangeover DHV
mode changeo
ase swi pool so
Operating lev
DHW flow swite
nostat | Status i
Consumer requent 10V | Temp
V | Optg mode chang-
ver HC3 | Het gen loc
ource heat | Excess h
vel HC2 | Operating le
ch | Circ pump thermo-
nfo suppl source | Ch
est VK2 10V | Pressu
measurement 10V
eover HCs ¦ Optg mo
k ¦ Error/alarm mess
eat discharge ¦ Rele
vel HC3 ¦ Room the
ostat ¦ Pulse count ¦ I
arg prio DHW sol fu
re measurement 10
ode
sage ¦
ase swi
rmostat
Dewpoint
el boil ¦
V ¦ Rel
7472 F Contact type H21 module 3 NO
7474 F Input value 1 H21 module 3 0 0 1000
7475 F Funct value 1 H21 module 3 0 -100 500
7476 F Input value 2 H21 module 3 10 0 1000
7477 F Funct value 2 H21 module 3 100 -100 500
7478 F Temp sensor H21 module 3 None _
/ // 0 ľ None | Solar flow sensor B63 | Solar return sensor B64
7481 F Function input H22 module 3
Ditto 7471
7482 F Contact type H22 module 3 NO
7484 F Input value 1 H22 module 3 0 0 1000
7485 F Funct value 1 H22 module 3 0 -100 500
7486 F Input value 2 H22 module 3 10 0 1000
7487 F Funct value 2 H22 module 3 100 -100 500
7488 F Temp sensor H22 module 3 None
7491 F Voltage out GX21 module 3 5 Volt
7492 I Funct input EX21 module 3 None ! Counter 1st burner stage ! Heat gen lock ! Error. /alarm messag e ! Excess heat disch arge
7493 0 Cont type EX21 module 3 NO -
7498 F Funct output UX21 module 3
None | Boiler pump Q1 | DHW pump Q3 | DHW interm
Q6 | Heat circuit pump HC3 Q20 | Collector pump Q5 |
pool K18 | Collector pump 2 Q16 | Instant WH pump Q3
circ pump Q33
Solar pump ext
34 ¦ Solid fuel b
¦ Heat circuit pump H
t exch K9 ¦ Solar pum
oiler pump Q10
IC1 Q2 ¦ Heat circuit
p buffer K8 ¦ Solar p
pump HC2
ump swi
7499 F Sign logic out UX21 module3
Standard | Inverted
Standard
Page 45
erating line er level nction fault value - × ±
ð De Mir Ξ
Ξ
5
7500 F Signal output UX21 module 3
0.10V ¦ PWM
010V 1
7504 F Temp val 10V UX21 module3 100 5 130 °C
7505 F Funct output UX22 module 3
Ditto 7498
7506 F Sign logic out UX22 module3
Standard | Inverted
Standard
7507 F Signal output UX22 module 3
0.10V | PWM
010V
7511 F Temp val 10V UX22 module3 100 5 130 °C
Input/or utput t est
7700 Relay test
No test | Everything off | Burner stage T2 | DHW pump
circ mix valve cl Y2 | Relay output QX1 | Relay output Q
module 1 | Relay output QX21 module 2 | Relay output
QX21 module 3 | Relay output QX22 module 3 | Relay of
Q3 | Heating c
X21 module 1
QX22 module
output QX23 m
ircuit pump Q2 | Heat
| Relay output QX22
2 | Relay output QX23
odule 3
ing circ mix valve op
module 1 ¦ Relay ou
3 module 2 ¦ Relay c
o Y1 ¦ Heat
htput QX23
output
7730 I Outside temp B9 - -50.0 50 °C
7732 1 Flow temp B1 - 0.0 140 °C
7750 I DHW temp B3 - 0.0 140 °C
7760 1 Boiler temp B2 - 0.0 140 °C
7780 F Output test UX21 module 1 / 0 100 %
7781 F Output signal UX21 module 1 0 0 100
[Output signal UX21 module 1]
None ¦ Closed (000), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V ¦ PWM %
None
7782 F Output test UX22 module 1 / 0 100 %
7783 F Output signal UX22 module 1 0 0 100
[Output signal UX22 module 1]
None | Closed (ooo), Open () | Pulse | Frequency Hz
| Voltage V | PWM %
None
7784 F Output test UX21 module 2 / 0 100 %
7785 F Output signal UX21 module 2 0 0 100
[Output signal UX21 module 2]
None | Closed (000), Open () | Pulse | Frequency Hz
| Voltage V | PWM %
None
7786 F Output test UX22 module 2 / 0 100 %
7787 F Output signal UX22 module 2 0 0 100
[Output signal UX22 module 2]
None | Closed (000), Open () | Pulse | Frequency Hz
| Voltage V | PWM %
None -
7788 F Output test UX21 module 3 / 0 100 %
7789 F Output signal UX21 module 3 0 0 100
[Output signal UX21 module 3]
None | Closed (000), Open () | Pulse | Frequency Hz
| Voltage V | PWM %
None
7790 F Output test UX22 module 3 / 0 100 %
7791 F Output signal UX22 module 3 0 0 100
[Output signal UX22 module 3]
None ¦ Closed (000), Open () ¦ Pulse ¦ Frequency Hz
| Voltage V ¦ PWM %
None
7820 I Sensor temp BX1 - -28.0 350 °C
7821 I Sensor temp BX2 - -28.0 350 °C
7830 I Sensor temp BX21 module 1 0 -28 350 °C
7831 I Sensor temp BX22 module 1 0 -28 350 °C
Page 46
Operating line User level Function Default value Min. Max. Unit
7832 I Sensor temp BX21 module 2 0 -28 350 °C
7833 I Sensor temp BX22 module 2 0 -28 350 °C
7834 I Sensor temp BX21 module 3 0 -28 350 °C
7835 I Sensor temp BX22 module 3 0 -28 350 °C
7844 F Input signal H1 0 0 65535
7844 F [Output signal H1]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7845 F Input signal H2 module 1 0 0 65535
7845 F [Output signal H2 module 1]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7845 F Input signal H21 module 1 0 0 65535
7845 F [Output signal H21 module 1]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7846 F Input signal H22 module 1 0 0 65535
7846 F [Output signal H22 module 1]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7847 F Input signal H2 module 2 0 0 65535
7847 F [Output signal H2 module 2]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7847 F Input signal H21 module 2 0 0 65535
7847 F [Output signal H21 module 2]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7848 F Input signal H22 module 2 0 0 65535
7848 F [Output signal H22 module 2]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7849 F Input signal H2 module 3 0 0 65535
7849 F [Output signal H2 module 3]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7849 F Input signal H21 module 3 0 0 65535
7849 F [Output signal H21 module 3]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7850 F Input signal H22 module 3 0 0 65535
7850 F [Output signal H22 module 3]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7858 F Input signal H3 0 0 65535
7858 F [Output signal H3]
None ¦ Closed (ooo), Open () ¦ Pulse ¦ Frequency Hz
¦ Voltage V
None
7870 I Burner fault S3
ov ¦ 230V
- -
7881 I 1st burner stage E1
ov ¦ 230V
- -
7884 I SLT error message L1
ov ¦ 230V
-
7950 I Input EX21 module 1
ov ¦ 230V
0V
Page 47
line ne
ing svel t val
erat erle fault - ×
ð Us De Mir N 5
7951 1 Input EX21 module 2
ov | 230v
0V
7952 I Input EX21 module 3
ov ¦ 230V
0V
State
8000 I State heating circuit 1 - -
8001 I State heating circuit 2 - -
8002 I State heating circuit 3 - -
8003 I State DHW - -
8004 I State cooling circuit 1 - -
8005 I State boiler - -
8007 I State solar - -
8008 I State solid fuel boiler - -
8010 I State buffer - -
8011 I State swimming pool -
8022 I State supplementary source - -
Diagnos tics c ascade
8100 I Priority/state source 116 -
through
8130
8101 I State source 116 -
through Missing | Faulty | Manual control active | Heat generation
8131 DHW circuit 8) | Temporarily unavailable 7) | Outside temp
limit active | Not released | Released
8138 I Cascade flow temp 0 0 140 °C
8139 1 Cascade flow temp setp 0 0 140 °C
8140 1 Cascade return temp 0 0 140 °C
8141 I Cascade return temp setp 0 0 140 °C
8150 I Source seq ch'over current 0 0 990 h
Diagnos tics h eat generation
8300 1 1st burner stage T2
Off | On
- -
8301 I 2nd burner stage
Off ¦ On
- -
8308 I Boiler pump speed 0 0 100 %
8310 I Boiler temp - 0.0 140.0 °C
8311 I Boiler setpoint - 0.0 140.0 °C
8312 I Boiler switching point 0 0 140 °C
8314 I Boiler return temp - 0.0 140.0 °C
8315 I Boiler return temp setpoint 0 0 140 °C
8316 I Flue gas temp 0 0 350 °C
8318 I Flue gas temp max 0 0 350 °C
8326 I Burner modulation 0 0 100 %
8330 F Hours run 1st stage 0 0 65535 h
8331 F Start counter 1st stage - 0 199'999 -
8332 F Hours run 2nd stage 0 0 65535 h
8333 F Start counter 2nd stage 0 0 199999 -
8505 Ι Speed collector pump 1 0 0 100 %
8506 I Speed solar pump ext exch 0 0 100 %
8507 Ι Speed solar pump buffer 0 0 100 %
Page 48
Dperating line Jser level unction Default value /in. /lax. Jnit
8508 Speed solar pump swi pool 0 0 100 %
8510 1 Collector temp 1 - -28.0 350 °C
8511 1 Collector temp 1 max 0 -28.0 350
8512 1 Collector temp 1 min 0 -28.0 350 °C
8513 1 dt collector 1/DHW - -168.0 350 °C
8514 dt collector 1/buffer _ -168.0 350
8515 dt collector 1/swimming pool 0 -168.0 350
8519 1 Solar flow temp 0 -28.0 350 °C
8520 1 Solar return temp 0 -28.0 350 0°C
8521 1 Solar throughput 0 0 500 l/min
8526 F 24-hour vield solar energy 0 0 999 9 kWh
8527 F Total vield solar energy 0 0 9999999 9 kWh
8530 F Hours run solar vield - 0 65535 h
8531 F Hours run collect overtemp _ 0 65535 h
8543 1 Speed collector nump 2 0 0 100 %
8547 1 Collector temp 2 0 -28 350 °C
8548 1 Collector temp 2 max -28 -28 350 °C
8549 1 Collector temp 2 min 3500 -28 350 °C.
8550 1 dt collector 2/DHW 0 -168 350 °C.
8551 1 dt collector 2/buffer 0 -168 350 °C.
8552 1 dt collector 2/swimming pool 0 -168 350 ି
ଜୁନ
8560 1 Solid fuel boiler temp 0 0 140 °C.
8561 1 Solid fuel boiler setpoint 0 0 140 °C.
8563 1 Solid fuel boiler return temp 0 0 140 0°C
8564 1 Solid fuel boiler return setn 0 0 140 °C
8568 1 Speed solid fuel boiler nump 0 0 100 %
8570 F Hours run solid fuel boiler 0 0 65535 h
Diagnos tics o U 00000 11
8700 1 _ -50.0 50.0 ംറ
8703 1 _ -50.0 50.0 °C
8704 1 _ -50.0 50.0 °C
8720 1 Rel room humidity _ 0 100 %
8721 1 0 50.0 /0
°C
8722 1 Dewnoint temp 1 _ 0 50.0 °C
8730 1 _ 0 50.0 _
0/00 1 Off | On
8731 I Heat circ mix valve op Y1
Off¦ On
- -
8732 I Heat circ mix valve cl Y2
Off | On
- -
8735 I Speed heating circuit pump 1 0 0 100 %
8740 Ι Room temp 1 - 0.0 50.0 °C
8741 Ι Room setpoint 1 - 4.0 35.0 °C
8742 0 Room temp 1 model - 0.0 50.0 °C
8743 I Flow temp 1 - 0.0 140.0 °C
8744 Ι Flow temp setpoint 1 - 0.0 140.0 °C
8749 I Room thermostat 1
No demand | Demand
No demano d -
8751 I Cooling circuit pump 1
Off | On
- -
Page 49
a
line
line
- alue
atinç leve u u rit «
Oper User ца
Н
Defa Min. Max. Cuit
8752 I Cool circ mix valve 1 open - -
8753 I Cool circ mix valve 1 close - -
8754 I Diverting valve cooling 1 - -
8756 I Flow temp cooling 1 - 0 140 °C
8757 I Flow temp setp cooling 1 - 0 140 °C
8760 I Heating circuit pump 2
Off | On
- -
8761 I Heat circ mix valve 2 open
Off ¦ On
- -
8762 I Heat circ mix valve 2 close - -
8765 I Speed heating circuit pump 2 0 0 100 %
8770 I Room temp 2 - 0.0 50 °C
8771 1 Room setpoint 2 - 4.0 35 °C
8772 0 Room temp 2 model - 0.0 50 °C
8773 I Flow temp 2 - 0.0 140 °C
8774 1 Flow temp setpoint 2 - 0.0 140 °C
8779 I Room thermostat 1
No demand | Demand
No der nand -
8790 I Heating circuit pump 3
Off | On
- -
8791 Ι HC mixing valve 3 open - -
8792 I HC mixing valve 3 closed - -
8795 I Speed heating circuit pump 3 0 0 100 %
8800 I Room temp 3 - 0.0 50 °C
8801 1 Room setpoint 3 - 4.0 35 °C
8802 0 Room temp 3 model - 0.0 50 °C
8803 I Flow temp setpoint 3 - 0.0 140 °C
8804 I Flow temp 3 - 0.0 140 °C
8809 I Room thermostat 3
No demand ¦ Demand
No der nand -
8820 I DHW pump
Off¦On
- -
8825 I Speed DHW pump 0 0 100 %
8826 I Speed DHW interm circ pump 0 0 100 %
8827 1 Speed inst DHW heater pump 0 0 100 %
8830 I DHW temp 1 - 0.0 140 °C
8831 I DHW temp setpoint - 8.0 80 °C
8832 I DHW temp 2 - 0.0 140 °C
8835 1 DHW circulation temp - 0.0 140 °C
8836 I DHW charging temp 0 0 140 °C
8850 1 DHW primary controller temp 0 0 140 °C
8851 1 DHW primary controller setp 0 0 140 °C
8852 1 DHW consumption temp 0 0 140 °C
8853 1 Instant WH setpoint 0 0 140 °C
8875 1 Flow temp setp VK1 5 5 130 °C
8885 1 Flow temp setp VK2 5 5 130 °C
8895 1 Flow temp setp swimming pool 5 5 130 °C
8900 || Swimming pool temp 0 0 140 °C
Page 50
٩
g lin e alue
ratin lev tion iult v
Ope Jsei Defa Min. Мах Jnit
8901 1 Swimming pool setpoint 24 8 80 °C
8930 I Primary controller temp - 0.0 140.0 °C
8931 I Primary controller setpoint - 0.0 140.0 °C
8950 I Common flow temp - 0.0 140.0 °C
8951 I Common flow temp setpoint - 0.0 140.0 °C
8952 Ι Common return temp 0 0 140 °C
8957 Ι Common flow setp refrig 0 0 140 °C
8962 Ι Common output setpoint 0 0 100 %
8980 Ι Buffer temp 1 - 0.0 140.0 °C
8981 Ι Buffer setpoint 0 0 140 °C
8982 I Buffer temp 2 - 0.0 140.0 °C
8983 I Buffer temp 3 0 0 140 °C
9005 I Water pressure 1 - 0.0 10.0 bar
9006 I Water pressure 2 - 0.0 10.0 bar
9009 I Water pressure 3 0 0 10 bar
9031 I Relay output QX1 - -
9032 I Relay output QX2
Off ¦ On
- -
9033 I Relay output QX3
Off ¦ On
- -
9034 I Relay output QX4
Off ¦ On
- -
9035 I Relay output QX5
Off ¦ On
- -
9050 I Relay output QX21 module 1 - -
9051 I Relay output QX22 module 1 - -
9052 I Relay output QX23 module 1 - -
9053 I Relay output QX21 module 2 - -
9054 I Relay output QX22 module 2 - -
9055 I Relay output QX23 module 2 - -
9056 I Relay output QX21 module 3
9057 I Relay output QX22 module 3
9058 I Relay output QX23 module 3
Page 51

