Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of
others, and to protect the product and the connected equipment. These warning notices are
accompanied by a clarification of the level of caution to be observed.
Qualified Personnel: This device/system may only be set up and operated in conjunction with this
manual. Qualified personnel are only authorized to install and operate this equipment in accordance with
established safety practices and standards.
Unit Repair and Excluded Liability:
•The user is responsible for all changes and repairs made to the device by the user or the user’s
agent.
• All new components are to be provided by Siemens Milltronics Process Instruments.
• Restrict repair to faulty components only.
• Do not reuse faulty components.
Warning: Cardboard shipping package provides limited humidity and moisture protection. This product
can only function properly and safely if it is correctly transported, stored, installed, set up, operated, and
maintained.
This product is intended for use in industrial areas. Operation of this equipment in a residential area
may cause interference to several frequency based communications.
Note: Always use product in accordance with specifications.
Copyright Siemens AG 2011. All Rights
Disclaimer of Liability
Reserved
This document is available in bound version and in
electronic version. We encourage users to purchase
authorized bound manuals, or to view electronic
versions as designed and authored by Siemens
Milltronics Process Instruments. Siemens Milltronics
Process Instruments will not be responsible for the
contents of partial or whole reproductions of either
bound or electronic versions.
While we have verified the contents of this
manual for agreement with the
instrumentation described, variations remain
possible. Thus we cannot guarantee full
agreement. The contents of this manual are
regularly reviewed and corrections are
included in subsequent editions. We welcome
all suggestions for improvement.
Technical data subject to change.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments.
Contact SMPI Technical Publications European Authorized Representative
at the following address:
Technical Publications Siemens AG
Siemens AG Industry Sector
Siemens Milltronics Process Instruments 76181 Karlsruhe
1954 Technology Drive, P.O. Box 4225 Deutschland
Peterborough, Ontario, Canada, K9J 7B1
Email: techpubs.smpi@siemens.com
•For a selection of Siemens Milltronics level measurement manuals, go to:
www. siemens.com/processautomation. Under Process Instrumentation, select
Measurement
•For a selection of Siemens Milltronics weighing manuals, go to:
www. siemens.com/processautomation. Under Weighing Technology, select
Weighing Systems
and then go to the manual archive listed under the product family.
and then go to the manual archive listed under the product family.
The Manual ...............................................................................................................................................1
Technical Support ....................................................................................................................................3
Abbreviations and Identifications ...........................................................................................3
Pointek CLS200/300 Digital ...............................................................................................5
Features .....................................................................................................................................................6
System Implementation .........................................................................................................................7
Setting the PROFIBUS address .............................................................................................54
Bus Termination ........................................................................................................................54
Power Demands ........................................................................................................................54
Cyclic versus Acyclic Data .....................................................................................................54
Status .......................................................................................................................................................55
Status Byte .................................................................................................................................55
Configuration Example .............................................................................................................62
PROFIBUS PA Parameters ............................................................................................... 63
High Frequency Oscillator ...................................................................................................................73
Detection Range ....................................................................................................................................74
The Pointek CLS200 electrode ...........................................................................................................74
The Pointek CLS300 electrode ...........................................................................................................75
Sensor Test .............................................................................................................................................76
PROFIBUS PA electronics: mode of operation ..............................................................................77
Pointek CLS200 Digital Pressure versus Temperature Curves ..................................................78
CLS200 compact and extended rod versions, threaded ..................................................78
Appendix H: Shortening the cable .............................................................................. 113
Pointek CLS200 Digital, Cable Version ...............................................................................113
Pointek CLS300 Digital, Cable Version ...............................................................................116
Index .................................................................................................................................. 119
Table of C on t en ts
iv
Page 7
Safety Notes
Special attention must be paid to warnings and notes highlighted from the rest of the text
by grey boxes.
1
WARNING: relates to a caution symbol on the product, and means
that failure to observe the necessary precautions can result in
death, serious injury, and/or considerable material damage.
WARNING
1
: means that failure to observe the necessary
precautions can result in death, serious injury, and/or considerable
material damage.
