Siemens POL220 Series, POL220.00, POL220.10, POL220.15, POL220.05 User Manual

User Guide
Document No. 125-1902
June 26, 2018
Page 1 of 16
Product Description
The Economizer Controller allows the use of unconditioned outside air to cool a building. The Free Cooling air determination is based on customer temperature and humidity selections, as well as optional Demand Control Ventilation (DCV) strategies with CO2 level selection.
Features
Economizer control provides “free cooling” based on single or dual dry bulb temperature, or combination temperature + humidity sensors.
Wide temperature shut-off setpoint range selection and Btu/lb selection range selectable by DIP switches.
Potentiometers allow accurate adjustment of DCV, exhaust fan levels, and minimum damper position.
Versions with remote minimum position damper adjustments accept either 0 to 10 Vdc or 135 Ohm potentiometer signals.
Used with Siemens OpenAir® damper actuators.
Flexible sensor inputs accept 10K or 3K
standard NTC sensors, or Siemens QFM2160U combination temperature/humidity 0 to 10V sensor for enthalpy control.
LED Indication when in Free Cooling operation, DCV operation and exhaust fan operation as well as during sensor failure.
Quick installation and easy commissioning.
Two-stage cooling control.
Occupancy input with default capability.
Quick connect I/O with 1/4” spade connections.
Anti-freeze protection.
Brownout protection.
Product Numbers
Economizer
Controller
Single
Economizer
Controller
Multi-pack (20)
Remote
Potentiometer
Input Type
POL220.05
POL220.00
BSG61 (0-10 Vdc)
POL220.10
POL220.15
LVC2 (135)
Item Number 125-1902, Rev. GA
Contents
Economizer Controller
Two No. 6 3/4” self-tapping screws
Accessory
985-960 Jumper Accessory
Warning/Caution Notations
CAUTION/ATTENTION
Equipment damage or loss of data may occur if you do not follow a procedure as specified.
Risque de dégâts matériels ou de perte de données, en cas de non-respect des procédures à suivre.
WARNING/AVERTISSEMENT
Personal injury may occur if you do not follow a procedure as specified.
Risque de blessures graves en cas de non-respect des procédures à suivre.
Prerequisites
For proper Economizer Controller operation, read this User Guide carefully, and follow the instructions in the Economizer Controller Start-up/ Commissioning Mode section. Failure to do so may result in damage to the product or create a hazardous condition. Installation of this controller must be performed by a trained HVAC service technician.
Document No. 125-1902 User Guide June 26, 2018
Page 2 of 16 Siemens Industry, Inc.
Basic Economizer Control Modes
1. Control Mode 1: Fixed Dry-bulb (Single dry-bulb) Outside air and mixed air temperature sensors are used.
2. Control Mode 2: Differential Dry-bulb (Dual Dry-Bulbs) Outside air, return air, and mixed air temperature sensors are used.
3. Control Mode 3: Combination Fixed Enthalpy and Fixed Dry-bulb Control Outside air temperature and humidity sensors, and mixed air temperature sensors are used.
4. Control Mode 4: Combination of Differential Enthalpy and Fixed Dry-bulb Outside air temperature and humidity sensors, return air temperature and humidity sensors, and mixed air temperature sensors are used.
Specifications
Electrical Ratings:
Input Voltage: 24 Vac ±25%; 50/60 Hz (Class 2). Nominal Power Consumption (at 24 Vac, 60 Hz): 4 VA. Relay Contact Rating at 30 Vac (maximum power from Class 2 input only): 1.5A run, 3.5A inrush.
NOTE:
All inputs and outputs must be 24 Vac Class 2.
Ambient Ratings:
Temperature: -40°F to 149°F (-40°C to 65°C). Humidity: 5 to 95 percent RH (non-condensing).
Inputs:
Combination Temperature/Humidity Sensor (QFM2160U): 5-wire (18, 20, or 22 AWG cable) connection.
Dry Bulb Temperature Sensor 10K Ohm Type II NTC (QAM2030.010) or 3K NTC: 2-wire (18, 20, or 22 AWG cable) connection.
