Siemens Pointek CLS200,Pointek CLS300 Operating Instructions Manual

Capacitance Switches
Pointek CLS200/CLS300 (Standard)
Operating Instructions 09/2009
SITRANS
Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed.
Qualified Personnel: This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.
Unit Repair and Excluded Liability:
The user is responsible for all changes and repairs made to the device by the user or the user’s
agent.
All new components are to be provided by Siemens Milltronics Process Instruments Inc.
Restrict repair to faulty components only.
Do not reuse faulty components.
Warning: Cardboard shipping package provides limited humidity and moisture protection. This product can only function properly and safely if it is correctly transported, stored, installed, set up, operated, and maintained. This product is intended for use in industrial areas. Operation of this equipment in a residential area may cause interference to several frequency based communications.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2009. All Rights Reserved
This document is available in bound version and in electronic version. We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions.
While we have verified the contents of this manual for agreement with the instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. Please check the website shown below for the latest manual revisions. We welcome all suggestions for improvement.
Technical data subject to change.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI Technical Publications European Authorized Representative at the following address:
Technical Publications Siemens AG Siemens Milltronics Process Instruments Inc. Industry Sector 1954 Technology Drive, P.O. Box 4225 76181 Karlsruhe Peterborough, Ontario, Canada, K9J 7B1 Deutschland Email: techpubs.smpi@siemens.com
For a selection of Siemens Milltronics level measurement manuals, go to:
www. siemens.com/processautomation. Under Process Instrumentation, select
Measurement
For a selection of Siemens Milltronics weighing manuals, go to:
www. siemens.com/processautomation. Under Weighing Technology, select
Weighing Systems
© Siemens Milltronics Process Instruments Inc. 2009
and then go to the manual archive listed under the product family.
and then go to the manual archive listed under the product family.
Level
Continuous

Table of Contents

Safety Notes .....................................................................................................................................1
Safety marking symbols ............................................................................................................1
The Manual ......................................................................................................................................1
Application Examples .................................................................................................................2
Technical Support ...........................................................................................................................2
Abbreviations and Identifications ...........................................................................3
Pointek CLS200/300 Standard ...................................................................................4
Pointek CLS200/300 Applications ................................................................................................5
Pointek CLS200/300 Features .......................................................................................................5
Specifications: standard model ...............................................................................6
Pointek CLS200/300......................................................................................................................... 6
Power............................................................................................................................................. 6
Performance................................................................................................................................. 6
Interface ........................................................................................................................................ 6
Alarm Outputs.............................................................................................................................. 6
Mechanical................................................................................................................................... 7
Environmental.............................................................................................................................. 9
Process ....................................................................................................................................... 10
Approvals (verify against product nameplate)................................................................... 10
Installation: Pointek CLS200 Standard ..................................................................12
Location ..........................................................................................................................................12
Mounting .........................................................................................................................................12
Mounting Restrictions ..............................................................................................................13
CLS200 Dimensions ..................................................................................................................14
Process Cautions .........................................................................................................................15
Installation: Pointek CLS300 Standard ..................................................................16
Location ..........................................................................................................................................16
Mounting .........................................................................................................................................16
Mounting Restrictions ..............................................................................................................17
Process Cautions .........................................................................................................................18
CLS300 Dimensions ......................................................................................................................19
Wiring: Pointek CLS200/300 standard ...................................................................20
Relay Output Connection ............................................................................................................21
Solid-state Switch ........................................................................................................................21
Diode Protection ........................................................................................................................22
Power Connection ...................................................................................................................22
Functionality Test ..........................................................................................................................23
Operation: Pointek CLS200/300 standard model .................................................24
User Interface ................................................................................................................................24
Indicators ....................................................................................................................................24
Alarm Output ..............................................................................................................................25
Switch Bank ...............................................................................................................................26
Setup ............................................................................................................................................27
Start Up ........................................................................................................................................28
Table of Contents
i
Troubleshooting: Pointek CLS200/300 standard model .....................................31
Appendix A: Technical References .......................................................................32
Operating Principles .....................................................................................................................32
High Frequency Oscillator ...........................................................................................................32
Detection Range ............................................................................................................................32
The Pointek CLS200 electrode ...................................................................................................33
The Pointek CLS300 electrode ...................................................................................................34
Table o f C on t en t s
Pointek CLS200 Standard Pressure versus Temperature Curves ....................................35
CLS200 compact and extended rod versions, threaded ..................................................35
CLS200 cable version, threaded ............................................................................................36
CLS200 sanitary compact and extended rod versions .....................................................36
CLS200 compact and extended rod, ASME welded flange ............................................36
CLS200 cable, ASME welded flange ....................................................................................37
CLS200 compact and extended rod, EN welded flange ...................................................37
CLS200 cable, EN welded flange ...........................................................................................37
Pointek CLS300 Standard Pressure versus Temperature Curves ....................................38
CLS300 standard, extended rod and cable versions, threaded .....................................38
CLS300 high temperature rod version, threaded ...............................................................38
CLS300 standard, extended rod and cable versions, ASME welded flange ..............39
CLS300 high temperature rod version, ASME welded flange ........................................39
CLS300 standard, extended rod and cable versions, EN welded flange .....................40
CLS300 high temperature rod version, EN welded flange ..............................................40
Appendix B: Maintenance and Repairs ................................................................41
Unit Repair and Excluded Liability ............................................................................................41
Appendix C: Product Nameplates .........................................................................42
Pointek CLS200 ..............................................................................................................................42
Pointek CLS300 ..............................................................................................................................43
Appendix D: Hazardous Area Installation ............................................................44
Instructions specific to hazardous area installations ..........................................................44
Appendix E: Dimensions - CLS200 .........................................................................47
Appendix F: Dimensions - CLS300 .........................................................................55
Threaded Processs Connection ............................................................................................55
High Temperature Rod Version, threaded ..............................................................................57
Non-insulated Cable Version, threaded ..............................................................................58
Insulated Cable Version, threaded ...........................................................................................59
CLS300 - Flanged Process Connections ..............................................................................60
Flange Facing Table .................................................................................................................60
Rod Version, welded flange .......................................................................................................61
High Temperature Rod Version, welded flange ....................................................................62
Non-insulated Cable Version, welded flange ........................................................................63
Insulated Cable Version, welded flange ..................................................................................64
Appendix G: Shortening the cable .........................................................................65
Pointek CLS200 Standard, Cable Version ............................................................................65
Pointek CLS300 Standard, Cable Version ............................................................................68
Appendix H: Application for Pointek CLS200/300 Standard ..............................69
Level Detection ..........................................................................................................................69
Alarm Signaling .........................................................................................................................69
ii
Fault Signaling ...........................................................................................................................70
Glossary ............................................................................................................................71
Index ..................................................................................................................................73
Table of Contents
iii
Table o f C on t en t s
iv