Note:
means important information about the product or that part of the operating
manual.
Safety marking symbols
In manual On ProductDescription
WARNING: refer to accompanying documents (manual)
for details.
Earth (ground) Terminal
Protective Conductor Terminal
Pointek CLS200/300
The Manual
Note: Please follow the installation and operating procedures for a quick, trouble-free
installation and to ensure the maximum accuracy and reliability of your Pointek CLS200/
300. This manual applies to the Pointek CLS200/300 Digital models only.
Pointek CLS200/300 is available in two models, Standard and Digital. For information on
the CLS200/300 Standard model, please see manual 7ML19985JH02.
This manual will help you set up your Pointek CLS200/300 Digital for optimum
performance. There are two installation options:
•the unit can be used as a standalone device, controlled locally
•the unit can be installed on a network, and controlled either remotely via PROFIBUS
PA, or locally using the local user interface (LUI)
Note: This manual applies to CLS200/300 Digital devices manufactured
after August 2010. For Units manufactured prior to August 2010 please use
Operating Instructions 7ML19985JJ01.
1.
This symbol is used when there is no corresponding caution symbol on the product.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 1
Page 8
Sections in this manual are designated as follows:
1.Digital: Information is applicable to any CLS200/300 Digital unit (indicated by Digital
in the page footers)
•
Pointek CLS200/300 Digital
and to the manual
Specifications
•
•
Installation: Pointek CLS200 Digital
•
Appendix A: Technical References
•
Appendix B: Maintenance and Repairs
•
Appendix D: Product Nameplates
•
Appendix E: Hazardous Area Installation
•
Appendix F: Dimensions - CLS200 Digital
•
Appendix G: CLS300 Digital Dimensions
•
Appendix H: Shortening the cable
2.Standalone: Information is applicable to units installed as a standalone device
(indicated by Standalone in the page footers), and to units installed on a PROFIBUS
PA network:
Wiring: CLS200/300 Digital
Pointek CLS200/300
•
•
Local Operation: Pointek CLS200/300 Digital (Standalone)
3.PROFIBUS PA: Information is applicable only to units connected to PROFIBUS PA
(indicated by PA on the side tabs and PROFIBUS PA in the page footers).
Wiring: connecting CLS200/300 Digital to a PROFIBUS PA network
We always welcome suggestions and comments about manual content, design, and
accessibility. Please direct your comments to techpubs.smpi@siemens.com.
- an introduction to Pointek CLS200/300 Digital model
For other Siemens Milltronics level measurement manuals, go to:
www.siemens.com/level
and look under Level Measurement.
Application Examples
The application examples used in this manual illustrate typical installations using
Pointek CLS200/300; other configurations may also apply.
In all examples, substitute your own application details. If the examples do not apply to
your application, check the applicable parameter reference for the available options.
Page 2Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
P
Page 9
Technical Support
Support is available 24 hours a day.
To find your local Siemens Automation Office address, phone number and fax number go
to:
www.siemens.com/automation/partner
•Click on the tab Contacts by Product then drill down to find your product group
•Select the team Techni c a l S upp o r t. Click on Next.
•Click on the appropriate continent, then select the country followed by the city.
Click on Next.
For on-line technical support go to:
www.siemens.com/automation/support-request
•Enter the device name or order number, then click on Search, and select the
appropriate product type. Click on Next.
•You will be prompted to enter a keyword describing your issue. Then either
browse the relevant documentation, or click on Next to email a detailed
description of your issue to Siemens Technical Support staff.