DCV (CO2) Sensor (QPA2000): 3- wire (18, 20, or 22 AWG cable) 0 to 10 Vdc control signal
Outputs:
Actuator (GCA151.1P GMA151.1P, GQD151.1P): 4-wire (18 AWG) Actuator Signal: 2 to 10 Vdc. Actuator Input Resistance: 100K ohm. The controller provides 7 VA max. to operate the damper actuator. Exhaust Fan: Contact closure.
Auxiliary Equipment:
RDY2000 Commercial Thermostat
LVC2 (135 Ω) Control Board for remote minimum
damper positioning (POL220.10 and POL220.15)
BSG61 (0-10 Vdc) for remote minimum damper positioning (POL220.00 and POL220.05)
Wire the electrical connections using 1/4” female,
insulated spade connections.
Approvals:
UL listed per UL873. CE RCM cUL Listed per CSA – C22.2 No. 24
Suitable for plenum installation UL/NEMA Type 1
Dimensions: 5.10” × 4.70” × 1.10” (130 mm × 120 mm × 28 mm)
Weight: 0.49 lbs (221 g)
Required Tool
Phillips Screwdriver
Expected Installation Time
15 minutes
Installation
Mount the controller to sheet metal ductwork or a panel using two self-tapping screws (provided). The mounting location must protect the controller from the elements and ultraviolet rays.
Document No. 125-1902
User Guide
June 26, 2018
Siemens Industry, Inc. Page 3 of 16
Figure 1. Controller Mounted to Ductwork.
Outdoor, Return Air, and Mixed Air Sensor Operating and Mounting Instructions
Location and Mounting
The Economizer Controller accepts signals from either the QAM2030.010 (10K, Type II) dry bulb temperature sensor, or 3K NTC temperature sensor. It provides single or differential temperature based economizer control or the QFM2160U combination temperature/humidity sensor for single or dual enthalpy-based economizer control.
CAUTION/ATTENTION:
Do not mix sensors. Temperature sensors must all be either 10K Ohm Type II NTC, or 3K NTC.
Ne mélangez pas de détecteurs. Les détecteurs de température doivent tous être l'un ou l'autre le Type II d'Ohm de 10 Ko NTC, ou 3 Ko NTC.
For differential dry bulb operation, use two QAM2030.010 (10K Type II NTC) or 3K NTC temperature sensors.
Figure 2. 3K NTC Curve.
NOTE: 3K NTC sensors must follow this curve.
Sensor Mounting
1. Mount the sensor in any orientation, exposing it to freely circulating air, using the two mounting screws provided with the sensor. Choose a location that protects it from rain, snow, and direct sunlight.
2. Connect the appropriate Type II NTC 10K or 3K sensor for: o Outside Air: Connect to the OAT and COM
terminals of the device.
o Return Air (Differential): Connect to the RAT
and COM terminals of the device.
o Mixed Air: Connect to the MAT and COM
terminals of the device.
Figure 3. Type II NTC 10K or 3K Sensor Connections.
3. Connect the QFM2160U Combination Temperature/Humidity sensor for Enthalpy control. o Outside Air: Connect to the OAT, COM, and
OAH terminals of the device.
o Return Air (Differential): Connect to the
RAT, COM, and RAH terminals of the device.
Figure 4. QFM2160U Combination
Temperature/Humidity Sensor Connections.
Document No. 125-1902 User Guide June 26, 2018
Page 4 of 16 Siemens Industry, Inc.
NOTE: QFM2160U Combination Temperature/
Humidity Sensors must be powered by an external 24 Vac power supply.
CO2 Sensor – Demand Control Ventilation (DCV)
1. Mount the QPA2000 CO2 Sensor in an area with unobstructed air circulation. See QPA…Series
Indoor Air Quality Room Sensors Installation Instructions (129-435).
2. Connect the sensor to the IAQ and COM terminals of the controller. See Figure 4.
NOTE: CO2 sensors must be powered by an
external 24 Vac power supply.
Powering the Economizer Controller
To power the Economizer Controller, connect a 24 Vac external power supply source.
Figure 5. Connecting to Power Supply Source.
