Siemens RVP550,RVP540 Installation Instructions Manual

Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 1/28
74 319 0312 0
G2488
en
Installation Instructions
Energy Manager / Heating Controller
RVP540 RVP550
Place of installation
In a dry room, e.g. the boiler room
Installation choices:
- Control panel (in the panel front, on the inner wall, or
on a DIN rail)
- Control cabinet
- Sloping front of a control desk
Permissible ambient temperature: 0...50 °C
Electrical installation
The local regulations for electrical installations must
be complied with
Cable strain relief must be ensured
Cables from the controller to the actuators and
pumps carry mains voltage
Sensor cables should not be run parallel to mains car-
rying cables
To protect the solar collector sensor from voltage
surges (caused by lightning for example), the separately available conduit box for overvoltage protection (AGS2S.200/109) should be installed
Permissible cable lengths
For all sensors, thermostats and external contacts:
Copper cable 0.6 mm dia. max. 20 m Copper cable 1.0 mm
2
max. 80 m
Copper cable 1.5 mm
2
max. 120 m
For room units:
Copper cable 0.25 mm
2
max. 25 m
Copper cable 0.5 mm
2
max. 50 m
For the data bus:
0.75...2.5 mm
2
according to Data Sheets N2030E and N2032E
Mounting and wiring the base
Wall mounting
1. Separate base from the controller.
2. Hold base against the wall. Marking TOP must be at the top!
3. Mark fixing holes on the wall.
4. Drill holes.
5. If required, knock out holes on the base for the cable entry glands.
6. Screw base to the wall.
7. Wire up the base.
DIN rail mounting
1. Fit rail.
2. Separate base from the controller.
3. If required, knock out holes on the base for the cable
entry glands.
4. Fit base to the rail. Marking TOP must be at the top!
5. If required, secure the base (depending on the type of
rail).
6. Wire up the base.
Flush panel mounting
Panel cutout required: 92 x 138 mm
Maximum thickness: 3 mm
1. Separate base from the controller.
2. If required, knock out holes on the base for the cable entry glands.
3. Insert base in the panel cutout from behind until stop is reached. Marking TOP must be at the top!
4. Push lateral tongues behind the front panel (refer to illustration below).
2462Z06
Wrong Correct Place tongues on both sides correctly – they may not be located inside the cutout!
5. Wire up the base. Make sure the cable lengths are such that there is sufficient space to open the control panel door.
Commissioning
Preparatory checks
1. DO NOT switch on power yet.
2. Check wiring according to the plant connection diagram.
3. Ensure correct position and location of the levers by
turning the fixing screws (refer to illustration on the lat­eral wall of the unit).
2522Z13
4. Insert controller in the base until stop is reached.
Marking TOP must be at the top!
5. Tighten fixing screws alternately.
6. Check the motorized valves: See if
they are correctly installed (observe direction of flow
as indicated on the valve body)
the manual lever is disengaged.
7. Note with underfloor and ceiling heating systems:
The limit thermostat must be correctly adjusted. During the functional test, the flow temperature may not ex­ceed the maximum permissible level (usually 55 °C). If it does, proceed immediately as follows:
- Either close the valve manually, or
- Switch off the pump, or
- Close the pump isolating valve
2/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
8. Switch on power. The display must show something (e.g. time of day). If not, the reason may be one of the following:
- No mains voltage
- Main fuse blown
- Mains isolator or main switch not set to ON
9. If one of the operating mode buttons flashes, a room unit or contact H1 overrides the controller. Select op­erating mode
on the room unit; switch off contact
H1.
General information about operation
Setting elements:
Setting knob
Display; an operating line is assigned to each setting
Buttons for selecting and adjusting setting values:
Next operating line below Next operating line above Decrease the displayed value Increase the displayed value
Adopting a setting value:
The setting value is adopted by selecting the next op­erating line (or by pressing one of the operating mode buttons)
Entering --.- / --:-- / --- (deactivating a function):
Keep
or depressed until the required display
appears
Block jump function:
To select a single operating line quickly, 2 button combinations can be used:
Press and to select the next line block above. Press
and to select the next line block below.
