Siemens RVS13 User Manual

O
N
0210.5Volt
2
RVS13... RVS53... AVS75...
AVS37... QAA75... QAA78...
User Manual
Edition 2.1 Controller series B CE1U2357en
6. July 2006
Building Technologies
QAA55...
HVAC Products
2/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6. July 2006
Contents
1 Summary ......................................................................................................... 8
1.1 Type summary................................................................................................. 9
2 Safety notes................................................................................................... 10
2.1 Product liability ..............................................................................................10
3 Mounting and installation............................................................................... 11
3.1 Regulations.................................................................................................... 11
3.2 Basic units RVS… ......................................................................................... 11
Planning......................................................................................................... 11
Mounting method........................................................................................... 11
Dimensions and drilling plan.......................................................................... 12
3.2.1 Connection terminals of RVS13.123 .............................................................12
3.2.2 Connection terminals of RVS13.143 .............................................................13
3.2.3 Connection terminals of RVS53.183 .............................................................13
Terminal markings ......................................................................................... 14
3.3 Extension module AVS75.390....................................................................... 16
Dimensions and drilling plan.......................................................................... 16
Connections................................................................................................... 16
3.3.1 Connection terminals of AVS75.390.............................................................. 16
Terminal markings ......................................................................................... 17
3.4 Operator unit AVS37.294 ..............................................................................18
Connections................................................................................................... 18
Dimensions.................................................................................................... 18
3.5 Room unit QAA55.110................................................................................... 19
Planning......................................................................................................... 19
installation...................................................................................................... 19
Connections................................................................................................... 19
Dimensions and drilling plan.......................................................................... 19
3.6 Room unit QAA75.61x................................................................................... 20
Planning......................................................................................................... 20
Mounting method........................................................................................... 20
Connections................................................................................................... 20
Dimensions and drilling plan.......................................................................... 21
3.7 Wireless components .................................................................................... 22
3.7.1 Radio module AVS71.390 ............................................................................. 22
Planning......................................................................................................... 22
Mounting method........................................................................................... 22
Connection ....................................................................................................22
Dimensions and drilling plan.......................................................................... 22
Radio link....................................................................................................... 22
3.7.2 Room unit QAA78.610................................................................................... 23
Planning......................................................................................................... 23
Mounting with base....................................................................................... 23
Mounting without base.................................................................................. 24
Connection / power supply ............................................................................ 24
Radio link....................................................................................................... 24
3/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products Contents 6. July 2006
Dimensions and drilling plan ..........................................................................25
3.7.3 Wireless outside sensor AVS13.399..............................................................26
Mounting method ...........................................................................................26
Connections ...................................................................................................26
Radio link .......................................................................................................26
Dimensions and drilling plan ..........................................................................27
3.7.4 Radio repeater AVS14.390 ............................................................................28
Mounting method ...........................................................................................28
Connections ...................................................................................................28
Radio link .......................................................................................................28
Dimensions and drilling plan ..........................................................................28
3.7.5 Checking the wireless components ...............................................................29
3.8 Power supply AVS16.290 ..............................................................................29
Mounting notes ..............................................................................................29
Mounting method ...........................................................................................29
Connections ...................................................................................................29
4 Commissioning ..............................................................................................32
4.1 Basic units......................................................................................................32
5 Handling.........................................................................................................33
5.1 QAA75... / QAA78... / AVS37… .....................................................................33
5.1.1 Operation .......................................................................................................33
Operating elements........................................................................................33
Display choices ..............................................................................................34
Selection of space heating mode...................................................................34
Selecting DHW heating..................................................................................35
Adjusting the room temperature setpoint .......................................................35
Presence button.............................................................................................35
Displaying information....................................................................................35
5.1.2 Programming .................................................................................................38
Setting principle .............................................................................................38
Example “Setting the time of day“..................................................................38
5.1.3 User levels .....................................................................................................39
Setting structure for “Enduser“.......................................................................40
Setting structure for ”Heating engineer“.........................................................40
5.1.4 Overview of settings.......................................................................................41
5.2 QAA55... ........................................................................................................51
5.2.1 Operation .......................................................................................................51
Operating elements........................................................................................51
Display choices ..............................................................................................51
5.2.2 Programming .................................................................................................51
6 The settings in detail ......................................................................................52
6.1 Time of day and date .....................................................................................52
6.2 Operator section ............................................................................................52
Operation and display ....................................................................................52
Heating circuit assignment.............................................................................53
Room sensor..................................................................................................54
Device data ....................................................................................................54
4/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products Contents 6. July 2006
6.3 wireless.......................................................................................................... 54
Binding........................................................................................................... 54
Device list wireless ........................................................................................ 54
6.3.1 time programs................................................................................................ 55
switching points ............................................................................................. 55
Standard program.......................................................................................... 55
6.3.2 Holidays......................................................................................................... 55
6.3.3 Heating circuits .............................................................................................. 56
operating mode.............................................................................................. 56
Setpoints........................................................................................................ 56
heating curve ................................................................................................. 57
ECO functions ...............................................................................................59
Flow temperature setpoint limitations ............................................................ 60
room influence ............................................................................................... 60
Room temp limitation..................................................................................... 61
Boost heating................................................................................................. 62
Quick setback ................................................................................................ 62
Optimum start / stop control ..........................................................................64
Increase of Reduced setpoint........................................................................ 64
Overtemp prot pump heating circuit ..............................................................65
Mixing valve control ....................................................................................... 65
Floor curing function ...................................................................................... 66
recooling ........................................................................................................ 67
6.4 Domestic hot water........................................................................................ 68
Setpoints........................................................................................................ 68
release........................................................................................................... 68
Priority ...........................................................................................................68
legionella function.......................................................................................... 69
circulating pump ............................................................................................69
6.5 Boiler .............................................................................................................70
Setpoints........................................................................................................ 70
Minimum limitation of the return temperature ................................................ 70
6.6 Solar .............................................................................................................. 71
Charging controller (dT)................................................................................. 71
Start function .................................................................................................71
Frost protection for the collector .................................................................... 71
Overtemperature protection for the collector ................................................. 72
Evaporation temperature of medium ............................................................. 73
6.7 DHW storage tank ......................................................................................... 73
Charging control ............................................................................................ 73
Overtemperature protection........................................................................... 73
recooling ........................................................................................................ 73
Electric immersion heater .............................................................................. 73
6.8 Configuration ................................................................................................. 75
Heating circuits 1 and 2 ................................................................................. 75
DHW sensor B3............................................................................................. 75
DHW controlling element Q3 ......................................................................... 75
output relay QX.............................................................................................. 76
Input sensor BX1,2 ........................................................................................ 77
input H1 / H2.................................................................................................. 77
Types of sensors/readjustments.................................................................... 80
Building and room model............................................................................... 81
Frost protection plant..................................................................................... 81
5/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products Contents 6. July 2006
Sensor state...................................................................................................81
parameter reset..............................................................................................81
Plant diagrams ...............................................................................................81
Device data ....................................................................................................82
6.9 Faults .............................................................................................................83
6.10 Maintenance / service ....................................................................................83
Maintenance functions ...................................................................................83
Chimney sweep .............................................................................................83
Manual control ...............................................................................................84
simulations .....................................................................................................84
Telephone customer service..........................................................................84
6.11 Input / output test ...........................................................................................85
6.12 State of plant..................................................................................................85
Messages.......................................................................................................85
6.13 Diagnostics heat source.................................................................................87
6.14 Diagnostics consumers..................................................................................88
6.15 List of displays ...............................................................................................89
6.15.1 Error code ......................................................................................................89
6.15.2 Maintenance code..........................................................................................89
7 Plant diagrams ...............................................................................................90
7.1 Basic diagram RVS13.123.............................................................................90
7.1.1 Basic diagram RVS13.12x with AVS75.390 ..................................................90
7.2 Basic diagram RVS13.143.............................................................................91
7.2.1 Basic diagram RVS13.14x with AVS75.390 ..................................................91
7.3 Basic diagram RVS53.183.............................................................................92
7.4 Extra functions ...............................................................................................92
Circulating pump ............................................................................................92
Electric immersion heater ..............................................................................92
Collector pump and collector sensor..............................................................93
Pump H1/2 .....................................................................................................93
Boiler pump....................................................................................................93
Bypass pump .................................................................................................94
Heating circuit pump HCP..............................................................................94
2. DHW sensor...............................................................................................94
Return sensor ................................................................................................95
Legend ...........................................................................................................95
8 Technical data................................................................................................97
8.1 Basic units RVS…..........................................................................................97
8.2 extension module AVS75.390........................................................................98
8.3 Operator unit and room units AVS37... / QAA7x… / QAA55.. .......................99
8.4 Power supply AVS16.290 ............................................................................100
8.5 Radio module AVS71.390............................................................................100
8.6 Wireless outside sensor AVS13.399............................................................101
8.7 Radio repeater AVS14.390 ..........................................................................101
8.8 sensor characteristics ..................................................................................103
6/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products Contents 6. July 2006
8.8.1 NTC 1 k .......................................................................................................103
8.8.2 NTC 10 k .....................................................................................................104
8.8.3 PT1000 ........................................................................................................ 104
7/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products Contents 6. July 2006
1 Summary
The present User Manual describes the products listed below and covers handling and configuration of the units for readers ranging from endusers to heating engineers.
ASN Name
RVS13.123 Basic unit boiler RVS13.143 Basic unit boiler RVS53.183 Basic unit boiler AVS75.390 Extension module AVS37.294 Operator unit QAA75.610 Room unit, wired QAA75.611 Room unit with backlight, wired QAA78.610 Room unit, wireless QAA55.110 Room unit AVS16.290 Power section AVS71.390 radio module AVS14.390 radio repeater AVS13.399 Wireless outside sensor
The following products are described in separate pieces of documentation:
QAC34 Outside temperature sensor NTC 1 k QAD36 Strap-on temperature sensor NTC 10 k QAZ36 Immersion temperature sensor NTC 10 k
8/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 1 Summary 6. Juli 2006
wireless
1.1 Type summary
Operation with room unit Operation with operator unit
D
T
F
(optionally together with room unit)
D
T
F
Wire-bound
B
A
C
2359Z03
D
T
B
A
C
2359Z01
A Basic unit RVS… B Power section AVS16… C Room unit QAA55… / QAA75… / QAA78… D Outside sensor AVS13… E Operator unit AVS37… F Radio module AVS71…
B
A
E
C
2359Z04
D
T
B
A
E
C
2359Z02
9/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 1 Summary 6. Juli 2006
2 Safety notes
2.1 Product liability
The products may only be used in building services plant and applications as
described in this document
When using the products, all requirements specified in chapters "Handling" and
"Technical data" must be satisfied
Local regulations (for installation, etc.) must be complied with
Do not open the units. If not observed, warranty by Siemens becomes void
10/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 2 Safety notes 6. Juli 2006
3 Mounting and installation
3.1 Regulations
Electrical installation
Planning
Mounting location
Mounting method
Prior to installing the controller, power must be turned off
The connections for mains and low-voltage are separated
The wiring must be made in compliance with the requirements of safety class II. This
means that sensor and mains cables must not be run in the same duct
3.2 Basic units RVS…
Air circulation around the unit must be ensured, allowing the unit to emit the heat produced by it. A clearance of at least 10 mm must be provided for the unit's cooling slots at the top and bottom of the housing. That space should not be accessible and no objects should be placed there. If the controller is enclosed in another (insulating) casing, a clearance of up to 100 mm must be observed around the cooling slots
The controller is designed conforming to the directives for safety class II devices mounted in compliance with these regulations
Power to the controller may only be supplied when completely fitted. If this is not observed, there is a risk of electric shock hazard near the terminals and through the cooling slots
The controller may not be exposed to dripping water
Permissible ambient temperature when mounted and when ready to operate:
0...50 °C
Power cables must be clearly segregated from low-voltage cables (sensors) observing a distance of at least 100 mm
boiler
Control panel
Housing for wall mounting
Screwed
On DIN rail
A2
A1
2359Z09
B1
A: Mounting / B: Removal
Note: To mount the controller on a DIN rail, a mounting clip is required!
B2
2359Z11
11/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Dimensions and drilling plan
Total height required
Dimensions in mm
L
BL1B1
2358M01
L B H L1 B1
RVS53… RVS13… AVS75.390
2359Z10
280.7 120.7 51.7 270 110
180.7 120.7 51.7 170 110
108.7 120.7 51.7 98 110
Dimension X:
For connectors with tongues: Minimum 70 mm For connectors without tongues: Minimum 60 mm
x
3.2.1 Connection terminals of RVS13.123
U s R Q P N L
QX1 N - - - -
S05011100002 0
1PRVS13.123/1 09
Q2 N
050111A 000020RVS13.123/109
Q3 N
SK2
SK1 4 S3
T2
T1
N L1
S3
L1
N L
2359Z46
M
BX2 M BX1 - - M H1 M B9 M B3 - - M B2 - -
n n n k h f b b b
b
CL-
CL+
CL-
CL+
CL-
CL+
X50
X60
X30
BSB
G+
CL-
CL+
12/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
3.2.2 Connection terminals of RVS13.143
G+ CL- CL
U t s R Q P N L
QX1 N
Y2 N
Y1
Q2 N
Q3 N
SK2
SK1 4 S3
T2
T1
N L1
S3
L1
050110A 000020RVS13.143/109
S050110000020
1PRVS13.143/109
N L
2359Z47
M
BX2 M BX1 M B1 M H1 M B9 M B3 - - M B2 - G+
n n p n k h f b b b
b
CL-
CL+
CL-
G+
CL-
CL+
CL+
CL-
CL+
X50
X60
X30
BSB
3.2.3 Connection terminals of RVS53.183
U t sU t sRQ PN L
- - - - - - -
S050113000020
1PRVS53.183/109
QX2 N
Y6 N
Y5
050113A 000020RVS53.183/109
Q6 N
QX1 N
Y2 N
Y1
Q2 N
Q3 N
SK2
SK1 4 S3
T2
T1
N L1
S3
L1
N L
2359Z48
- - - - - - M
n p n n p n k h f b b b
b
H2 M B12 M BX2 M BX1 M B1 M H1 M B9 M B3 - - M B2 - G+
CL-
CL+
CL-
CL+
CL-
CL+ - -
+
X50
X60
X30
BSB
13/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Terminal markings
Mains voltage
Low-voltage
Use Terminal Type of connector
L Phase AC 230 V basic unit N L AGP4S.05A/109
Protective earth N Neutral conductor L1 Phase AC 230 V burner S3 Output burner fault L1 Phase burner P AGP8S.07A/109
Protective earth N Neutral conductor T1 Burner 1st stage on T2 Phase burner 1st stage S3 Input burner fault 4 Input burner 1st stage hours run SK1 Safety loop Q AGP8S.02E/109 SK2 Safety loop N Neutral conductor R AGP8S.03A/109
Protective earth Q3 DHW charging pump / diverting valve N Neutral conductor S AGP8S.03B/109
Protective earth Q2 1st heating circuit pump Y1
1st heating circuit mixing valve opening
T AGP8S.04B/109
N Neutral conductor
Protective earth Y2 1st heating circuit mixing valve closing N Neutral conductor U AGP8S.03C/109
Protective earth QX1 1st multifunctional output N Neutral conductor S AGP8S.03B/109
Protective earth Q6 2nd heating circuit pump Y5 2nd heating circuit mixing valve opening T AGP8S.04B/109 N Neutral conductor
Protective earth Y6 2nd heating circuit mixing valve closing N Neutral conductor U AGP8S.03C/109
Protective earth QX2 2nd multifunctional output
Use Terminal Type of connector
BSB Service tool OCI700 - ­X60 Radio module AVS71.390 - ­X50 extension module AVS75.390 ­X30 Operator unit / boiler control panel -
AVS82.490/109 AVS82.491/109
CL+ BSB data AGP4S.02A/109 CL- BSB ground b
CL+ Room unit 2 data AGP4S.02A/109 CL- Room unit 2 ground b
CL+ Room unit 1 data AGP4S.02A/109 CL- Room unit 1 ground b AGP4S.03D/109
14/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Use Terminal Type of connector
G+ Room unit power supply 12 V
B2 Boiler sensor AGP4S.02B/109 M Ground f
B3 DHW sensor top AGP4S.02C/109 M Ground h
B9 Outside sensor AGP4S.02D/109 M Ground k
H1 Digital / DC 0...10 V input AGP4S.02F/109 M Ground n
B1 Flow temperature sensor HC1 AGP4S.02G/109 M Ground p
BX1 Multifunctional sensor input 1 AGP4S.02F/109 M Ground n
BX2 Multifunctional sensor input 2 AGP4S.02F/109 M Ground n
B12 Flow temperature sensor HC2 AGP4S.02G/109 M Ground p
H2 Digital input AGP4S.02F/109 M Ground n
15/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
3
Dimensions and drilling plan
Connections
3.3 Extension module AVS75.390
Planning, mounting location and mounting method are in compliance with the basic modules.