Safety Notes

Special attention must be paid to warnings and notes highlighted from the rest of the text by grey boxes.
1
WARNING: relates to a caution symbol on the product, and means that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage.
WARNING
1
: means that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage.
CAUTION: means that failure to observe the necessary precautions can result in considerable material damage.
Note:
means important information about the product or that part of the operating
manual.

Safety marking symbols

In manual On Product Description
Caution: refer to accompanying documents (manual) for details.
Earth (ground) Terminal
Pointek CLS200/300
Protective Conductor Terminal

The Manual

Note: Please follow the installation and operating procedures for a quick, trouble-free
installation and to ensure the maximum accuracy and reliability of your Pointek CLS200/
300. This manual applies to the Pointek CLS200/300 Standard model only.
Pointek CLS200/300 is available in two models, standard and digital. For information on the CLS200/300 digital model, please see manual 7ML19985JJ01.
This manual will help you set up your Pointek CLS200/300 Standard for optimum performance.
Sections in this manual are designated as follows:
Pointek CLS200/300 Standard
model and to the manual
Specifications: standard model
Installation: Pointek CLS200 Standard
1.
This symbol is used when there is no corresponding caution symbol on the product.
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 1
- an introduction to Pointek CLS200/300 Standard
Installation: Pointek CLS300 Standard
Appendix A: Technical References
Appendix B: Maintenance and Repairs
Appendix C: Product Nameplates
Appendix D: Hazardous Area Installation
Appendix E: Dimensions - CLS200
Appendix F: Dimensions - CLS300
Appendix G: Shortening the cable
We always welcome suggestions and comments about manual content, design, and accessibility. Please direct your comments to techpubs.smpi@siemens.com.
For other Siemens Milltronics level measurement manuals, go to: www.siemens.com/level
and look under Level Measurement.

Application Examples

The application examples used in this manual illustrate typical installations using Pointek CLS200/300; other configurations may also apply.
Pointek CLS200/300
In all examples, substitute your own application details. If the examples do not apply to your application, check the applicable parameter reference for the available options.

