Siemens POINTEK CLS 300, Milltronics POINTEK CLS 300 Instruction Manual

Page 1
POINTEK CLS 300
CAPACITANCE
Instruction Manual December 2001
LIQUIDS/SOLIDS
Page 2
Safety Guidelines
Qualified Personnel
This device/system may only be set up and op er ated in conjunction with this manual. Qualified personn el ar e only authorized to install and operate this equip m ent in accordance with established safety practices and standards.
Warning: This product can only function properly and safely if it is correctly transported,
stored, installed, set up , operated, and maintained.
Note: Always us e p r oduct in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2000. All Rights Reserved
This document is available in bound version and in electronic version. We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for t he contents of partial or whole reproductions of eit her bound or electronic versions.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI Technical Publications at th e following address:
Technical Publicat ions Siemens Milltronics Process Instruments Inc. 1954 Technology Drive, P.O. Box 4225 Peterborough, Ontari o, Canada, K9J 7B1 Email: techpubs@siemens-milltronics.com
While we have verified the contents of this manual for agreement w it h t h e instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We w elcome all suggestions for improvement.
Technical data subject to change.
For the library of SMPI instr uct ion manuals, visit: www.siemens-milltronics.com
© Siemens Milltronics Process Instruments Inc. 2001
Page 3
Table of Contents
Introduction to the Pointek CLS 300.............................................................................................2
Pointek CLS 300 Outputs .................................................................................................2
Pointek CLS 300 Features ...............................................................................................2
Pointek CLS 300 Applications.........................................................................................2
Specifications .................................................................................................................................. 3
Installation........................................................................................................................................ 6
Location ..............................................................................................................................6
Configuration and Dimensions...................................................................................................... 7
Standard Version..............................................................................................................8
High Temperature Version .............................................................................................9
Rod Version......................................................................................................................10
Changing Probe Length.................................................................................................10
Cable................................................................................................................................................ 12
Cable Tensile Strength ..................................................................................................13
Cable Weights.................................................................................................................13
Shortening the Cable .....................................................................................................13
Mounting......................................................................................................................................... 14
Multiple units...................................................................................................................14
Wall Restriction...............................................................................................................14
Process Cautions............................................................................................................15
Interconnection ............................................................................................................................. 16
Trip Amplifier ...................................................................................................................16
Relay Output Connection ..............................................................................................17
Solid State Switch ..........................................................................................................17
Diode Protection .............................................................................................................17
Ancillary 2-Wire Output Connection...........................................................................18
Power Connection (3 or 4 wire connection).............................................................18
Operation ........................................................................................................................................ 19
Setup .................................................................................................................................19
Start Up.............................................................................................................................20
Alarm Output....................................................................................................................21
Troubleshooting............................................................................................................................. 24
Maintenance ...................................................................................................................24
Appendix I: Application Notes..................................................................................................... 25
Application Notes...........................................................................................................25
Appendix II: CE Conformity .......................................................................................................... 26
Index................................................................................................................................................ 27
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 1
Page 4
Introduction to the Pointek CLS 300
Note: Pointek CLS 300 is to be used only in the manner outlined in this instruction manual.
The Pointek CLS 300 capacitance level switch provides output on high or low process material levels. When the measured material is at the desired level, the change in
capacitance is sensed and a level alarm is triggered. This could be either a high level alarm (material rising to reach the desired level) or a low level alarm (material falling to reach
desired level).
Pointek CLS 300 Outputs
One form C (SPDT) relay
One isolated, non-polarized, solid-state switch
Pointek CLS 300 Features
NPT, BSPT, JIS (other connections on request)
Corrosion resistant construction, PFA, Ceramic, and 316L stainless steel wetted
parts
25m (82 ft) maximum insertion length
Rugged shear and abrasion resistant probe
Fully adjustable process alarm: level, time delay
Field adjustable insert length
ESD protection to 55 kv continuous discharge
Active shield technology
Pointek CLS 300 Applications
Liquids, slurries, powders, granules, and solids
Chemical and petrochemical
High pressure and temperature
Power Industry (fly-ash)
Page 2 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Page 5
Specifications
Probe
Process Connections
NPT/BSPT/JIS
Wetted Parts
Standard Version: AISI 316L/PFA/Peek
1
2
High Temperature Version: AISI 316L/Ceramics
Probe Lengths
Rod Version: min. 350mm (14") - max. 1000mm (40") Rope/Cable Version: min. 500mm (20") - max. 25000mm (985")
Max. Tensile Force
1900kg (4188lbs)
Pressure Range
3
Standard Version: -1 to +35 barg (-14.6 to +511 psig) High Pressure Version: -1 to +100 barg (-14.6 to +1460 psig)
Temperature Range
3
Standard Version: -40 to 200° C (-40 to 392° F) High Temperature Version: -40 to 400° C (-40 to 752° F) Min. Dielectric Constant (>r): 1.5
Enclosure
Aluminium
Epoxy Coated
Yes
NEMA/CSA/IP-Rating
4/Type4/IP65
Cable Inlet
2 X ½" NPT
Certifications
CENELEC/FM/CSA
1
Other process connections available on request. See Probe: Standard on page 5, or Probe: Cable on page 5.