L
Dimensions in mm
BL1B1
2358M01
L B H L1 B1 AVS75.390
The AVS75.390 extension module must be connected to terminal
using the AVS83.490/109 connecting cable. The connectors are coded.
108.7 120.9 51.7 98 110
X50 of the basic unit
3.3.1 Connection terminals of AVS75.390
STN L
QX2
AVS75.390/109
S050110000020
N
1PAVS75.390/109
QX22 N
QX21
N L
050110A 000020
2359Z49
1
= Mixing heating circuit2
12
- - -
M
H2 M BX22 M BX21 - - - -
n n n
X30
16/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Terminal markings
Mains voltage
Low-voltage
Use Terminal Type of connector
L Phase AC 230 V basic unit N L AGP4S.03E/109
Protective earth N Neutral conductor QX21 Mixing valve opening T AGP8S.04B/109 N Neutral conductor
Protective earth QX22 Mixing valve closing N Neutral conductor S AGP8S.03B/109
Protective earth QX23 Heating circuit pump
Use Terminal Type of connector
X30 Operator unit / boiler control panel -
AVS82.491/109
BX21 Flow temperature sensor HC2 AGP4S.02F/109 M Ground n
H2 Digital input AGP4S.02F/109 M Ground n
17/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Mounting method
3.4 Operator unit AVS37.294
Installation Removal
2358Z30
2358Z31
2358Z32
Connections
Dimensions
Panel cutout
The AVS37.294 operator unit must be connected to terminal X30 of the basic unit using the AVS82.491/109 connecting cable.
The connectors are coded.
27
17
2358M03
96
144
90
42.4
(144)
0.5...3.0
0
+0.8
92
(96)
+1
138
0
2358M05
18/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Planning
installation
3.5 Room unit QAA55.110
The room unit should be located in the main living room while giving consideration to the following points:
The place of installation should be chosen such that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)
In the case of wall mounting, there must be sufficient clearance above the unit, enabling it to be fitted and removed
When the unit is removed from its base, power is disconnected so that the unit is out of operation.
2284Z33a
2284Z34a
Connections
Dimensions and drilling plan
The controller may not be exposed to dripping water
34
562
1
1 CL+ BSB data
2284Z40
2 CL- BSB ground
2284M02
1
6
9
9
96
7
4
2284Z35a
4,2
56
12
56
60
2359Z27
60
19/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Planning
Mounting method
3.6 Room unit QAA75.61x
The room unit should be located in the main living room while giving consideration to the following points:
The place of installation should be chosen such that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)
In the case of wall mounting, there must be sufficient clearance above the unit, enabling it to be fitted and removed
When the unit is removed from its base, power is disconnected so that the unit is out of operation.
Connections
2359Z25
2359Z20
2359Z26
2359Z24
Terminal Marking QAA75.610 QAA75.611
1 CL+ BSB data BSB data 2 CL- BSB ground BSB ground 3 G+ Reserved Power supply DC 12 V
2359Z21
20/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Dimensions and drilling plan
4,2
56
60
100
2359Z50
56
60
80
82
42
185
100
2359Z12
21/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Planning
Mounting method
3.7 Wireless components
The wireless components should be located such that transmission will be as interferencefree as possible. The following criteria must be observed:
Not in the vicinity of electrical cables, strong magnetic fields or equipment such as PCs, TV sets, microwave ovens, etc.
Not near larger metal structures or constructional elements with fine metal meshes such as special glass or special concrete
The distance to the transmitter should not exceed 30 meters or 2 floors
3.7.1 Radio module AVS71.390
The radio module extends the product range through the introduction of wireless communication. With this type of device, system components such as room units transmit data with no need for using cables.
Do not install the radio module inside metal casings (e.g. inside the boiler).
Connection
Dimensions and drilling plan
LED
A
Button
B
2359Z23
2359Z57
The prefabricated cable must be connected to terminal X60 of the controller. Prior to connecting the module, the basic unit must be disconnected from power!
2354Z11
43
Radio link
Establishment of the radio link is described in the following sections which cover the different radio-controlled units.
22/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Planning
Mounting with base
3.7.2 Room unit QAA78.610
The room unit should be located in the main living room while giving consideration to the following points:
The place of installation should be chosen such that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.5 meters above the floor)
In the case of wall mounting, there must be sufficient clearance above the unit, enabling it to be fitted and removed
2359Z26
2359Z20
2359Z25
2359Z21
2359Z22
23/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Mounting without base
Connection / power supply
Radio link
Establishing the link
Testing
2359Z61
The room unit is powered by three 1.5 V Alkali batteries type AA (LR06).
Establish the radio link in the vicinity of the radio module prior to mounting so that all system components are within easy reach.
Prerequisite for the radio link is that all components receive power, which means that the radio module must be correctly connected to the basic unit and the batteries must be correctly installed in the room unit.
1. Press the button on the installed radio module for at least 8 seconds until the LED on the radio module starts flashing at high frequency.
2. Press the OK button on the room unit to switch to programming.
3. Press the Info button for at least 3 seconds and select operating level “Commissioning“ with the setting knob. Then, press the OK button.
4. Select operating page “Wireless“ and press the OK button.
5. Select operating line “Used as“ (operating line 40) and make the appropriate selection. Then, press the OK button.
6. Select operating line “Binding“ (line 120). Then, press the OK button.
7. Set the setting knob to “Yes“ and press the OK button. Link establishment is started.
8. The display shows the progress of link establishment in %. This process can take 2 to 120 seconds.
9. The link is established when “Unit ready” appears and the LED on the radio module extinguishes.
The test is made to check the quality of the radio link.
The test can be stopped by pressing the ESC button
While the radio link can be opened on the boiler, the test should be made at the
location where the room unit will be installed
On the room unit, as described above (points 2 to 4), select operating page “Wireless“ and activate the test mode on operating line “Test mode“ (line 121). Example of a display during the test: The digits on the left show telegrams that have been sent, the digits on the right telegrams that have been received. The test will be ended after 24 telegrams. The test will be considered
Operator section Testmode
successful when at least 50 % of the telegrams
2359Z140
24/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Dimensions and drilling plan
sent have been received.
If the test was not successful, some other mounting location should be chosen or the AVS14.390 radio repeater should be used.
4,2
56
60
100
2359Z50
56
60
80
82
42
185
100
2359Z12
25/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Mounting method
3.7.3 Wireless outside sensor AVS13.399
The radio transmitter must be installed inside the building
The radio transmitter’s mounting location should be chosen such that batteries
can be easily changed
Radio transmitter Outside sensor
2359Z30
2359Z33
2359Z54
2359Z32
2359Z59
2359Z31
2359Z53
Battery
AAA
AAA
Battery transit tab
2359Z55
Connections
The outside sensor is to be connected via a 2-core cable; the wires are interchangeable. Power is supplied by two 1.5 V Alkali batteries type AAA (LR03).
Radio link
Tip: Establish the radio link in the vicinity of the radio module prior to mounting so
that all system components are within easy reach.
Prerequisite for the radio link is that all components receive power, which means that the radio module must be correctly connected to the basic unit and the batteries must be correctly installed in the room unit.
26/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Establishing the link
Testing
Dimensions and drilling plan
LED
1. Press the button on the radio module for at least 8 seconds until the LED on the radio module starts flashing at high frequency.
2. Press the button on the transmitter of the wireless
AAA
outside sensor for at least 8 seconds until that LED also starts flashing at high frequency.
3. The link is established when the LED on the radio
Button
module extinguishes.
4. Press the button on the transmitter of the wireless outside sensor briefly again until the LED extinguishes.
The test is made to check the quality of the radio link.
The test can be stopped by pressing the ESC button
While the radio link can be opened on the boiler, the test should be made at the
location where the room unit will be installed
1. Press button on the transmitter of the wireless outside sensor 3 to at most 8
seconds until the LED start flashing at low frequency.
2. When radio communication works, the LED on the radio module flashes briefly
at 10-second intervals.
3. After the test, press the button on the transmitter of the wireless outside sensor
again briefly until the LED extinguishes.
AAA
2359Z58
2359Z16
100
90
4,2
12
56
60
2359Z27
32
56
60
79,8
5,5
4
49,5
2524, 5
Ø 14,1
91,6
49,7
3
6
5,5
1811M02
1811M01
27/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Mounting method
Connections
Radio link
Establishing the link
Testing
Dimensions and drilling plan
3.7.4 Radio repeater AVS14.390
To establish the radio link, the device must be temporarily connected to power prior to mounting, enabling the radio link to be opened and tested
The radio repeater must be fitted inside the building
1
Power is supplied via the enclosed power pack. The wires are interchangeable.
Tip: Establish the radio link in the vicinity of the radio module prior to mounting so
that all system components are within easy reach.
Prerequisite for the radio link is that all components receive power, which means that the radio module must be correctly connected to the basic unit and power must be correctly supplied to the radio repeater.
1. Press the button on the radio module for at least 8 seconds until the LED on the radio module starts flashing at high frequency.
2. Press the button on the installed radio repeater until the LED starts flashing at high frequency.
3. The link is established when the LED on the radio module extinguishes.
The test is made to check the quality of the radio link.
The test can be stopped by pressing the ESC button
While the radio link can be opened on the boiler, the test should be made at the
location where the room unit will be installed
1. Press button on the radio repeater for 3 to at most 8 seconds until the LED starts flashing at low frequency.
2. When radio communication works, the LED on the radio module flashes briefly at 10-second intervals.
3. After the test, press the button on the radio repeater again briefly until the LED extinguishes.
2359Z30
2
2359Z33
Button
4,2
2359Z16
4
LED
2359Z31
2359Z56
100
12
90
32
56
60
2359Z27
56
60
28/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Mounting notes
Mounting method
3.7.5 Checking the wireless components
To check whether the connections to the required system components are operational, consult operating lines 130 through 135 on operating page “Wireless“ (operating level “Commissioning“).
3.8 Power supply AVS16.290
The boiler control panel is designed for installation in floor-standing or wall-hung oil or gas boilers and may only be used for that purpose. For installation, the following points must be observed:
Power to the control panel may be supplied only after it is completely fitted in the cut­out. Extension modules or dummy covers for which cutouts are provided must also be fitted beforehand
Dimensions of cutout 92 x 92 mm, sheet metal thickness 0.5 to 3.0 mm
The boiler control panel must be secured with the 4 clips provided on the panel
Power to the control panel may be supplied only after it is completely fitted in the cut-
out. Extensions or dummy covers for which cutouts are provided must also be fitted beforehand
Control panel wiring to the connection terminals does not feature strain relief so that the cables must be secured inside the boiler
The local regulations for electrical installation must be complied with.
installation Removal
2358Z27
2358Z28
2358Z29
Connections
Mains
Terminal Marking Leiterfarben
L Phase AC 230 V Blue
Protective earth Geen + yellow
N Neutral conductor Blue
Connection to basic unit
Terminal Marking Leiterfarben
1 L Phase AC 230 V basic unit Brown 2
Protective earth Geen + yellow 3 N Neutral conductor Blue 4 4 Phase AC 230 V burner Black 5 5 Input burner fault -
29/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Mains supply to RVS… basic unit
Dimensions
S1
1A
3B
2A
4B
Si
1
2
N
L
C2
1A
3B1
STB
PE
Si Fuse 6.3AT S1 Mains switch with green glow lamp STB Safety limit thermostat 110°C H1 Signal lamp (SLT tripped)
N1L
2358A16
L1 S3
H1
1
12345
35
80
90
96
96
48
2358M02
30/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
0.5...3.0
2358M04
(96)
92
+0.8
0
+0.8
92
(96)
0
31/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 3 Mounting and installation 6. Juli 2006
Prerequisites
functional check
Operating state
Diagnostics
4 Commissioning
To commission the units, the following steps must be carried out:
Prerequisite is correct mounting and correct electrical installation and, in the case of wireless systems, correctly working radio links to all the auxiliary units
Make all plant-specific settings. Special attention must be paid to operating page ”Configuration“. For that purpose, the relevant operating level is to be selected as follows:
Press the OK button on the room unit to switch to programming. Press the Info button for at least 3 seconds and select operating level “Commissioning“ with the setting knob. Then, press the OK button.
Make the functional check as described below
Reset the attenuated outside temperature
(operating page “Diagnostics of consumers“, operating line “Outside temp attenuated“ (operating line 8703))
To facilitate commissioning and fault tracing, the controller allows output and input tests to be made. With these tests, the controller’s inputs and outputs can be checked. To make the tests, select operating page “Input/output test“ and go through all available operating lines.
The current operating state can be checked on operating page “State“.
For detailed diagnostics of the plant, check operating pages “Diagnostics heat source“ and “Diagnostics consumer”.
Checking the LED
4.1 Basic units
LED off: No power supply LED on: Ready to operate LED flashes Local faults
LED
2359Z33
32/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 4 Commissioning 6. Juli 2006
Operating elements
A
A
Room unit
5 Handling
5.1 QAA75... / QAA78... / AVS37…
5.1.1 Operation
Selecting the heating mode
Selecting the DHW heating mode
Quitting the setting
Confirmation of setting
djustment of room Comfort setpoint Navigation and settings
Presence button
Operator unit
Displaying information
2359Z06
Selecting the DHW heating mode
Selecting the heating mode
Displaying information
Confirmation of setting
Chimney sweep function STB test
2359Z62
Quitting the setting
Service connector (BSB)
Manual control
djustment of room Comfort setpoint Navigation and settings
33/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Display choices
display
Display showing all available segments.
Selection of space heating mode
Press the button to switch between the different operating modes. The choice made is indicated by a bar which appears below the symbols.
Automatic operation Automatic operation controls the room temperature according to the time program.
Charactersitics of automatic operation:
Heating mode according to the time program
Temperature setpoints according to heating program “Comfort setpoint“ or
“Reduced setpoint“
Protective functions active
Automatic summer / winter changeover (ECO functions)
Continuous operation Continuous operation maintains the room temperature at the selected operating level.
Characteristics of continuous operation:
Heating mode with no time program
Protective functions active
Summer/winter heating limit and automatic 24-hour heating limit (ECO functions)
Protective mode When using Protection, the heating system is off. But it remains protected against frost (frost protection temperature), provided there is no power failure.
Characteristics of Protection:
Heating to the Comfort setpoint
Heating to the Reduced setpoint
Heating to the frost protection setpoint
Info level activated
Programming activated
ECO function active Heating system temporarily off
Process running – please wait
Change battery
Burner in operation (only oil / gas burner)
Holiday function active
Reference to heating circuit
Maintenance / special mode
Error messages
Xxxxxxxxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxxxxxxxx
Xxxxxxxxxxxxxxxxxxxxxxxxxxx
2358Z07
or
Heating to the Comfort setpoint Heating to the Reduced setpoint
During continuous operation with comfort setpoint: not active During continuous operation with reduced setpoint: Active
34/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Heating off
Temperature according to frost protection
Protective functions active
Automatic summer / winter changeover (ECO functions) and automatic 24-hour
heating limit active
Selecting DHW heating
The button is used to switch DHW heating mode on and off. The choice made is indicated by a bar which appears below the symbols.
DHW heating mode
On The DHW is heated according to the selected switching program.
Off No DHW heating, but the protective function is active.
DHW push
To do this, keep the DHW operating mode button on the operator or room unit depressed for at least 3 seconds.
The DHW push can also be started when:
The operating mode is “Off“
Operating mode changeover acts via H1 or centrally (LPB)
All heating circuits have assumed the holiday mode
Adjusting the room temperature setpoint
Turn the setting knob to increase or decrease the Comfort setpoint
.
For the Reduced setpoint
Press the OK button
Select operating page “Heating circuit“ and
Adjust the “Reduced“ setpoint
Each time you make a readjustment, wait at least 2 hours, allowing the room temperature to adapt.
