Siemens Powermite 599 MT Series, Powermite 599 MT SSC61.5U, Powermite 599 MT SSC61U Technical Instructions

Page 1
Powermite 599
Technical Instructions
MT Series SSC Electronic
Document No. 155-313P25
EA 599-15
January 12, 2018
Description
Features
Application
Product Numbers
The Powermite 599 MT SSC61U and SSC61.5U electroni c valve actuators require a 24 Vac or 24 Vdc supply and a 0 to 10 Vdc control signal. They proportionally control Powermite 599 MT Series valves with a 7/32-inch (5.5 mm) stroke and a threaded valve bonnet that fits the actuators.
UL listed for plenum installations.
Direct-coupled installation without special tools.
Manual override.
Visual position indication.
The Powermite 599 MT SSC61 series electronic actuators and MT Series valves are used in closed loop heat ing and cooling applications. They control hot or chilled water or steam (<5 psi) for convectors, fan coil units, unit conditioners, radiation, reheat coils, and similar t erminal units. The SSC61 series actuators accept a plenum cable or 3/8­inch flex conduit connection.
Table 1. Product Num bers.
Actuator Operating Mode Actuator Prefix Code
SSC61U
SSC61.5U
Non-spring Return
(Fail-in-Pl ace)
Spring Return
(Fail-Safe)
261
262
Ordering a Valve Plus Actuator Assembly
To order a com plete valve plus actuator assembl y from the factory, combine the actuator prefix code with the suffix of the valve product number. See Technical Bulletin
TB251, Powermite 599 Series MT Series Terminal Unit Valve and Actuator Assembly Selection (155-306P25) for selecti on procedures.
To order an actuator only, use the product number.
Siemens Industry, Inc.
Page 2
Technical Instructions MT Series SSC Electronic Valve Actuator, 24 Vac/dc Proportional Control Document Number 155-313P25 January 12, 2018
Specifications
Operating voltage 24 Vac ±20%, 24 Vdc ±20%
Power requirements
Control characteristics
Functional operation
Agency certification
Ambient conditions
Physical characteri stics
Frequency 50/60 Hz ±2 Hz Power supply 24 Vdc or earth ground isolating,
Class 2, 24 Vac transf ormer NOTE: Do not power more than
10 actuators with one
transformer. SSC61U power consumption 2 VA SSC61.5U power consumption 3 VA at ultra cap load,
2 VA at normal operati on
Control signal (Y ) Voltage 0 to 10 Vdc (default) or 0 to 20 mA with
external 500 ohm, 0. 2W resi stor Current 0.1 mA Running time
at 50/60 Hz 30 sec ±10% Spring return, SSC61.5U only (Figure 1) 30 seconds
Nominal stroke 7/32-inch (5.5 mm) Nominal force 67 lb (300N) Stroke/signal relationship Linear Capacitor charge time (Figure 1) maximum 180 seconds Spring return (SSC61.5U only) Non-mechanical, electronic return fails
to stem up (0 position) UL UL873 Listed cUL Certified to CSA C22.2 No. 24-93 Ambient temperature
Operation 41°F to 122°F (5°C to 50°C) with Transport and storage -13°F to 158°F (-25°C to +70°C)
Ambient humidity 0 to 90% rh (non-condensing) Media temperature 35°F to 230°F (2°C to 110°C) Wiring Connecti on Plenum cable or 3/8-inch flex conduit Weight 0.61 lb (0.27 kg) Dimensions See Figure 7
Page 2 Siemens Industry, Inc.
Page 3
MT Series SSC Electronic Valve Actuator, 24 Vac/dc Proportional Control Technical Instructions
Document Number 155-313P25
January 12, 2018
Operation
The stroke of the actuator shaft is proportional to the control signal on terminal Y. A 0 Vdc control signal ret racts the shaft. In the event of a power failure with no control voltage, the SSC61U fails-in-place and holds its last position.
In the event of a power failure, the SSC61.5U returns to the stem up position. The SSC61.5U includes an electronic return mechanism that functions as follows (Figure 1):
At power-up (t0), a capacitor must charge to its maximum capacity (Max, tc). This will take a maximum of 180 seconds, during which time no actuator movement occurs.
Once the capacitor is fully charged (tc), normal actuator operation occurs.