Technical Support

Support is available 24 hours a day.
To find your local Siemens Automation Office address, phone number and fax number go to:
www.siemens.com/automation/partner
Click on the tab Contacts by Product then drill down to find your product group (+Process Automation > +Process Instrumentation > +Level Measuring Instruments).
Select the team Technical Suppo r t . Click on Next.
Click on the appropriate continent, then select the country followed by the city. Click on Next.
For on-line technical support go to:
www.siemens.com/automation/support-request
Enter the device name or order number, then click on Search, and select the appropriate product type. Click on Next.
You will be prompted to enter a keyword describing your issue. Then either browse the relevant documentation, or click on Next to email a detailed description of your issue to Siemens Technical Support staff.
Siemens A&D Technical Support Center: phone +49 180 50 50 222
fax +49 180 50 50 223
Page 2 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01

Abbreviations and Identifications

Short form Long Form Description Units
CE / FM / CSA Conformitè Europèene / Factory
Mutual / Canadian Standards Association
ε
r
ESD Electrostatic Discharge
Ex Explosion Proof safety approval
Exd Flame Proof method of protection
FEP Fluorinated Ethylene Polymer modified polymer
FKM/FPM Fluorelastomer
FFKM/FFPM Perfluoroelastomer
IS Intrinsically Safe method of protection
LCD Liquid Crystal Display
LUI Local User Interface
μF micro Farads 10
μs micro Seconds 10
NC normally closed relay contact position
NO normally open relay contact position
pF pico Farads 10
PDM Process Device Manager configuration tool
PEEK Polyaryletheretherketone organic polymer
PPS Polyphenylene Sulfide polymer
PTFE Polytetrafluoroethylene thermoplastic
PVDF Polyvinylidene Fluoride engineered
safety approval
relative dielectric constant
for hazardous area
for hazardous area
-6
-6
-12
fluoropolymer
fluoropolymer
Pointek CLS200/300
Farad
Seconds
Farad
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 3

Pointek CLS200/300 Standard

CLS200 Standard model
CLS300 Standard model
Notes:
• Pointek CLS200/300 is available in two models: the standard model, and the digital model with integral local display. For information on the CLS200/300 Digital, please see manual 7ML19985JJ01.
• Pointek CLS200/300 is to be used only in the manner outlined in this instruction manual, otherwise protection provided by the equipment may be impaired.
• This product is intended for use in industrial areas. Operation of this equipment in a residential area may cause interference to several frequency based communications.
Pointek CLS200/300 is a versatile capacitance switch, ideal for level detection of interfaces, solids, liquids, slurries, and foam, and for simple pump control. The switch responds to the presence of any material with a relative dielectric constant of 1.5 or more by detecting a change in capacitance, which is registered as a change in oscillating
Pointek CLS200/300
frequency.
The switch can be set to detect before contact or on contact with the probe. The design of the CLS200 standard allows the instrument to operate independently of the tank wall or pipe, so it does not require an external reference electrode for level detection in a non­conductive vessel such as concrete or plastic. The CLS300 standard requires a connection to earth/ground for effective capacitance measurement.
The power supply is galvanically isolated and can accept voltages in the range 12 to 250 V AC/DC, depending on the application. The materials used in the probe construction provide a high level of chemical resistance, and an excellent temperature rating on the process wetted portion of the probe: up to 125 °C (257 °F) for the CLS200 and 400 °C (752 °F) for the CLS300.
Page 4 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Modular design and construction provide a wide choice of configurations, including rod, cable, and sanitary versions. When used with a SensGuard protection cover, the CLS200 sensor is protected from shearing, impact, and abrasion, in tough primary processes.

Pointek CLS200/300 Applications

Pointek CLS200/300 is designed for level detection and simple pump control in a variety of applications:
Liquids, solids (powder and granules), slurries, interface detection (for example, oil/ water), and foam detection
Foods and pharmaceuticals
Chemical and petrochemical
High pressure and temperature

Pointek CLS200/300 Features

Potted construction protects components from shock, vibration, humidity, and/or condensation
High chemical resistance on probes
Level detection independent of tank wall/pipe (CLS200 only)
Freely programmable set up covers wide range of applications/materials
Integrated Local User Interface (LUI) for ease of use
Rigid and cable versions available
Operation in safety related systems for overspill in accordance with IEC61508/61511 SIL2
Patented Active Shield minimizes the effect of product build-up at the sensor mounting point (CLS300 only)
Pointek CLS200/300
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 5

Specifications: standard model

Note: Siemens Milltronics makes every attempt to ensure the accuracy of these
specifications, but reserves the right to change them at any time.