Presence button
If the rooms are not used for a certain period of time, you can press the occupancy button to reduce the room temperature, thus saving heating energy. When the rooms are occupied again, press again the occupancy button to resume heating operation.
Heating to the Comfort setpoint Heating to the Reduced setpoint
The occupancy button is only active in automatic operation
The current selection is active until the next switching action according to the heating
program occurs
Displaying information
The Info button is used to display information.
35/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
AUTO
A
Room temperat ure
vailable information
Possible displays
Exceptional cases
4 8 12 16 20 24
0
2359Z140
Certain information lines are hidden, depending on the type of unit, unit configuration and operating state.
Depending on the type of unit, configuration and operating state, some of the info lines listed below may not appear. Displays:
Possible error messages from the error code list on page 6.15.1
Possible maintenance alarms from the maintenance code list on page 6.15.2
Possible special mode messages
Other displays:
Room temperature State DHW
Room temperature minimum State boiler
Room temperature maximum State solar
Boiler temp State solid fuel boiler
Outside temperature State buffer storage tank
Outside temp min Date and time of day
Outside temp max Telephone customer service
DHW temp 1
State heating circuit 1
State heating circuit 2
State heating circuit P
In exceptional cases, the display shows one of the following symbols:
Error messages If this symbol appears, a plant fault occurred. In that case, press the Info button to obtain more information.
AUTO
Maintenance or special mode If this symbol appears, a maintenance alarm is delivered or the plant has changed to special mode. In that case, press the Info button to obtain more information.
AUTO
Error 30:Flow sensor 1 Text3 Text4
4 8 12 16 20 24
0
2359Z140
Error 30:Flow sensor 1 Text3 Text4
4 8 12 16 20 24
0
2359Z140
A list of possible displays is given on page 88.
Reset function
The reset function for meters and the resettable parameters appears on the bottom line of the display, provided a reset is permitted on the current operating line (enduser / commissioning / heating engineer).
Reset ? yes
4 8 12 16 20 24
0
2359Z140
After activation with the OK button, the display shows a flashing “Yes“.
36/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
manual control
Setpoint adjustment with manual control
Chimney sweep function
SLT test
Reset ?
4 8 12 16 20 24
0
yes
2359Z140
After confirmation with the OK button, the relevant parameter or meters will be reset.
When manual control is active, the relays are no longer energized and deenergized according to the control state, but are set to a predefined manual operating state depending on their function. The burner relay energized in manual control can be deenergized by the electronic temperature controller (TR).
After manual control has been activated, a change to the basic display must be made. There, the maintenance / special mode symbol
appears. Press the Info button to switch to info display “Manual mode“, where the setpoint can be adjusted.
The chimney sweep function is activated by a short press (maximum 3 seconds) on the chimney sweep button. It produces the operating state required for making flue gas measurements.
The SLT test (SLT = safety limit thermostat) is activated by a long press (longer than 3 seconds) on the chimney sweep button. The button must be kept depressed during the entire test. If released, the test will be aborted. The SLT test is shown on the display.
The test must be made by qualified staff since the boiler temperature will be raised above the maximum limitations.
37/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
5.1.2 Programming
Setting principle
Example “Setting the time of day“
Settings that cannot be made directly with the help of operating elements are made through programming. For this purpose, the individual settings are structured in the form of operating pages and operating lines, thus forming practical groups of settings. The following example which shows the setting of the time of day and date shall explain this.
When pressing the ESC button, you go back one step; adjusted values will not be
If no setting is made for 8 minutes, the unit will automatically return to the basic
Operating lines may be hidden, depending on the type of unit, thev configuration and
operation Display example Description
1
2
adopted
display
user level
Room temperat ure
0
Time of day and dat e
Text3
Operator sect ion
0
AUTO
4 8 12 16 20 24
AUTO
4 8 12 16 20 24
You see the basic display. If the basic display is not shown, press the ESC button to return to it.
Press the OK button.
2359Z140
The bottom section of the display shows a number of operating pages. Turn the setting knob until operating page “Time of day and date“ appears.
To confirm, press the OK button.
2359Z140
3
AUTO
In the bottom section of the display, the first operating line of operating page
Time of day and d ate
Hours / minutes
4 8 12 16 20 24
0
“Time of day and date“ appears. Turn the setting knob until operating line “Hours / minutes“ appears.
2359Z140
To confirm, press the OK button.
4
AUTO
The display shows the hours flashing. Turn the setting knob until the hours of
Time of day and date
Hours / mi nutes
4 8 12 16 20 24
0
the time of day are correct.
To confirm, press the OK button.
2359Z140
38/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
5
AUTO
The display shows the minutes flashing.
Time of day and dat e
Hours / minut es
4 8 12 16 20 24
0
Turn the setting knob until the minutes of the time of day are correct.
2359Z140
To confirm, press the OK button.
6
AUTO
The settings are saved, the display stops flashing. You can continue to make other
Uhrzeit und Datum
Stunden / Minuten
4 8 12 16 20 24
0
settings, or you press the operating mode button to return to the basic display.
Example of menu structure
7
Now, you have returned to the basic display.
Time of day and date Operator section
Wireless
Time program heating circuit 1 Time program heating circuit 2 Time program heating circuit P
Holidays heating circuit 1
Diagnostics of consumers
Hours / minutes Month / day Year
Start of summer time End of summer time
Hours 1...24 h Minutes 0...60 min
5.1.3 User levels
Certain user levels only allow certain user groups to make settings. To reach the required user level, proceed as follows:
operation Display example Description
1
Room temperat ure
AUTO
You see the basic display.
If the basic display is not shown,
press the ESC button to return to it.
Press the OK button.
2359Z139
2
4 8 12 16 20 24
0
AUTO
2359Z140
You are on user level “Enduser“.
Press the Info button for 3 seconds.
Time of day and dat e
Text3
Operator sect ion
4 8 12 16 20 24
0
AUTO
2359Z140
You are given a choice of user
levels.
Turn the setting knob until the
required user level is reached.
Enduser Text3
Commissioning
4 8 12 16 20 24
0
39/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
2359Z140
Press the OK button.
3
To reach the OEM level, enter the relevant code.
Setting structure for “Enduser“
The example given here shows that certain user levels do not allow certain settings to be made. The example shows them highlighted. On the unit, they are hidden.
Enduser
Time of day and dat e
Text3
Operator sect ion
0
Commissioning
AUTO
4 8 12 16 20 24
Heating engineer
You are now on the required user level.
2359Z140
OEM
Time of day and date Operator section
Wireless
Time program heating circuit 1 Time program heating circuit 2 Time program heating circuit P
Holidays heating circuit 1
Diagnostics of consumers
Setting structure for ”Heating engineer“
Time of day and date Operator section
Wireless
Time program heating circuit 1 Time program heating circuit 2 Time program heating circuit P
Holidays heating circuit 1
Commissioning
Hours / minutes Month / day Year
Start of summer time End of summer time
Heating engineer
OEMEnduser
Hours / minutes Month / day Year Start of summer time End of summer time
Hours 1...24 h Minutes 0...60 min
2359Z139
Hours 1...24 h Minutes 0...60 min
Diagnostics of consumers
40/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
235 9Z139
5.1.4 Overview of settings
The table below shows all available settings up to the heating engineer level. However, certain operating lines may be hidden, depending on the type of unit.
Legend
Operating line
User level
Function
Time of day and date 1 E Hours/minutes - 00:00 23:59 hh:mm 2 E Day/month - 01.01 31.12 tt.MM 3 E Year - 2004 2099 jjjj 5 F Start of summertime 25.03 01.01 31.12 tt.MM 6 F End of summertime 25.10 01.01 31.12 tt.MM Operator section 20 E Language
German ¦ …
22 F Info
Temporarily ¦ Permanently
26 F Operation lock
Off ¦ On
27 F Programming lock
Off ¦ On
40 I Used as
Room unit 1 ¦ Room unit 2 ¦ Operator unit ¦Service unit
42 I Assignment room unit 1
Heating circuit 1 ¦ Heating circuits 1 and 2
44 I Operation HC2
Commonly with HC1 ¦ Independently
46 I Operation HCP
Commonly with HC1 ¦ Independently
48 I Action occupancy button
None ¦ Heating circuit 1 ¦ Heating circuit 2 ¦ Commonly
54 F Readjustment room sensor 0.0 -3 3 °C 70 F Software version - 0 99.9 ­wireless 120 I Binding
No ¦ Yes
121 I Test mode
Off ¦ On
130 I Room unit 1
Missing ¦ Ready ¦ No reception ¦ Change batt
131 I Room unit 2
Missing ¦ Ready ¦ No reception ¦ Change batt
132 I Outside sensor
Missing ¦ Ready ¦ No reception ¦ Change batt
133 I Repeater
Missing ¦ Ready ¦ No reception
134 I Operator unit
Missing ¦ Ready ¦ No reception ¦ Change batt
135 I Service unit
Missing ¦ Ready ¦ No reception ¦ Change batt
E = enduser I = commissioning F = heating engineer ZN = line number
Default value
German
Temporarily
Off
Off
Room unit 1
Heating circuit 1
Commonly with HC1
Commonly with HC1
Heating circuit 1
No
Off
Min
-
-
-
-
-
-
-
-
-
- -
- -
- -
- -
- -
- -
Max
Unit
41/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Operating line
User level
Function
138 I Delete all devices
No ¦ Yes
No
Default value
Min
Max
Unit
-
Time prog heating circuit 1 500 E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
Mo - Su
-
501 E 1st phase on 6:00 00:00 24:00 hh:mm 502 E 1st phase off 22:00 00:00 24:00 hh:mm 503 E 2nd phase on 24:00 00:00 24:00 hh:mm 504 E 2nd phase off 24:00 00:00 24:00 hh:mm 505 E 3rd phase on 24:00 00:00 24:00 hh:mm 506 E 3rd phase off 24:00 00:00 24:00 hh:mm 516 E Default values
No ¦ Yes
No
-
Time prog heating circuit 2 520 E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
Mo - Su
-
521 E 1st phase on 6:00 00:00 24:00 hh:mm 522 E 1st phase off 22:00 00:00 24:00 hh:mm 523 E 2nd phase on 24:00 00:00 24:00 hh:mm 524 E 2nd phase off 24:00 00:00 24:00 hh:mm 525 E 3rd phase on 24:00 00:00 24:00 hh:mm 526 E 3rd phase off 24:00 00:00 24:00 hh:mm 536 E Default values
No ¦ Yes
No
-
Time program 3 / HCP 540 E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
Mo - Su
-
541 E 1st phase on 6:00 00:00 24:00 hh:mm 542 E 1st phase off 22:00 00:00 24:00 hh:mm 543 E 2nd phase on 24:00 00:00 24:00 hh:mm 544 E 2nd phase off 24:00 00:00 24:00 hh:mm 545 E 3rd phase on 24:00 00:00 24:00 hh:mm 546 E 3rd phase off 24:00 00:00 24:00 hh:mm 556 E Default values
No ¦ Yes
No
-
Time program 4 / DHW 560 E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su
Mo - Su
-
561 E 1st phase on 6:00 00:00 24:00 hh:mm 562 E 1st phase off 22:00 00:00 24:00 hh:mm 563 E 2nd phase on 24:00 00:00 24:00 hh:mm 564 E 2nd phase off 24:00 00:00 24:00 hh:mm 565 E 3rd phase on 24:00 00:00 24:00 hh:mm 566 E 3rd phase off 24:00 00:00 24:00 hh:mm 576 E Default values
No ¦ Yes
No
-
Holidays heating circuit 1
42/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Operating line
User level
Function
Default value
Min
Max
Unit
642 E Start --.-- 01.01 31.12 tt.MM 643 E End --.-- 01.01 31.12 tt.MM 648 E Operating level
Frost protection ¦ Reduced
frost protection
-
Holidays heating circuit 2 652 E Start --.-- 01.01 31.12 tt.MM 653 E End --.-- 01.01 31.12 tt.MM 658 E Operating level
Frost protection ¦ Reduced
frost protection
-
Holidays heating circuit P 662 E Start --.-- 01.01 31.12 tt.MM 663 E End --.-- 01.01 31.12 tt.MM 668 E Operating level
Frost protection ¦ Reduced
frost protection
-
Heating circuit 1 710 E Comfort cooling
20.0 ZN 712 ZN 716 °C
setpoint 712 E Reduced setpoint 16 ZN 714 ZN 710 °C 714 E Frost protection setpoint 10.0 4 ZN 712 °C 716 F Comfort setpoint max 35.0 ZN 710 35 °C 720 E Heating curve slope 1.50 0.10 4.00 ­721 F Heating curve displacement 0.0 -4.5 4.5 °C 726 F Heating curve adaption
Off ¦ On
Off
-
730 E Summer/winter heating limit 18 / 8 30 °C 732 F 24-hour heating limit -3 / -10 10 °C 740 I Flow temp setpoint min 8 8 ZN 741 °C 741 I Flow temp setpoint max 80 ZN 740 95 °C 750 F room influence 20 / 1 100 % 760 F Room temp limitation 1 / 0.5 4 °C 770 F Boost heating 5 / 0 20 °C 780 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint
-
790 F Optimum start control max 0 0 360 min 791 F Optimum stop control max 0 0 360 min 800 F Reduced setp increase start / -30 10 °C 801 F Reduced setp increase end -15 -30 ZN 800 °C 820 F Overtemp prot pump circuit
Off ¦ On
On
-
830 F Mixing valve boost 10 0 50 °C 832 F Actuator:type
2-position ¦ 3-position
3-position
-
833 F Switching differential 2-pos 2 0 20 °C 834 F actuator: running time 120 30 873 s 850 I Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually
Off
-
851 I Floor curing setp manually 25 0 95 °C 860 I Recooling storage tank
Off ¦ Heating mode ¦ Always
Always
-
43/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Operating line
User level
Function
Default value
Min
Max
Unit
Heating circuit 2 1010 E Comfort cooling
20.0 BZ 1012 BZ 1016 °C
setpoint 1012 E Reduced setpoint 16 BZ 1014 BZ 1010 °C 1014 E Frost protection setpoint 10.0 4 BZ 1012 °C 1016 F Comfort setpoint max 35.0 BZ 1010 35 °C 1020 E Heating curve slope 1.50 0.10 4.00 ­1021 F Heating curve displacement 0.0 -4.5 4.5 °C 1026 F Heating curve adaption
Off ¦ On
Off
-
1030 E Summer/winter heating limit 18 − − − / 8 30 °C 1032 F 24-hour heating limit -3 / -10 10 °C 1040 I Flow temp setpoint min 8 8 BZ 1041 °C 1041 I Flow temp setpoint max 80 BZ 1040 95 °C 1050 F Room influence 20 / 0 100 % 1060 F Room temp limitation 1 / 0.5 4 °C 1070 F Boost heating 5 − − − / 0 20 °C 1080 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint
-
1090 F Optimum start control max 0 0 360 min 1091 F Optimum stop control max 0 0 360 min 1100 F Reduced setp increase start / -30 10 °C 1101 F Reduced setp increase end -15 -30 BZ 1100 °C 1120 F Overtemp prot pump circuit
Off ¦ On
On
-
1130 F Mixing valve boost 10 0 50 °C 1132 F Actuator:type
2-position ¦ 3-position
3-position
-