6 The settings in detail

6.1 Time programs

For the heating circuits and DHW heating, a number of switching programs are available. They are activated in Automatic mode and control the change of temperature levels (and the respective setpoints) via the set switching times.

Entering the switching times The switching times can be combined, i.e. either in common for several days or in the form of separate times for individual days. The preselection of groups of days like for instance Mo...Fr and Sa-Su that use the same switching times simplifies setting of the switching programs.

na points Line no. Operating line
9 HC1 HC2 HC3 4/DHW 5
500 520 540 560 600 Preselection
Mo – Su¦Mo – Fr¦Sa – Su¦Mo¦¦Su
501 521 541 561 601 1st phase on
502 522 542 562 602 1st phase off
503 523 543 563 603 2nd phase on
504 524 544 564 604 2nd phase off
505 525 545 565 605 3rd phase on
506 526 546 566 606 3rd phase off
Standard program

Switch

Line no. Operating line
516, 536, 556, 576, 616 Default values
No¦Yes

All time programs can be reset to their factory settings. Each time program has its own operating line to make this reset.

i In that case, individual settings will be lost!

6.2 Holidays

Line no. Operating line
HC1 HC2 HC3
641 651 661 Preselection
Period 18
642 652 662 Start
643 653 663 End
648 658 668 Operating level
Frost protection | Reduced

The holiday program is used to switch the heating circuits to a selectable operating level according to calendar dates. Up to 8 independent holiday periods can be entered.

/ Important:

The holiday program can only be used in Automatic mode.

Page 52

6.3 Heating circuits

For the heating circuits, various functions are available which can be individually set for each heating circuit.

Operating mode Line no . . Operating line
HC1 HC2 HC3
700 1000 1300 Operating mode Protection | Automatic | Reduced | Comfort
You ca
mode t
n directly
outton on
select o the oper perating mode for the heating circuits via the operating rator units.
In Prote
(frost p
ection mo ode, the l
tempera
neating system is off. But it remains protected against frost
ture) provided there is no power failure.
Charac
• Heat
teristics
ing OFF
of Protec tion mode:
Tem Prote perature accordin g to frost protection.
  • Auto
    heat
matic su mmer / w
active
i nter changeover (ECO functions) and automatic 24-hour
Automa
prograr
atic mode
n.
e controls s the room temperature according to the selected time
Charac
• Heat
• Tem
teristics
ing mod
perature
of Autom
e accordi
setpoints
atic mode:
ng to the time program.
s per heating program "Comfort setpoint"
  • Prote
  • Auto
ective fui
matic su
nctions ao
mmer / w
ctive.
v inter changeover (ECO functions)
Reduced ( The red
level.
duced op erating n node maintains the room temperature at the set operating
Charac
• Heat
• Prote
teristics
ing mod
ective fu
of Reduc
e without
nctions ac
ed mode:
time program.
ctive.
Comfort The Co
level.
omfort op erating m node maintains the room temperature at the set operating
Charac
Heat
Prote
Auto
heat
teristics
ing mod
ective fui
matic su
ing limit
of Comfc
e without
nctions ad
mmer / w
are inacti
ort mode:
time program.
ctive.
v inter changeover (ECO functions) and automatic 24-hour
ve in Comfort mode.
Page 53

Setpoints

Line no. Operating line
HC1 HC2 HC3
710 1010 1310 Comfort setpoint
712 1012 1312 Reduced setpoint
714 1014 1314 Frost protection setpoint
716 1016 1316 Comfort setpoint max

Room temperature.

