Siemens Powers TH 188 Technical Instructions

Page 1
Powers
Controls
TH 188 Unit Mounted Thermostat
With 20 Scim
Restrictor
With 40 Scim
Restrictor
Document No. 155-064P25
TH 188-2
April 1, 2005
TM
Description
Features
Application
Product Numbers
The TH 188 Unit Mounted Thermostat is a remote bulb, gradual acting pneumatic instrument that maintains a pre-selected temperature by positioning pneumatic devices that control a heating or cooling medium.
Replacement thermostats are available for Honeywell models LP916Bxxxx and Johnson Controls model T-3300-2.
Liquid filled sensing element
Direct acting (DA), reverse acting (RA), and heating-cooling models (HC)
Mounting bracket provided
The TH 188 thermostat is mounted in fan coil units and unit ventilators to control a space temperature in applications where a wall thermostat cannot be used.
In unit ventilator applications, where the unit mounted thermostat pilots a Limitem, use a thermostat having a 40 scim (11ml/s) restrictor. The Limitem has a built-in bleed to prevent control air from being trapped.
To assure good control, the remote bulb sensing element must be located so that space air passes over it continuously.
Table 1.
Thermostat Action
and
Model Number
Product Number
(5.5 ml/s)
(11 ml/s)
*Use 188-0024, but change restrictor.
HC (DA & RA) TH 188 HC --- 188-0030
DA TH 188D --- 188-0031 RA TH 188R 188-0024
Honeywell HC LP916Bxxxx --- 188-0033
Johnson HC T-3300-2 --- 188-0034
*
Siemens Industry, Inc.
Page 2
Technical Instructions TH 188 Unit Mounted Thermostat
Control action Heating (DA) and Cooling (RA)
Type & Model
No.
Heating (DA)
Cooling (RA)
Changeover
Document Number 155-064P25 April 1, 2005
Specifications
Direct acting only
Operating
Physical
Reverse acting only Operating range 60° to 85° F (16° to 29° C) Operating pressure 30 psi (207 kPa) max. Sensitivity range 1 to 5.25 psi per degree F (12 to 65 kPa per degree C) Factory sensitivity setting 2.25 psi per degree F (28 kPa per degree C) Temperature response 0.2° F (0.1° C) Maximum ambient temperature Case 135°F (57°C) Bulb 231°F (111°C) Scale graduations 1°F (0.55°C) Normal air supply pressure See Table 2 Air usage *HC, 40 scim restrictor 45 scim (12 ml/s) DA, 40 scim restrictor 40 scim (11 ml/s) RA, 20 scim restrictor 25 scim (7 ml/s) Air capacity *HC, 40 scim rest. 35 scim (9.5 ml/s) *HC, 40 scim rest. cooling 120 scim (33 ml/s) DA, 40 scim restrictor 35 scim (9.5 ml/s) RA, 20 scim restrictor 120 scim (33 ml/s) Thermal system Remote bulb, liquid filled *HC air usage and air capacity is the same for Powers, Honeywell, and Johnson. Weight 3 lbs. (1.36 kg) Dimensions See Figure 9 Air connections Barbed fitting for 1/4-inch (6.4 mm) OD plastic tubing Finish Corrosion resistant zinc chromate
Page 2 Siemens Industry, Inc.
Table 2. Air Supply Pressure and Changeover.
Powers HC
25 Psi (172 kPa) 18 psi (124 kPa) 21 psi (145 kPa)
TH 188 HC
Powers DA
25 psi (172 kPa) -- --
TH 188D
Powers RA
-- 25 psi (172 kPa) --
TH 188R
Honeywell HC
18 psi (124 kPa) 13 psi (90 kPa) 15 psi (103 kPa)
Lp916Bxxxx
Johnson HC
20 psi (138 kPa) 15 psi (103 kPa) 17 psi (117 kPa)
T-3300-2
Page 3
TH 188 Unit Mounted Thermostat Technical Instructions
Extension shaft 188-101
Document Number 155-064P25 April 1, 2005
Accessories
Operation
(See Figure 1).