2
For a chemical resistance list for PFA/Peek /Ceramic, contact your local distributor.
3
See the Pressure/Temperature Curve in Appendix I: Application Notes on p. 25.
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 3
Page 6
Power Supply and Transmitter
Supply Voltage
2 - 250 Vac/dc any polarity galvanically isolated
Power consumption
2VA/2Watt
Wiring connections
Max. 2.5mm
Temperature ranges
Operation (Storage): -40 to 85° C (-40 to 185° F)
Signal indicators
Three: 1. Adjustment control
Adjustment Potentiometers
Two: 1. Time delay adjustment
Adjustment Switches
5PST dip switch:
Min. Sensitivity
1% change in actual capacitance
Max. Temperature Drift
0.2% of Actual Capacitance Value
Measurement Frequency
600 (kHz) max.
ESD protection
Protected to 55kV continuous discharge
2
2. Output status
3. Power
2. Sensitivity adjustment
time delay select
fail safe selection
time delay test/adjust
high/low sensitivity
Output Functions
Relay Contact
Contact: Form C (SPDT) (selectable NC or NO contact) Max. Contact Load (dc): 5A/30V dc Max. Contact Load (ac): 8A/250V ac (cosn=1) Max. Switching Capacity: 150Watt/2000VA Min. Contact Load: 10mA/5Vdc
Time Delay (ON and/or OFF): 1 - 60 sec.
Solid State switch
Output: Galvanically isolated Safety: Non-polarity sensitive transistor Max. Load: 2 Watt Max. Switch Voltage: 250Vac/300Vdc Max. Load Current: 100mA Voltage Drop Below 1 Volt typical @ 50mA Time Delay (On and/or Off) 1 - 60 sec.
Two (2) Wire Switch
With customer supplied external trip devices
Page 4 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Page 7
Probe - Standard
Length
350mm (14") to 1000mm (40")
Process Size (in inches)
NPT: ¾ , 1, 1¼, 1½ BSPT: ¾, 1, 1½ JIS: 1, 1½
Insulating
Material
Standard Version: PFA High Temperature Version: Ceramic No insulation on active probe
Tensile
kg load
Not applicable
Probe Diameter
19mm
Probe - Cable
Length
500mm (20") to 25000mm (985")
Process Size
NPT/BSPT: 1¼" minimum
Insulating
AISI 316L SS PFA insulation optional
Tensile
1900 kg (4188 lbs.)
Electrode Dimensions
Cable: Insulated: 9mm (0.35"
Weight: 32 x 250mm (1.26 x 9.84") Butterfly: 175 x168mm (6.89 x 6.61")
Material
kg load
Non insulated: 6mm (0.24"
Approvals
CE, CSA, NRTL/C, FM, CENELEC Please verify against device nameplate.
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 5
Page 8
Installation
Location
Notes:
Installation shall only be performed by qualified personnel and in accordance with local
governing regulations.
This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
The Pointek CLS 300 as supplied in the standard probe lengths is normally mounted on the vessel top (high detection alarm) or through the tank wall at the detection level (high or low detection alarm).
The cable version is designed for top mounting. The cable suspends vertically so that it reaches into the process at the desired detection level (high or low detection alarm).
Angle Horizontal
Vertical
Page 6 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Page 9
Configuration and Dimensions
191
(7.5")
146
(5.8")
CABLE/ROPE
insulated – 9mm (0.35")
non insulated – 6mm (0.24")
Ø32
(1.26")
136
(5.4")
181
(7.1")
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 7
Page 10
Standard Version
/
59mm
(2.3")
Lid
Lid Clip
½” NPT
76mm
(3")
120mm
(4.7")
Electronics
Enclosure
Active Shield
Probe
145mm
(5.7")
370mm
(14.6")
Page 8 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Ø19mm
(0.75")
Page 11
High Temperature Version
/
Ceramic Active Shield Insulator and Thermal Isolator
Provides a ceramic Active Shield insulator and a Thermal Isolator for when the process temperature is greater than 200E C / 392E F and/or for when the product to be detected is very abrasive. The high temperature version is rated for applications up to 400E C / 752E F.