1133 F Switching differential 2-pos 2 0 20 °C 1134 F Actuator: running time 120 30 873 s 1150 I Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually
Off
-
1151 I Floor curing setp manually 25 0 95 °C 1160 F Recooling storage tank
Off ¦ Heating mode ¦ Always
Always
-
Heating circuit P 1300 E Operating mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
1310 E Comfort cooling
Automatic
20.0 BZ 1012 BZ 1016 °C
-
setpoint 1312 E Reduced setpoint 16 BZ 1014 BZ 1010 °C 1314 E Frost protection setpoint 10.0 4 BZ 1012 °C 1316 F Comfort setpoint max 35.0 BZ 1010 35 °C 1320 E Heating curve slope 1.50 0.10 4.00 ­1321 F Heating curve displacement 0.0 -4.5 4.5 °C 1326 F Heating curve adaption
Off ¦ On
Off
-
1330 E Summer/winter heating limit 18 − − − / 8 30 °C
44/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Operating line
User level
Function
Default value
Min
Max
Unit
1332 F 24-hour heating limit -3 / -10 10 °C 1340 I Flow temp setpoint min 8 8 BZ 1041 °C 1341 I Flow temp setpoint max 80 BZ 1040 95 °C 1350 F Room influence 20 / 0 100 % 1360 F Room temp limitation − − − − − − / 0.5 4 °C 1370 F Boost heating 5 − − − / 0 20 °C 1380 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot setpoint
Down to reduced setpoint
-
1390 F Optimum start control max 0 0 360 min 1391 F Optimum stop control max 0 0 360 min 1400 F Reduced setp increase start / -30 10 °C 1401 F Reduced setp increase end -15 -30 BZ 1100 °C 1420 F Overtemp prot pump circuit
Off ¦ On
1450 I Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦ Functional/curing heating¦ Manually
On
Off
-
-
1451 I Floor curing setp manually 25 0 95 °C 1455 I Floor curing setp current 0 0 95 °C 1456 I Floor curing day current 0 0 32 °C 1460 F Recooling storage tank
Off ¦ Heating mode ¦ Always
Always
-
Domestic hot water 1610 E Nominal setpoint 55 ZN 1612 ZN 1614 OEM °C 1612 F Reduced setpoint 40 8 ZN 1610 °C 1620 I Release
24h/day ¦ Time programs HCs ¦ Time program 4/DHW
1630 I Charging priority
Absolute ¦ Shifting ¦ None ¦ MC shifting, PC absolute
1640 F Legionella function
Off ¦ Periodically ¦ Fixed weekday
Time programs HCs
MC shifting, PC absolute
Fixed weekday
1641 F Legionella funct periodically 3 1 7 1642 F Legionella funct weekday
Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦ Friday ¦ Saturday ¦ Sunday
Montag
-
-
-
Days
1644 F Legionella funct time / 00:00 23:50 hh:mm 1645 F Legionella funct setpoint 65 55 95 °C 1646 F Legionella funct duration 30 / 10 360 min 1647 F Legionella funct circ pump
Off ¦ On
1660 I Release of the circulating pump
Time program 3/HCP ¦ DHW release ¦ Time program 4/DHW
1661 I Circulating pump cycling
Off ¦ On
On
DHW release
On
-
-
-
1663 F Circulaton setpoint 45 8 80 °C boiler 2210 F Setpoint min 40 ZN 2211 OEM
Setpoint manual
°C
control
2212 F Setpoint max 80
Setpoint manual
ZN 2213 OEM
°C
control
45/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Operating line
User level
Function
Default value
Min
Max
Unit
2270 F Rücklaufsollwert Minimum 8 8 95 °C Solar 3810 F Temp diff on 8 ZN 3811 40 °C 3811 F Temp diff off 4 0 ZN 3812 °C 3812 F Charg temp min DHW st tank / 8 95 °C 3830 F Collector start function / 5 60 min 3831 F Min run time collector pump 60 5 120 s 3840 F Collector frost protection / -20 5 °C 3850 F Collector overtemp prot / 30 200 °C 3860 F Evaporation heat carrier − − − − − − / 60 200 °C DHW storage tank 5020 F Flow setpoint boost 16 0 30 °C 5022 F Type of charging
With B3 ¦ With B3/B31 ¦ With B3, legio B3/B31
With B3/B31
-
5050 F Charging temp max 80 8 ZN 5051 OEM °C 5055 F Recooling temp 60 8 95 °C 5056 F Recooling heat gen/HC
Off ¦ On
5057 F Recooling collector
Off ¦ Summer ¦ Always
5060 F Electric immersion heater:operating mode
Substitute ¦ Summer ¦ Always
5061 F Electric immersion heater:release
24h/day ¦ DHW release¦ Time program4/ DHW
5062 F El immersion heater control
External thermostat ¦ DHW sensor
Off
Off
Substitute
DHW release
DHW sensor
-
-
-
-
-
Configuration 5710 I Heating circuit 1
Off ¦ On
5715 I Heating circuit 2
Off ¦ On
5730 I DHW sensor B3
Sensor ¦ Thermostat
5731 I DHW controlling element Q3
None ¦ Charging pump ¦ Diverting valve
5890 I Relay output QX1
None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Boiler pump Q1 ¦
Bypass pump Q12 ¦ Alarm output K10 ¦ 2nd pump speed
HC1 Q21 ¦ 2nd pump speed HC2 Q22 ¦ 2nd pump speed
HCP Q23 ¦ Heating circuit pump HKP Q20 ¦ H2 pump
Q18
5891 I Relay output QX2
None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Boiler pump Q1 ¦
Bypass pump Q12 ¦ Alarm output K10 ¦ 2nd pump speed
HC1 Q21 ¦ 2nd pump speed HC2 Q22 ¦ 2nd pump speed
HCP Q23 ¦ Heating circuit pump HKP Q20 ¦ H2 pump
Q18
5930 I Sensor input BX1
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ Return
sensor B7
5931 I Sensor input BX2
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ Return
sensor B7
On
On
Sensors
charging pump
None
None
None
None
-
-
-
-
-
-
-
-
46/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Operating line
User level
Function
5950 I Function input H1
Optg mode change HCs+DHW ¦ Optg mode changeover HCs ¦ Optg mode changeover HC1 ¦ Optg mode changeover HC2 ¦ Optg mode changeover HCP ¦ Heat generation lock ¦ Error/alarm message ¦ Min flow temp setpoint ¦ Heat request ¦ Pressure measurement
5951 I Contact type H1
NC ¦ NO
5952 I Min flow temp setpoint H1 70 8 Tkmax
Default value
Min
Optg mode change HCs+DHW
NO contact
Max
-
Unit
-
°C
(120°C) 5954 I Heat request 10V H1 100 5 130 °C 5956 I Pressure value 3.5V H1 5.0 0.0 10.0 bar 5960 I Function input H2
Optg mode change HCs+DHW ¦ Optg mode changeover HCs ¦ Optg mode changeover HC1 ¦ Optg mode changeover HC2 ¦ Optg mode changeover HCP ¦ Heat generation lock ¦ Error/alarm message ¦ Min flow temp setpoint ¦ Heat request ¦ Pressure measurement
5961 I Contact type H2
NC ¦ NO
Optg mode change HCs+DHW
NO contact
-
-
5962 I Min flow temp setpoint H2 70 8 TKmax °C 5964 I Heat request 10V H2 100 5 130 °C 5966 I Pressure value 3.5V H2 5.0 0.0 10.0 bar 6097 F Sensor type collector 0 -20 20 °C 6098 F Readjustm collector sensor 0 -3 3 °C 6100 F Readjustm outside sensor 0.0 -3.0 3.0 °C 6110 F Time constant building 15 0 50 h 6120 F Frost protection plant
Off ¦ On
6200 I Saving sensors
No ¦ Yes
6205 F Reset to default parameters
No ¦ Yes
On
No
No
-
-
-
6212 I Check no heat source 1 - 0 199999 ­6215 I Check no storage tank - 0 199999 ­6217 I Check no heating circuits - 0 199999 ­6220 F Software version - 0 99.9 ­error 6710 I Reset:alarm relay
No ¦ Yes
No
-
6740 F Flow temp 1 alarm / 10 240 min 6741 F Flow temp 2 alarm / 10 240 min 6743 F Boiler temp alarm / 10 240 min 6800 F History 1 - F Error code 1 - 0 255 ­6802 F History 2 - F
Error code 1
- 0 255 -
6804 F History 3 - F
Error code 1
- 0 255 -
6806 F History 4 - F
Error code 1
- 0 255 -
6808 F History 5 -
47/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Operating line
User level
F
Error code 1
Function
Default value
Min
Max
Unit
- 0 255 -
6810 F History 6 - F
Error code 1
- 0 255 -
6812 F History 7 - F
Error code 1
- 0 255 -
6814 F History 8 - F
Error code 1
- 0 255 -
6816 F History 9 - F
Error code 1
- 0 255 -
6818 F History 10 - F
Error code 1
- 0 255 -
Maintenance/service 7040 F Burner hours interval / 10 10000 h 7041 F Burner hrs since maintenance 0 0 10000 h 7042 F Burner start interval / 60 65535 ­7043 F Burn starts since maint 0 0 65535 ­7044 F Maintenance Interval − − − − − − / 1 240 7045 F Time since maintenance 0 0 240 7130 E Chimney sweep function
Off ¦ On
7140 E manual control
Off ¦ On
Off
Off
-
-
months months
7150 I Simulation outside temp - -50 50.0 °C 7170 I Telephone customer service - Input/output test 7700 I relay test
No test ¦ Everything off ¦ 1st burner stage T2 ¦ DHW pump Q3 ¦ Heating circuit pump Q2 ¦ Heat circ mix valve op Y1 ¦ Heat circ mix valve cl Y2 ¦ Heating circuit pump Q6 ¦ Heat circ mix valve op Y5 ¦ Heat circ mix valve cl Y6 ¦ Relay output QX1 ¦ Relay output QX2
No test
-
7730 I Outside temp B9 - -50 50 °C 7732 I Flow temp B1 - 0 140 °C 7734 I Flow temp B12 - 0 140 °C 7750 I DHW temp B3 - 0 140 °C 7760 I Boiler temp B2 - 0 140 °C 7820 I Sensor temp BX1 - -28 200 °C 7821 I Sensor temp BX2 - -28 200 °C 7840 I Voltage signal H1 0 0 10 Volt 7841 I Contact state H1
Open ¦ Closed
7846 I Contact state H2
Open ¦ Closed
7870 I Burner fault S3
0V ¦ 230V
7881 I 1st burner stage E1
0V ¦ 230V
Open
Open
-
-
0V -
0V -
State of plant 8000 I State heating circuit 1 - ­8001 I State heating circuit 2 - ­8002 I State heating circuit P - -
48/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Operating line
User level
Function
Default value
Min
Max
Unit
8003 I State DHW - ­8005 I State boiler - ­8007 I State solar - ­Diagnostics heat source 8300 I 1st burner stage T2
Off ¦ On
- -
8310 I Boiler temp - 0.0 140.0 °C 8311 I Boiler temp setpoint - 0.0 140.0 °C 8314 I Boiler return temp - 0.0 140.0 °C 8330 F Hours run 1st stage 0 0 65535 h 8331 F Start counter 1st stage - 0 199'999 ­8510 I Collector temp 1 - -28.0 200.0 °C 8511 I Collector temp 1 max 0 -28.0 200.0 °C 8512 I Collector temp 1 min 0 -28.0 200.0 °C 8513 I dT collector 1/DHW - -28.0 200.0 °C 8530 F Hours run solar yield - 00:00 65535 °C 8531 F Hours run collect overtemp - 00:00 65535 °C Diagnostics consumers 8700 I Outside temperature - -50.0 50.0 °C 8703 I Outside temp attenuated - -50.0 50.0 °C 8704 I Composite outside temperature - -50.0 50.0 °C 8730 I Heating circuit pump Q2
Off ¦ On
8731 I Heat circ mix valve op Y1
Off ¦ On
8732 I Heat circ mix valve cl Y2
Off ¦ On
- -
- -
- -
8740 I Room temp 1 - 0.0 50.0 °C 8741 I Room setpoint 1 - 4.0 35.0 °C 8743 I Flow temp 1 - 0.0 140.0 °C 8744 I Flow temp setpoint 1 - 0.0 140.0 °C 8760 I Heating circuit pump Q6
Off ¦ On
8761 I Heat circ mix valve op Y5
Off ¦ On
8762 I Heat circ mix valve cl Y6
Off ¦ On
- -
- -
- -
8770 I Room temp 2 - 0.0 50.0 °C 8771 I Room setpoint 2 - 4.0 35.0 °C 8773 I Flow temp 2 - 0.0 140.0 °C 8774 I Flow temp setpoint 2 - 0.0 140.0 °C 8800 I Room temp P - 0.0 50.0 °C 8801 I Room setpoint P - 4.0 35.0 °C 8803 I Flow temp setpoint P - 0.0 140.0 °C 8820 I DHW pump Q3
Off ¦ On
- -
8830 I DHW temp 1 - 0.0 140.0 °C 8831 I DHW temp setpoint - 8.0 80.0 °C 8832 I DHW temp 2 - 0.0 140.0 °C 8835 I DHW circulation temp - 0.0 140.0 °C
49/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Operating line
User level
Function
Default value
Min
Max
Unit
8950 I Common flow temp - 0.0 140.0 °C 8951 I Common flow temperature setpoint - 0.0 140.0 °C 9000 I Flow temp setpoint H1 - 5.0 130.0 °C 9001 I Flow temp setpoint H2 - 5.0 130.0 °C 9005 I Water pressure H1 - 0.0 10.0 bar 9031 I Relay output QX1
Off ¦ On
9032 I Relay output QX2
Off ¦ On
- -
- -
50/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Operating elements
Display choices
display
5.2 QAA55...
5.2.1 Operation
Heating to the Comfort setpoint
Heating to the Reduced setpoint
Display showing all available segments.
2358Z34
Burner in operation (only oil / gas burner)
Error messages
Configuration
settings
Used as
Direct adjustment
2354Z09
5.2.2 Programming
A long press on the occupancy button enables the service level to be accessed.
ru = 1 (factory setting) The room unit is addressed as room unit 1 ru = 2 The room unit is addressed as room unit 2
P1 = 1 (factory setting) Automatic storage:
A setpoint readjustment with the knob is adopted either by pressing the operating mode button or without any further confirmation (timeout).
P1 = 2 Storage with confirmation:
A setpoint readjustment with the knob is adopted only after pressing the operating mode button.
51/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 5 Handling 6. Juli 2006
Summer- / wintertime changeover
Operation and display
Info
6 The settings in detail
6.1 Time of day and date
The controller has a yearly clock with time of day, weekday and date. To ensure that the controller works properly, both the time of day and date must be correctly set.
Line no. Operating line
1 Hours/minutes 2 Day/month 3 Year 5 Start of summertime 6 End of summertime
The dates set for the changeover from wintertime to summertime, and vice versa, ensure that on the first Sunday after the set date the time of day will change from 02:00 (wintertime) to 03:00 (summertime), and from 03:00 (summertime) to 02:00 (wintertime).
6.2 Operator section
Line no. Operating line
20 Language 22 Info
26 Operation lock 27 Programming lock 40 Used as
Temporarily: After pressing the Info button, a change to the “predefined“ basic display
Temporarily Permanently
Room unit 1 Room unit 2 Operator unit Service unit
is made after a maximum of 8 minutes or by pressing the operating mode button (with the QAA78… only 2 minutes) .
Continuously: After pressing the Info button, a change back to the “new“ basic display
is made after a maximum of 8 minutes. The info value selected last will be adopted by the new basic display. This setting is not possible with the QAA78…
Operation lock
Programming lock
52/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
When operation lock is activated, the following operating elements can no longer be adjusted: Heating circuit operating mode, DHW operating mode, room Comfort setpoint (setting knob), and occupancy button.
When programming lock is activated, parameter values can still be displayed, but can no longer be changed.
Temporary deactivation of programming lock.
Within the programming level, the programming lock can temporarily be overridden. To do this, press the OK and ESC buttons simultaneously for 3 seconds. Temporary deactivation of the programming lock is maintained until programming is quit
Used as
Heating circuit assignment
assignment room unit 1
Operation HC2
Constant deactivation of programming lock.
First, make the temporary deactivation, then go to operating line “Programming lock“ (operating line 27) and deactivate the programming lock
This operating line is used to select usage of the operator unit. Depending on use, additional settings will then be required under “Assignment room unit 1“. When using several operator sections, it is thus possible to match individual units to specific requirements. If several operator units are used, each application may only be used once.
Room unit 1
The operator unit supports the heating circuits released on operating line “Assignment room unit 1” (operating line 42) and activated in the basic unit. Operating lines 42 through 48 remain active.
Room unit 2
The operator unit only supports heating circuit 2. Operating lines 42 through 48 remain inactive.
Operator unit / service unit
The operator unit supports the heating circuits activated in the basic unit. Operating line 42 remains inactive. Operating lines 44 through 48 are active.
When using this setting, the operator unit does not acquire and deliver the room temperature.