Setting procedure
1. Make settings on the operating lines according to the instructions provided by your local Siemens HVAC Products sales office.
2. Select plant type on operating line 100.
3. Make the required settings on the controller. All func­tions and operating lines required for the selected type of plant will be activated and can be set. Operating lines that are not used will be hidden.
4. Enter the adjusted values in the table!
5. Set the general functions (independent of the type of plant).
Commissioning and functional check
Specific operating lines for the functional check:
200 = output test 201 = input test 296 = functional test oil- / gas-fired boiler 345 = functional test solar 395 = functional test wood-fired boiler 545 = functional test d.h.w. storage tank 745 = functional test heating circuit 888 = output test P1 894 = output test Ux
If Er (ERROR) appears on the display: Refer to operating
line 50 to find the fault
Operating elements
Room temperature setpoint knob Adjustment of nominal room temperature setpoint
Setting buttons Parameter settings (+ / -)
Operating line selection buttons (Prog) Selection of parameters / switching operating lines
Display Showing actual values and settings
Operating mode buttons heating circuit Operating mode changes to:
Automatic operation Continuous operation Standby
Operating mode button d.h.w.
D.h.w. heating ON / OFF Manual d.h.w. push
Function button with LED for manual operation
Manual operation ON / OFF
8
Green button with signal lamp
Green operation ON / OFF
9
Info button Display of plant values
10
Connection facility for PC tool Diagnostics and service with OCI69 / ACS69
An illuminated button or signal lamp indicates that the relevant function is activated.
C
0 4 8 12 16 20 24
1 2 3 4 5 6 7 8 9 10
°C
20
26
14
Info
RVP540
6
5
4
1
7
8 9
2392 Z54a
10
3
2
Front of RVP540 and RVP550
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 3/28
Connection diagrams
Markings of connection terminal on the low-voltage side
Termi­nal
Terminals Termi-
nal
Terminals
M Ground H1 Input H1 (contact or DC 0…10 V) Ux Output DC 0…10 V B104 Temperature sensor P1 PWM output B103 Temperature sensor B109 Temperature sensor M Ground sensors M Ground sensors B102 Temperature sensor B108 Temperature sensor B101 Temperature sensor NTC / LG-Ni 1000
with automatic identification B107 Temperature sensor MD Ground PPS (room unit, BMU) B106 Temperature sensor A6 Data PPS (room unit, BMU) M Ground sensors MB Ground bus (LPB) B105 Temperature sensor DB Data bus (LPB)
Markings of connection terminal on the mains voltage side
Termi­nal
Terminals Termi-
nal
Terminals
Q110 Multifunctional output Q104 Multifunctional output Q109 Multifunctional output Q103 Multifunctional output F3 Phase Q109 / Q110 F1 Phase Q103 / Q104 F7 Phase Q108 E1 AC 230 V input Q108 Multifunctional output Q102 Multifunctional output Q107 Multifunctional output F5 Phase Q102 F6 Phase Q107 Q101 Multifunctional output Q106 Multifunctional output F4 Phase Q101 Q105 Multifunctional output L Live conductor AC 230 V F2 Phase Q105 / Q106 N Neutral conductor
Electrical connections
2392A03
M
B108
M
B105
H1
B104
B103
M
B106
B101
MD
A6
MB
DB
F2
N
Q105
Q106
F6
Q107
L
F4
Q101
F5
Q102
E1
F1
Q103
B107
Q104
B102
B109
Ux
M
Q108
F7
F3
Q109
Q110
P1
N
N
LPB
D1 D2
4/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Selection
Selecting the plant type:
Select the required type of plant (basic diagram number) on operating line 100 (refer to page 8). The selection activates all functions that are required for the specific plant and shows the operating lines needed. In addition, operating parameters 120 through 173 will be set to their default values required for the basic plant.