Siemens IA/DT Technical Support Center: phone +49 (0)911 895 7222
Abbreviations and Identifications
Pointek CLS200/300
Short formLong FormDescriptionUnits
CE / FM / CSA Conformitè Europèene / Factory
Mutual / Canadian Standards
Association
ε
r
ESDElectrostatic Discharge
ExExplosion Proofsafety approval
ExdFlame Proofmethod of protection
FEPFluorinated Ethylene Polymermodified polymer
FKM/FPMFluorelastomer
FFKM/FFPMPerfluoroelastomer
ISIntrinsically Safemethod of protection
LCDLiquid Crystal Display
LUILocal User Interface
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 3
safety approval
relative dielectric
constant
for a hazardous area
for a hazardous area
Page 10
Short formLong FormDescriptionUnits
μFmicro Farads10
μsmicro Seconds10
NCnormally closedrelay contact position
NOnormally openrelay contact position
pFpico Farads10
PDMProcess Device Managerconfiguration tool
PEEKPolyaryletheretherketoneorganic polymer
PPSPolyphenylene Sulfidepolymer
PTFEPolytetrafluoroethylenethermoplastic
PVDFPolyvinylidene Fluorideengineered
-6
-6
-12
fluoropolymer
fluoropolymer
Farad
Seconds
Farad
Pointek CLS200/300
Page 4Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
P
Page 11
Pointek CLS200/300 Digital
window in lid
integral local
display
standalone unitunit on a network
window in lid
integral local
display
hub or gland/
optional
M12 plug
hub or gland
Notes:
• Pointek CLS200/300 is available in two models: the standard model, and the digital
model with integral local display. For information on the CLS200/300 Standard,
please see manual 7ML19985JH02.
• Pointek CLS200/300 is to be used only in the manner outlined in this instruction
manual, otherwise protection provided by the equipment may be impaired.
• This product is intended for use in industrial areas. Operation of this equipment in a
residential area may cause interference to several frequency based
communications.
Pointek CLS200/300 is a versatile capacitance switch, ideal for level detection of
interfaces, solids, liquids, slurries, and foam, and for simple pump control. The switch
responds to the presence of any material with a relative dielectric constant of 1.5 or more
by detecting a change in capacitance, which is registered as a change in oscillating
frequency.
The switch can be set to detect before contact or on contact with the probe. The design
of the CLS200 Digital allows the instrument to operate independently of the tank wall or
pipe, so it does not require an external reference electrode for level detection in a non-
conductive vessel such as concrete or plastic
to earth/ground for effective capacitance measurement.
The power supply is galvanically isolated and can accept voltages in the range 12 to
30 V DC (12 to 24 V DC for Intrinsically Safe (IS) models), depending on the application.
The materials used in the probe construction provide a high level of chemical resistance,
and an excellent temperature rating on the process wetted portion of the probe: up to
125 °C (257 °F) for the CLS200 and 400 °C (752 °F) for the CLS300.
1
. The CLS300 Digital requires a connection
Pointek CLS200/300
1.
Refer to
Approvals
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 5
-
CLS200
on page 13 for CE applications.
Page 12
Modular design and construction provide a wide choice of configurations, including rod,
cable, and sanitary versions. Pointek CLS200/300 Digital can be used either:
Applications
Level Detection
Pointek CLS200/300 is designed for level detection and simple pump control in a variety of
applications:
•Liquids, solids (powder and granules), slurries, interface detection (for example, oil/
•Foods and pharmaceuticals
•Chemical and petrochemical
•High pressure and temperature
Pointek CLS200/300
Alarm signalling
The solid-state switch can be set to react either to a diagnosed fault in the instrument, or
to a change in the process level.
Fault Signalling
Pointek CLS200/300 can actively report information on its own status via PROFIBUS PA
when used as part of a network, or by means of a pre-defined output status at the solid
state switch and on the Local User Interface (LUI).
•as a standalone unit, programmed locally using the local user interface, or
•installed as part of a network, programmed remotely using SIMATIC PDM on a
Profibus PA network (or locally using the Local User Interface).
water), and foam detection
Features
•Potted construction protects components from shock, vibration, humidity, and/or
condensation
•High chemical resistance on probes
•Level detection independent of tank wall/pipe (CLS200 only)
•Freely programmable set up covers wide range of applications/materials
•Integrated Local User Interface (LUI) for ease of use
•Rigid and cable versions available
•Communication via PROFIBUS PA (profile version 3.0, Class B)
•Intrinsically Safe (IS) transmitter design for hazardous areas (requires external
barrier or IS power supply)
•Patented Active Shield minimizes the effect of product build-up at the sensor
mounting point (CLS300 only)
1.