If a subsequent power failure
Figure 1. SSC61.5U Electronic Spring Return
Mechanism.
occurs (tn) longer than 5 seconds, the capaci tor discharges (td) and the actuator returns to its norm al spring return position.
CAUTION:
Before applying power, make certain a valve is connected to the actuator.
If applying power to the act uator when a valve is not connected, the actuator will respond to a control si gnal and the shaft will extend until it reaches its maximum end stop. Thereafter, it will not respond to any signal.
If this occurs:
1. Disconnect power.
2. Turn the manual positi on indi cator (see Figure 5 and Figure 6) on the top of the actuator to the 0 positi on and verify that the actuator shaft retracts completely.
3. Connect a v alve to the actuat or, and reapply power. The actuator will return to normal operation.
Siemens Industry, Inc. Page 3
Page 4
Technical Instructions MT Series SSC Electronic Valve Actuator, 24 Vac/dc Proportional Control Document Number 155-313P25 January 12, 2018
Operation, Continued
Calibration Stroke
Mounting and Installation
The SSC61x writes its calibration stroke parameters to nonvolatile memory on the first start-up of the actuat or. Successive start-ups bypass the calibration stroke unless the memory is manually cleared. If installing the actuator on a different valve (such as on a replacement valve), manually clear the calibration stroke from memory as follows:
1. Remove the terminal cover using a Phillips head screwdriver.
2. Locate the hol e on the circuit board with the shorting bars.
3. With power appl ied to the unit, insert and gently twist a flat-blade screwdriver to electrically connect the shorting bars (Fi gure 2). The SSC61x then performs a new cali bration stroke.
4. Secure the terminal cover back in place.
Figure 2. Manually Clearing Calibration
Stroke from Memory.
Mount the actuator in one of the allowable positions shown in Figure 3.
Wiring
Figure 3. Mounting Position.
When mounting the actuator in a plenum, the proper cable must be attached to meet local codes.
Allow 8 inches (200 mm) above the actuator and 8 inches (200 mm) behind the cable for service.
Use earth ground isolating, step-down Class 2 transformers. Do not use autotransformers.
Determine the supply transformer rating by summing the total VA of all actuators used. The maximum rating for a Class 2 step-down transformer is 100 VA.
Do not power more than 10 actuators by one transformer. (Use 0.5 amp fuse on secondary per actuator.)
CAUTION:
Terminals must be properly wired for correct function and full life of the actuator.
Page 4 Siemens Industry, Inc.
Page 5
MT Series SSC Electronic Valve Actuator, 24 Vac/dc Proportional Control Technical Instructions
Document Number 155-313P25
January 12, 2018
Wiring Diagrams
G, G0 24 Vac or 24 Vdc operating
voltage Y 0 to 10 Vdc control signal G0 System neutral G System potential
R1 500 ohm resistor
(optional for 0 to 20 mA operation)
Figure 4. SSC61U and SSC61. 5U Wiring.
Manual Override
Start-up
For manual posit ioning, use the manual override knob in the center of the position indicator, See Figure 5.
Figure 5. Manual Override.
Check the wiring and the position indicat or (Figure 6 ).
Positio n Indicator Output Shaft
0 Retracted 1 Extended
Figure 6. Top View of Position Indicator
(Shown in the 0 Position).
Siemens Industry, Inc. Page 5
Page 6
Technical Instructions MT Series SSC Electronic Valve Actuator, 24 Vac/dc Proportional Control Document Number 155-313P25 January 12, 2018
Troubleshooting Service Disposal
Dimensi ons
Check the wiring for proper connections. If the actuator is inoperative, replace the unit.
The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domesti c garbage.
Dispose of the dev ice through channels provi ded f or this purpose.
Comply wit h all local and currently applicable l aws and regulati ons.
Figure 7. SSC61 Series Actuator Dimensions in Inches (Millimeters).
Service Envelop e
Minimum access space recommended: 8 inches (200 mm) above the actuator and beside the terminal cover.
Information in this publication is based on c urrent specific ations. The company reserves the right to make changes in specifications and models as design improvements are introduced. Product or company n ames mentioned herein may b e the trademarks of their res pective ow ners. © 2018 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 USA Tel. +1-847-215-1000
Your feedback is important to us. If you have
comments about this document, please send them
tosbt_technical.editor.us.sbt@siemens.com
Document No. 155-313P2 5
Printed in the USA