The setpoint setting ranges are obtained as a result of the interdependency of setpoints. This is shown in the following graph: The individual setpoints required for each heating circuit can be adjusted.

Page 54

Heating curve

Line no. Operating line
HC1 HC2 HC3
720 1020 1320 Heating curve slope
721 1021 1321 Heating curve displacement
726 1026 1326 Heating curve adaption

The heating curve generates the flow temperature setpoint, which is used to maintain a certain flow temperature depending on the prevailing weather conditions.

The heating curve can be adjusted with a number of settings, thus matching heat output and room temperature to individual needs.

Heating curve slope As the heating curve slope is raised, the flow temperature increases the quicker the lower the outside temperature or, in other words, if the room temperature is not correct at low outside temperatures but correct at higher outside temperatures, the heating curve slope requires readiustment.

ncreasing the setting: Raises the flow temperature, especially when outside temperatures are low.
Decreasing the setting: Lowers the flow temperature, especially when outside temperatures are low.

The set heating curve is based on a room temperature setpoint of 20 °C. If the room temperature setpoint is adjusted, the heating curve adapts automatically to the new value.

Heating curve displacement

Parallel displacement of the heating curve is used to change the flow temperature evenly across the entire outside temperature range or, in other words, if the room temperature is always too high or too low, a readjustment must be made via parallel displacement.

Heating curve adaption

i

With this function the controller automatically adapts the heating curve to prevailing conditions.

i To assure this function, following must be observed:

  • A room sensor must be connected.
  • "Room influence" must be set to a value between 1 and 99.
  • There should be no thermostatic radiator valves in the reference room (mounting location of room temperature sensor) (if such valves are present, they must be set to their fully open position).
Page 55
ECO functions
Line no. Operating line
HC1 HC2 HC3
730 1030 1330 Summer/winter heating limit
732 1032 1332 24-hour heating limit
733 1033 1333 Ext'n 24-hour heating limit
No¦Yes

Summer/winter heating limit

The summer / winter heating limit is used to switch the heating on and off in the course of the year, depending on temperature conditions. In Automatic mode, switching on / off takes place automatically, so there is no need for the user to do this manually. By changing the setting, the respective periods of time will be shortened or extended.

Increase: Winter operation will start earlier
Summer operation will start later.
Decrease: Winter operation will start later
Summer operation will start earlier .

• The function is not active in operating mode "Continuously Comfort temperature"

  • The display will show "ECO"
  • To give consideration to the building's thermal dynamics, the outside temperature is attenuated

SWHG Summer/winter heating limit

TAged Attenuated outside temperature

  • T Temperature
  • Days
Page 56

24-hour heating limit.

The 24-hour heating limit is used to switch the heating on and off in the course of the day, depending on the outside temperature. This function is used primarily during intermediate seasons (spring and autumn) to respond to short-time temperature variations.

Example:

Operating line E.g.
Comfort setpoint (TRw) 22 °C
24-hour heating limit (THG) -3 °C
Changeover temperature (TRw – THG) heating off =19 °C
Switching differential (fixed -1 °C
Changeover temperature heating on =18 °C

A change in value shortens or extends the corresponding heating phases.

Increase: Heating mode will start earlier,
changeover to ECO later.
Decrease: Heating mode will start later,
changeover to ECO earlier.

  • The function is not active in operating mode "Continuously Comfort temperature"
    • The display shows ECO.
    • To give consideration to the building's thermal dynamics, the outside temperature is attenuated
Page 57

Extension: 24-hour heating limit

The "24-hour heating limit" function (line 732) switches the heating system off when the actual outside temperature has risen to a level of one adjusted differential below the current operating level. Setting an "extended 24-hour heating limit" defines when to turn on heating again.

Extension 24-hour heating limit = No

The heating is switched on again when the present actual outside temperature (TA) drops again below the adjusted differential minus 1 K. The building dynamics (building structure and insulation) are not taken into consideration.

Extension 24-hour heating limit = Yes

The heating is switched on again when the mixed actual outside temperature (TAgem) drops again below the adjusted differential minus 1 K. The building dynamics (building structure and insulation) are taken into consideration.

  • 733 Setting Yes / No in operating lines 733, 1033 or 1333
  • TRw Room temperature setpoint
  • TA Actual outside temperature
  • TAgem Composite outside temperature
  • THG 24-hour heating limit
  • T Temperature
  • t Time of day
Page 58
Line no. Operating line
HC1 HC2 HC3
740 1040 1340 Flow temp setpoint min
741 1041 1341 Flow temp setpoint max
742 1042 1342 Flow temp setpoint room stat

This limitation can be used to select a range for the flow temperature setpoint. If the flow temperature setpoint demanded by the heating circuit reaches the relevant limit and the heat request increases or decreases, the flow temperature setpoint will be maintained at the maximum or minimum limit.

TVw Current flow temperature setpoint TVmax Flow temp setpoint max TVmin Flow temp setpoint min

Flow temperature setpoint: Room thermostat

On applications with room thermostat, the heating circuit is switched on only when the room thermostat calls for heat.

A fixed or weather-compensated temperature value is called for, depending on the selected setting:

Selection Compensation variant
Temperature request according to the heating curve
895 °C Temperature request according to the set value*
* In Constant made and

In Comfort mode only –

outside the Comfort there is no temperature demand and the heating curve remains switched off

i

The room thermostat can be connected via an Hx input (H1, H2 (module 1-3), H3) to the controller or an extension module.

Adaption of flow temperature when setpoint is fixed
Line no. Operating line
HC1 HC2 НС3
744 1044 1344 Swi-on ratio room stat
/ 199%

i The function is used for room temperature control with a room thermostat.

The flow temperature can be adapted based on demand if the flow temperature setpoint is preset using parameter setting (line 742/1042/1342).

---Setting "---" deactivates the function.

1...99%

Function is activated.

Page 59
Line no. Operating line
HC1 HC2 HC3
750 1050 1350 Room influence
Compensation variants

* Different types of compensation are available when using a room temperature sensor.

Selection Compensation variant
% Weather compensation alone*
199 % Weather compensation with room influence*
100 % Pure room compensation
* Outside sensor requir ed.
Weather compensation alone The flow temperature is calculated via the heating curve, depending on the composite outside temperature.
This compensatic
because with this
temperature.
on variant calls for a correct adjustment of the heating curve setting the control system gives no consideration to the room
Weather compensation with room influence The deviation of t taken into accoun considered, ensuing the second seco he current room temperature from the setpoint is acquired and
it when controlling the room temperature. Heat gains can thus be
ring more accurate room temperature control.
The authority of the deviation is set as a percentage value. The better the reference room (correct room temperature, correct mounting location, etc.) the higher the value can be set.
Example:
Approx. 60% Good reference room
Approx. 20 % Unfavorable reference room
i To provide the fur nction, following must be considered:
• A room sensor must be connected
  • Room influence" must be set to a value between 1 and 99 %
  • There should be no thermostatic radiator valves in the reference room (mo
    location of room temperature sensor) (if such valves are present, they mus
    set to their fully open position).
Pure room compensation The flow temperature is controlled depending on the room temperature setpoint, the current room temperature and the progression of room temperature.
For example, a slight increase in room temperature leads to an immediate reduction in flow temperature.
i To provide the fur nction, following must be considered:
A room sensor must be connected.
  • "Room influence
e" must be set to 100%.
There should b location of the d be no thermostatic radiator valves in the reference room (mounting he room sensor). (If such valves are present, they must be set to

their fully open position).

Page 60
Line no. Operating line
HC1 HC2 HC3
760 1060 1360 Room temp limitation

The "Room temperature limitation" function enables the heating circuit pump to be deactivated if the room temperature exceeds the current room temperature setpoint by more than the adjusted differential.

The heating circuit pump is activated again as soon as the room temperature returns to a level below the current room temperature setpoint.

During the time the "Room temperature limitation" function is active, no heat request is sent to the heat source.

i

Room temperature limitation does not function with pure weather compensation.

Boost heating
Line no. Operating line
HC1 HC2 HC3
770 1070 1370 Boost heating

Boost heating is used to reach the new setpoint more quickly when switching from the Reduced setpoint to the Comfort setpoint, thus shortening the heating up time.

During boost heating, the room temperature setpoint is raised by the value set here.

A higher setting leads to shorter heating up times, a lower setting to longer heating up times.

i

Boost heating can be provided with or without room sensor.

Page 61
Quick setback
Line no. Operating line
HC1 HC2 HC3
700 4000 4000 Outlak aathaak
100 1080 1380 QUICK SELDACK

During quick setback, the heating circuit pump is deactivated and, in the case of mixing circuits, the mixing valve is fully closed.

Function with room When using a room temperature sensor, the function keeps the heating switched sensor off until the room temperature has dropped to the level of the reduced setpoint or the frost level. When the room temperature has fallen to the reduced level or the frost level, the heating circuit nump will be activated and the mixing valve will be released

Function without room Quick setback switches the heating and building time constant off for a certain sensor period dependent on the outside temperature.