The Thermal Isolator provides a separation distance between a high process temperature inside the vessel and the electronic housing outside the vessel. This reduces the operating temperature of the electronics to a value equal to or less than 85EC/185EF.
See Temperature and Pressure Recommendations for Application on page 25.
59mm (2.3”)
76mm
120mm
(3”)
Lid
(4.7”)
Lid Clip
½ “ NP
Electronics
Enclosure
Thermal Isolator
Active Shield
Probe
240mm
(9.4”)
Note: dependent on probe configuration
Warning: Do not cover the Thermal Isolator section of this Point Level Switch device with insulation material.
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 9
19mm
(0.73”)
Page 12
Rod Version
The rod version of the CLS 300 is available in standard lengths from 350mm (14") up to 1000mm (40"). Other lengths using stainless steel or other metals can be attached as an electrode when required. Ensure that the thread end conforms to the exact dimensions as shown below. Rod lengths beyond 1000mm (40") are not recommended.
1.5mm by 45 (0.06")
3 mm (0.12”)
12mm (0.47")
Flat sides
= 18mm
(0.71")
Ø19 mm
(0.75" )
Ø11 mm
(0.43”)
9mm
(0.35")
M5
17mm (0.67")
34mm
(1.3")
37mm
(1.5")
M10
Changing Probe Length
The probe length can be shortened in the field by cutting the electrode.
Warning: To prevent damage, do not apply torque directly to the main probe assembly.
Option 1 If the electrode is removable:
1. Remove the electrode by releasing the set screw and turning the threaded electrode end counter-clockwise.
2. Place the upper part of the electrode in a vice as shown.
3. Use a wrench to loosen the
lower portion of the electrode.
Page 10 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Page 13
Option 2 If electrode is NOT removable:
1. With unit mounted in place,
place two wrenches as shown.
2. Hold the upper wrench steady and turn the lower one counter­clockwise to loosen the lower portion of the electrode.
The Wrong Way
If the process connection itself is put in the vice, the probe’s internal parts will rotate along with the wrench and the unit may fail.
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 11
Page 14
Cable
/
t
/
59mm (2.3")
Lid Clip
½” NPT
Electronics
Enclosure
Lid
76mm
(3")
120mm
(4.7")
145mm
(5.7")
nominal value
Active Shield
Cable
Insulated – 9mm (0.35")
Non insulated – 6mm (0.24")
Probe
Weigh
Flexible
Extension
(Customer -
specified
length)
25m
(82 feet)
Max
250mm
(9.85")
Page 12 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Ø32mm
(1.26")
175mm (6.9")
Page 15
Cable Tensile Strength
Do not exceed the tensile strength of the cable at 1900kg/4188lbs.
Always confirm that the load carrying capability of the silo/tank roof is sufficient to withstand the actual force on the cable conditions, especially where the force will be, or could be, as great as 1900kg/4188 lbs. A cable (rope) probe with a PFA jacket reduces the amount of possible product build-up on the probe as well as the tensile force on the cable.
Cable Weights
A standard weight with optional attachable Butterfly enhancer is available for the cable version. We recommend the Butterfly weight for lower dielectric constant materials (often in solids) because it increases the change in capacitance when the material comes in contact with the cable end. This occurs when the silo is quite tall (> 15 m/45 ft) and the dielectric
constant is less than (
>
< 4).
r
Shortening the Cable
Methods
An angle grinder (preferably with a disc suitable for stainless steel)
or
Wire cutters (suitable for piano cable
Ø6 – 9mm).
Procedure
1. Remove Butterfly (if present) from weight.
2. Loosen the three set screws and pull weight from the cable.
3. Grind/cut the cable to the required length, and then remove rough edges from the
cable.
4. Ensure that cable strands are properly seated in the lay of the cable (i.e. no wire
strands sticking outside the normal cable profile). Make sure ALL strands are
properly seated before continuing the assembly.
5. Push the weight onto the cable while simultaneously rotating it counter-
clockwise around the cable. Make sure that no cable strands are pushed out of
their position in the cable and that the cable is fully inserted.