Line no. Operating line
42 assignment room unit 1
Heating circuit 1 Heating circuits 1 and 2
44 Operation HC2
Commonly with HC1 Independently
46 Operation HCP
Commonly with HC1 Independently
48 Action occupancy button
None Heating circuit 1 Heating circuit 2 Commonly
As room unit 1 (setting 40), the action of the relevant operator section on heating circuit 1 or on both heating circuits can be assigned. The latter is required especially when using 2 heating circuits and only 1 room unit.
Depending on operating line 40, the action of operation (operating mode button or setting knob) on room unit 1, on the operator unit or service unit can be defined for heating circuit 2.
Commonly with HC1
Operation acts jointly on heating circuits 1 and 2.
Independently
The action of operation is queried on the display as soon as the operating mode button is pressed or the setting knob is operated.
53/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Operation HCP
A
ction occupancy button
Room sensor
Device data
Depending on operating line 40, the action of operation (operating mode button or setting knob) on room unit 1, on the operator unit or service unit can be defined for heating circuit P.
Commonly with HC1
Operation acts jointly on heating circuits 1 and 2.
Independently
Operating mode changes or readjustments of the Comfort setpoints are to be made in programming mode.
The action of the occupancy button on the operator unit can be assigned to the relevant heating circuits. If only 1 heating circuit is assigned, the occupancy button always acts on that heating circuit.
Line no. Operating line
54 Readjustment room sensor
The temperature display can be readjusted.
Line no. Operating line
70 Software version
The display shows the current version of the room unit.
Binding
Binding
Test mode
Device list wireless
6.3 wireless
Line no. Operating line
120 Binding 121 Test mode
For more detailed information, refer to the descriptions of the wireless components in section 3.7.
When commissioning the system, the wireless peripheral devices (room unit) are assigned to the basic unit.
Usage of the operator unit (operating line 40) must be correctly set before the binding!
The test mode is used for checking the wireless communication. The test should be made when the installation is fully completed.
Line no. Operating line
130 Room unit 1
131 Room unit 2
132 Outside sensor
133 Repeater
134 Operator unit
135 Service unit
138 Delete all devices
Missing Ready No reception Change batt
Same as on operating line 130
Same as on operating line 130
Same as on operating line 130
Same as on operating line 130
Same as on operating line 130
54/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Delete all devices
Entering the switching times
switching points
Standard program
The wireless connection to all devices will be canceled. If radio communication is required again, a new binding must be established.
6.3.1 time programs
For the heating circuits and DHW heating, a number of switching programs are available. They are activated in "Automatic" operation and control the change of the temperature levels (and the associated setpoints) via the selected switching times.
The switching times can be set in a combined way, that is, either commonly for several days or in the form of separate times for individual days. When preselecting groups of days like for instance Mo...Fr and Sa...Su that use the same switching times, setting of the switching programs is simplified.
HC1 HC2 3/HCP 4/DHW
500 520 540 560 Preselection
501 521 541 561 1st phase on 502 522 542 562 1st phase off 503 523 543 563 2nd phase on 504 524 544 564 2nd phase off 505 525 545 565 3rd phase off 506 526 546 566 3rd phase off
HC1 HC2 3/HCP 4/DHW
516 536 556 576 Default values
All time programs can be reset to their default settings. Each time program has its own operating line to make the reset.
In that case, individual settings will be lost!
Line no. Operating line
Mo - Su Mo - Fr Sa - Su Mo - Su
Line no. Operating line
6.3.2 Holidays
HC1 HC2 HCP
642 652 662 Start 643 653 663 End 648 658 668 Operating level
The holiday program is used to switch the heating circuits to a selectable operating level according to calendar dates.
The holiday program can only be used in “Automatic“ operation
55/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Line no. Operating line
Frost protection Reduced
operating mode
Setpoints
Room temperature
6.3.3 Heating circuits
For the heating circuits, there are various functions available which can be individually set for each heating circuit.
Line no. Operating line
1300 Operating mode
The operating mode of heating circuits 1 and 2 is selected directly with the operating mode button while the operating mode of heating circuit P is to be selected in programming mode (operating line 1300).
This setting is used to switch between the different operating modes. The functionality corresponds to operating mode selection with the operating mode button. For details, refer to section ”Operation“.
Line no. Operating line
HC1 HC2 HCP
710 1010 1310 Com fort set point 712 1012 1312 Red uced set point 714 1014 1314 Frost protect ion setpoint 716 1016 1316 Comfort setpoint ma x
The room temperature can be shifted according to different setpoints. These setpoints become active depending on the selected operating mode, thus producing different temperature levels in the rooms. The ranges of adjustable setpoints result from the interdependencies, as this is shown in the following diagram.
Protection Automatic Reduced Comfort
TRK
TRKmax
TRR
TRF
0 2 4 6 8 10 12 14 16 18 20 22 24 26 °C
TRKmax Comfort setpoint max TRK Comfort cooling
setpoint TRR Reduced setpoint TRF Frost protection setpoint
2358Z01
Frost protection
In Protection mode, the room temperature is prevented from falling below a certain level. This means that the frost protection setpoint of the room temperature will be maintained.
Comfort setpoint max
The room temperature can be shifted according to different setpoints. These setpoints become active depending on the selected operating mode, thus producing different temperature levels in the rooms. The ranges of adjustable setpoints result from the interdependencies, as this is shown in the following graph.
56/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
heating curve
Heating curve slope
Line no. Operating line
HC1 HC2 HCP
720 1020 1320 Heating curve slope 721 1021 1321 Heating curve displacement 726 1026 1326 Heating curve adaption
The heating curve is used to generate the flow temperature setpoint, which is used to maintain a certain flow temperature level depending on the prevailing weather conditions. The heating curve can be adjusted with a number of settings, thus matching heat output and room temperature to individual needs.
When the heating curve slope is raised, the rate of flow temperature increase is the quicker the lower the outside temperature or, in other words, if the room temperature is not correct at low outside temperatures but at higher outside temperatures, the heating curve slope requires readjustment. Increase adjustment: Raises the flow temperature, especially when outside
temperatures are low.
Decrease adjustment: Lowers the flow temperature, especially when outside
temperatures are low.
Heating curve displacement
Heating curve adaption
°C
100
90
80
70
60
50
40
30
20 10 0 -10 -20
4
3
3,5
2,75 2,5 2,25
-30
2
1,75
1,5
1,25
1
0,75
0,5
0,25
2000D02
°C
Parallel displacement of the heating curve is used to change the flow temperature evenly across the entire outside temperature range or, in other words, if the room temperature is always too high or too low, a readjustment must be made with the help of parallel displacement. Adaptation of the heating curve is used by the controller to automatically adapt the heating curve to the prevailing conditions. In that case, a readjustment of the heating curve slope and parallel displacement is not required. It can only be switched on or off.
To provide this function, following must be observed:
A room sensor must be connected
The ”Room influence“ setting must be selected between 1 and 99
There should be no thermostatic radiator valves in the reference room (mounting
location of the room sensor) (If such valves are installed, they must be set to their fully open position)
57/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
ECO functions
Summer/winter heating limit
HC1 HC2 HCP
Line no. Operating line
730 1030 1330 Summer/winter heating limit 732 1032 1332 24-hour heating limit
The summer / winter heating limit is used to switch the heating on and off in the course of the year, depending on the temperature conditions. In “Automatic“ mode, switching on / off takes place automatically, so there is no need for the user to do this manually. By changing the setting, the respective periods of time will be shortened or extended. Increase: Winter operation will start
Summer operation will start
earlier
later
24-hour heating limit
Decrease: Winter operation will start
Summer operation will start
later
earlier
The function is not active in operating mode ”Continuously Comfort temperature“
The display will show ECO
To give consideration to the building’s thermal dynamics, the outside temperature will
be attenuated
Example:
T
°C
20
19
18
17
16
ON
OFF
501015
TAged
SWHG
SWHG
SWHG
+1 °C
-1 °C
2358Z08
t
SWHG Summer/winter heating limit TAged Attenuated outside temperature t Temperature t Days
The 24-hour heating limit is used to switch the heating on and off in the course of the day, depending on the outside temperature. This function is used primarily during intermediate seasons (spring and autumn), enabling the system to respond to short­time temperature variations.
Example:
Setting line E.g.
Comfort setpoint (TRw) 22°C 24-hour heating limit (THG) -3°C Changeover temperature (TRw-THG) heating off = 19°C
Switching differential (fixed) -1°C Changeover temperature heating on = 18°C
58/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
By changing the value entered, the respective heating periods will be shortened or extended. Increase: Heating mode will start
changeover to ECO
earlier,
later.
Decrease: Heating mode will start
The function is not active in operating mode ”Continuously Comfort temperature“
The display will show ECO
To give consideration to the building’s thermal dynamics, the outside temperature will
be attenuated
Flow temperature setpoint limitations
HC1 HC2 HCP
740 1040 1340 Flow temp setpoint min 741 1041 1341 Flow temp setpoint max
Using this limitation, a temperature range for the flow temperature setpoint can be defined. If the flow temperature setpoint demanded by the heating circuit reaches the relevant limit and heat request increases or decreases, the flow temperature setpoint
TV
max
akt
min
later,
changeover to ECO earlier.
Line no. Operating line
TVw
TVmin
TVmax
2358Z09
room influence
Pure weather compensation
0 10 20 30 40 50 60 70 80 90 100
°C
will be maintained at the maximum or minimum limit.
TVw Current flow temperature setpoint TVmax Flow temperature setpoint maximum Tvmin Flow temp setpoint min
HC1 HC2 HCP
Line no. Operating line
750 1050 1350 Room influence
Types of compensation: When a room temperature sensor is used, there is a choice of 3 different types of compensation.
Setting Type of compensation
− − − % Pure weather compensation *
1…99 %
Weather compensation with room influence *
100 % Pure room compensation
* Outside sensor required
The flow temperature is calculated via the heating curve, depending on the composite outside temperature. This type of compensation calls for a correct adjustment of the heating curve since in that case the control gives no consideration to the room temperature.
59/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Weather compensation with room influence
Pure room compensation
Room temp limitation
Deviations of the actual room temperature from the setpoint are acquired and taken into account when controlling the temperature. Heat gains can thus be considered, facilitating more accurate room temperature control. The authority of deviation is set as a percentage figure. The better the reference room (correct room temperature, correct mounting location, etc.) the higher the value can be set.
Example:
Approx. 60 % Good reference room conditions Approx. 20 % Unfavorable reference room conditions
To provide the function, following must be considered:
A room sensor must be connected
“Room influence“ must be set to a value between 1 and 99 %
There should be no thermostatic radiator valves in the reference room (mounting
location of the room sensor). (If such valves are installed, they must be set to their fully open position)
The flow temperature is controlled depending on the room temperature setpoint, the current room temperature and the progression of the room temperature. For example, a slight increase in room temperature causes an immediate drop of the flow temperature.
To provide the function, following must be considered:
A room sensor must be connected
“Room influence“ must be set to 100 %
There should be no thermostatic radiator valves in the reference room (mounting
location of the room sensor). (If such valves are installed, they must be set to their fully open position)
HC1 HC2 HCP
Line no. Operating line
760 1060 1360 Room temp limitation
In the case of pump heating circuits, a switching differential for temperature control must be set. The function necessitates a room temperature sensor.
Room temperature limitation does not work in the case of pure weather compensation.
°C
TRx
TRw+SDR
TRw
t
ON
P
OFF
TRx Actual value room temp TRw Room temperature setpoint SDR Room’s switching differential P Pump T Time of day
2371D02
Boost heating
HC1 HC2 HCP
Line no. Operating line
770 1070 1370 Boost heating
60/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Boost heating is used to reach the new setpoint more quickly when switching from the Reduced setpoint to the Comfort setpoint, thus reducing the heating up time. During boost heating, the room temperature setpoint is raised by the value set here. A higher setting leads to shorter heating up times, a lower setting to longer heating up times.
Boost heating is possible with or without room sensor.
Quick setback
Example
°C
TR
w
20
TR
15
x
DTRSA
2371D03
t
TRw Room temperature setpoint TRx Actual value of the room temperature DTRSA Increase of the room temperature setpoint
HC1 HC2 HCP
Line no. Operating line
780 1080 1380 Quick setback
Off Down to reduced setpoint Down to frost prot setpoint
During quick setback, the heating circuit pump is deactivated and, in the case of mixing circuits, the mixing valve is fully closed.
Function with room sensor:
When using the room sensor, the function keeps the heating switched off until the room temperature has dropped to the level of the Reduced setpoint or the frost level. When the room temperature has fallen to the Reduced level or the frost level, the heating circuit pump will be activated and the mixing valve will be released.
Function without room sensor:
Quick setback switches the heating off for a certain period of time, depending on the outside temperature and the building time constant.
Duration of quick setback when Comfort setpoint minus Reduced setpoint = 2 °C (e.g. Comfort setpoint = 20 °C, Reduced setpoint =18 °C).
Outside temperature
0 2 5 10 15 20 50
Building time constant:
gemischt:
15 °C 0 3.1 7.7 15.3 23 30.6 76.6 10 °C 0 1.3 3.3 6.7 10 13.4 33.5 5 °C 0 0.9 2.1 4.3 6.4 8.6 21.5 0 °C 0 0.6 1.6 3.2 4.7 6.3 15.8
-5 °C 0 0.5 1.3 2.5 3.8 5.0 12.5
-10 °C 0 0.4 1.0 2.1 3.1 4.1 10.3
-15 °C 0 0.4 0.9 1.8 2.6 3.5 8.8
-20 °C 0 0.3 0.8 1.5 2.3 3.1 7.7
Duration of quick setback in hours
61/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Quick setback is possible with or without room sensor
62/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Optimum start / stop control
Optimum start control max
Optimum stop control max
Line no. Operating line
HC1 HC2 HCP
790 1090 1390 Optimum start control max 791 1091 1391 Optimum stop control max
The change from one temperature level to the other is optimized in a way that the Comfort setpoint will be reached at the relevant switching time.
The change from one temperature level to the other is optimized in a way that the Comfort setpoint minus 1/4 °C will be reached at the relevant switching time.
Optimum start / stop control is possible with or without room sensor
0
Xein Xaus
24
Increase of Reduced setpoint
TRx
TRw
ZSP
Xein Switch-on time shifted forward Xaus Switch-off time shifted forward ZSP Time program TRx Actual value room temperature TRw Room temperature setpoint
1/4 °C
2358Z02
HC1 HC2 HCP
Line no. Operating line
800 1100 1400 Red setpoint increase start 801 1101 1401 Red setpoint increase end
The function is used primarily in connection with heating systems having
little spare
capacity (e.g. low-energy houses). In that case, the heating up time would be too long if outside temperatures are low. When the Reduced setpoint is raised, the rooms are prevented from cooling down to too low levels, thus shortening the heating up time when changing to the Comfort setpoint.
TR
TRwA2TRwA1
TRK
TRR
2358Z06
-15
TRwA1 Red setpoint increase start TRwA2 Red setpoint increase end
63/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
-5
TAgem
TRK Comfort setpoint
A
TRR Reduced room temperature setpoint Tagem composite outside temperature
Overtemp prot pump heating circuit
HC1 HC2 HCP
820 1120 1420 Overtemp prot pump circuit
In the case of heating plant with pump heating circuits, the flow temperature of the heating circuit can be higher than the flow temperature called for by the heating curve, due to higher requests from other heat consumers (mixing heating circuit, DHW charging, external heat demand), or a parameterized minimum heat pump temperature. As a result of this too high flow temperature, the pump heating circuit would assume excessive temperatures. Function “Overtemperature protection for pump heating circuits” ensures that the energy supply for pump heating circuits corresponds to the demand from the heating curve by activating / deactivating the pump.
Mixing valve control
HC1 HC2
830 1130 Mixing valve boost 832 1132 Actuator type
833 1133 Switching differential 2-pos 834 1134 Actuator running time
Only with RVS13.143 and RVS53.183
Mixing valve boost
For mixing, the actual value of the boiler flow temperature must be higher than the required setpoint of the mixing valve flow temperature since otherwise that temperature cannot be controlled. The controller generates the boiler temperature setpoint based on the increase set here and the current flow temperature setpoint.
ctuator:type
Selection of the type of actuator determines the way the control action impacts the type of mixing valve actuator used.
Switching differential 2­pos
For the 2-position actuator, the 2-position switching differential must also be adapted. This is not required when using 3-position actuators.
actuator: running time
Setting the actuator running time for the mixing valve used.