Example

Duration of quick setback when Comfort setpoint minus Reduced setpoint = 2 °C (e.g. Comfort setpoint = 20 °C and Reduced setpoint =18 °C)

Building g time cons stant [h]
Composite outside 0 2 5 10 15 20 50
temperature Duratio n of quick setback [h]
15 °C 0 3.1 7.7 15.3 23 30.6 76.6
10 °C 0 1.3 3.3 6.7 10 13.4 33.5
5 °C 0 0.9 2.1 4.3 6.4 8.6 21.5
O°O 0 0.6 1.6 3.2 4.7 6.3 15.8
-5 °C 0 0.5 1.3 2.5 3.8 5.0 12.5
-10 °C 0 0.4 1.0 2.1 3.1 4.1 10.3
-15 °C 0 0.4 0.9 1.8 2.6 3.5 8.8
-20 °C 0 0.3 0.8 1.5 2.3 3.1 7.7

Quick setback is possible with or without room temperature sensor

Optimum start/stop Line no. Operating line
HC1 HC2 HC3
control 790 1090 1390 Optimum start control max
791 1091 1391 Optimum stop control max
794 1094 1394 Heat up gradient
Optimum start control max Optimu
in a wa
The se
m start c
y that the
tting "Op
ontrol op
e Comfor
timum sta
timizes the change from one temperature level to the othe
t setpoint is achieved at the switching times.
art control max" limits the period of precontrol.
Optimum stop control
max
Optimu
Comfor
The se
m stop c
t setpoin
tting "Op
ontrol ad
t -1/4 °C
timum sto
vances changeover of the temperature level to achieve
at the switching times.
op control max" limits the period of precontrol.
Page 62

  • Xon Forward shift of switch-on time Xoff Forward shift of switch-off time
  • ZSP Time program
  • TRx Actual value of room temperature
  • TRy Room temperature setpoint

i Optimum start/stop control can be performed with or without room temperature sensor. A room model is used to calculate optimum start / stop control.

Heating up gradient

The heating up gradient defines the period required to increase the room temperature by 1°C.

If the room temperature does not reach the "Comfort" setpoint at the respective switching times, the setting must be increased.

The heating up gradient is only effective when optimum start up is active.

Increase of "Reduced" setpoint

Line no. Operating line
HC1 HC2 НС3
800 1100 1400 Reduced setp increase start
801 1101 1401 Reduced setp increase end

The function is used primarily on heating systems with only little spare capacity (e.g. low-energy houses). In such cases, the heating up time at low outside temperatures would be too long. When the Reduced setpoint is raised, the rooms are prevented from cooling down to too low levels, thus shortening the heating up time when changing to the Comfort setpoint.

  • TRwA1 Reduced setp increase start
  • TRwA2 Reduced setp increase end
  • TRK Comfort setpoint
  • TRR Reduced room temperature setpoint

Page 63
Frost protection HC pump
Line no. Operating line
HC1 HC2 HC3
810 1110 1410 Frost prot plant HC pump
Off ¦ On

Under the setting "On", the corresponding HC pump is operated for active plant frost protection. (see description of plant frost protection)

Overtemperature protection pump heating circuit

Line no. Operating line
HC1 HC2 HC3
820 1120 1420 Overtemp prot pump circuit

In the case of heating plants with pump heating circuits, the flow temperature of the heating circuit can be higher than the flow temperature called for by the heating curve, the reason being higher requests from other heat consumers (mixing heating circuit, DHW charging, external heat demand), or a parameterized minimum heat pump temperature. As a result of this too high flow temperature, the pump heating circuit would assume excessive temperatures.

Function "Overtemperature protection for pump heating circuits" ensures that the energy supply for pump heating circuits corresponds to the demand from the heating curve by activating / deactivating the pump.

Page 64
Control of mixing valve HC1 Line no. НСЗ Operating line
830 1130 1430 Mixing valve boost
832 1132 1432 Actuator type
2-position | 3-position
833 1133 1433 Switching differential 2-pos
834 1134 1434 Actuator running time
835 1135 1435 Mixing valve Xp
836 1136 1436 Mixing valve Tn
Mixing valve boost To ensur
be highe
controlle
setpoint
re proper
er than th
er adds th
and use
r mixing v
ne demar
ne mixing
s the valu
valve flow temperature control, the flow temperature must
ided setpoint of the mixing valve flow temperature. The
g valve boost set here to the current flow temperature
ue as the value for heat generation setpoint.
Actuator type 2-positi
The con
delivers
closes a
on
troller us
a signal,
utomatic
es only c
the conr
ally.
one relay output to drive the actuator. When the output
nected valve opens. When there is no signal, the valve
3-positi
The con
opening
on
troller dr
the conr
ives the a
nected va
actuator with 2 relay outputs. One output is used for alve, the other for closing it.
Switching differential 2-
pos
For a 2-
This is r
position a
ot requir
actuator,
ed when
the 2-position switching differential must also be adapted.
using a 3-position actuator.
Actuator running time For the 3-position actuator, the running time of the mixing valve actuator can be adjusted. The actuator running time has no impact on 2-position actuators.
Mixing valve Xp By setting the right proportional band Xp for the mixing valves actuator, the control behavior of the actuator is matched to those of the plant (controlled system). The proportional band Xp influences the controller's P-action. The P band Xp is the range by which the input variable x (controlled variable) must change to adjust the output variable y (manipulated variable) throughout the entire positioning range. The smaller the value the greater the jump. The illustration depicts the reciprocal value 1/Xp = Kp.
Mixing valve Tn By settir
actuator
Tn influe
ng the rig
is match
ences the
ht integraned to the controll al action time Tn, the control action of the mixing valve's
e behavior of the plant (controlled system).
er's I-response.

It is the required of the I-portion to undertake the same manipulated variable change at the given input signal (controlled variable), as immediately provided by the P-portion. The smaller the Tn the larger/faster the slope.

Page 65

"Floor curing" function

Line no. Operating line
HC1 HC2 HC3
850 1150 1450 Floor curing function
Off | Functional heating | Curing heating | Functional/curing
heating | Manually
851 1151 1451 Floor curing setp manually
856 1156 1456 Floor curing day current
857 1157 1457 Floor curing days completed

The "Floor curing" function ensures controlled drying of the floor. It controls the flow temperature in accordance with a certain temperature profile.

  • Observe the relevant standards and regulations of the company supplying the floor!
    • Proper functioning is ensured only when the plant is correctly installed (hydraulic system, electrical installation, settings)! Deviations may damage the attic!
    • The function can be aborted prematurely by choosing Off.
    • Maximum limitation of the flow temperature remains active.
Floor curing function Off The function is deactivated Function heating (Fh): The 1st part of the temperature profile is run automatically. Floor curing heating (Fh): The 2nd part of the temperature profile is run automatically Functional and floor curing heating The entire temperature profile (first and second part) is traversed automatically. Floor curing heating and functional heating The entire temperature profile (first and second part) is traversed automatically. Manual In manual mode, no temperature profile is used. The required flow temperature must be set individually for every heating circuit using parameter Floor curing set manually. The function is automatically ended after 25 days Floor curing setp The flow temperature setpoint for the "Manual floor curing" function can be set manually separately for each heating circuit. Â First, start the "Floor curing" function, then adjust the setpoint manually. The start value is 25 °C and can be manually readjusted at any time. Floor curing setp manually (TVFm) can only be adjusted within the 2 limit values Flow temperature setpoint maximum (TVMax) and Flow temperature setpoint minimum (TVmin). The function ends after the function days (Fh+Bh = 25 days) expire or the function is switched off via the parameter start day (day 0) which is not counted as a functional day. Attic day present Displays the current day and the current setpoint of the "Floor curing" function in Present setpoint for attic progress.
Page 66

Floor curing days completed

The completed number of days are continuously stored and retained until the function is started the next time.

The temperature is regarded maintained if the deviation from the setpoint is less than 2 Kelvin. The periods of time the flow temperature is correct are added up by a meter.

If the required temperature is not reached after more than 1 hour, the meter is stopped until the deviation is again smaller than 2 K.

After a power failure, the plant resumes the floor curing function at the point in time the power failure occurred.

Temperature profile In Automatic modes, the controller ensures automatic completion of the selected temperature profile.

The temperature change is always made at midnight. The start day (day 0), that is, the period of time from activation to midnight does not count as a functional day. The setpoint used for the start day is the value of the first functional day.

During "Floor curing mode", the profile temperature is limited within the 2 limit values Flow temperature setpoint maximum (TVMax) and Flow temperature setpoint minimum (TVmin).

The function is ended when the functional days have elapsed or when the function is deactivated via the respective parameter.

Page 67
Excess heat draw
Line no. Operating line
HC1 HC2 НС3
861 1161 1461 Excess heat draw
Off | Heating mode | Always

The source, input Hx or a storage tank can trigger an excess heat draw.

If excess heat draw is activated, excess heat can be made available to heat transfer. This can be selected separately for each heating circuit.

Off

Excess heat draw is deactivated.

Heating mode.

Excess heat is drawn only when the controller operates in heating mode.

Always

Excess heat is drawn in all operating modes.

r storage tank / Line no. Operating line
HC1 HC2 HC3
ry controller 870 1170 1470 With buffer
872 1172 1472 With prim contr/system pump

With buffer

Buffe prima

No

Hydraulically speaking, the heating circuit is connected upstream of the buffer storage tank and cannot draw any heating or cooling energy from it. The heat or refrigeration request is forwarded to the heat/refrigeration source upstream of the buffer storage tank.

Yes

The heating circuit is connected after the buffer storage tank. It draws heat or cooling energy from the buffer storage tank and its temperature request is taken into account by buffer management.

With primary controller /

system pump

No

Hydraulically speaking, the heating circuit is connected upstream of the primary controller / system pump and cannot draw any "precontrolled" heating or cooling energy. The heat or refrigeration request is always forwarded to the heat/refrigeration source upstream of the primary controller.

Yes

The heating circuit is connected downstream of the primary controller / system pump. The primary controller ensures control of a valid heat or refrigeration request, or the system pump is activated.

Page 68

Speed control

Speed-controlled pumps can be connected to outputs Ux.