Heating, Direct Acting, 25 psi (172 kPa) Supply
Cooling, Reverse Acting, 18 psi (124 kPa) Supply
Remote bulb mounting kit 808-517 Limit stop kit (25 sets/kit) 188-144 Restrictor replacement kit
five 20 scim (5.5 ml/s) and five 40 scim (11 ml/s) 188-159 Thermostat mounting bracket 188-077
NOTE: Pressures used refer to thermostats calibrated to Powers pressures. See Table 2
for Honeywell and Johnson Controls supply pressures.
When the remote bulb senses a falling temperature, the liquid within the thermal system contracts. This allows the pre-load spring to lift the sensitivity arm and throttling pin, which is in contact with the arm. The throttling pin lifts off the nozzle seat reducing the pressure behind the nozzle. This is the direct acting signal of the thermostat. The reduced pressure passes through the return line to a Normally Open (NO) valve. This allows more of the heating medium to flow through the heating coil increasing the heat supplied to the space.
When there is a rise in temperature sensed by the remote bulb, the liquid within the thermal system expands. This expansion moves the sensitivity arm and throttling pin downward, increasing the load on the throttling pin and moving it closer to the seat in the nozzle. Pressure builds up in the chamber below the nozzle until the force of the increased air pressure against the bottom of the throttling pin exactly balances the downward force of the sensitivity arm. This increased pressure reduces the flow of heating medium through the heating coil by closing the normally open valve and reducing the heat supplied to the space.
With an 18 psi (124 kPa) supply pressure, the channel connecting the direct acting signal to the return line port is closed, and the channel connecting the reverse acting signal to that same return line port is opened.
Heating-Cooling Changeover
When the remote bulb senses a falling temperature, the liquid within the thermal system contracts, allowing the spring pressure to move the sensitivity arm away form the throttling pin. This allows the built-up pressure to bleed off, lowering the pressure on the reverse acting stage of the thermostat. Thus, the spring pressure opens the supply valve and closes the exhaust valve, increasing the pressure in the return line.
With an 18 psi (124 kPa) air supply, the switch spring exerts enough force to overcome the 18 psi (124 kPa) air pressure acting on the switch diaphragm. The ball valve is therefore kept closed, allowing no air to reach the changeover diaphragm. An air pressure increase to 25 psi (172 kPa) will exert enough force on the switching diaphragm to overcome the force of the switch spring and cause the switch diaphragm to move upward. This unseats the switch ball valve and allows full supply pressure to act on the changeover diaphragm. The air pressure force on top of the changeover diaphragm moves the diaphragm down to compress the changeover rod spring. Attached to the changeover rod and changeover poppet. The motion of the diaphragm, rod and poppet assembly closes the reverse acting port to the return line and opens the direct acting port, making the thermostat direct acting. Lowering the air supply back to 18 psi (124 kPa) will reverse the changeover procedure and the thermostat will again be reverse acting.
Siemens Industry, Inc. Page 3
Page 4
Technical Instructions TH 188 Unit Mounted Thermostat Document Number 155-064P25 April 1, 2005
Operation, continued
Figure 1. Thermostat Operation.
Calibration
General
The thermostats are factory calibrated at 72° F (22° C) and 7-1/2 psi (52 kPa) control pressure.
1. Determine the temperature at the remote bulb.
2. Set pointer to the temperature found. Dial increments are approximately five degrees on the major divisions with one degree subdivisions, beginning at 60° F clockwise to 85° F.
3. Loosen (do not remove) the return line test port screw. Slip the rubber line over test port and connect to test gauge (Figure 2).
Figure 2. Test Port and Gauge used for Calibration.
4. With the knob set at the temperature of the remote bulb, the output (return line) pressure should be between 7 and 8 psi (48 and 55 kPa) for all models. If the output pressure is not 7 to 8 psi (48 and 55 kPa), remove knob after loosening its set screw. Then rotate the set point adjustment post until pressure is 7 to 8 psi.
5. Replace knob and set pointer to temperature of the bulb, lock, and then turn to desired setting.
The thermostat is now in calibration.
Page 4 Siemens Industry, Inc.
Page 5
TH 188 Unit Mounted Thermostat Technical Instructions Document Number 155-064P25 April 1, 2005
Calibration, continued
Single Action
The direct acting or reverse acting thermostat may be calibrated at any pressure. It is suggested that 7-1/2 psi (52 kPa) be used.