Floor curing function
HC1 HC2 HCP
850 1150 1450 Floor curing function
851 1151 1451 Floor curing setp manually 1455 Floor curing setp current 1456 Floor curing day current
Line no. Operating line
Line no. Operating line
2-position 3-position
Line no. Operating line
Off Functional heating (Fh) Curing heating (Bh) Functional/curing heating Curing heating/ functional heating Manually
64/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Floor curing function
The floor curing function ensures controlled drying of the floor. It controls the flow temperature in accordance with a certain temperature profile. Drying of the floor is ensured via the floor heating system and the mixing or pump heating circuit.
Off:
Function is deactivated.
Functional heating (Fh) :
The first part of the temperature profile is automatically completed.
Floor curing heating (Bh)
The second part of the temperature profile is traversed automatically.
Functional and floor curing heating
The entire temperature profile (first and second part) is traversed automatically.
Floor curing heating and functional heating
The entire temperature profile (first and second part) is traversed automatically.
Manually
It is not a temperature profile that is completed, but the floor setpoint is controlled manually.
Observe the relevant standards and regulations of the floor manufacturer!
Proper functioning is ensured only when the plant is correctly installed (hydraulic
system, electrical installation, settings)! If not observed, the floor might get damaged!
The function can be aborted prematurely by choosing Off
Maximum limitation of the flow temperature remains active
recooling
[TVw]
55
[Tag
2358Z10
]
50
45
40
35
30
25
20
0
11
X
1 25
57
Fh
5101518
Bh
Fh + Bh
X Start day Fh functional heating Bh floor curing heating
HC1 HC2 HCP
Line no. Operating line
860 1160 1460 Recooling storage tank
The surplus heat stored in the heat exchanger can be drawn off by space heating. This can be adjusted separately for each heating circuit. (Also refer to operating page “DHW storage tank“, operating line “Recoolign boiler/HC“)
65/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Setpoints
release
Priority
6.4 Domestic hot water
Line no. Operating line
1610 Nominal setpoint 1612 Reduced setpoint
The DHW can be heated up to different setpoints. These setpoints are activated depending on the selected operating mode, thus leading to different temperature levels in the DHW storage tank.
TWWN
TWWR
0 10 20 30 40 50 60 70 80 90 100 °C
TWWR DHW reduced setpoint TWWN DHW nominal setpoint TWWmax DHW nominal setpoint maximum
Line no. Operating line
1620 Release
24h/day Time programs HCs Time program 4 / DHW
24h/day
The DHW temperature is constantly maintained at the nominal DHW setpoint, independent of any time programs.
Example:
Time programs HCs
The DHW setpoint is switched between the nominal DHW setpoint and the reduced DHW setpoint according to the heating circuits’ time programs. The first switch-on point of each period is shifted forward in time by one hour.
Example:
Time program 4 / DHW
For DHW heating, time switch program 4 of the local controller is used. The set switching times of that program are used to switch between the nominal DHW setpoint and the reduced DHW setpoint. This way, the DHW is heated independently of the heating circuits.
Example:
Line no. Operating line
1630 Charging priority
Absolute Shifting None MC shifting, PC absolute
TWWmax
2358Z11
66/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
legionella function
legionella function
Legionella funct time
Legionella funct circ pump
circulating pump
When both space heating and DHW heating demand heat, the “DHW priority“ function ensures that during DHW charging the boiler’s capacity is used primarily for DHW.
Absolute priority
The mixing and pump heating circuit stay locked until DHW heating is finished.
Shifting priority
If the capacity of the heat source is not sufficient, the mixing and pump heating circuit will be restricted until DHW is heated up.
No priority
DHW heating and space heating take place at the same time. In the case of tightly sized boilers and mixing heating circuits, it can occur that the DHW setpoint will not be reached if space heating demands considerable amounts of heat.
Mixing heating circuit shifting, pump heating circuit absolute
The pump heating circuits stay locked until the DHW storage tank is heated up. If the capacity of the heat source is not sufficient, the mixing heating circuits will also be restricted.
Line no. Operating line
1640 Legionella function
Off Periodically Fixed weekday
1641 Legionella funct periodically 1642 Legionella funct weekday
Monday…Sunday
1644 Legionella funct time 1645 Legionella funct setpoint 1646 Legionella funct duration 1647 Legionella funct circ pump
Periodically
The legionella function is repeated according to the period of time set (line 1641). If the legionella setpoint is attained via a solar plant, independent of the period of time set, the period of time will be newly started.
Fixed weekday
The legionella function can be activated on a fixed weekday (operating line 1642). When using this setting, heating up to the legionella setpoint takes place on the selected weekday, independent of previous storage tank temperatures.
The legionella function is started at the time set. The DHW setpoint is raised to the adjusted legionella setpoint and DHW charging is started. If no time is parameterized, the legionella function is started on the respective day together with the first normal release of DHW heating. If on this day is no Release (continuously reduced) the legionella function will be prepared.
During the time the legionella function is performed, the DHW circulating pump can be activated.
During the time the legionella function is performed, there is a risk of scalding when opening the taps.
Line no. Operating line
1660 Circulating pump release
Time program 3 / HCP
67/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
DHW release Time program 4 / DHW
1661 Circulating pump cycling 1663 Circulaton setpoint
Circulating pump cycling
When the function is activated, the circulating pump is switched on for 10 minutes within the release time and then switched off again for 20 minutes.
Circulaton setpoint
If a sensor is installed in the DHW distribution pipe, the controller will monitor its actual value during the time the legionella function is performed. The adjusted setpoint must be maintained at the sensor during the adjusted dwelling time.
6.5 Boiler
Setpoints
Line no. Operating line
2210 Setpoint min 2212 Setpoint max
The controlled boiler temperature setpoint can be limited by selecting setpoint minimum and setpoint maximum. These limitations can be regarded as protective functions for the boiler. In normal operation, minimum limitation of the boiler temperature is the lower limit value of the controlled boiler temperature setpoint, depending on the boiler’s operating mode. In normal operation, maximum limitation of the boiler temperature is the upper limit value of the controlled boiler temperature setpoint and, at the same time, setpoint of the electronic limit thermostat (TR).
The setting range of setpoint minimum and setpoint maximum is limited by the setpoint of manual control.
Example when using boiler operating mode “Automatic“:
TK
°C 80
70
60
50
40
0
30
20 10 0 -10 -20
Minimum limitation of the return temperature
Line no. Operating line
2270 Return setpoint min
Return setpoint min
If the boiler return temperature falls below the return temperature setpoint, maintained boiler return temperature becomes active. Maintained boiler return temperature makes it possible to impact the consumers via the following settings:
“Return influence consumers“, using operating line line 2272
“Control bypass pump“, using operating line 2291
TK
mi n
TK
Legend TK Boiler temp
TK
max
w
SDK
°C
TA
TKw Boiler temperature setpoint ...TKmax Maximum limitation:boiler
TKmin Minimum limitation of the
SDK Switching diff Tagem Composite outside
2371Z26
gem
temperature
boiler temperature
temperature
68/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Charging controller (dT)
6.6 Solar
Line no. Operating line
3810 Temp diff on 3811 Temp diff off 3812 Charg temp min DHW st tank
To charge the DHW storage tank via the heat exchanger, a certain temperature differential between collector and storage tank is required, and the minimum charging temperature must be reached.
T
Tkol
SdEin
SdAus
TSp
On OFF
Tkol Collector temp On / Off Collector pump SdEin Temperature differential ON SdAus Temperature differential OFF
Start function
Line no. Operating line
3830 Collector start function 3831 Min run time collector pump
Collector start function
If the collector temperature cannot be accurately acquired during the time the pump is deactivated (especially in the case of vacuum tubes), the pump can be switched on from time to time.
Min run time collector pump
The function periodically activates the collector pump for at least the selected minimum running time.
Frost protection for the collector
Line no. Operating line
3840 Collector frost protection
When there is risk of frost at the collector, the collector pump will be activated to prevent the heat-carrying medium from freezing.
If the collector temperature falls below the frost protection temperature, the
collector pump will be activated: TKol < TKolFrost
When the collector temperature returns to a level of 1 °K above the frost protection
temperature, the collector pump will be deactivated again: TKol > TKolFrost + 1
Overtemperature protection for the collector
Line no. Operating line
235 8Z12
t
69/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
3850 Collector overtemp prot
If there is risk of overtemperature at the collector, storage tank charging is continued to reduce the amount of surplus heat. When the storage tank’s safety temperature is reached, charging will be stopped.
T
Tkol
TKolUe
1°C
TSp
TSpSi
TSp
On Off
TSpMax
TSpSi Storage tank safety temperature TSp Storage tank temperature TKolUe Collector temperature for overtemperature protection TSpmax Maximum charging temperature Tkol Collector temp On / Off Collector pump t Temperature t Time of day
2358Z14
1°C
t
70/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Evaporation temperature of medium
Line no. Operating line
3860 Evaporation heat carrier
If there is a risk of the heat carrying medium evaporating due to high collector temperatures, the collector pump will be deactivated to prevent it from exceeding certain temperature levels. This is a protective pump function.
6.7 DHW storage tank
Charging control
Line no. Operating line
5020 Flow setpoint boost 5022 Type of charging
Flow setpoint boost
Type of charging
Overtemperature protection
recooling
Recooling heat gen/HC
Recooling collector
Electric immersion heater
The DHW request to the boiler is made up of the current DHW setpoint plus the adjustable charging boost.
The storage tank can be charged using up to 2 sensors. It is also possible to combine partial charging with 1 sensor and the legionella function with 2 sensors (setting 3).
Line no. Operating line
5050 Charging temperature max
Solar energy charges the DHW storage tank up to the adjusted maximum DHW charging level.
The protective collector overtemperature function can reactivate the collector pump until the maximum storage tank temperature is reached.
Line no. Operating line
5055 Recooling temperature 5056 Recooling boiler/HC 5057 Recooling collector
For recooling the DHW storage tank, there are 2 functions available:
Heating energy can be drawn off either by space heating or the DHW storage tank.
This can be selected separately for each heating circuit (operating page “Heating circuit 1…“)
If the collector is cold, the energy can be emitted to the environment via the
collector’s surfaces
Line no. Operating line
5060 El imm heater optg mode
With B3
With B3/B31 With B3, legio B3/B31
Off Summer Always
Substitute
71/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
electric immersion heater:operating mode
electric immersion heater:release
Summer Always
5061 El immersion heater release
24h/day DHW release Time program 4 / DHW
5062 El immersion heater control
External control thermostat DHW sensor
Substitute
The electric immersion heater is only used if the boiler delivers a fault status message or if it has been shut down via boiler lock. This means that in normal situations the DHW is heated by the boiler.
Summer
The electric immersion heater is used as soon as all connected heating circuits have switched to summer operation. The DHW is again heated by the boiler as soon as at least one of the heating circuits has switched back to heating mode. But the electric immersion heater is also used if the boiler delivers a fault status message or has been shut down via boiler lock.
Always
DHW is heated with the electric immersion heater throughout the year. This means that with this application, the boiler is never required for DHW heating.
24h/day
The electric immersion heater is always released, independent of time programs.
Example:
2358Z24
El immersion heater control
0 6121824
h
DHW release
The electric immersion heater is switched on and off according to the DHW release.
Example:
0 612 24
17
2358Z25
h
Time program 4 / DHW
For the electric immersion heater, time program 4/DHW of the local controller is used.
Example:
0 6121824
2358Z26
h
External control thermostat
The storage tank is charged with an external control thermostat without setpoint compensation of the controller.
DHW sensor
72/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Heating circuits 1 and 2
DHW sensor B3
DHW controlling element Q3
output relay QX
The storage tank is charged with an external control thermostat, but with setpoint compensation of the controller. Important: To ensure that setpoint compensation works correctly, the external control thermostat must be set to its minimum setting value.
6.8 Configuration
HC1 HC2 - -
5700 5710 - - Heating circuit 1, 2
Using this setting, the heating cicuits can be switched on and off.
Line no. Operating line
5730 DHW sensor B3
Sensors
The collector calculates the switching points including the switching differential from the DHW setpoint and the acquired DHW storage tank temperature.
Control thermostat
The DHW temperature is controlled based on the switching state of a control thermostat connected to B3.
When using a DHW control thermostat, Reduced mode is not possible. This means that when Reduced mode is active, DHW heating with the control thermostat is locked.
The adjustment of the nominal DHW temperature setpoint must be equal to or higher
than the setpoint adjustment on the control thermostat (thermostat calibrated at switch-off point)
The flow temperature setpoint for DHW must be set to a minimum of 10 °C (with
impact on the charging time)
In that case, the DHW is not protected against frost
Line no. Operating line
5731 DHW actuating device Q3
None
No DHW charging via Q3.
Charging pump
The DHW is heated up with a pump connected to terminals Q3 / Y3.
Diverting valve
The DHW is heated up with a diverting valve connected to terminals Q3 / Y3. With this setting, pump Q2 becomes a boiler pump, provided the boiler pump is not yet defined for use at a multifunctional relay output QX...
Line no. Operating line
5890 Relay output QX1
Line no. Operating line
Sensors thermostat
None charging pump Diverting valve
73/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
None Circulating pump Q4 Electric immersion heater DHW K6 Collector pump Q5 H1 pump Q15 boiler pump Q1 bypass pump Q12 alarm output K10
2. 2nd pump speed HC1 Q21
2. 2nd pump speed HC2 Q22
2. 2nd pump speed HCP Q23 Heating circuit pump HCP Q20 H2 pump Q18
5891
Relay output QX2
None Circulating pump Q4 Electric immersion heater DHW K6 Collector pump Q5 H1 pump Q15 boiler pump Q1 bypass pump Q12 alarm output K10
2. 2nd pump speed HC1 Q21
2. 2nd pump speed HC2 Q22
2. 2nd pump speed HCP Q23 Heating circuit pump HCP Q20 H2 pump Q18
Only with RVS53.183
Depending on the selection made, setting of the relay outputs assigns appropriate extra functions to the basic diagrams. For detailed information, refer to section “Plant diagrams“.
DHW circulating pump Q4
The connected pump serves as a DHW circulating pump. Operation of the pump can be scheduled as required on operating page “DHW”, operating line “Circulating pump release”.
DHW electric immersion heater K6
Using the connected electric immersion heater, the DHW can be heated up according to operating page “DHW storage tank“, operating line “Electric immersion heater“. DHW heating mode must be switched on in addition.
The electric immersion heater must be equipped with a safety limit thermostat!
Collector pump Q5
When using a solar collector, a circulating pump for the collector circuit is required.
Pump H1 Q15
Pump H1 can be used for an additional consumer. Together with an external request for heat at input H1, it is possible to operate an air heater or similar.
Boiler pump Q1
The connected pump is used for circulating the boiler water.
Bypass pump Q12
The connected pump serves as a boiler bypass pump for maintaining the boiler return temperature.
Alarm output K10
74/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Input sensor BX1,2
input H1 / H2
The alarm relay signals faults, should they occur. The relay is energized with a delay of 2 minutes. When the fault is corrected, that is, when the error message is no longer present, the relay will be deenergized with no delay.
If the fault cannot immediately be corrected, it is still possible to reset the alarm relay. This is made on operating page “Faults“.
2. 2nd pump speed
This function facilitates the control of a 2-speed heating circuit pump, allowing the pump’s capacity to be lowered in reduced mode (e.g. during night setback). In that case, multifunctional relay QX is used to activate the 2nd pump speed in the following manner: 1st speed output Q2/Q6/Q20
2nd speed output Q21/Q22/Q23
Pump state
Off Off Off On Off Part load On On Full load Off On Unused / not permitted
Heating circuit pump HCP Q20
Pump heating circuit P will be activated.
Switching program
For heating circuit P, only time program 3/P is available. For more detailed information, refer to section "Time program".
Line no. Operating line
5930,5931 Sensor input BX1,2
None DHW sensor B31 Collector sensor B6 Return sensor B7
DHW circulation sensor B39
Depending on the selection made, setting of the sensor input assigns appropriate extra functions to the basic diagrams. For detailed information, refer to section “Plant diagrams“.
Function “Return sensor B7“ must be predefined by the boiler manufacturer.