Line no. Operating line
HC1 HC2 HC3
880 1180 1480 Pump speed reduction
Operating level | Characteristic
882 1182 1482 Pump speed min
883 1183 1483 Pump speed max
888 1188 1488 Curve readj at 50% speed
890 1190 1490 Flow setp readj speed ctrl
No¦Yes

Pump speed reduction Operating level The heating circuit pump speed is calculated by present operating level. At the Comfort level or during the time the floor curing function is performed, the pump is controlled at the parameterized maximum speed At the Reduced level, the pump is controlled at the parameterized minimum speed. Characteristic For the compensation variant weather compensation (with or without influence) the heating circuit pump speed is maintained at the minimum parameterized speed as long as heat demand can be covered. The heating curve is increased in order to cover heat demand at a reduced speed. The increase in flow temperature can be parameterized. The setting defines the flow increase in percentages at minimum speed for the heating circuit pump The speed is increased only after the maximum permitted flow setpoint is reached. Pump speed min /max Using these settings, minimum and maximum limitation of the pump speed is provided. Characteristic curve Percentage for flow setpoint boost at 50% speed. correction at 50% speed. Flow setpoint correction. Voc speed control The heat request from the heating curve is increased by the parameterized percentage. Heat request = Room setpoint + (flow setpoint – room setpoint) * 1 2 No The request to generation is not increased. The speed is reduced until heat transfer is correct as per the characteristic curve calculation if the present flow

temperature is warmer than the heating curve at 100% speed

Page 69

Remote control

Line no. Operating line
HC1 HC2 HC3
900 1200 1500 Optg mode changeover
None | Protection | Reduced | Comfort | Automatic

Changeover of operating mode

In the case of external changeover via inputs H1 / H2 / H3, the operating mode to be used can be selected.

Frost protection for the heating circuit

Frost protection for the heating circuit is always active.

If the flow temperature falls below 5 °C, the controller switches on heating circuit pumps – regardless of the present operating mode for heating.

When the flow temperature returns to a level above 7°C, the controller will switch the pumps off again after 5 minutes.

Page 70

6.4 Cooling circuit

To be able to operate the cooling circuit, an appropriate partial diagram "Heating / cooling" must be used.

The system starts to operate in cooling mode when the room temperature rises above the Comfort cooling setpoint (902). The cooling function must be activated (901 = Auto) and enabled in accordance with the time program (907).

Furthermore, the criteria "Cooling limit at OT" (operating line 912) and "Lock time at end of heating" (operating line 913) must be met.

Cooling mode is cancelled in a 2-pipe system (with active cooling) when a consumer requires heat.

It is possible to charge DHW and heat (using another heating circuit) a heating circuit during cooling mode with a 4-pipe system.

Operating mode L Line no. Operating line
ę 901 Operating mode
Off ¦ Automatic
TI
ro
he operating
oom or oper
g mode can be selected either via the operating mode button on the ator unit or via the above operating line.
i Ti
a
his setting is room unit. s the same as the cooling mode selecting using the cooling button on
Off TI he cooling f function is deactivated.
Automatic TI
pr
if
he cooling f
rogram (907
required.
function is automatically enabled on the basis of the selected time 7), the holiday program and the occupancy button, and then activated
Manual mode lf
bu
the cooling
utton can be
enable signal is set to 24h/day via operating line 907, then the cooling
e used as an on/off button. (Manual mode)
Setpoints L Line no.
902
Operating line Comfort setpoint
Comfort setpoint In
he
or
n cooling mo
ere. The Co
n the room
ode, room temperature control maintains the Comfort setpoint adjusted
omfort setpoint for cooling can also be adjusted with the setting knob
unit.
[ i In
te
the summe
mperature
er, the Comfort setpoint is shifted as a function of the outside (918 - 920).
Page 71

Flow setp at

Flow setp at

OT 25°C

OT 35°C

Line no. Operating line
907 Release
24h/day ¦ Time programs HCs ¦ Time program 5

Parameter "Release" determines the time program in accordance with which cooling is enabled.

  • 24 hours a day Cooling is permanently enabled (24 hours a day)
  • Time programs, HCs Cooling is enabled in accordance with the heating circuit's time program

Time program 5 / DHW Release of cooling takes place in accordance with time program 5.

Coolina curve Line no. Operating line
908 Flow temp setp at OT 25°C
909 Flow temp setp at OT 35°C

Flow temperature Based on the cooling curve, the controller determines the required flow temperature at a certain composite outside temperature. The cooling curve is determined by defining 2 fixed points (flow temperature setpoint at 25 °C and 35 °C).

This determines the flow temperature required for cooling at a composite outside temperature of 25°C without giving consideration to summer compensation.

Determines the flow temperature required for cooling at a composite outside temperature of 35°C , without giving consideration to summer compensation.

The set cooling curve is based on a room temperature setpoint of 25°C. If the room temperature setpoint is changed, the cooling curve is automatically adapted.

Page 72

CE1U2354en_021 2013-09-02

FCO

heating

Cooling limit at OT (outside temperature)

Lock time at end of

If the composite outside temperature rises above the cooling limit temperature,
cooling is released; cooling is disabled when the outside temperature drops to at
least 0.5°C below the cooling limit temperature.

a limit at OT

To avoid too rapid a change to cooling at the end of the heating phase, the cooling function is disabled for the period of time which can be set here. This "locking period" begins when there is no heating demand from heating circuit 1. and heating requests from heating circuit 2 or heating circuit P are not taken into consideration.

i The locking period is ignored if the cooling function is enabled via the operating mode button.

Summer compensation
Line no. Operating line
918 Summer comp start at OT
919 Summer comp end at OT
920 Summer comp setp increase

In summer, the cooling Comfort setpoint (902) is shifted upwards as the outside temperature increases. This saves cooling energy, and prevents too great a differential between the room and the outside temperature.

i The resulting room temperature setpoint (cooling) can be displayed on the info

Summer comp start at OT

End of summer compensation at OT

Summer compensation setpoint increase

Summer compensation takes full effect at this outside temperature (920) Any further increase of the outside temperature will have no more impact on the "Comfort" setpoint.

This setting defines the maximum by which the "Comfort" setpoint is raised.

TA Outside temperature

continuously.

Summer compensation starts to take effect at the outside temperature level set here. If the outside temperature continues to rise, the "Comfort" setpoint is raised

Page 73

Limitations of flow temperature setpoint

Line no. Operating line
923 Flow temp setp min OT 25°C
924 Flow temp setp min OT 35°C

A low limit can be defined for the flow temperature required for cooling. The limit curve is determined by defining 2 fixed points.

In addition, there is a minimum limit for the resulting flow temperature setpoint, which must not fall below 5 °C.

Flow temp setp min at OT 25°C

t Defines the lowest permissible flow temperature at a composite outside temperature of 25°C.

Flow temp setp min at OT 35°C

Defines the lowest permissible flow temperature at a composite outside temperature of 35°C.

If there is no valid outside temperature available, the controller uses the value □ "Flow temp setp min OT = 35 °C".

TVKwFlow temperature setpoint for cooling (with minimum limitation)TVKw_unbFlow temperature setpoint for cooling (without minimum limitation)TAgemThe composite outside temperature

Line no. Operating line
928 Room influence

Compensation variants

"Room influence"

When using a room temperature sensor, there is a choice of 3 different types of compensation.

Selection Compensation variant
% Weather compensation alone*
199 % Weather compensation with room influence*
100 % Pure room compensation

* Outside sensor required.

Weather compensation alone

The flow temperature is calculated based on the cooling curve, depending on the composite outside temperature.

This compensation variant demands a correct adjustment of the cooling curve since in that case the control gives no consideration to the room temperature.

Page 74

Weather compensation The deviation of the current room temperature from the setpoint is acquired and with room influence taken into account when controlling the room temperature. This way, consideration is given to room temperature deviations, ensuring more accurate room temperature control. The authority of the deviation is set as a percentage value. The better the reference room conditions (correct room temperature, correct mounting location, etc.), the higher the value can be set Example Approx. 60% Good reference room Approx. 20 % Unfavorable reference room i To provide the function, following must be considered: Room temperature sensor must be connected • "Room influence" must be set to a value between 1 and 99. • There should be no controlled valves in the reference room (mounting location of the room sensor) (If such valves are installed, they must be set to their fully open position) The flow temperature is controlled depending on the room temperature setpoint, Pure room compensation the current room temperature and the progression of room temperature. For example, a slight increase in room temperature leads to an immediate reduction in flow temperature. i To provide the function following must be considered: Room temperature sensor must be connected • "Room influence" must be set to 100% • There should be no thermostatic radiator valves in the reference room (mounting location of room sensor); if such valves are installed, they must be fully opened. Room temperature limitation The room temperature limitation function makes it possible to disable the cooling circuit pump if the room temperature falls by more than the programmed offset from the effective room setpoint (with summer compensation, operating line 920). The heating circuit pump will be activated again as soon as the room temperature returns to a level below the current room temperature setpoint. While the "Room temperature limitation" function is active no cooling request is sent to the heat source

The function is deactivated in the following situations:

  • No room temperature sensor
  • "Room temp limitation" = ---
  • "Room influence" (928) = --- (pure weather compensation)

Page 75
Frost protection CC pump
Line no. Operating line
937 Frost prot plant CC pump
Off ¦ On

Under the setting "On", the corresponding CC pump is operated for active plant frost protection.

Control of mixing valve Line no. Operating line
938 Mixing valve decrease
939 Actuator type
940
941 Actuator running time
942 Mixing valve Xp
943 Mixing valve Th
945 Mixing valve in heating mode
Control ¦ Open
Mixing valve decrease The refrigeration request from the mixing circuit to the producer is reduced by the set value. The purpose of this reduction is to enable the mixing valve controller to compensate for the temperature variations produced by the refrigeration source (2-position control).
Actuator type 2-position
The controller uses only one relay output to drive the actuator. When the output delivers a signal, the connected valve opens. When there is no signal, the valve closes automatically.
3-position
The contro
opening th
bller drives the actuator with 2 relay outputs. One output is used for e connected valve, the other for closing it.
Switching differential □2-
pos
For the 2-position actuator, the 2-position switching differential must also be adapted. The switching differential has no impact on 3-position actuators.
Actuator: running time For the 3-position actuator, the running time of the mixing valve actuator can be adjusted. The actuator running time has no impact on 2-position actuators.
Mixing valve Xp By setting the right proportional band Xp for the mixing valves actuator, the control behavior of the actuator is matched to those of the plant (controlled system). The proportional band Xp influences the controller's P-action. The P band Xp is the range by which the input variable x (controlled variable) must change to adjust the output variable y (manipulated variable) throughout the entire positioning range. The smaller the value the greater the jump. The illustration depicts the reciprocal value 1/Xp = Kp.
Mixing valve Tn By setting the right integral action time Tn, the control action of the mixing valve's actuator is matched to the behavior of the plant (controlled system).
Tn influences the controller's I-response.
It is the required of the I-portion to undertake the same manipulated variable change at the given input signal (controlled variable), as immediately provided by the P-portion. The smaller the Tn the larger/faster the slope
Page 76

Mixing valve in heating mode

This defines the position of mixing valve 1 (Y1 / Y2) when heating mode is active. This parameter has no impact on systems with hydraulically separate heating and cooling circuits.