Refer to
Approvals
Page 6Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
P
-
CLS200
on page 13 for CE applications.
1
Page 13
System Implementation
Basic PLC configuration with PROFIBUS PA
PROFIBUS PA
PROFIBUS DP
DP/PA
coupler
active PLC
PC/laptop
PDM
Point ek CLS30 0
(PROFIBUS PA)
Pointek CLS200
(PROFIBUS PA)
Pointek CLS200
(PROFIBUS PA)
Pointek CLS200/300 supports PROFIBUScommunication protocol, and SIMATIC PDM
software.
Pointek CLS200/300
Programming
Pointek CLS200/300 carries out its level measurement function according to the set of
built-in parameters. You can make parameter changes locally via the local user interface,
or from a remote location via a PC using SIMATIC PDM software.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 7
Page 14
Specifications
Note: Siemens Milltronics makes every attempt to ensure the accuracy of these
specifications, but reserves the right to change them at any time.
Pointek CLS200/300
Power
•bus voltage
- general purpose12 to 30 V DC, 12.5 mA
- Intrinsically Safe12 to 24 V DC, 12.5 mA
•starting current <
• fault current (max. uninterrupted current
minus current of normal operation)0 mA
• fault disconnect equipment (FDE) yes
• auxiliary sourcebus powered
• separate supply necessaryno
Performance
Repeatabilityapprox. ± 2 mm for a conductive
current of normal operationyes
fluid
Interface
Specifications
Configuration
• locally, using local user interface (LUI), for standalone operation, or
• remotely, using SIMATIC PDM on a Profibus PA network
Local Digital Display
•LCD
Output (bus)PROFIBUS PA (IEC 61158 CPF3 CP3/2)
Bus physical layer: IEC 61158-2 MBP(-IS)
• polarity-independentyes
• simultaneous communication
with Master Class 24 (max.)
Cyclic User data (normal operation)
• byte output2 bytes representing one value
• byte input0
• device profilePROFIBUS PA Profile for Process Control
Devices Version 3.0, Class B
• function blocks1
• discrete input1
Page 8Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 15
• logical inversionparameterizable
Simulation functions
•outputyes
• inputyes
• failsafeparameterizable (last usable value,
substitute value, erroneous value)
Block Structure
•physical block1
• transducer block1
• transducer block discrete inputyes
• monitoring measuring limitsyes
Alarm Outputs
• solid-state switchgalvanically isolated
non-polarity sensitive transistor
rated 30V DC or peak AC max., 82mA max
voltage drop below 1 V typical @ 50 mA
• time delaycontrolled by software
2 delay timers: alarm ON delay and alarm OFF delay)
• hysteresis100% adjustable, in 1 count increments
• failsafe operationFailsafe High or Failsafe Low
• terminalremovable terminal block, 2.5 mm
2
max.
1
on the display
Specifications
Diagnostics
• inputreed contact: for test function
1.
The frequency value is always represented in ‘counts’: see
more detail.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 9
Counts
on page 73 for
Page 16
Mechanical
Specifications
Electrode - CLS200 Digital
Model
Rod5500 mm/
Sanitary 5500 mm/
Cable30000 mm/
Length
(max)
216.5”
216.5”
1181.1”
Connections
• Threaded:
¾”, 1", or 1 ½"
BSPT (R), BSPP
(G) or NPT; 1 ¼”
NPT only
• Welded flange:
ASME: 1”, 1 ½”, 2”,
3” or 4”
DN 25, 40, 50, 80
or 100
1", 1 ½ ", 2”, 2 ½"
and 3”sanitary
clamp
• Threaded:
¾ ", 1", or 1 ½"
BSPT (R), BSPP
(G) or NPT; 1 ¼”
NPT only
• Welded flange:
ASME: 1”, 1 ½”, 2”,
3” or 4”
DN 25, 40, 50, 80
or 100
1
Process
Extension
316L¹
stainless
steel
316L¹
stainless
steel
FEP
(Fluorinated
Ethylene
Polymer)
Tensile
(max)
n/a
n/a
180 kg/
400 lbs
Wetted Parts
1
•316L
stainless
steel (optional
PFA coating)
• FKM seals
(optional FFKM)
• PPS probe
(optional PVDF)
1
stainless
•316L
steel
• FKM seals
(optional FFKM)
• PPS probe
(optional PVDF)
1
stainless
•316L
steel
• FEP jacketed
cable
• FKM seals
(optional FFKM)
• PPS probe
(optional PVDF)
1.