During the setting procedure, the basic diagram number on the display flashes. The required number must be confirmed by pressing the + / - buttons twice for 3 seconds. Then, the basic diagram number will stop flashing.
Example:
2392a04
04
8 12162024
123
4567
89
10
Plant type
The basic plant diagram for the required type of plant and additional setting information will be provided by your local
Siemens Building Technologies / HVAC Products sales office.
Designations of relays and sensors
The relay designations used in the supplied basic diagram have the following meaning:
Relays Function (use) Relays Function (use)
K1 Heat pump stage 1 Y7 Maintained boiler return temperature, oil / gas
OPEN
K2 Heat pump stage 2 Y8 Maintained boiler return temperature, oil / gas
CLOSED K3 Release of external wood-fired boiler Y9 Maintained boiler return temperature, wood OPEN K4 Oil- / gas-fired boiler, stage 1 Y10 Maintained boiler return temperature, wood
CLOSED K5 Oil- / gas-fired boiler, stage 2 Y14 Diverting valve partial storage tank charging K6 Electric immersion heater for d.h.w. Y¯14 Inverted Y14 signal K8 Solar collector pump or diverting valve heat exchanger 2 Y15 Diverting valve for return K¯8 Inverted K8 signal Y¯15 Inverted Y15 signal K9 Solar bypass valve or heat exchanger pump Q1 Boiler pump of oil- / gas-fired boiler K¯9 Inverted K9 signal Q2 Heating circuit pump K10 Alarm output Q3 D.h.w. charging pump K11 Overtemperature protection Q¯3 Inverted Q3 signal K¯11 Inverted K11 signal Q4 D.h.w. circulating pump K12 Solar collector pump or diverting valve heat exchanger 1 Q5 Solar collector pump 1 K13 Output K13 for free time switch program Q9 Heat pump circulator K14 Release of external oil- / gas-fired boiler Q10 Pump of wood-fired boiler K15 Release of external heat pump Q11 Storage tank heat transfer pump K16 Electric immersion heater for buffer storage tank Q12 Oil / gas bypass pump K17 Flue gas temperature sensor function Q13 D.h.w. storage tank heat transfer pump K18 Output for solar swimming pool heating Q14 System pump K¯18 Inverted K18 signal Q15 Pump H1 Y1 Heating circuit mixing valve OPEN Q16 Solar collector pump 2 Y2 Heating circuit mixing valve CLOSED Q17 Additional pump Q17 for heat pump stage 2 Y3 Diverting valve d.h.w. E1 Mains input Y4 Heat generation lock L Live conductor (mains connection) Y¯4 Inverted Y4 signal N Neutral conductor (mains connection)
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 5/28
Sensor designations
The sensor designations used in the supplied basic diagram have the following meaning:
Sensor Function (use) Types of
sensors
Sensor Function (use) Types of sen-
sors
B1 Heating circuit flow sensor LG-Ni 1000 B7 Return sensor oil / gas LG-Ni 1000 B2 Sensor of oil- / gas-fired boiler LG-Ni 1000 B71 Return sensor heat pump LG-Ni 1000 B21 Heat pump flow sensor LG-Ni 1000 B72 Return sensor wood LG-Ni 1000 B22 Sensor of wood-fired boiler LG-Ni 1000 B73 Return sensor heating circuit LG-Ni 1000 B3 D.h.w. sensor 1 LG-Ni 1000 B8 Flue gas sensor Pt 1000 B31 D.h.w. sensor 2 LG-Ni 1000 B9 Outside sensor LG-Ni 1000
NTC 600 B32 D.h.w. sensor 3 LG-Ni 1000 B10 Common flow sensor LG-Ni 1000 B33 D.h.w. sensor 4 LG-Ni 1000 B13 Sensor for solar swimming pool
heating
LG-Ni 1000
B4 Buffer storage tank sensor 1 LG-Ni 1000 M Ground sensors H1, U1, P1 – B41 Buffer storage tank sensor 2 LG-Ni 1000 H1 Contact or DC 0…10 V input – B42 Buffer storage tank sensor 3 LG-Ni 1000 U1 DC 0…10 V output – B43 Buffer storage tank sensor 4 LG-Ni 1000 P1 PWM output – B6 Solar collector sensor 1 LG-Ni 1000 /
Pt 1000
A6 PPS data
B61 Solar collector sensor 2 LG-Ni 1000 /
Pt 1000
MD PPS ground
B62 Solar collector flow sensor DB LPB data B63 Solar flow sensor for yield measurement LG-Ni 1000 MB LPB ground B64 Solar return sensor for yield measure-
ment
LG-Ni 1000
Parameter list
Settings to be made on the «Enduser» level
Settings that meet individual enduser needs.