Controls The valve provides control in heating and cooling mode.

Open The valve is used for control in cooling mode, it is open in heating mode.

Dewpoint monitoring Line no. Operating line
Dempentering 946 Lock time dewpoint monitor
947 Flow temp setp incr hygro
948 Flow setp incr start at r.h.
950 Flow temp diff dewpoint
Dewpt monitor locking time When the closes the connected dewpoint monitor detects the formation of condensation it contact, thereby deactivating the cooling .
time dewpoint monitor" set here starts when the contact opens again.
an be resumed only when the locking time has elapsed.
The dewpoint monitor must be assigned to the H input as "dewpoint monitor
Flow setp increase hygro To prevent the formation of condensation due to excess indoor air humidity, hydrostat can be used to implement a fixed increase in the flow temperat

As soon as the room humidity exceeds the value set on the hygrostat, its contact closes and the flow temperature setpoint is increased by the set amount.

The hygrostat must be assigned to the H input as "Flow setpt increase hygro".

Flow setp incr start at r.h. To prevent the formation of condensation due to excess indoor air humidity, a DC 0...10 V humidity measurement can be used to implement a continuous increase in the flow temperature.

If the relative humidity in the room exceeds the value defined by "Flow setp incr start at r.h." the flow temperature setpoint is increased continuously. The start of the increase (BZ 948) and the maximum increase (BZ 947) can be programmed.

The humidity sensor must be assigned to the H.. input as "Relative room humidity 10V".

dT TVKw Increase of flow temperature setpoint r.F. Relative humidity BZ Operating line

Page 77

Flow temp diff dewpoint Th

The dewpoint temperature is determined on the basis of the relative humidity of the indoor air and the associated room temperature.

To prevent the formation of condensation on surfaces, a minimum limit is applied to the flow temperature so that it remains above the dewpoint temperature by the value set here (950).

Function can be switched off using setting "- - -".

The humidity sensor must be assigned to an Hx.. input as "Relative room humidity 10V", and a room temperature sensor must also be available (assigned to the H.. input as "Room temperature 10V" or room unit).

TVKw Flow temperature setpoint cooling

  • TTP Dewpoint temperature
  • TA Outside temperature
  • BZ Operating line
Iffer storage Line no. Operating line
k/primary controllor 962 With buffer
No¦Yes
963 With prim contr/system pump
No ¦ Yes

With buffer storage tank

B ta

If a buffer storage tank is installed, it must be selected whether the cooling circuit may draw cooling energy from it.

No

Hydraulically speaking, the cooling circuit is connected upstream of the buffer storage tank, which means that it cannot draw any cooling energy from it. The refrigeration request is forwarded to the producer upstream of the buffer storage tank.

Yes

The cooling circuit is connected after the buffer storage tank. It draws cooling energy from the buffer storage tank and its temperature request is taken into account by buffer management.

Page 78

With primary controller / system pump

The setting defines whether the primary controller/system pump has an impact on the cooling circuit.

No

Hydraulically speaking, the cooling circuit is connected upstream of the primary controller/system pump and cannot draw any "precontrolled" cooling energy. The refrigeration request is always forwarded to the producer located upstream of the primary controller.

Yes

The cooling circuit is connected downstream from the primary controller/system pump. The primary controller ensures control of a valid refrigeration request, or the system pump is activated.

Remote control

Line no. Operating line
969 Optg mode changeover

In the case of external changeover via inputs H1 / H2 / H3, the operating mode to be used can be selected.

Page 79

6.5 DHW

The unit controls the DHW temperature according to the time program, or continuously, to the required setpoint. Priority of DHW charging over space heating can be selected.

The controller features a legionella function with a number of setting choices, fighting legionella viruses both in the storage tank and in the circulation pipe. The circulating pump is controlled according to the selectable time program and the operating mode.

Selection of operating mode ECO

ine no. Operating line
1601 Optg mode selection Eco
None ¦ Instantaneous water heater ¦ DHW storage tank ¦ Inst water heater + st tank

DHW charging can be switched on and off via the DHW operating mode button on the unit, or switched to ECO mode.

ECO mode applies only to select components listed here:

Instantaneous water heaters

ECO mode applies only to instantaneous water heaters. The keep hot function is deactivated.

DHW storage tank

ECO mode applies only to DHW storage tank.

In ECO mode, DHW heating is restricted by controllable heat sources. These heat sources are switched on only if the DHW temperature falls below the reduced level or if the "Legionella" function is active.

i The manual push can also be activated in ECO mode.

ECO is not possible when using a thermostat.

Instantaneous heater + storage tank

ECO mode applies only to instantaneous heater and DHW storage tank.

Page 80

Setpoints

Line no. Operating line
1610 Nominal setpoint
1612 Reduced setpoint
1614 Nominal setpoint max

The DHW can be heated up according to different setpoints. These setpoints are activated depending on the selected operating mode, thus leading to different temperature levels in the DHW storage tank.

Nominal DHW setpoint TWWmax Nominal DHW setpoint maximum

Release

Example

Line no. Operating line
1620 Release
24h/day ¦ Time programs HCs ¦ T'prog 4/DHW or low-tariff
24h / day

The DHW temperature is constantly maintained at the nominal DHW setpoint, independent of any time programs

Time programs HCs

The DHW setpoint changes between the nominal DHW setpoint and the reduced DHW setpoint according to the heating circuits' time program. The first switch-on point of each phase is shifted forward in time by 1 hour.

Example

Page 81
Time program 4 / DHW

DHW heating makes use of time program 4 of the local controller. The set switching times of that program are used to switch between the nominal DHW setpoint and the reduced DHW setpoint. This way, the DHW storage tank is charged independently of the heating circuits.

Example

Priority

Line no. Operating line 1630 Charging priority Absolute | Shifting | None | MC shifting, PC absolute

When both space heating and DHW heating demand heat, the "DHW priority" function ensures that during DHW charging the boiler's capacity is used primarily for DHW.

Absolute priority

Mixing and pump heating circuits are locked until the DHW reaches the required temperature level.

Shifting priority

If the heat source is no longer able to meet the demand, the mixing and pump heating circuits are restricted until the DHW reaches the required temperature level.

No priority

DHW charging occurs in parallel to heating mode. In the case of tightly sized boilers and mixing heating circuits, it can occur that the DHW setpoint will not be reached if space heating demands considerable amounts of heat.

Mixing heating circuit shifting, pump heating circuit absolute

The pump heating circuits remain locked until the DHW storage tank is heated up. If the heat source is no longer able to meet the demand, the mixing heating circuits will be restricted as well.

Page 82

"Legio

"Logionolla" function Line no. Operating line
Legionena function 1640 Legionella function
Off | Periodically | Fixed weekday
1641 Legionella funct periodically
1642 Legionella funct weekday
MondaySunday
1644 Legionella funct time
1645 Legionella funct setpoint
1646 Legionella funct duration
1647
1648 Legio funct circ temp diff
"Legionella" function Off
5 The "Legio nella" function is deactivated.
Periodical ly
The legionella function is repeated according to the interval set (1641). The legionella setpoint is attained via a solar plant, independent of the period of time set, the period of time will be newly started.
Fixed weekday
The leaion ella function can be activated on a fixed weekday (1642). When using
this setting heating up to the legionella setpoint takes place on the selected
weekday i ndependent of previous storage tank temperatures
weekaay, h
Legionella funct time Defines the time of day the "Legionella" function is started. The setpoint is
increased a at this time and DHW charging started.
If no time is parameterized, the "Legionella" function is started on the respective day together with the first normal release of DHW heating. If on this day is no Release (continuously reduced) the legionella function will be prepared.
alle function is politicated if DUNA booting is switched off (Operating mode
= Off or the e holiday function is activated if DHW heating is switched off (Operating mode
e holiday function controls the heating circuits) as soon as DHW heating
I back on (Operating mode = On or end of holidays).
Legionella function
setpoint
The DHW storage tank is heated to the entered setpoint (55-95°C).
For the "Legionella" function to be regarded as fulfilled, the sensor at the top of the
storage tank (B3) or both sensors (B3 and B31) must reach the legionella setpoint,
depending on the type of charging (line 5022); that setpoint must then be
maintained for the set duration of the function.
The higher the setpoint, the shorter the required dwelling time to safely kill off any
legionella in the DHW.
Legionella funct duration The define circulation The defined minimum period to maintain the legionella setpoint in the storage tank a circulation pipes.
Legionella funct circ During the period of time the legionella function is performed, the DHW circulating pump can be activated

During the period of time the legionella function is carried out, there is a risk of scalding when opening the taps.

Page 83

Legionella funct circ The circulating pump continues to operate until the temperature at circulation sensor B39 achieves setpoint (line 1645) minus the circulation difference (line 1648),

and the set duration of the function (line 1646) has elapsed.

The error message (Number: 127) is sent is the circulation pipe fails to achieve the required level for 48 hour.

If the temperature differential is not set, the temperature at sensor B39 is not monitored during the period of time the "Legionella" function is performed.