Or 1.4404 material.
Page 10Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 17
Electrode - CLS300 Digital
1
Model
Rod
Length
(max)
1000 mm/40”
(19 mm/
0.75” dia.)
Cable25000 mm/
985”
High
1000 mm/40”
Te mp e ra t u re
version
Process
Connections
• Threaded:
¾”, 1", or 1 ½" BSPT
(R), BSPP (G) or NPT;
1 ¼” NPT only
• Welded flange:
ASME: 1”, 1 ½”, 2”, 3” or
4”
DN 25, 40, 50, 80 or
100
• Threaded:
1 ½" BSPT (R), BSPP
(G) or NPT; 1 ¼” NPT
only
• Welded flange:
ASME: 1 ½”, 2”, 3” or
4”
DN 40, 50, 80 or 100
• Threaded:
¾”, 1", or 1 ½" BSPT
(R), BSPP (G) or NPT;
1 ¼” NPT only
• Welded flange:
ASME: 1”, 1 ½”, 2”, 3” or
4”
DN 25, 40, 50, 80 or
100
Tensile
(max)
n/a
1900 kg/
4188 lbs
n/a
Wetted Parts
1
• 316L
stainless steel
• FKM seals (optional
FFKM)
• PFA lining on Active
Shield
• PEEK isolators
1
stainless steel
• 316L
Active Shield and
cable weight
1
stainless steel
• 316L
cable (optional PFA
jacketed cable)
• FKM seals (optional
FFKM)
• PEEK isolators
1
stainless steel
• 316L
• Ceramic isolators
Specifications
Active Shield Length (CLS300 only):
Active
Length
Shield
Standard
length
Extended
shield
Extended
shield
1.
Or 1.4404 material.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 11
Note: The use of approved watertight conduit hubs/glands is required for Type 4 /
NEMA 4, Type 6 / NEMA 6, IP68 (outdoor applications). For CE requirements the use
of EMC rated cable entries is required for all CLS200 devices.
Weight varies based on configuration. For example:
• compact Pointek CLS200, 1 kg (2.20 lb.) approx.
100 mm (4”) insertion length,
¾” process connection
• locationindoor/outdoor
• altitude500 0 m (16,405 ft.) max.
• ambient temperature–40 to 85 °C (–40 to 185 °F), (in potentially explosive
atmospheres, note the temperature classes)
• LUI (local user interface)–30 to 85 °C (–22 to 185 °F)
• storage temperature–40 to 85 °C (–40 to 185 °F)
• relative humiditysuitable for outdoor (Type 4 / NEMA 4 / IP65 standard,
IP68 optional)
• installation categoryI
• pollution degree4
Process
Note: Please see
page 78 and
• relative dielectric1.5 minimum
constant (ε
• CLS200 temperature:
- without thermal isolator –40 to 85 °C (–40 to 185 °F)
- with thermal isolator–40 to 125 °C (–40 to 257 °F)
1.
Or 1.4404 material.
2.
at process connection
Page 12Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Pointek CLS200 Digital Pressure versus Temperature Curves
Pointek CLS300 Digital Pressure versus Temperature Curves
)
r
2
on
on page 80.