Line no. Operating line
5950 Function input H1
Optg mode change HCs+DHW Optg mode changeover HCs Optg mode changeover HC1 Optg mode changeover HC2 Optg mode changeover HCP Heat generation lock Error/alarm message minimum flow temperature setpoint Heat request pressure measurement
5951 contact type input H1
NC NO
75/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Function of input H1 / H2
5952 Min flow temp setpoint H1 5954 Heat request 10V H1 5956 Pressure value 3.5V H1
Line no. Operating line
5960 Function input H2
Optg mode change HCs+DHW Optg mode changeover HCs Optg mode changeover HC1 Optg mode changeover HC2 Optg mode changeover HCP Heat generation lock Error/alarm message minimum flow temperature setpoint Excess heat discharge
Heat request (nur bei RVS13..)
pressure measurement (nur bei RVS13..)
5961 Contact type H2
NC NO
5962 Min flow temp setpoint H2 5964 5966
Heat request 10V H2 Pressure value 3.5V H2
(nur bei RVS13..) (nur bei RVS13..)
Changeover of operating mode
heating circuit
The operating modes of the heating circuits are switched to Protection mode via terminals H1/H2 (e.g. using a remote telephone switch).
Domestic hot water
DHW heating is locked only when using setting 1: HCs+DHW.
Heat generation lock
The heat source will be locked via terminals H1/H2. All temperature requests made by the heating circuits and by DHW will be ignored. Frost protection for the boiler will be maintained.
The chimney sweep function can be activated although heat generation lock is switched on.
Error/alarm message
Input H1 generates a controller-internal error message. If the “Alarm output” (relay outputs QX2-4, operating lines 5891 – 5894) is appropriately configured, the error message will be forwarded or displayed by an additional contact (e.g. external lamp or horn).
Minimum flow temperature setpoint TVHw
The adjusted minimum flow temperature setpoint will be activated when the switch connected to terminal H1 (e.g. an air heater function for a warm air curtain) closes its contact.
Heat request
Heat generation receives heat requests in the form of voltage signals (DC 0...10 V). The associated setpoint is to be adjusted on operating line 5954.
76/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Input H1 / H2
Minimum flow temperature setpoint H1 / H2
Heat request 10V H1/H2
Pressure measurement
The voltage signal active at input H1 is converted to a pressure value in a linear manner. The pressure value at 0.5 V is fixed at 0 bar. The pressure value at 3.5 V can be adjusted using parameter ”Pressure value 3.5 V H1” (line 5956).
NC
The contact is normally closed and must be opened to activate the selected function.
NO
The contact is normally open and must be closed to activate the selected function.
Function “Min flow temp setpoint” on operating line 5950 is activated via contact H1. The boiler maintains the temperature level set here until contact H1 opens again or until a higher heat request is delivered.
If several heat requests are received at the same time (LPB, contact H1, DHW, or from the controller itself), the highest of them will automatically be selected.
TVw
°C 80
70
60
50
40
0
30
30 20 10 0 -10
TVw
TVHw
2355Z20
TA
°C
gem
TVHw minimum flow temperature setpoint TVw Flow temperature setpoint
The voltage signal present at input H1/H2 is converted to a temperature value in a linear manner and then forwarded as the flow temperature setpoint. The flow temperature setpoint corresponding to the voltage level of 10 V can be adjusted with parameter “Heat request 10V H1/H2“.
77/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
[v]
10
S = 5°C
8
6
4
2
T = 50°C
T = 70°C
T = 90°C
T = 110°C
T = 130°C
2379Z26
0
T = maximum value of heat request S = minimum limitation of heat request = 5 °C
Pressure value 3.5V H1/H2
The voltage signal present at input H1/H2 is converted to a pressure value in a linear manner. The pressure value at 3.5 V can be adjusted with parameter ”Pressure value 3.5V H1/H2”. Example:
Types of sensors/readjustments
Line no. Operating line
6097 Sensor type collector
6098 Readjustm collector sensor 6100 Readjustm outside sensor
Sensor type collector
Selection of type of sensor used. The controller will use the respective temperature characteristic.
Readjustm collector sensor Readjustm outside sensor
The temperature display can be readjusted.
The measured value of the outside temperature can be readjusted by +/- 3 K.
10 20 30 40
p
4
2
1
0
NTC Pt 1000
50 60 70 80 90 100 110 120
D35 = 4bar
0.5 V
3.5 V
D
D
130
35
= 2bar
35
= 1bar
H1
[°c]
2359Z136
78/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Building and room model
Frost protection plant
Line no. Operating line
6110 Time constant building
When the outside temperature varies, the room temperature changes at different rates, depending on the building's thermal storage capacity. The above setting is used to adjust the response of the flow temperature setpoint to varying outside temperatures.
Example:
> 20
The room temperature will respond more
slowly to outside temperature variations.
10 - 20
This setting can be used for most types of buildings.
< 10
The room temperature will respond more
quickly to outside temperature variations.
Line no. Operating line
6120 Frost protection plant
The pumps are activated depending on the
current outside temperature, even if there
is no request for heat.
Outside temperature Pump Diagram ...-4 °C Continuously on ON
-5...1.5 °C On for 10 minutes at 6-hour intervals takt
1.5°C... Continuously off OFF
ON
Sensor state
parameter reset
Plant diagrams
takt
OFF
2371Z30
-2
01234-3-4-5-6 -1
TA °C
Line no. Operating line
6200 Save sensors
At midnight, the basic unit saves the states at the sensor terminals. If, after storage, a sensor fails, the basic unit generates an error message. This setting is used to ensure immediate saving of the sensors. This becomes a requirement when, for instance, a sensor is removed because it is no longer needed.
Line no. Operating line
6205 Reset to default parameters
All parameters can be reset to their default values. Exempted from this are the following operating pages: Time of day and date, operator section, radio communication, and all time programs.
Line no. Operating line
6212 Check no. heat source 1 6215 Check no. storage tank 6217 Check no. heating circuits
79/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Check no heat source 1
Check no storage tank
Check no. heating circuits
Example
To identify the current plant diagram, the basic unit generates a check number. The check number is made up of the lined up part diagram numbers. For the meaning of the numbers for the relevant operating lines, refer to the following tables:
Solar Oil / gas boiler
0 No solar
1 Solar with collector sensor
and pump
00 No boiler 01 1-stage burner 03 1-stage burner, boiler pump 05 1-stage burner, bypass pump 07 1-stage burner, boiler pump
Bypass pump
DHW storage tank
0 No DHW storage tank
1 electric immersion heater 2 Solar connection 4 charging pump 5 Charging pump, solar
connection 13 Diverting valve 14 Diverting valve, solar
connection
Heating circuit P Heating circuit 2 Heating circuit 1
0 No heating circuit 2 Heating circuit pump
00 No heating circuit 02 Heating circuit pump 03 Heating circuit pump,
mixing valve
00 No heating circuit 01 Circulation via boiler pump 02 Heating circuit pump 03 Heating circuit pump,
mixing valve
Heat source: Solar with collector sensor and pump,
1-stage burner and boiler pump Storage tank: Charging pump and solar connection Heating circuit 1: Heating circuit pump and mixing valve
B6
B2
K4
Q5
Q3
B3
B31
B9
Y1
Q2
B1
RG1
2358A14
Displays on the operator unit:
Check no heat source 1 101 Check no storage tank 5 Check no. heating circuits 3
The check numbers are always arranged from the right. Preceding 0s are not shown.
Device data
Line no. Operating line
6220 Software version
The software version indicated here represents the current version of the basic unit.
6.9 Faults
80/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
A
cknowledgements
Temperature alarms
Error history
When a fault is pending, an error message can be displayed on the info level by pressing the Info button. The display describes the cause of the fault.
Line no. Operating line
6710 Reset alarm relay
When a fault is pending, an alarm can be triggered via relay QX... The QX... relay must be appropriately configured. This setting can be used to reset the alarm relay.
Line no. Operating line
6740 Flow temp 1 alarm 6741 Flow temp 2 alarm 6743 Boiler temp alarm
The difference of setpoint and actual temperature is monitored. A control offset beyond the set period of time triggers an error message.
Line no. Operating line
6800…6819 History
The basic unit stores the last 10 faults in nonvolative memory. Any additional entry deletes the oldest in the memory. For each error entry, error code and time of occurrence will be saved.
Maintenance functions
Burner hours interval, burner start interval
Burner hours run, burner starts since maintenance
Chimney sweep
6.10 Maintenance / service
Line no. Operating line
7040 Burner hours interval 7041 Burner hrs since maintenance 7042 Burner start interval 7043 Burn starts since maint 7044 Maintenance Interval 7045 Time since maintenance
As soon as the selected number of burner hours run or the selected number of burner starts has elapsed, a maintenance alarm will be displayed. Counted for the alarm are the number of hours run and the number of starts of the first burner stage (input E1).
The current value is summated and displayed. On this operating line, the value can be reset to 0.
Line no. Operating line
7130 Chimney sweep function
The burner will be switched on. To achieve continuous burner operation, the only switch-off point used is the boiler temperature's maximum limitation (TKmax). First, all connected loads will be locked, enabling the boiler temperature to reach the setpoint of 64 °C as quickly as possible. When the minimum temperature of 64 °C is attained, the available heating circuits are switched on one by one, using a dummy load, to make sure that the heat generated by the boiler is drawn off so that the burner will remain in operation. For safety reasons, the maximum boiler temperature limitation (TKmax) remains active as long as the chimney sweep function is active.
The function is deactivated by setting -.- on this operating line, or automatically after a timeout of 1 hour.
81/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Manual control
Setpoint adjustment with manual control
simulations
Telephone customer service
Line no. Operating line
7140 Manual control
When manual control is activated, the relay outputs are no longer energized and deenergized according to the control state but are set to a predefined manual control state in accordance with their functions (see table below). The burner relay energized in manual control can be deenergized by the electronic temperature controller (TR).
Marking Output State Oil / gas boiler Burner 1st stage K4 On boiler pump Q1 On Bypass pump Q12 On Solar Collector pump Q5 Off DHW charging pump Q3 On Diverting valve Q3 Off circulating pump Q4 On
electric immersion heater K6 On Heating circuits 1...3 Heating circuit pump Q2
Mixing valve opening /
closing
Heating circuit pump 2nd
speed
extra functions pump H1 Q15 On Pump H2 Q18 On alarm output K10 Off
Q6 Q20 Y1/Y2 Y5/Y6 Q21 Q22 Q23
On
Off
On
After manual control has been activated, a change to the basic display must be made. There, the maintenance/special mode symbol
appears. Press the Info button to switch to info display “Manual mode“, where the setpoint can be adjusted.
Line no. Operating line
7150 Simulation outside temp
To facilitate commissioning and fault tracing, outside temperatures in the range from
-50 to +50 °C can be simulated. During simulation, the actual, the composite and the attenuated outside temperature will be overridden by the set simulated temperature. During simulation, calculation of the 3 mentioned outside temperatures continues and the temperatures are available again when simulation is completed.
The function is deactivated by setting -.- on this operating line, or automatically after a timeout of 5 hours.
Line no. Operating line
7170 Telephone customer service
Setting of phone number that appears on the info display.
6.11 Input / output test
Line no. Operating line
7700…7881
82/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Messages
State heating circuit
The input / output test is used to check the correct functioning of the connected components. When selecting a setting from the relay test, the relevant relay is energized, thus putting the connected component into operation. The correct functioning of the relays and wiring can thus be tested.
Important:
During the relay test, limitation of the boiler temperature by the electronic limit thermostat (TR) remains activated. Other limitations are deactivated.
Selector sensor values are updated within a maximum of 5 seconds. The display is made with no measured value correction.
6.12 State of plant
The current operating state of the plant is visualized by means of state displays.
Setting Operating line
8000 State heating circuit 1 8001 State heating circuit 2 8002 State heating circuit P 8003 State DHW 8005 State boiler 8007 State solar
Enduser (info level) Commissioning, heating engineer Limit thermostat has cut out Limit thermostat has cut out Manual control active Manual control active Floor curing function active Floor curing function active Overtemp protection active Restricted, boiler protection Restricted, DHW priority Restricted, buffer priority Heating mode restricted Forced discharging buffer storage tank Forced discharging DHW Forced discharging heat source Forced heat release Overrun active Forced heat release Opt start control + boost heating optimum start control Boost heating Heating mode Comfort Heating mode Comfort optimum stop control Heating mode Reduced Heating mode Reduced Frost protection room active Frost protection flow active Frost protection plant active Frost protection active
83/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
State DHW
State boiler
Summer operation Summer operation 24-hour Eco active Setback Reduced Setback frost protection Room temp lim Off Off
Enduser (info level) Commissioning, heating engineer Limit thermostat has cut out Limit thermostat has cut out Manual control active Manual control active Recooling via collector
Recooling active Discharging protection active Charging time limitation active Charging locked Charging lock active Forced, max stor tank temp Forced, max charging temp Forced, legionella setpoint Forced, nominal setpoint Forced charging active Charging electric, legionella setpoint Charging electric, nominal setpoint Charging electric, Red setpoint Charging electric, frost setpoint El imm heater released Charging el im heater Push, legionella setpoint Push, nominal setpoint Push active Charging, legionella setpoint Charging, nominal setpoint Charging, reduced setpoint Charging active Frost protection active Frost protection active Overrun active Overrun active Charged, max stor tank temp Charged, max stor tank temp Charged, max charg temp Charged, max charg temp Charged, legio temp Charged, legio temp Charged, nominal temp Charged, nominal temp Charged, Reduced temp Charged, Reduced temp Off Off
Recooling via Ht gen /HCs
Enduser (info level) Commissioning, heating engineer
SLT has cut out SLT has cut out SLT test active SLT test active Fault Fault Limit thermostat has cut out Limit thermostat has cut out Manual control active Manual control active Chimney sweep function, high-fire Chimney sweep function, low-fire Chimney sweep function active Locked, manually Locked, automatically Locked Minimum limitation, high-fire Minimum limitation, low-fire Minimum limitation active Minimum limitation active Protective startup, high-fire Protective startup, low-fire Return temperature limitation, high-fire Return temperature limitation, low-fire Released, high-fire Released, low-fire Overrun active In operation Released Released Frost protection plant active Frost protection active Off Off
84/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
State solar
Enduser (info level) Commissioning, heating engineer
Manual control active Manual control active Fault Fault Frost protection collector active Frost protection collector active Recooling active Recooling active Max stor tank temp reached Max stor tank temp reached Evaporation protection active Evaporation protection active Overtemp protection active Overtemp protection active Max charg temp reached Max charg temp reached charging DHW charging DHW Charg buffer stor tank Charg buffer stor tank Charg swimm pool Charg swimm pool Min charg temp not reached Temp diff insufficient Radiation insufficient Radiation insufficient
6.13 Diagnostics heat source
For making diagnostics, the various setpoints, actual values, relay switching states and meter readings can be displayed.
Line no. Operating line
8610…8699
85/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
6.14 Diagnostics consumers
For making diagnostics, the various setpoints, actual values, relay switching states and meter readings can be displayed.
Line no. Operating line
8700…9099
86/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
6.15 List of displays
6.15.1 Error code
Error code
10 Outside temperature sensor error 6 20 Boiler temperature 1 sensor error 9 30 Flow temperature 1 sensor error 6 32 Flow temperature 2 sensor error 6 40 Return temperature 1 sensor error 6 50 DHW temperature 1 sensor error 9 52 DHW temperature 2 sensor error 9 57 DHW circulation temperature sensor error 6 60 Room temperature 1 sensor error 6 65 Room temperature 2 sensor error 6 68 Room temperature 3 sensor error 6 73 Collector temperature 1 sensor error 6 83 BSB wire short-circuit 6 85 BSB radio communication fault 6 98 Extension module 1 fault (common fault status message) 6 109 Fault boiler temperature supervision 9 117 Upper pressure limit (crossed) 6 118 Critical lower pressure limit (crossed) 6 121 Alarm flow temperature 1 (HC1) 6 122 Alarm flow temperature 2 (HC2) 6 127 Legionellentemperatur nicht erreicht 6 131 Burner fault 9 146 Configuration error sensor / controlling element 3 171 Alarm contact input H1 active 6 172 Alarm contact input H2 active 6
Description of error Priority
6.15.2 Maintenance code
Maintenance code
1 Burner hours run exceeded 6 2 Burner starts exceeded 6 3 Maintenance interval exceeded 6 5 Water pressure heating circuit too low
10 Replace battery of outside sensor 6 18 Water pressure 2 heating circuit too low
87/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 6 The settings in detail 6. Juli 2006
Description of maintenance Priority
9
(pressure dropped below lower limit 1)
9
(pressure dropped below lower limit 2)
Standard diagram
7 Plant diagrams
The various applications are shown in the form of basic diagrams and extra functions. The basic diagrams show possible applications that can be implemented without using the multifunctional outputs.