6. Re-fasten the weight by tightening the three set screws.
7. Re-attach Butterfly (if required) to the weight.
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 13
Page 16
Mounting
Multiple units
500mm
(20”) min
End View Side View
500mm
(20”) min
Sensors must be 500mm (20") apart.
Wall Restriction
500mm
(20”) min
Mount diagonally if vertical space is restricted.
Note: These drawings
are not to scale.
50mm* (2”)min
Page 14 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
50mm* (2”)min
* standard version
Page 17
Process Cautions
p
Caution: Keep unit out of path of falling
material.
Caution: Protect probe from falling
material.
Caution: Consider material surface
configuration when installing unit.
Caution: Tensile load must not exceed
probe or vessel rating.
Note: buildu
500mm
(20”) min
of material in active shield area does not affect switch.
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 15
Page 18
Interconnection
t
Trip Amplifier
Loosen the lid clip and remove the enclosure cover to access connectors and electronics. The identification label is on the underside of the enclosure cover.
Relay contac
8A – 250Vac
5A – 30Vdc
Solid state switch 100mA – 250Vac 100mA – 300Vdc Max: – 2VA
Notes:
Switch and potentiometer settings are for illustration purposes only. Refer to
Setup on page 19.
Relay contact terminals are for use with equipment having no accessible live
parts and wiring having insulation suitable for at least 250V ac
Maximum working voltage between adjacent relay contacts shall be 250V ac
Warning:
All field wiring must have insulation suitable for at least 250V ac.
Page 16 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Page 19
Relay Output Connection
Solid State Switch
Relay shown in de-energized state.
K2 contact ratings:
8A at 250V ac
5A at 30V dc
Switch shown in de-energized state.
K3 contact ratings:
250V ac,100mA, max, non-
polarized (max 2VA)
300V dc, 100mA max, non-
polarized (max 2VA)
Solid-state switch to customer’s control
or instrumentation device
Diode Protection
When driving an external relay with either the solid stated switch and/or relay outputs using dc power, protection diodes must be connected in the correct polarity across the relay coil to prevent possible switch/relay damage resulting from inductive spikes generated by the relay coil.
Switch capacity:
250V ac
100mA max 2VA/2W max
300V dc.
relay coil
Customer supplied diode protection
100mA max 2VA/2W max
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 17
relay coil
Customer supplied diode protection
Page 20
Ancillary 2-Wire Output Connection
t
Optically isolated switch. (Customer supplied; we suggest Phoenix DEK-OE-5DC/48DC/100 or equivalent)
Outpu
See Power Connection below.
V dc
Power Connection (3 or 4 wire connection)
Nominal 24V dc 48 V dc
DC volts 22-26 46-50
R (S) 120 234
12 – 250 V
(ac/dc)
Page 18 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Page 21
Operation
Setup
Note: Setup can be done in the field with the Pointek CLS 300 mounted into process, or in
the shop prior to mounting.
Dip Switch 1
Set ON to change alarm relay status immediately when the sensor detects a change in
frequency. Use this setting when time is critical.
Set OFF to change the alarm relay status with a delay by the amount set on
potentiometer #1 (P1). Use this setting when you want to slow the response to account for turbulence or false readings.
Dip Switch 2
Set ON to change alarm relay status immediately when the sensor detects a change in
frequency. Use this setting when time is critical.
Set OFF to change the alarm relay status with a delay by the amount set on
potentiometer #1 (P1). Use this setting when you want to slow the response to account for turbulence or false readings.
Dip Switch 3
Set OFF to indicate Low fail-safe selection.
Set ON to indicate High fail-safe selection.
Dip Switch 4
Set ON to test the delay of the alarm relays as set by the potentiometer #1 (P1).
Set OFF for normal operation.
Dip Switch 5
Delay ON
Set ON for normal sensitivity on the
sensor. Use this setting when you are measuring dry solids or non-conductive liquids.
Delay OFF
Fail-safe
Delay test
Sensitivity
Set OFF for low sensitivity on the
sensor. Use this setting to measure conductive liquids or wet conductive solids which are likely to build up.
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 19
Switches shown in OFF position
Page 22
On Off
Delay On
S1 - 1
Disabled Disabled High Test Normal
Enabled Enabled Low Normal low
Delay Off
S1 - 2
Fail-safe
S1 - 3
Delay Test
S1 – 4
Sensitivity
S1 - 5
Start Up
After the CLS is properly mounted and the switch bank set up, apply power to the unit. The green LED (L3) lights to indicate the unit is powered and operational.