Page 19
• CLS200 pressure (vessel):
- rod version–1 to 25 bar g/–14.6 to 365 psi g (nominal)
- cable version–1 to 10 bar g/–14.6 to 150 psi g (nominal)
- sliding coupling version–1 to 10 bar g/–14.6 to 150 psi g (nominal)
• CLS300 temperature:
1
- rod/cable version–40 to 200°C (–40 to 392 °F)
- high temperature version –40 to 400 °C (–40 to 752 °F)
• CLS300 pressure (vessel): –1 to 35 bar g/–14.6 to 511 psi g (nominal)
Approvals
CLS200
• General Purpose CSA, FM, CE, C-TICK
• Flameproof Enclosure ATEX II 1/2 G EEx d[ia] IIC T6...T4
with IS ProbeATEX II 1/2 D T100°C
• Dust Ignition Proof ATEX II 1/2 D T100°C
with IS ProbeCSA/FM Class II, Div. 1, Gr. E, F, G
CSA/FM Class III T4
• Explosion Proof Enclosure CSA/FM Class I, Div. 1, Gr. A, B, C, D
with IS ProbeCSA/FM Class II, Div. 1 Gr. E, F, G
• Intrinsically Safe
2
• Non-incendiveCSA/FM Class I, Div. 2, Gr. A, B, C, D
• Non-SparkingATEX II 3 G Ex nA II T6...T4
• Marine Lloyds Register of Shipping, Categories ENV1,
• Others Pattern Approval (China)
CSA/FM Class III T4
ATEX II 1 G EEx ia IIC T6...T4
ATEX II 1/2 D IP6X T100°C
CSA/FM Class I, Div. 1, Gr. A, B, C, D
CSA/FM Class II, Div. 1, Gr. E, F, G
CSA/FM Class III T4
CSA/FM Class II, Div. 2, Gr. F, G
CSA/FM Class III T4 or T6
ATEX II 2 D IP6X T100°C
ENV2 and ENV5
Specifications
Note: EN 61326 (CE EMC) testing was conducted on the Pointek CLS200 while
mounted in a metallic vessel and wired using shielded cable, where the cable was
terminated in an EMC cable gland at the device entry point. In addition, units with a
flange process connection were mounted using a metallic gasket.
1.
at process connection
2.
barrier or Intrinsically Safe power supply required for Intrinsically Safe protection
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 13
Page 20
CLS300
• General Purpose CSA, FM, CE, C-TICK
• Dust Ignition ProofATEX II 1/2 D, 2 D IP6X T100°C
• Dust Ignition Proof CSA/FM Class II, Div. 1, Gr. E, F, G
with IS ProbeCSA/FM Class III T4
• Flameproof EnclosureATEX II 1/2 G EEx d[ia] IIC T6...T4
with IS ProbeATEX II 1/2 D T100°C
• Explosion Proof CSA/FM Class I, Div. 1, Gr. A, B, C, D
with IS ProbeCSA/FM Class II, Div. 1, Gr. E, F, G
CSA/FM Class III T4
• Intrinsically Safe
1
ATEX II 1 G EEx ia IIC T6...T4
ATEX II 1/2 D, 2 D IP6X T100°C
CSA/FM Class I, Div. 1, Gr. A, B, C, D
CSA/FM Class II, Div. 1, Gr. E, F, G
CSA/FM Class III T4
• Marine Lloyds Register of Shipping, Categories ENV1,
ENV2 and ENV5
• OthersPattern Approval (China)
Note: EN61326 (CE EMC) testing was conducted on the Pointek CLS300 while
mounted in a metallic vessel and wired using shielded cable. Units with flange
process connections were tested while mounted in a metallic vessel with a metallic
gasket and with shielded cables.
Specifications
1.
barrier or Intrinsically Safe power supply required for Intrinsically Safe protection
Page 14Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 21
Installation: Pointek CLS200 Digital
High level alarmLow level alarm
normal process
level
normal process
level
vertical
horizontal
Notes:
• Installation shall only be performed by qualified personnel and in accordance with
local governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
• The housing may only be opened for maintenance, local operation, or electrical
installation.
• Before installing the instrument, verify that the environment complies with any
restrictions specified on the product nameplate.
• To comply with CE EMC regulations, where applicable, the CLS200 should be installed
in accordance with the testing details on page 13.
Location
Recommended:
•Provide a sun shield to protect the transmitter from direct heat radiation.
Precautions:
•Avoid mounting Pointek CLS200 in locations subject to strong vibrations in the
vicinity, whenever possible.
•Do not exceed the permissible ambient temperature limits (see
page 12 for details).