Dual Action
On the HC thermostat, calibration should be at 7-1/2 psi (52 kPa) for both DA and RA. This is due to the use of one thermal system and a reversing relay to give the action desired. If calibrated at 7-1/2 psi (52 kPa) for winter, the summer calibration will be 7-1/2 psi (52 kPa). If 9 psi (62.1 kPa) is used for winter, 6 psi (41.4 kPa) will be summer’s calibrated pressure. Figure 3 shows the relationship of the DA and RA calibration points. If the same pressure is desired for both seasons, the RA section of the thermostat needs to be recalibrated (follow the RA calibration procedures).
Figure 3. Dual Action Calibratio n Points.
Reverse Acting Stage
See Table 1 for pressures and changeover pressures. The reverse acting stage is factory adjusted and does not require field adjustment. If the
adjustment is disturbed, re-adjust as follows:
1. With the main air supplies set for 25 psi (172 kPa), connect a PRV with gauge to the
supply side of thermostat and set at 25 psi (172 kPa).
2. Remove knob and cover from thermostat, as shown in Figure 4.
3. Open bleed screw on test port and connect gauge.
4. Rotate adjustment post to give an output within 1/2 psi (3.4 kPa) of calibration pressure.
5. Adjust PRV for 18 psi (124 kPa) air supply; observe the control pressure. If it is not
within 1/2 psi (3.4 kPa) of calibration pressure, adjust the reverse acting adjustment until it is. Apply thread locker to the screw setting.
6. Remove test port gauge; close bleed screw.
7. Replace cover and knob.
8. Lock knob in place with pointer at bulb temperature.
9. Set knob at desired temperature setting.
Siemens Industry, Inc. Page 5
Page 6
Technical Instructions TH 188 Unit Mounted Thermostat Document Number 155-064P25 April 1, 2005
Calibration, continued
Heat-Cool Thermostat Changeover
See Table 1 for air pressures and changeover pressures. The changeover is a factory adjustment; it is sealed with thread locker and does not
require field adjustment. If for some reason this adjustment is disturbed, re-adjust as follows: (See Figure 4)
1. Supply the thermostat with an air supply equal to the appropriate changeover
pressure.
2. With the exhaust adjustment (center screw) backed out several turns, turn the
switch spring adjustment (outer screw) down snug, and then back off, until air can be heard bleeding out.
3. Turn the exhaust adjustment down snug and back off approximately 1/8 turn.
4. Seal both screws with thread locker to prevent further movement.
Installation
Figure 4. Heating/Cooling Changeover.
A mounting bracket (188-077) is included for mounting the thermostat within the
various units.
Figure 5 shows a typical installation where the mounting bracket is fastened to the
partition with two sheet metal screws (034-257).
Mount the remote sensing bulb in the air stream of the return air (near the inlet of
the fan).
Avoid metal-to-metal contact between the bulb and unit to prevent the soft copper
sensing bulb wearing through due to the rubbing action caused by the unit vibrating.
Use the adhesive backed cable clip (141-311) supplied with the thermostat to fasten
the capillary and/or bulb in the return air stream.
If there is not enough room to mount the thermostat in a convenient location, or if
the set point dial must be in the same compartment as the fan switch, order an extension shaft kit (188-101). The thermostat may be mounted in any convenient location within the eight-inch length of the shaft extension cable shown in Figure 6.
Page 6 Siemens Industry, Inc.
Page 7
TH 188 Unit Mounted Thermostat Technical Instructions
Complaint
Check
Possible Cause
Corrective Action
Document Number 155-064P25 April 1, 2005
Installation, contintued
Preventive Maintenance
Return line
pressure
0 psi (0 kPa)
Return line
pressure 18
psi (124 kPa)
or greater
Figure 5. Unit Mounted.
The construction of the TH 188 Thermostat makes it virtually maintenance-free. But like any pneumatic thermostat, it should be checked for calibration at least once each year (usually just before the heating season).
Supply Air No Air As Required
*Heating 25
psi
(172 kPa)
*Cooling 18
psi (124
kPa)
Supply Air Pressure Too High As Required
*Heating 25
psi (172
kPa)
Calibration Out of calibration Recalibrate
Restrictor Clogged or dirty Clean or replace
Sensing element Loss of charge Replace sensing element
Direct acting stage Internal binding or leaking Replace thermostat
Calibration Out of calibration Recalibrate
Throttling pin Dirt built up around pin Clean or replace nozzle ass’y
Reverse acting stage Internal binding or leaking Replace thermostat
Calibration Out of calibration Recalibrate
Throttling pin Dirt built up around pin Clean or replace
Direct acting stage Internal binding Replace thermostat
Figure 6. Mounting with Extension Sha ft.