Pointek CLS200/300

Power
• supply 12 to 250 V AC/DC (0 to 60 Hz)
• power consumption 2W max.
Performance
• Repeatability ±1% of measurement
Interface
• configuration locally, using dip switches and potentiometers
• local display 3 LED indicators
• output relay contact and solid-state switch
• polarity-independent yes
• failsafe relay and solid-state switch can be de-energized in the absence of a sensor signal
Alarm Outputs
Specifications: standard
• relay 1 Form C (SPDT) contact (selectable NC or NO contact) max. switching voltage/current (DC): 30 V DC / 5 A max. switching voltage/current (AC): 250 V AC / 8 A (resistive load)
• solid-state switch rated 30 V DC or peak 30 V AC, 82 mA
• time delay ON/OFF alarm, selectable
1 to 60 seconds duration
• hysteresis dependent on
• failsafe operation Failsafe High or Failsafe Low
• delay timers 2: Alarm ON to OFF and Alarm OFF to ON
Page 6 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
ε
: max. 2 mm (0.08”) @ εr= 1.5
r
Mechanical
Electrode - CLS200 Standard
Model
Rod 5500 mm/
Sanitary 5500 mm/
Cable 30 m/
Length
(max)
216.5”
216.5”
98.4 ft
Process Con-
nections
• Threaded: ¾”, 1", or 1 ½" BSPT (R), BSPP (G) or NPT; 1 ¼” NPT only
• Welded flange: ASME: 1”, 1 ½”, 2”, 3” or 4” DN 25, 40, 50, 80 or 100
1", 1 ½ ", 2”, 2 ½"
and 3”sanitary
clamp
• Threaded: ¾ ", 1", or 1 ½" BSPT (R), BSPP (G) or NPT; 1 ¼” NPT only
• Welded flange: ASME: 1”, 1 ½”, 2”, 3” or 4” DN 25, 40, 50, 80 or 100
1
Extension
316L¹ stain-
less steel
316L¹ stain-
less steel
FEP (Fluori-
nated Ethyl-
ene
Polymer)
Tensile
(max)
n/a
n/a
180 kg/
400 lbs
Wetted Parts
1
stainless
•316L steel (optional PFA coating)
• FKM seals (optional FFKM)
• PPS probe (optional PVDF)
1
stainless
•316L steel
• FKM seals (optional FFKM)
• PPS probe (optional PVDF)
1
stainless
•316L steel
• FEP jacketed cable
• FKM seals (optional FFKM)
• PPS probe (optional PVDF)
Specifications: standard
1.
Or 1.4404 material.
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 7
Electrode - CLS300 Standard
Model
Rod
(19 mm/
0.75” dia.)
Length
(max)
1000 mm/40”
Process Connec-
tions
• Threaded: ¾”, 1", or 1 ½" BSPT (R), BSPP (G) or NPT; 1 ¼” NPT only
• Welded flange: ASME: 1”, 1 ½”, 2”, 3” or
Tensile
(max)
n/a
Wetted Parts
1
stainless steel
• 316L
• FKM seals (optional FFKM)
• PFA lining on Active Shield
• PEEK isolators
4” DN 25, 40, 50, 80 or 100
Cable 25000 mm/
985”
• Threaded: 1 ½" BSPT (R), BSPP (G) or NPT; 1 ¼” NPT only
• Welded flange: ASME: 1 ½”, 2”, 3” or 4” DN 40, 50, 80 or 100
1900 kg/
4188 lbs
1
stainless steel
• 316L Active Shield and cable weight
1
stainless steel
• 316L cable (optional PFA jacketed cable)
• FKM seals (optional FFKM)
• PEEK isolators
1
High Tem-
perature
version
1000 mm/40”
• Threaded: ¾”, 1", or 1 ½" BSPT (R), BSPP (G) or NPT; 1 ¼” NPT only
n/a
stainless steel
• 316L
• Ceramic isolators
• Welded flange: ASME: 1”, 1 ½”, 2”, 3” or 4”
Specifications: standard
DN 25, 40, 50, 80 or 100
Page 8 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Active Shield Length (CLS300 only):
Length
Minimum insertion length
Active Shield
Standard length
Extended shield
Extended shield
Threaded Flanged Rod version
125 mm/4.92” 105 mm/4.13” 350 mm/13.78” 500 mm/19.69” 350 mm/13.78”
250 mm/9.84” 230 mm/9.06” 50 0 mm/19.69” 1000 mm/40” 500 mm/19.69”
400 mm/15.75” 380 mm/14.96” 750 mm/29.53” 1000 mm/40” 750 mm/29.53”
Cable
version
High Temp.
version
Enclosure
• termination removable terminal block, conductor cross-section 2.5 mm
2
max.
• construction epoxy-coated aluminum with gasket
• optional thermal isolator 316L
1
stainless steel
• cable entry 2 x M20 thread (option: 1 x 1/2” NPT with adaptor,
and 1 x plugged entry)