Buttons Explanation Line
1
Press one of the operating line selection buttons.
This will take you directly to programming mode “Enduser“.
2
Press the operating line selection buttons to select the required operating line.
The following parameter list contains all settings that can be made.
• • •
3
Press the + or – button to set the required value. The setting will be stored as soon as you leave the programming mode or change to another line.
4
To leave programming mode “Enduser“, press any of the operating mode but­tons.
è Note:
If no button is pressed for about 8 minutes, the controller will automatically re­turn to the operating mode selected last.
Continu­ous display
6/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Overview of the enduser parameters
Line Function Range Unit Resolution Factory
setting
Setting the clock
1 Time of day 00:00...23:59 h / min .... : ....
2 Weekday 1...7 Day ...... day
3 Date 01.01...31.12 Day /
month
.... : ....
4 Year 2001...2094 Year ...... year
Time switch program for the heating circuit
5 Weekday – preselection heating circuit
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day ...... day
6 Switch-on time 1st period heating circuit 00:00...24:00 h / min .... : ....
h / min
06:00
7 Switch-off time 1st period heating circuit 00:00...24:00 h / min .... : ....
h / min
22:00
8 Switch-on time 2nd period heating circuit 00:00...24:00 h / min .... : ....
h / min
- -:- -
9 Switch-off time 2nd period heating circuit 00:00...24:00 h / min .... : ....
h / min
- -:- -
10 Switch-on time 3rd period heating circuit 00:00...24:00 h / min .... : ....
h / min
- -:- -
11 Switch-off time 3rd period heating circuit 00:00...24:00 h / min .... : ....
h / min
- -:- -
Free time switch program
12 Weekday – preselection free time switch program
1-7 7-day lock
1...7 Individual days
1-7 / 1...7 Day ...... day
13 Switch-on time 1st period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
06:00
14 Switch-off time 1st period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
22:00
15 Switch-on time 2nd period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
- -:- -
16 Switch-off time 2nd period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
- -:- -
17 Switch-on time 3rd period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
- -:- -
18 Switch-off time 3rd period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
- -:- -
Time switch program for d.h.w. heating
19 Weekday – preselection d.h.w.
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day ...... day
20 Switch-on time 1st period d.h.w. 00:00...24:00 h / min .... : ....
h / min
06:00
21 Switch-off time 1st period d.h.w. 00:00...24:00 h / min .... : ....
h / min
22:00
22 Switch-on time 2nd period d.h.w. 00:00...24:00 h / min .... : ....
h / min
- -:- -
23 Switch-off time 2nd period d.h.w. 00:00...24:00 h / min .... : ....
h / min
- -:- -
24 Switch-on time 3rd period d.h.w. 00:00...24:00 h / min .... : ....
h / min
- -:- -
25 Switch-off time 3rd period d.h.w. 00:00...24:00 h / min .... : ....
h / min
- -:- -
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 7/28
Line Function Range Unit Resolution Factory
setting
D.h.w. values
26 Nominal setpoint of the d.h.w. temperature (TBWw)
TBWR Line 770 TBWmax Line 750
EXP
TBWR...TBW max
°C ...... °C 55
Heating circuit values
27 Reduced setpoint of the room temperature (TRRw)
TRF Line 28 TRN Setpoint knob
TRF...TRN °C ...... °C 16
28 Frost protection setpoint of the room temperature
(TRFw)
TRR Line 27
4...TRR °C ...... °C 10
29 Summer / winter changeover temperature 8...30 °C ...... °C 17