Indicators
Three LEDs indication the following:
L1 (yellow) = sensor status: When P2 is properly set, this LED indicates when
the sensor is in contact with the process material (material capacitance is greater than set point, P2).
L1 is off when the sensor is out of contact with the process material (material capacitance is less than set point).
L2 (red) = output status: This LED indicates the relay and solid switch
contact status. Refer to Operation\Output Status below.
L3 (green) = power: This LED is on when the Pointek CLS is properly
powered.
Page 20 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Page 23
Alarm Output
Alarm Output Status
Covered Uncovered
Setpoint Adjustment
As reference, and to assist adjusting the alarm setpoint for reliable and accurate detection of the process material, we have categorized the materials and applications into two cases.
Follow the setup procedure associated with the case which includes your application.
Case 1
General applications, characterized by the following:
dry solids
low viscosity liquids
hygroscopic / wet solids
high viscosity and high conductivity liquids
Case 2
Interface detection:
e.g. liquid A / liquid B, foam / liquid
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 21
Page 24
Trip Amplifier
Case 1
Preparation
Ensure that L3 (green) is ON
Turn both potentiometers, P1 and P2, fully CCW (counter-clockwise)
Set S1 switches 1 to 4 to OFF and S1 switch 5 to ON (normal sensitivity)
Configuration
1. With sensor uncovered and a minimum 100mm free space all around, turn P2 CW until L1 (yellow) goes ON.
2. Turn P2 CCW until L1 goes OFF.
Case 2
Preparation
Ensure that L3 (green) is ON
Turn potentiometer P1 fully CCW (counter-clockwise)
Turn P2 fully CW (clockwise)
Set S1 switches 1 through 5 to OFF
Configuration
1. Immerse the sensor in the material that has the lowest dielectric constant. L1 (yellow)
should be ON. (If L1 does not light, set S1 switch 5 to ON [normal sensitivity].)
2. Adjust P2 CCW until L1 goes OFF.
3. Immerse the sensor in the material that has the highest dielectric constant; L1 should
come ON.
Page 22 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Page 25
Delay
The alarm actuation can be delayed for either, or both, ON alarm and OFF alarm conditions.
Set S1-1 and S1-2. (Refer to Setup\ Switch Bank on p. 19.)
Adjust the delay time from 1 to 60 seconds by setting potentiometer P1
Operation
After completing the setup, replace the Pointek CLS lid and lid clip. The unit is now in service, providing level detection of your process.
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 23
Page 26
Troubleshooting
Symptom Observation Action
No alarm response L3 (green LED) off Check power supply
Check sensitivity, S1-5,
Alarm won’t switch when material level moves down the electrode
L1 (yellow) doesn’t respond to reducing level on the electrode
L1 (yellow) responds to reducing level on the electrode
electrode, connections to sensor input on trip amplifier (and zener barrier continuity if used)
Check that relay and L2 (red LED) changes state when S1-3 is toggled
Alarm doesn’t switch when material level moves up the electrode
L1 (yellow) doesn’t respond to the sensing electrode approaching or touching
L1 (yellow) responds to increasing level on the electrode
L1 (yellow) flashes when approaching the alarm trip­point
Check sensitivity S1-5, electrode, (and zener barrier continuity, if used)
Check that relay and L2 (red LED) changes state when S1-3 is toggled
Maintenance
The Pointek CLS 300 requires no regular maintenance or cleaning. Even with significant build­up on the CLS 300 level detector electrode, the level switch will continue to operate. Build-up of material on the active shield area has little or no effect on the performance of the CLS 300.
Page 24 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Page 27
Appendix I: Application Notes
Application Notes
Temperature and Pressure Recommendations for Application
Note: 1 bar = 100 Pascals
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 25
Page 28
Appendix II: CE Conformity
WRITTEN DECLARATION OF CONFORMITY
We,
Siemens Milltronics Process Instruments B.V. Nikkelstraat 10 - 4823 AB BREDA - The Netherlands
Declare, solely under own responsibility, that the product
Point Level Switch,
Pointek CLS 300
Mentioned in this declaration, complies with the following standards and/or normative documents:
Requirements Remarks Certificate No.