Damper Actuator Connection to the Economizer Controller
1. Connect the appropriate Siemens OpenAir Damper Actuator to the controller actuator input as shown.
2. Select the appropriate modulating (2 to 10 Vdc) spring return damper actuator to operate the Economizer damper. See Table 1.
Figure 6. Damper Actuator Connections.
Table 1. Damper Actuator Selection.
Damper Actuator
Part Number
Torque Rating
Description
GQD151.1P
20 lb-in
Spring Return, 2 to 10 Vdc Signal, Plenum-rated
GMA151.1P
62 lb-in
Spring Return, 2 to 10 Vdc Signal, Plenum-rated
GCA151.1P
160 lb-in
Spring Return, 2 to 10 Vdc Signal, Plenum-rated
Figure 7. Economizer Control Adjustments.
Document No. 125-1902
User Guide
June 26, 2018
Siemens Industry, Inc. Page 5 of 16
Economizer Controller Startup/Commissioning Mode
Factory default settings: All DIP switches are in the OFF (down position).
NOTE:
Use a small, flat-blade screwdriver to select DIP switches. Ensure that the switches are fully in the ON or OFF position.
All potentiometers are in the middle position (arrow pointing upwards).
Initialization
1. Connect the sensor inputs and other auxiliary equipment.
2. Use the DIP switch to select a 3K or 10K sensor (see Figure 7).
3. Use the DIP switch to select Single (SNGL) or Differential (DIFF) mode (see Figure 7).
4. Apply power to the controller (see Figure 5).
5. The controller will perform up to a 20-second auto detection to determine the type of sensor input(s).
If you experience a transient power failure during initialization, the compressors will not suddenly restart because the outputs are deactivated.
Commissioning Mode
This Commissioning mode (COMM) adjusts the Minimum Position of the outside air damper. In the Commissioning mode, the damper will be overridden by Effective MIN POS, or DCV ACT, whichever is greater.
Effective MIN POS is determined by either the onboard MIN POS potentiometer or the Remote MIN POS potentiometer:
Move the DIP switch on the bottom of the controller to the COMM position (see Figure 7) to enter the Commissioning mode. When the Free Cooling LED and DCV LED blink red, this indicates that the controller is in the Commissioning mode. CC1 and CC2 are energized in the Commissioning mode, and the exhaust fan responds to the outside air damper.
Determining Required Airflow
The Consulting Engineer defines the minimum damper position by the minimum outdoor airflow required in the building during the occupied period. To determine the minimum amount of outside air to bring in the building, use these basic guidelines:
The OA rate can be calculated by this formula:
OA
% =
MAT−RAT
OAT−RAT
A minimum 10°F temperature differential between OA and RA must be maintained; otherwise, this formula doesn’t work well.
OR
An airflow measuring station can be used to directly tune the outdoor airflow volumetric rate to designed value. OA rate can be calculated
from formula 𝑂𝐴% =
OAV
SAV
=
OAV
OAV+RAV
, where
minimum differential temperature between OA and RA is not required.
Setting Minimum Position in Commissioning Mode
If a Remote Positioning Potentiometer is being used:
1. Turn the MIN POS potentiometer to the fully closed, 0 position.
2. Turn the DCV ACT potentiometer to the fully closed, 0 position
3. Adjust the Remote MIN POS Potentiometer until the designed OA flow rate is met.
4. After the Remote MIN POS Potentiometer adjustment is complete, turn the DCV ACT potentiometer until designed DCV OA flow rate is met. The DCV ACT setting should be greater than the Remote MIN POS Potentiometer setting.
5. When these adjustments are completed, set the DIP switch to AUTO to resume normal operation.
If the onboard MIN POS Potentiometer is being used:
1. Turn the Remote MIN POS Potentiometer to the fully closed, 0 position.
2. Turn the DCV ACT potentiometer to the fully closed, 0 position,
3. Turn the MIN POS potentiometer until designed OA flow rate is met.
4. After MIN POS adjustment is complete, turn the DCV ACT potentiometer until designed DCV OA flow rate is met. The DCV ACT should be greater than MIN POS.
5. After all MIN POS and DCV ACT adjustments are completed, set the DIP switch to AUTO to resume normal operation.
Loading...
+ 11 hidden pages