7.1 Basic diagram RVS13.123
DHW heating with diverting valve
Q3
B3
B2
K4
B9
Q2
RG1
2358A01
Q3
B3
B2
K4
B9
RG1
Standard diagram
Q2
7.1.1 Basic diagram RVS13.12x with AVS75.390
Q3
B3
B2
K4
B9
Q2
RG1
2358A12
B9
Y1
Q2
B1
RG1
2358A15
88/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 7 Plant diagrams 6. Juli 2006
7.2 Basic diagram RVS13.143
Standard diagram
DHW heating with diverting valve
Q3
B3
B2
T2
B9
Y1
Q2
B1
RG1
2358A02
Q3
B3
B2
K4
B9
RG1
Standard diagram
Q2
7.2.1 Basic diagram RVS13.14x with AVS75.390
Q3
B3
B2
K4
Q6
B12
Y5
RG2
2358A12
B9
Y1
Q2
B1
RG1
2358A02
89/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 7 Plant diagrams 6. Juli 2006
Standard diagram
7.3 Basic diagram RVS53.183
Q3
B9
Y5
Y1
Circulating pump
B3
B2
K4
Q6
B12
RG2
7.4 Extra functions
The auxiliary functions can be selected via operating page “Configuration” and complement the basic diagrams of the respective controllers. The type and number of auxiliary functions that can be applied depend on the multifunctional outputs and inputs QX… or BX…
Q2
B1
RG1
2358A02
Electric immersion heater
Q3
Q4
B3
2358A04
90/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 7 Plant diagrams 6. Juli 2006
K6
Collector pump and collector sensor
Q3
B3
2358A05
Pump H1/2
B6
Q3
B3
Q5
B31
2358A06
Q15/18
2358A09
Boiler pump
91/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 7 Plant diagrams 6. Juli 2006
Bypass pump
B2
K4
Q1
2358A07
B2
K4
Heating circuit pump HCP
2. DHW sensor
Q12
2358A08
Q20
RG1
2358A10
92/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 7 Plant diagrams 6. Juli 2006
Return sensor
Q3
B3
B31
2358A11
B2
Legend
Mains voltage
K4
2358A13
B7
Diagram Function Connection
K4 Burner 1st stage T1, T2 Q1 boiler pump QX1, QX2 Q2 1. eating circuit pump,
Q2
boiler pump Q3 DHW charging pump / diverting valve Q3 Q4 circulating pump QX1, QX2 Q5 Collector pump QX1, QX2 Q6 2. Heating circuit pump Q6 Q12 Bypass pump QX1, QX2 Q15/18 Pump H1/2 QX1, QX2 Q20 heating circuit pump HCP QX1, QX2 Y1 1. eating circuit mixing valve Y1, Y2 Y5 2. eating circuit mixing valve Y5, Y6 K6 electric immersion heater QX1, QX2
93/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 7 Plant diagrams 6. Juli 2006
Low-voltage
Diagram Function Connection
B1 Flow temperature sensor HC1 B1 B12 Flow temperature sensor HC2 B12 B2 Boiler temperature sensor TK1 B2 B3 DHW sensor top B3 B31 2. DHW sensor bottom BX1, BX2 B6 Collector sensor BX1, BX2 B7 Return sensor BX1, BX2 B9 Outside sensor B9 RG1 Room unit 1 CL-, CL+ RG2 Room unit 2 CL-, CL+
94/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 7 Plant diagrams 6. Juli 2006
Power supply
Wiring of terminals
Functional data
Inputs
Outputs
Interfaces
Degree of protection and safety class
Standards, safety, EMV etc.
Climatic conditions
8 Technical data
8.1 Basic units RVS…
Rated voltage AC 230 V (±10%) Rated frequency 50 / 60 Hz Max. power consumption RVS13.123: 7.5 VA
RVS13.143: 8 VA
RVS53.x83: 10 VA Fusing of supply lines max. 10 AT (Power supply and outputs) solid or stranded wire (twisted or with
ferrule): 1 core: 0.5...2.5 mm 2 cores 0.5...1.5 mm2
Software class A Mode of operation to EN 60 730 1b (automatic operation) Digital inputs H1 and H2 safety extra low-voltage for potentialfree
low-voltage contacts: voltage with contact open: DC 12 V current with contact closed: DC 3 mA
Analog input H1 protective extra low-voltage operating
range: DC (0...10) V internal resistance: > 100 k
Mains inputs S3 and 4 AC 230 V (±10 %)
internal resistance: > 100 k
Sensor input B9 Sensor inputs B1, B2, B3, B12, BX1 and
BX2
Perm. sensor cables (copper)
with cross-sectional area: Max. length
Relay outputs Rated current range Max. switch-on current Max. total current (of all relays) Rated voltage range BSB Max. cable length
Basic unit – peripheral device Max. total length Min. cross-sectional area Degree of protection of housing to
NTC1 k (QAC34)
NTC10k (QAZ36, QAD36)
0.25 0.5 0.75 1.0 1.5 mm 20 40 60 80 120 m
AC 0.02…2 (2) A 15 A for
1 s
AC 6 A AC (24...230) V (for potentialfree outputs) 2-wire connection, not interchangeable
200 m 400 m (max. cable capacitance) 60 nF)
0.5 mm
2
IP 00
EN 60 529 Safety class to EN 60 730 low-voltage-carrying parts meet the
requirements of safety class II, if correctly
installed Degree of contamination to EN 60 730 normal contamination CE conformity to EMC directive
- Immunity
- Emissions Low-voltage directive
- Electrical safety
89/336/EEC
- EN 61000-6-2
- EN 61000-6-3 73/23/EEC
- EN 60730-1, EN 60730-2-9 Storage to EN 60721-3-1 class 1K3, temperature -20…65°C Transport to EN 60721-3-2 class 2K3, temperature -25…70 °C
2
2
95/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 8 Technical data 6. Juli 2006
Weight
Power supply
Wiring of terminals
Functional data
Inputs
Outputs
Interfaces
Degree of protection and safety class
Standards, safety, EMV etc.
Climatic conditions
Operation to EN 60721-3-3 class 3K5, temperature 0...50 °C
(noncondensing)
Weight (excl. packaging) RVS13.123: 566 g
RVS13.143: 566 g RVS53.183: 776 g
8.2 extension module AVS75.390
Rated voltage AC 230 V (±10%) Rated frequency 50 / 60 Hz Max. power consumption 4 VA Fusing of supply lines max. 10 AT (Power supply and outputs) solid or stranded wire (twisted or with
ferrule): 1 core: 0.5...2.5 mm 2 cores 0.5...1.5 mm
Software class A Mode of operation to EN 60 730 1b (automatic operation) Digital inputs H2 safety extra low-voltage for potentialfree
low-voltage contacts:
voltage with contact open: DC 12 V
current with contact closed: DC 3 mA
Analog input H2 protective extra low-voltage operating
range: DC (0...10) V
internal resistance: > 100 k
Mains input L AC 230 V (±10 %)
internal resistance: > 100 k
Sensor inputs BX6, BX7 NTC10k (QAZ36, QAD36)
Perm. sensor cables (copper)
with cross-sectional area: Max. length
Relay outputs Rated current range Max. switch-on current Max. total current (of all relays) Rated voltage range BSB Max. cable length
Basic unit – peripheral device Max. total length Min. cross-sectional area Degree of protection of housing to
0.25 0.5 0.75 1.0 1.5 mm 20 40 60 80 120 m
AC 0.02…2 (2) A 15 A for
1 s
AC 6 A AC (24...230) V (for potentialfree outputs) 2-wire connection, not interchangeable
200 m 400 m (max. cable capacitance) 60 nF)
0.5 mm
2
IP 00
EN 60 529 Safety class to EN 60 730 low-voltage-carrying parts meet the
requirements of safety class II, if correctly
installed Degree of contamination to EN 60 730 normal contamination CE conformity to
EMC directive
- Immunity
- Emissions Low-voltage directive
- Electrical safety
89/336/EEC
- EN 61000-6-2
- EN 61000-6-3
73/23/EEC
- EN 60730-1, EN 60730-2-9 Storage to EN 60721-3-1 class 1K3, temperature -20…65°C Transport to EN 60721-3-2 class 2K3, temperature -25…70 °C
2
2
2
96/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 8 Technical data 6. Juli 2006
Weight
Power supply
Room temperature measurement (only with QAA7x...)
Interfaces
Degree of protection and safety class
Standards, safety, EMV etc.
Climatic conditions
Weight
/ QAA55...)
Operation to EN 60721-3-3 class 3K5, temperature 0...50 °C
(noncondensing)
Weight (excl. packaging) 293 g
8.3 Operator unit and room units AVS37... /
QAA7x… / QAA55..
For devices without batteries:
Bus power supply
For devices with batteries:
Batteries Type of batteries
Battery life Measuring range 0..0.50 °C According to EN 12098:
Range 15...25 °C
Range 0..15 °C or 25...50 °C
Resolution AVS37../QAA75../QAA55..
Max. cable length basic unit – peripheral
device QAA78... BSB-RF
Degree of protection of housing to EN 60 529
Safety class to EN 60 730
Degree of contamination to EN 60 730 CE conformity to
EMC directive
- Immunity
- Emissions
Low-voltage directive
- Electrical safety
wireless For devices without batteries:
Storage to EN 60721-3-1 class 1K3, temperature –20...65 °C
Transport to EN 60721-3-2 class 2K3, temperature -20...70 °C
Operation to EN 60721-3-3 class 3K5, temperature 0...50 °C
For devices with batteries:
Storage to EN 60721-3-1 class 1K3, temperature -20…30 °C
Transport to EN 60721-3-2 class 2K3, temperature -20...70 °C
Operation to EN 60721-3-3 class 3K5, temperature 0...50 °C
Weight (excl. packaging)
BSB
3 pcs
1.5 V Alkali size AA (LR06) approx. 1.5 years
within tolerance of 0.8 K within tolerance of 1.0 K
1/10 K BSB-W, 2-wire connection, not interchangeable QAA75... / QAA55... = 200 m AVS37... = 3 m
frequency band 868 MHz IP20 für QAA7... / QAA55... IP40 for AVS37… IP20 (when mounted) normal contamination low-voltage-carrying parts meet the requirements of safety class III, if correctly installed normal contamination
89/336/EEC
- EN 61000-6-2
- EN 61000-6-3
73/23/EEC
- EN 60730-1, EN 50090-2-2
EN 300 220-1 (25-1000 MHz)
(noncondensing)
(noncondensing) AVS37.294: 160 g QAA75.61x: 170 g QAA78.610: 312 g QAA55.110: 115 g
97/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 8 Technical data 6. Juli 2006
Power supply
Functional data
Degree of protection and safety class
Standards, safety
8.4 Power supply AVS16.290
Nominal voltage Nominal frequency Fuse Max. power consumption Fuse protection for incoming cable
Schaltleistung STB
Degree of protection of housing to
EN 60 529
Safety class to EN 60 730
Degree of contamination to EN 60 730
CE conformity to
low-voltage directive electrical safety
AC 230 V (±10 %) 50 Hz 6,3 AT (5 x 20 mm)
0.4 VA max. 10 A
16 (12) A, AC 230 V (+-10 %), 50Hz
IP40 (when mounted)
low-voltage-carrying parts meet the requirements of safety class II, if correctly installed normal contamination
73/23/EEC EN 60730-1, EN 60730-2-9
Climatic conditions
Weight
Power supply
Interfaces
Degree of protection and safety class
Standards, safety, EMV etc.
Climatic conditions
Storage to EN 60721-3-1 class 1K3, temperature -20…65°C Transport to EN 60721-3-2 class 2K3, temperature -25…70 °C Operation to EN 60721-3-3 class 3K5, temperature 0...50 °C
(noncondensing)
Weight (excl. packaging) 310 g
8.5 Radio module AVS71.390
Powered via Basic units RVS… 5,5V DC Max. power consumption 0.11 VA max.
Connection to Basic units RVS…
(power supply, communication)
Radio transmitter BSB-RF
Degree of protection of housing to EN 60 529 Safety class to EN 60 730
Degree of contamination to EN 60 730 CE conformity to
EMC directive
- Immunity
- Emissions Low-voltage directive
- Electrical safety wireless
Storage to EN 60721-3-1 class 1K3, temperature -20…65°C Transport to EN 60721-3-2 class 2K3, temperature -25…70 °C Operation to EN 60721-3-3 class 3K5, temperature 0...50 °C
6-polar, prefabricated ribbon cable, fix
mounted
Length 1,5m
frequency band 868 MHz IP40
low-voltage-carrying parts meet the requirements of safety class III, if correctly installed normal contamination
89/336/EWG
- EN 61000-6-1, EN 61000-6-2
- EN 61000-6-3, EN 61000-6-4 73/23/EWG
- EN 60730, EN 50090-2-2 EN 300 220-1 , -3 (25-1000MHz) EN 301 489-1 , -3
(noncondensing)
98/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 8 Technical data 6. Juli 2006
Weight
Power supply
Interfaces
Degree of protection and safety class
Standards, safety, EMV etc.
Climatic conditions
Outside temperature acquisition
Weight
Weight (excl. packaging) 54 g
8.6 Wireless outside sensor AVS13.399
Batteries 2 pcs Type of batteries 1.5 V Alkali size AAA (LR03) Battery life approx. 2 years Radio transmitter BSB-RF
frequency band 868 MHz
Degree of protection of housing to EN 60 529 Safety class to EN 60 730
Degree of contamination to EN 60 730 CE conformity to
EMC directive
- Immunity
- Emissions Low-voltage directive
- Electrical safety wireless
For devices without batteries:
Storage to EN 60721-3-1 class 1K3, temperature –20...65 °C Transport to EN 60721-3-2 class 2K3, temperature -20...70 °C Operation to EN 60721-3-3 class 3K5, temperature 0...50 °C
For devices with batteries:
Storage to EN 60721-3-1 class 1K3, temperature -20…30 °C Transport to EN 60721-3-2 class 2K3, temperature -20...70 °C Operation to EN 60721-3-3 class 3K5, temperature 0...50 °C
Outside sensor QAC34/101
Measuring range -50...50 °C
Cable length max. 5 m
Weight (excl. packaging) radio transmitter: 160 g
IP20
low-voltage-carrying parts meet the requirements of safety class III, if correctly installed normal contamination
89/336/EEC
- EN 61000-6-2
- EN 61000-6-3
73/23/EEC
- EN 60730-1, EN 50090-2-2
EN 300 220-1 (25-1000 MHz)
(noncondensing)
(noncondensing)
outside sensor QAC34: 73 g 70 g cable
8.7 Radio repeater AVS14.390
Power supply
Interfaces
Degree of protection and safety class
99/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 8 Technical data 6. Juli 2006
Nominal voltage AC 230 V ±10 % (primary side AC/AC
adapter) Nominal frequency 50 Hz Max. power consumption 0.5 VA max.
Radio transmitter BSB-RF
Degree of protection of housing to EN 60 529 Safety class to EN 60 730
±6 %
frequency band 868 MHz IP20
low-voltage-carrying parts meet the requirements of safety class III, if correctly installed
Standards, safety, EMV etc.
Climatic conditions
Weight
Degree of contamination to EN 60 730 CE conformity to
EMC directive
- Immunity
- Emissions Low-voltage directive
- Electrical safety wireless
normal contamination
89/336/EEC
- EN 61000-6-2
- EN 61000-6-3 73/23/EEC
- EN 60730-1, EN 50090-2-2
EN 300 220-1 (25-1000 MHz) Storage to EN 60721-3-1 class 1K3, temperature -20…65°C Transport to EN 60721-3-2 class 2K3, temperature -25…70 °C Operation to EN 60721-3-3 class 3K5, temperature 0...50 °C
(noncondensing)
Weight (excl. packaging) radio repeater 112 g
power supply 195 g
100/106
Siemens Schweiz AG User Manual CE1U2357en HVAC Products 8 Technical data 6. Juli 2006
Loading...