Table 3. Troubleshooting.
*See Table 1 for Honeywell and Johnson Controls pressures.
Siemens Industry, Inc. Page 7
Excessive
cycling
*Cooling 18
psi (124
kPa)
Calibration Out of calibration Recalibrate
Restrictor Clogged or dirty Clean or replace
Sensing element Loss of charge Replace sensing element Reverse acting stage Improperly adjusted Re-adjust Reverse acting stage Internal leaks or binding Replace thermostat
Lever assembly Sticking/binding of levers As Required
Page 8
Technical Instructions TH 188 Unit Mounted Thermostat
Item
Part
Number
Description
Number
Req’d
Material
Document Number 155-064P25 April 1, 2005
Figure 7. See Tables 4 and 5.
Table 4. Parts List (See Figures 7 and 8).
1 -- Housing assembly 1 Zinc alloy 2 -- Cover plate 1 Aluminum 3 -- Upper lever 1 Aluminum 4 188-057 Sensing element 1 Copper 5 -- Adjustment post (HC & RA) 1 Steel 6 188-122 Knob 1 Zinc alloy 7 -- Adjustment knob (DA only) 1 Brass 8 034-370 8-32x1/4 sock. hd. set screw 1 --
9 -- Lower lever assembly 1 -­10 188-082 Nozzle assembly 1 -­11 188-080 Gasket 1 -­12 833-009 Seal Screw 1 Brass 13 -- Switch spring adjusting nut (HC only) 1 Brass 14 -- Exhaust adjusting screw 1 Brass 15 030-312K 6-32x5/16 pan hd. screw 1 Steel
15a -- Capillary clamp 1 Plastic
16 -- RA adjustment nut (HC & RA) 1 Brass 17 034-014K Restriction plate screw (HC & RA) 1 Brass
Page 8 Siemens Industry, Inc.
Page 9
TH 188 Unit Mounted Thermostat Technical Instructions
Item
Part
Number
Description
Number
Req’d
Material
Document Number 155-064P25 April 1, 2005
Figure 8. See Tables 4 and 5.
Table 5. Parts List (See Figures 7 and 8).
18 -- Restriction cover 1 Steel 19 * Restrictor (2 Tabs 20 scim) 1 Brass
* (4 Tabs 40 scim) Brass 20 * Restrictor gasket, upper 1 Rubber 21 * Restrictor gasket, lower 1 Rubber 22 -- Restrictor plate screw (long) (HC & RA) 1 Steel
-- Restrictor plate screw (long) (DA only) 1 Steel 23 -- Cover screw 2 Steel 24 -- Filter 1 Felt 25 -- Polytube adapter 2 Brass 26 -- Mounting washer (HC & RA) 1 Steel 27 -- Mounting screw (HC & RA) 1 Steel
-- Mounting nut (DA only) 1 Brass 28 -- Pre-load spring 1 Spring Wire
*These parts are in Restrictor Replacement Kit (188-159) shown under Accessories.
Siemens Industry, Inc. Page 9
Page 10
Technical Instructions TH 188 Unit Mounted Thermostat
+ 1 847-215-1000
Document Number 155-064P25 April 1, 2005
Dimensions
Dimensions in Inches (Millimeters)
HC and RA Thermostats
DA Thermostats
Information in this publication is based on current spec i fications. The company reserves the right to make changes in specifications and model s as design improvements are introduced. Powers is a registered tradem ark of Siemens Industry, Inc. Product or company names mentioned herein may be the trademarks of their respective owners. © 2005 Siemens I ndustry, Inc.
Siemens Industry, Inc.
Building Technologies Divis i on 1000 Deerfield Parkway Buffalo Grove, IL 60089
Figure 9. Dimensions.
Your feedback is im port ant to us. If you have comments about this document, pl ease send them to
sbt_technical.editor.us.sbt@siemens.com
Document No. 155-064P25
Printed in the USA
Page 10
Loading...