30 Slope of the heating curve 1.0...40 ...... 15
33 Actual value of the room temperature (TRx) 0...50 °C
General
34 Actual value of the outside temperature (TAx)
To set the attenuated outside temperature to Tax, press the + / ­buttons simultaneously for 3 s
-50...+50 °C
38 Resetting the enduser parameters
To reset the parameters of the enduser level to their standard values, press the + / - buttons simultaneously for 3 s
0 / 1 0
39 Resetting the heating circuit and d.h.w. time switch
programs
To reset the time switch programs of the enduser level to their standard values, press the + / - buttons simultaneously for 3 s
0 / 1 0
Holiday program
40 Preselection of the holiday period 1...8 ...... 1
41 Beginning of the holiday period
--.-- Inactive To deactivate the set holiday period, press the + / - buttons si­multaneously for 3 s
--.-- /
01.01...31.12
Day / month
.... . ....
day / month
--.--
42 End of the holiday period
--.-- Inactive To deactivate the set holiday period, press the + / - buttons si­multaneously for 3 s
--.-- /
01.01...31.12
Day / month
.... . ....
day / month
--.--
General / service
50 Indication of error signals
No display = no fault 10 = fault outside sensor 20 = fault boiler sensor oil / gas B2 25 = fault boiler sensor wood B22 26 = fault common flow sensor B10 28 = fault flue gas sensor B8 30 = fault flow sensor heating circuit B1 33 = fault flow sensor heat pump B21 40 = fault return sensor oil / gas B7 43 = fault return sensor wood B72 44 = fault return sensor heat pump B71 47 = fault common return sensor B73 50 = fault storage tank sensor / thermostat B3 52 = fault storage tank sensor / thermostat B31 55 = fault storage tank sensor / thermostat B32 56 = fault storage tank sensor / thermostat B33 61 = fault room unit 70 = fault storage tank sensor B4 71 = fault storage tank sensor B41 72 = fault storage tank sensor B42 73 = fault collector sensor B6 74 = fault collector sensor B61 75 = fault solar flow sensor B62 76 = fault storage tank sensor B43 79 = fault water / brine sensor B11 81 = short-circuit data bus (LPB) 82 = same bus address exists several times
86 = short-circuit PPS 100 = 2 clock time masters on the data bus (LPB) 127 = legionella temperature not reached 130 = maximum flue gas temperature exceeded
8/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Line Function Range Unit Resolution Factory
setting
134 = fault heat pump at input H1 135 = water / brine temperature too low 137 = fault heat pump at input E1 138 = fault control sensor heat pump (operating line 420) 145 = wrong PPS unit (BMU / room unit) 146 = configuration error (operating line 202) 147 = external heat source missing (PPS / LPB) 150 = fault BMU 171 = alarm signal at input H1 172 = alarm signal at input E1 211 = fault wood-fired boiler 231-239 = fault sensor input B101 - B109 241 = fault flow sensor yield measurement B63 242 = fault return sensor measurement B64
243 = fault swimming pool sensor B13
Oil- or gas-fired boiler
60 Chimney sweep
0 = OFF 1 = ON Outside the programming level, the + / - buttons can be used to activate / deactivate the second burner stage
0 / 1 0
Solar collectors
65 24-hour yield solar energy 0...999.9 kWh 0 66 Total yield solar energy
To reset the total yield to 0, press the + / - buttons simultaneously for 3 s
0...9999999.9 kWh 0
Heat pump
75 Acknowledgement of heat pump error messages
135 and 137
To reset the error messages to 0, press the + / - buttons simulta­neously for 3 s
0 / 1 0
Settings to be made on the «Heating engineer» level
Settings required for the configuration and parameterization by the heating engineer.