• ingress protection Type 4 / NEMA 4 / IP65 standard, IP68 optional
Note: The use of approved watertight conduit hubs/glands is required for Type 4 /
NEMA 4, Type 6 / NEMA 6, IP68 (outdoor applications).
Weight
Weight varies based on configuration. For example:
• compact Pointek CLS200/300, 1 kg (2.20 lb.) approx.
100 mm (4”) insertion length, 3/4” process connection
Specifications: standard
Environmental
• location indoor/outdoor
• altitude 20 00 m (6562 ft.) max.
• ambient temperature
- general applications –40 to 85 °C (–40 to +185 °F)
- in potentially explosive atmospheres refer to appropriate certificate
• storage temperature –40 to 85 °C (–40 to +185 °F)
• relative humidity suitable for outdoor (Type 4 / NEMA 4 / IP68)
• installation category II
• pollution degree 4
1.
Or 1.4404 material.
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 9
Process
Note: Please see
and
Pointek CLS300 Standard Pressure versus Temperature Curves
• relative dielectric constant (εr) 1.5 minimum
• CLS200 temperature:
- without thermal isolator –40 to 85 °C (–40 to 185 °F)
- with thermal isolator –40 to 125 °C (–40 to 257 °F)
• CLS200 pressure (vessel):
- rod version –1 to 25 bar g/–14.6 to 365 psi g (nominal)
- cable version –1 to 10 bar g/–14.6 to 150 psi g (nominal)
- sliding coupling version –1 to 10 bar g/–14.6 to 150 psi g (nominal)
• CLS300 temperature:
- rod/cable version –40 to 85°C (–40 to 185°F) without thermal isolator
- rod/cable version –40 to 200°C (–40 to 392 °F) with thermal isolator
- high temperature version –40 to 400 °C (–40 to 752 °F)
• CLS300 pressure (vessel): –1 to 35 bar g/–14.6 to 511 psi g (nominal)
Pointek CLS200 Standard Pressure versus Temperature Curves
1
2
Approvals (verify against product nameplate)
CLS200
on page 35.
Specifications: standard
• General Purpose CSA, FM, CE, C-TICK
• Dust Ignition Proof ATEX II 1/2 D T100°C
• Dust Ignition Proof CSA/FM Class II, Div. 1, Gr. E, F, G with IS Probe CSA/FM Class III T4
• Explosion Proof Enclosure CSA/FM Class I, Div. 1, Gr. A, B, C, D with IS Probe CSA/FM Class II, Div. 1 Gr. E, F, G
CSA/FM Class III T4
• Flame Proof Enclosure ATEX II 1/2 G EEx d[ia] IIC T6 to T4 with IS Probe ATEX II 1/2 D T100°C
• Marine Lloyds Register of Shipping, Categories ENV1,
ENV2 and ENV5
• Overfill Protection WHG (Germany)
• Others SIL/IEC61508 Declaration of Conformity
[SIL-2(overspill)] Pattern Approval (China)
1.
at process connection
2.
at process connection
Page 10 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
CLS300
• General Purpose CSA, FM, CE, C-TICK
• Dust Ignition Proof CSA/FM Class II, Div. 1, Gr. E, F, G with IS Probe CSA/FM Class III T4
ATEX II 1/2 D T100°C
• Explosion Proof CSA/FM Class I, Div. 1, Gr. A, B, C, D with IS Probe CSA/FM Class II, Div. 1, Gr. E, F, G
CSA/FM Class III T4
• Flame Proof Enclosure ATEX II 1/2G EEx d[ia] IIC T6 to T1 with IS Probe ATEX II 1/2 D T100°C
• Marine Lloyds Register of Shipping, Categories ENV1,
ENV2 and ENV5
• Overfill Protection WHG (Germany)
• Others SIL/IEC61508 Declaration of Conformity
[SIL-2(overspill)], Pattern Approval (China)
Specifications: standard
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 11

Installation: Pointek CLS200 Standard

High level alarm Low level alarm
normal process level
normal process level
vertical
horizontal
Notes:
• Installation shall only be performed by qualified personnel and in accordance with local governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding procedures.
• The housing may only be opened for maintenance, local operation, or electrical installation.
• Before installing the instrument, verify that the environment complies with any restrictions specified on the product nameplate.