Circulating nump Line no. Operating line
1660 Circulating pump release
Time program 3/HC3 | DHW release | Time program 4/DHW | Time program 5
1661 Circulating pump cycling
1663 Circulation setpoint
Release of circulating pump When using setting "Release DHW", the circulating pump runs when DHW heating is released. The other settings as per the applicable time program.
Circulating pump cycling When the function is activated, the circulating pump is switched on for a fixed time of 10 minutes within the release time and then switched off again for 20 minutes.
Circulation setpoint The circulation pump Q4 switches on as soon as the set value is breach if sensor B39 is located in the DHW distribution pipe. The pump then operates fixed for 10 minutes or more until the setpoint is once again achieved. A set difference of 8 K always exists between the setpoint for the DHW storage tank and the setpoint for sensor B39 (Par 1663). This ensures that the circulation setpoint can be achieved again and keeps the circulation pump from running continuously.
Example 1
  • DHW setpoint: 55°C (nominal setpoint).
  • Circulation setpoint: 45°C
  • → The circulating pump is activated when the temperature at the sensor drops below 45 °C and then runs for at least 10 minutes.
Example 2
  • DHW setpoint: 50°C
  • Circulation setpoint: 45°C
  • → The circulating pump is activated when the temperature at the sensor drops below 42 °C (50 °C - 8 K) and then runs for at least 10 minutes.
Remote control Line no.
1680
Operating line Optg mode changeover Name Loff Lon Line

In the case of external changeover via the Hx inputs, the operating mode for DHW heating to be used after changeover can be selected.

Page 84

6.6 Consumer circuits and swimming pool circuit

Summary

Other consumers, in addition to heating circuits HC1-HC3 and the cooling circuit, can be connected or controlled (e.g. door heating, swimming pools, etc.).

The controller can receive its temperature request via an Hx input and control the corresponding pumps via a relay output QX.

For the consumer circuits, the following settings are available:

An appropriately defined Hx input on the device or extension module (line 5950, 5960 or 6046, 6054, 6062) required to use consumer circuits / swimming pool circuit. The input can be defined as follows:

  • Cons request CC1, 2
  • Cons request 10V CC1, 2
  • Release swimming pool generation

Operating lines 5750 and 5751 are available to select whether the consumer circuits are used for heating or cooling.

The pumps are to be connected to the appropriately defined multifunctional relay outputs Qx.. (line 5890-5896 and 6030 - 6038).

The consumer circuit pumps (Q15 / Q18) are put into operation when there is a heat or refrigeration request at the respective input, or when excess heat draw is called for.

The swimming pool circuit (Q19) starts up when the release is pending at the corresponding input Hx and the swimming pool temperature is below the setpoint (line 2056).

2 Line no. Operating line
- VK1 VK2 SC
п 1859 1909 1959 Flow temp setp cons request, Flow temp
setpoint
1860 1910 1960 Frost prot plant VK pump,
Frost prot plant pool pump
1874 1924 1974 DHW charging priority
No¦Yes
1875 1925 1975 Excess heat draw
Off ¦ On
1878 1928 1978 With buffer
No¦Yes
1880 1930 1980 With prim contr/system pump
No¦Yes

Consumer circuits 1, Swimming pool circu

i The current flow temperature setpoints of the consumer circuits appear on operating lines 8875 and 8885 and that of the swimming pool circuit on operating line 8895.

Page 85
Flow temperature setpoint The consumer circuit is controlled to the set flow temperature as soon as a heat or refrigeration request is pending via a correspondingly defined Hx input.
For the swimming pool circuit, a request from swimming pool sensor B13 is required, in addition to the release at the Hx input.
Frost protection for the plant Defines whether the consumer circuit pumps and the swimming pool pump shall be
put into operation when frost protection for the plant responds.
DHW charging priority Defines whether the DHW charging priority impacts the applicable consumer circuit/swimming pool circuit.
The setting "Yes" gives priority to charging DHW over the corresponding consumer circuit. The setting "No" supplies DHW and consumer circuit equally with energy.
Excess heat draw The heat source, input Hx or a storage tank can trigger an excess heat draw.
When dissipation of surplus heat is activated, it can be drawn by the consumer circuits/swimming pool circuit. This can be selected separately for each consumer circuit/the swimming pool circuit.
Off
Excess heat draw is deactivated.
On
Excess heat draw is activated.
With buffer No
Hydraulically speaking, the consumer circuit/swimming pool circuit is connected
upstream of the buffer storage tank and cannot draw any heat or cooling energy
from it. The heat or refrigeration request is forwarded to the heat/refrigeration
source upstream of the buffer storage tank.
Yes
buffer storage tank. It draws heat or cooling energy from the buffer storage tank
and its temperature request is taken into account by buffer management.
With primary controller /
system pump
No
Hydraulically speaking, the consumer circuit/swimming pool circuit is connected
upstream of the primary controller/system pump and cannot draw any
"precontrolled" heat or cooling energy. The heat or refrigeration request is always
forwarded to the heat/refrigeration source upstream of the primary controller.
Yes
The consumer circuit / swimming pool circuit is connected downstream of the
primary controller / system pump. The primary controller ensures control of a valid
heat or refrigeration request, or the system pump is activated.
Page 86

6.7 Swimming pool

Summary

The controller facilitates swimming pool heating with solar energy or heat generation based on separately adjustable setpoints. In the case of solar heating, it is possible to select priority of swimming pool heating over storage tank charging.

Setpoints
Line no. Operating line
2055 Setpoint solar heating
2056 Setpoint source heating

Setpoint solar heating

When using solar energy, the swimming pool is heated up to this setpoint.

  • 1 The "Protective collector overtemperature" function can reactivate the collector pump until the maximum swimming pool temperature is reached.
  • i Solar swimming pool heating can be dependent on a release via one or two Hx inputs.
  • Setpoint source heating When using heating by the heat source, the swimming pool is heated up to this setpoint.

Priority

Line no. Operating line
2065 Charging priority solar
Priority 1 | Priority 2 | Priority 3
Priority 1

Swimming pool charge has the highest priority.

Priority 2

Swimming pool charge is second priority (after buffer storage tank and DHW storage tank).

Priority 3

i

Swimming pool charge is without priority (after buffer storage tank, DHW storage tank, heating circuits, consumer circuits).

Release and priority can also be influenced using Hx inputs.

Page 87
Swimming pool temp
max
Line no. Operating line
2070 Swimming pool temp max

If the swimming pool temperature reaches the maximum limit set here, the collector pump is deactivated. It is released again when the swimming pool temperature drops 1 °C below the maximum temperature limit.

Line no. Operating line
2080 With solar integration

Solar integration

Plant hydraulics

This setting is made to indicate whether the swimming pool can be charged by solar energy.

Page 88

6.8 Primary controller/system pump

Summary

The primary controller allows lower or higher flow temperatures by mixing to obtain flow temperatures for heating/cooling zones with setpoints higher or lower than those of the common flow.

The system pump can be used to overcome the pressure drop to remote heating/cooling zones.

Limitations of flow temperature setpoint

Line no. Operating line
2110 Flow temp setpoint min
2111 Flow temp setpoint max
2112 Flow temp setp cooling min

Flow temp setpoint

□min/max

This limitation can be used to select a range for the flow temperature setpoint. If the requested flow temperature setpoint reaches the relevant limit and the demand for heat increases or decreases, the flow temperature setpoint is maintained at the maximum or minimum limit.

TVw Present flow temperature setpoint

TVmax Flow temp setpoint maximum

TVmin Flow temp setpoint minimum

Flow temp setp cooling min

This limitation can be used to define the low limit for the flow temperature setpoint in cooling mode.

Frost protection for the plant

ine no. Operating line
2120 Frost prot plant syst pump
Off ¦ On

Defines whether to start up the system pump if plant frost protection is triggered.

Page 89

Control of mixing valve

Line no. Operating line
2130 Mixing valve boost
2131 Mixing valve decrease
2132 Actuator type
2-position 3-position
2133 Switching differential 2-pos
2134 Actuator running time
2135 Mixing valve Xp
2136 Mixing valve Tn

Mixing valve boost To ensure adequate mixing, the actual value of the boiler flow temperature must be higher than the required setpoint of the mixing valve flow temperature, enabling that temperature to be controlled. The controller generates the boiler temperature setpoint based on the increase set here and the current flow temperature setpoint.

Mixing valve decrease To ensure adequate mixing in cooling mode, the actual value of the cooling flow temperature must be lower than the required temperature setpoint of the mixing valve flow since otherwise that temperature could not be controlled. The controller generates the refrigeration request based on the decrease set here plus the current flow temperature setpoint and sends the request to the refrigeration plant.

Actuator type Selection of the type of actuator determines the way the control action impacts the type of mixing valve actuator used.

Switching differential 2pos For a 2-position actuator, the 2-position switching differential must also be adapted. This is not required when using 3-position actuators.

Actuator: running time Setting the running time for the actuator used with the mixing valve.

Mixing valve Xp The proportional band Xp influences the controller's P-action.

Xp is the range by which the input signal (control variable) needs to change for the output signal (manipulated variable) to be adjusted across the whole correcting span.

The smaller Xp, the greater the change of the manipulated variable.

Mixing valve Tn Tn influences the controller's I-behavior.

Tn is the time required by the I-action with a given input signal (control variable) to bring about the same change to the manipulated variable as that produced immediately by the P-action.

The smaller Tn, the steeper/faster the slope.

Page 90
DHW charging priority

2145 DHW charging priority

DHW charging priority

DHW and primary controller are equally supplied with heat.
Yes

No

The DHW storage tank has priority for heat supply

Primary

controller/system pump

Line no. Operating line
2150 Primary contr/system pump

Primary controller/system

If the plant uses a buffer storage tank, it is to be selected here whether –

hydraulically speaking – the primary controller or the system pump is installed upstream of or downstream from the buffer storage tank.

Page 91

6.9 Boiler

Operating mode

Line no. Operating line
2200 Operating mode
Continuous operation | Automatic | Auto, extended running time
2203 Release below outside temp
2204 Release above outside temp
2205 With Economy mode
Off¦On DHW¦On
2208 Full charging buffer
Off¦On

Operating mode

Continuous operation

The boiler is constantly released and the minimum boiler temperature maintained is the parameterized TKMin.

The boiler will only be locked when all connected heating circuits are set to Protection mode and when there is no valid temperature request.