Buttons Explanation Line
1
Press both operating line selection buttons for at least 3 seconds.
This will take you to programming level “Enduser”.
2
Press the operating line selection buttons to select the required operating line.
The parameter list on the next pages contains all operating lines on which set­tings can be made.
• • •
3
Press the + or – button to set the required value. The setting will be stored as soon as you leave the programming mode or change to another operating line.
4
To leave programming level “Heating engineer“, press one of the operating mode buttons.
è Note:
If no button is pressed for about 8 minutes, the controller will automatically return to the operating mode selected last.
Continu­ous display
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 9/28
Overview of the heating engineer parameters
Line Function Range Unit Resolution Factory
setting
General / service
Basic diagrams
100 Selection of the basic diagram
0
No basic diagram selected
1...99.998 Basic diagrams To adopt the selected diagram number, press the + / - buttons simul­taneously for 3 s
0...99.998 ...... 0
Configuration
Partial diagrams
120 Selection of partial diagram oil- / gas-fired boiler
0
Partial diagram inactive (OeG0)
1...9 Partial diagrams OeG1 through OeG9
0...9 ...... 0
121 Selection of partial diagram solar collectors
0
Partial diagram inactive (OeG0)
1...16 Partial diagrams Sol1 through Sol16
0...16 ...... 0
122 Selection of partial diagram wood-fired boiler
0 Partial diagram inactive (Ho0)
1...5 Partial diagrams Ho1 through Ho5
0...5 ...... 0
123 Selection of partial diagram heat pump
0 Partial diagram inactive (Wp0)
1...5
Partial diagrams Wp1 through Wp5
0...5 ...... 0
124 Display of partial diagram buffer storage tank
0 Partial diagram inactive (Sp0)
1...3 Partial diagrams Sp1 through Sp3
0...3 ...... 0
125 Display of partial diagram d.h.w. storage tank
0 Partial diagram inactive (BwSp0)
1...10 Partial diagrams BwSp1 through BwSp10
0...10 ...... 0
126 Selection of partical diagram combi storage tank
0 Partial diagram inactive (KoSp0)
1...6 Partial diagrams KoSp1 through KoSp6
0...6 ...... 0
127 Selection of partial diagram heating circuit
0 Partial diagram inactive (Rh0)
1...3 Partial diagrams Rh1 through Rh3
0...3 ...... 0
Hiding sensors that are not required
130 Source outside sensor
0 Signal via bus (PPS or LPB) 1 Signal via terminal
0 / 1 ...... 0
131 Reduction 1st d.h.w. sensor B3
0 Without sensor B3 1 With sensor B3
0 / 1 ...... 0
132 Reduction 2nd d.h.w. sensor B31
0 Without sensor B31 1 With sensor B31
0 / 1 ...... 0
133 Reduction 2nd buffer storage tank sensor B41
0 Without sensor B41 1 With sensor B41
0 / 1 ...... 0
135 Reduction wood-fired boiler return sensor B72
0 Without sensor B72 1 With sensor B72
0 / 1 ...... 0
136 Reduction heat pump flow sensor B21
0 Without sensor B21 1 With sensor B21
0 / 1 ...... 0
137 Reduction heat pump return sensor B71
0 Without sensor B71 1 With sensor B71
0 / 1 ...... 0
138 Reduction water / brine sensor B11
0 Without sensor B11 1 With sensor B11
0 / 1 ...... 0
Loading...
+ 19 hidden pages