Location

Recommended:
Provide a sun shield to protect the transmitter from direct heat radiation.
Precautions:
Avoid mounting Pointek CLS200 in locations subject to strong vibrations in the vicinity, whenever possible.
Do not exceed the permissible ambient temperature limits (see page 9 for details).
Environmental
on

Mounting

CLS200 Installation
Page 12 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Pointek CLS200 (compact threaded probe shown )
For high level alarm (level exceeds normal process level):
normally mounted into the vessel top, or
mounted through the tank wall at the detection level
For low level alarm (level drops below normal process level):
mounted through the tank wall at the detection level
Pointek CLS200 typical configuration with extensions:
Angle
High level alarm Low level alarm
normal process level
normal process level
50 mm (2") min
50 mm
(2") min
In nozzle
Close to tank walls
> 100mm
(4") Ø
50 mm (2") minimum
For high or low level alarm:
designed for top mounting. The probe suspends vertically so that it reaches into
the process at the desired detection level (high or low detection alarm).

Mounting Restrictions

Note:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 100 mm (4") between them, to prevent interference.
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 13
CLS200 Installation

CLS200 Dimensions

Sensors must be at least 100 mm (4") apart.
Side View
100 mm
(4") min
100 mm
(4") min
100 mm
(4") min
End View
Mount diagonally if space is restricted
Multiple Units
Dimensions for all versions of the Pointek CLS200 Standard can be found in
Dimensions - CLS200
starting on page 47.
CLS200 Installation
Page 14 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Appendix E:

Process Cautions

Cautions:
• The maximum allowable torque on a horizontally installed rod is 15 Nm.
• Keep unit out of path of falling material, or protect probe from falling material.
Caution: Tensile load must not exceed probe or vessel rating (See
Tensile
(max)
on page 7.).
Caution: Avoid areas where material build up occurs.
50 mm
(2") min
Caution: Consider material surface configuration when installing unit.
CLS200 Installation
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 15

Installation: Pointek CLS300 Standard

High level alarm Low level alarm
normal process level
normal process level
detection level
vertical
horizontal
Notes:
• Installation shall only be performed by qualified personnel and in accordance with local governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding procedures.
• The housing may only be opened for maintenance, local operation, or electrical installation.
• Before installing the instrument, verify that the environment complies with any restrictions specified on the product nameplate.

Location

Recommended:
Provide a sun shield to protect the transmitter from direct heat radiation.
Precautions:
Avoid mounting Pointek CLS300 Standard in locations subject to strong vibrations in the vicinity, whenever possible.
Do not exceed the permissible ambient temperature limits (see page 9 for details).
Environmental
on

Mounting

Pointek CLS300 typical configuration:
For high level alarm (level exceeds normal process level):
normally mounted into the vessel top, or
CLS300 Installation
Page 16 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
mounted through the tank wall at the detection level
For low level alarm (level drops below normal process level):
mounted through the tank wall at the detection level
Angled mounting
Angle
500 mm
(20") min
500 mm
(20") min
500 mm
(20") min
Side View (section)
Multiple Units
End View
Sensors must be 500 mm (20") apart.
Mount diagonally if space is restricted.
Pointek CLS300 cable version:
The cable version is designed for top mounting. The cable suspends vertically so that it reaches into the process at the desired detection level (high or low detection alarm).

Mounting Restrictions

Note:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 500 mm (20") between them, to prevent interference.
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 17
CLS300 Installation

Process Cautions

Wall Restriction
50 mm
(2") min
50 mm
(2") min
• The maximum allowable torque on a horizontally installed rod is 15 Nm.
• Keep unit out of path of falling material, or protect probe from falling material.
• Consider material surface configuration when installing unit.
• Tensile load must not exceed probe or vessel rating.
500 mm
(20") min
CLS300 Installation
Page 18 Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Note: Buildup of material in Active Shield area does not affect switch operation.

CLS300 Dimensions

Dimensions for all versions of the Pointek CLS300 Standard can be found in
Dimensions - CLS300
starting on page 55.
Appendix F:
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 19
CLS300 Installation
Loading...