Automatic

The boiler will be released as soon as there is at least one valid temperature request. Once the boiler is released, the required minimum boiler temperature will always be maintained. The boiler will be locked when no valid temperature request is active. This means that with this operating mode, the boiler setpoint will be maintained at the required minimum only if a temperature request is active.

Auto mode, with extended burner running time

The boiler will be released as soon as there is at least one valid temperature request. When the boiler is released, the burner will be switched on when the boiler temperature drops below the request from the consumers. The required minimum boiler temperature is maintained only if the burner had to be switched on due to a request from one of the consumers. This means that since the boiler temperature can drop below its minimum, depending on the request, this operating mode leads to a smaller number of burner switching cycles and, therefore, longer burner on times.

Page 92

On

Always released.

Off

Boiler does not participate in full charging of the buffer storage tank.

On

Boiler participates in full charging of the buffer storage tank.

The boiler continues to operate until the storage tank is fully charged to achieve a long runtime

temp

temp

Full charging buffer

Page 93

Setpoints

Line no. Operating line
2210 Setpoint min
2211 Setpoint min OEM
2212 Setpoint max
2213 Setpoint max OEM

Flow temp setpoint min/max

The controlled boiler temperature setpoint can be limited by setpoint minimum and maximum. These limitations can be regarded as protective functions for the boiler

In normal operation, minimum limitation of the boiler temperature is the lower limit value of the controlled boiler temperature setpoint, depending on the boiler's operating mode.

In normal operation, maximum limitation of the boiler temperature is the upper limit value of the controlled boiler temperature setpoint and, at the same time, setpoint of the electronic limit thermostat (TR).

i The setting range of setpoint minimum and setpoint maximum is limited by the setpoint of manual control.

Example when using boiler operating mode "Automatic":

The boiler temperature limitation OEM is a limit value for the min and max boiler temperature setpoint limitation (TKMax and TKMin).

Page 94
Multistage burner Line no.
2220 Release Integral stage2/mod
2221 Reset Integral stagez/mod
Integrals for stage 2 The temperature-time integral is a continuous summation of the temperature differential over the time. In this case, the decisive temperature differential is the amount the temperature exceeds burner's switch-on or switch-off setpoint. Through the generation of the temperature-time integral, it is not only the period of time that is considered, but also the extent of the crossing. This means that when the exceed is significant, burner stage 2 will be released or locked earlier than when the exceed is small.
Release integral of
burner stage 2
When, with burner stage 1, the temperature drops below the switch-on setpoint the release integral set here, the controller will release burner stage 2.
Reset integral of burner
stage 2
When, with burner stages 1 and 2, the temperature drops below the switch-off setpoint by the reset integral set here, the controller will lock burner stage 2.
Modulating burner
(damper actuator/UX)
Line no.
2232
2233
2234
2235
Operating line
Damper actuator run time
Modulating Xp
Modulating Tn
Modulating Tv
Damper actuator run time run time To ensure that control of the modulating burner works optimally, actuator running time must be set.
i It must be noted that the running time to be set only relates to the range.
Example Running time of damper actuator (90°) = 120 seconds.
Minimum position of damper actuator = 20°.
Maximum position of damper actuator = 80°.
Hence, the damper actuator running time effective for the control is as follows:
120s*(80
90
0°−20°)
)° = 80s
Positioning pulses For control operation, running time-dependent minimum positioning pulses a active that are defined as follows:
Actuator running time TS Minimum pulse length
7.5 s - 14.5 s ~ 200 ms
15 s - 29.5 s ~ 300 ms
30 s – 59.5 s ~ 500 ms
60 s – 119.5 s ~ 1.10 s
>120 s ~ 2.20 s
Page 95
Mixing valve Xp By setting the right proportional band Xp for the mixing valves actuator, the control behavior of the actuator is matched to those of the plant (controlled system). The proportional band Xp influences the controller's P-action. The P band Xp is the range by which the input variable x (controlled variable) must change to adjust the output variable y (manipulated variable) throughout the entire positioning range. The smaller the value the greater the jump. The illustration depicts the reciprocal value 1/Xp = Kp.
Mixing valve Tn By setting the right integral action time Tn, the control action of the mixing valve's actuator is matched to the behavior of the plant (controlled system).
Tn influences the controller's I-response.
It is the required of the I-portion to undertake the same manipulated variable change at the given input signal (controlled variable), as immediately provided by the P-portion. The smaller the Tn the larger/faster the slope.
Modulating preheat Tv By setting the right derivative action time, the control action of the mixing valve's actuator is matched to the behavior of the plant (controlled system).
Tv influences the controller's D-behavior. With Tv = 0, the D-action is deactivated.
Page 96
Boiler / burner control
Line no. Operating line
2240 Switching differential boiler
2241 Burner running time min

Switching differential of the boiler

The boiler control is designed as a two-point controller for which a switching difference can be entered

Minimum burner running time

If a minimum burner running time is parameterized, the burner's switch-off point will be raised by half the boiler's switching differential within that minimum on time. If within the minimum burner running time, the boiler temperature exceeds the setpoint by more than the full switching differential, the burner will also be shut down before the minimum on time has elapsed. On completion of the minimum on time, the burner's switch-off point will be set to the boiler temperature setpoint plus half the switching differential. This function only acts on the first burner stage.

tBRmin Minimum burner running time חח

Burner ( 0= off 1 = on)

TKw Boiler temp setpoint TKY Actual boiler temperature

  • SDK Switching differential of the boiler
Page 97

Overtemperature protection

Image: ne no.Operating line250Pump overrun time

Pump overrun time

If the first burner stage is switched off, or if the boiler request becomes invalid, a forced signal will be delivered during the parameterized pump overrun time. Consumer pumps do not switch off during the period of time such a forced signal is active.

Minimum limitation of the boiler temperature

Line no. Operating line
2260 Prot boil startup consumers
2261 Prot boil startup boil pump
2262 Optimum start control

Protective start-up The protective boiler start-up accelerates boiler boost heating below the boiler minimum temperature by switching off, reducing the consumer load, depending on hydraulic possibilities, or keeping the boiler pump turned off.

Optimum start control. For the switched on function (Graphic 1, 2), the controller calculates, based on boiler temperature gradients, the burner switch-on point to keep from dropping below the minimum boiler temperature.

When the function is deactivated (graph 3), the controller will switch the burner on at TKmin.

• With optimum burner start control and about 65% load

Page 98

TKx Actual value of the boiler temperature Tkmin boiler temperature minimum limitation

Minimum limitation of Line no. Operating line
the return temperature 2270 Return setpoint min
2271 Return setpoint min OEM
2272 Return influence consumers
Return setpoint min If the boiler maintained return temperature falls below the return temperature setpoint, boiler return temperature becomes active.
Maintain re
of a return
turn temperature influences consumers, bypass pump control or the use controller.
Return setpoint ⊡min
OEM
The return temperature minimum limitation OEM is the lower limit value for the return setpoint minimum.
Return influence consumers If, with the temperatur boiler released, the return temperature falls below the set minimum e, a locking signal will be calculated.
  • With pro
    load), the
    locking s
  • With mix
    accordar
per pump circuits (heating circuit pump, DHW charging pump, external
e consumer pumps will be deactivated, or will stay deactivated, if the
signal exceeds the relevant threshold value
ting heating circuits, the flow temperature setpoint will be lowered in
the with the value of the locking signal
Page 99
Minimum limitation of Line no. Operating line
the return temperature 2282 Actuator running time
2283 Mixing valve Xp
2284 Mixing valve Th
2285 Mixing valve Tv
Mixing valve Xp By setting
behavior o
The propor
The P ban
change to
positioning
depicts the
the right proportional band Xp for the mixing valves actuator, the control f the actuator is matched to those of the plant (controlled system). rtional band Xp influences the controller's P-action. d Xp is the range by which the input variable x (controlled variable) must adjust the output variable y (manipulated variable) throughout the entire g range. The smaller the value the greater the jump. The illustration e reciprocal value 1/Xp = Kp.
Mixing valve Tn By setting
actuator is
Tn influence
It is the rec
change at
the P-porti
the right integral action time Tn, the control action of the mixing valve's
matched to the behavior of the plant (controlled system).
ces the controller's I-response.
quired of the I-portion to undertake the same manipulated variable
the given input signal (controlled variable), as immediately provided by
on. The smaller the Tn the larger/faster the slope.
Modulating preheat Tv By setting
actuator is
Tv influenc
the right derivative action time, the control action of the mixing valve's matched to the behavior of the plant (controlled system).
ces the controller's D-behavior. With Tv = 0, the D-action is deactivated.
Bypass pump Line no.
2290
Operating line Switching diff bypass pump
Switching diff bypass pump Control of form of 2-p the bypass pump "according to the boiler return temperature" is in the position control for which a switching differential must be set.
Bypass pump 2291 Control bypass pump
Parallel burner operation ¦ Return temp
Control of the bypass pump The boiler bypass pump improves the circulation of water through the boiler, thus preventing the boiler temperature from falling below a certain level.
Parallel with the operation of the burner
The boiler bypass pump is switched according to the burner's on / off signals.
According
The boiler
boiler retur
g to the boiler return temperature
bypass pump is switched according to the minimum limitation of the
m temperature and the switching differential of the bypass pump.
Page 100
Frost protection
2200 Diant protection beller nump

The boiler pump switches on based on the current outside temperature even though there is no heat request.

Boiler frost protection only works if plant frost protection on line 6120 is switched on.

Electronic TC

10 Unit thermostat function

TC function

The electronic temperature controller monitors boiler temperature (TKx) and triggers when the set limit value (TC setpoint) is exceeded, resulting in the shutdown of the burner.

During normal control operation and relay test, the Boiler temperature maximum limitation (TKMax) is used as the TR setpoint, whereas during manual operation, it switched to the "adjustable" value TKMaxHand.

The temperature controller can be switched on and off using the TC function parameter. It is, however, always active during manual operation.

TCw Setpoint for "electronic TC"

Loading...