Environment Commercial, light Industrial, and industrial 2008949-KRQ/EMC 01-4230
EN 61326: 1998 Product group standard for “Electrical equipment for measurement,
control and laboratory use”, from which:
EN 50011: 1998 Emission – Class B
EN 61000-4-2: 1995 Electrostatic Discharge (ESD) Immunity EN 61000-4-3: 1996 Radiated Electro-Magnetic Field Immunity EN 61000-4-4: 1995 Electrostatic Fast Transient (EFT) Immunity EN 61000-4-5: 1995 Surge Transient Immunity EN 61000-4-6: 1996 Conducted Radio-Frequency Disturbances Immunity
ATEX Directive 94/9/EC Audit Report No. 2003068
II 1/ 2 GD EEx d [ia] IIC T6…T1
T 100 °C IP 66
EN 50014: 1992 General Requirements EN 50018: 1994 Flameproof Enclosures “d" EN 50020: 1994 Intrinsic Safety “i" EN 50284: 1999 Special Requirements for Category 1G Equipment EN 50281-1-1: 1998 Dust Ignition Proof
0344
KEMA 00ATEXQ3047
KEMA 00ATEX2040X
The notified body : N.V. KEMA – Utrechtseweg 310 – 6812 AR Arnhem – The Netherlands
97/23EC Pressure Equipment Directive Lloyd’s Register, DAD No.:
8033472, 8033473, 8033628
The notified body: Stoomwezen B.V. – Weena Zuid 168 – 3012 NC Rotterdam – The Netherlands
Location: Breda Named Representative: C.S. van Gils Date: Aug 31, 2001 Position: Managing Director
Note: For specific safety specifications, please consult the instrument label.
Page 26 Pointek CLS 300 – INSTRUCTION MANUAL 7ML19985CK03
Page 29
Index
2-Wire Connection .............................................18
3 or 4 wire connection........................................18
About Pointek CLS 300.........................................2
Adjusting Probe Length......................................10
Alarm Output......................................................21
Setpoint Adjustment.....................................21
Status............................................................21
Ancillary 2-Wire Output Connection...................18
Appendix............................................................25
Appendix II .........................................................26
Application Notes...............................................25
Applications .........................................................2
Approvals.............................................................5
Cable..................................................................12
Shortening it..................................................13
Tensile Strength............................................13
Weights.........................................................13
Ceramic Active Shield Insulator ...........................9
Configuration........................................................7
DECLARATION OF CONFORMITY.......................26
Dimensions...........................................................7
High Temperature Version..............................9
Standard Version ............................................8
Diode Protection.................................................17
Dip Switches......................................................19
Electrode
Shortening the Probe ....................................10
Enclosure cover
removing .......................................................16
Trip Amplifier.................................................16
LEDs ...................................................................20
Location................................................................6
Angle...............................................................6
Horizontal........................................................6
Vertical............................................................6
Maintenance......................................................24
Mounting............................................................14
Multiple Units................................................14
Process Concerns..........................................15
Wall Restriction.............................................14
Operation ...........................................................19
Alarm Output.................................................21
Set Up ...........................................................19
Start Up.........................................................20
Output status .....................................................20
Outputs ................................................................2
Pointek CLS 300 ...................................................2
Applications ....................................................2
Configuration...................................................7
Dimensions......................................................8
Features ..........................................................2
Outputs ...........................................................2
Power.................................................................20
Power Connection..............................................18
3 or 4 wire connection...................................18
Power Supply .......................................................4
Protection diodes ...............................................17
Relay Output Connection ...................................17
Rod Version........................................................10
Features ...............................................................2
High Temperature Version...................................9
Dimensions......................................................9
High Temperatures
Recommendations ..........................................9
Indicators ...........................................................20
Installation ...........................................................6
Location...........................................................6
Interconnection ..................................................16
Ancillary 2-Wire Output Connection..............18
Diode Protection............................................17
Power Connection.........................................18
Relay Output Connection ..............................17
Solid State Switch.........................................17
7ML19985CK03 Pointek CLS 300 – INSTRUCTION MANUAL Page 27
Sensor status.....................................................20
Set Up ................................................................19
Dip Switches.................................................19
Setpoint Adjustment..........................................21
Shield Insulator ....................................................9
Shortening Probe ...............................................10
Solid State Switch..............................................17
Solid stated switch ............................................17
Specifications.......................................................3
Standard Version .................................................8
Dimensions......................................................8
Start Up..............................................................20
Transmitter...........................................................4
Trip Amplifier......................................................16
Troubleshooting .................................................24
Page 30
Notes
Page 31
Page 32
c
*7ML19985CK03*
Loading...