Environmental
on
Mounting
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 15
Pointek CLS200 (compact probe)
For high level alarm (level exceeds normal process level):
•normally mounted into the vessel top, or
•mounted through the tank wall at the detection level
For low level alarm (level drops below normal process level):
•mounted through the tank wall at the detection level
CLS200 Installation
Page 22
Pointek CLS200 typical configuration with extensions:
Angle
High level alarmLow level alarm
normal process
level
normal process
level
50 mm (2") min
50 mm
(2")
min
In nozzle
Close to tank walls
> 100mm
(4") Ø
50 mm (2")
minimum
For high or low level alarm:
•designed for top mounting. The probe suspends vertically so that it reaches into
the process at the desired detection level (high or low detection alarm).
Mounting Restrictions
Note:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 100 mm (4") between them, to prevent
interference.
CLS200 Installation
Page 16Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 23
CLS200 Dimensions
Sensors must be at least 100 mm (4") apart.
Side View
100 mm
(4") min
100 mm
(4") min
100 mm
(4") min
End View
Mount diagonally if space is restricted
Multiple Units
Dimensions for all versions of the Pointek CLS200 Digital can be found in
Dimensions - CLS200 Digital
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 17
Appendix F:
starting on page 95.
CLS200 Installation
Page 24
Process Cautions
Cautions:
• The maximum allowable torque on a horizontally installed rod is 15 Nm.
• Keep unit out of path of falling material, or protect probe from falling material.
Caution: Tensile load must not exceed
probe or vessel rating (See
Tensile
(max)
on page 10.).
Caution: Avoid areas where material build up
occurs.
50 mm
(2") min
Caution: Consider material surface
configuration when installing unit.
CLS200 Installation
Page 18Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 25
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 19
CLS200 Installation
Page 26
Installation: Pointek CLS300 Digital
High level alarmLow level alarm
normal process
level
normal process
level
detection level
vertical
horizontal
Notes:
• Installation shall only be performed by qualified personnel and in accordance with
local governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
• The housing may only be opened for maintenance, local operation, or electrical
installation.
• Before installing the instrument, verify that the environment complies with any
restrictions specified on the product nameplate.
• To comply with CE EMC regulations, where applicable, the CLS300 should be installed
in accordance with the testing details on page 14.
Location
Recommended:
•Provide a sun shield to protect the transmitter from direct heat radiation.
Precautions:
•Avoid mounting Pointek CLS300 Digital in locations subject to strong vibrations in
the vicinity, whenever possible.
•Do not exceed the permissible ambient temperature limits (see
page 12 for details).
Environmental
on
Mounting
Pointek CLS300 typical configuration:
CLS300 Installation
For high level alarm (level exceeds normal process level):
Page 20Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
•normally mounted into the vessel top, or
•mounted through the tank wall at the detection level
For low level alarm (level drops below normal process level):
•mounted through the tank wall at the detection level
Page 27
Angled mounting
Angle
Sensors must be 500 mm (20") apart.
500 mm
(20") min
500 mm
(20") min
500 mm
(20") min
Side View
(section)
Mount diagonally if space is restricted.
Multiple Units
End View
Pointek CLS300 cable version:
The cable version is designed for top mounting. The cable suspends vertically so that it
reaches into the process at the desired detection level (high or low detection alarm).
Mounting Restrictions
Note:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 500 mm (20") between them, to prevent
interference.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 21
CLS300 Installation
Page 28
Process Cautions
Wall Restriction
50 mm (2")
min
50 mm (2") min
• The maximum
allowable torque on a
horizontally installed
rod is 15 Nm.
• Keep unit out of path
of falling material, or
protect probe from
falling material.
• Consider material
surface configuration
when installing unit.
• Tensile load must not
exceed probe or
vessel rating.
500 mm
(20") min
CLS300 Installation
Page 22Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 29
Note: Buildup of material in Active Shield area does not affect switch operation.
CLS300 Dimensions
Dimensions for all versions of the Pointek CLS300 Digital can be found in
CLS300 Digital Dimensions
starting on page 103.
Appendix G:
CLS300 Installation
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 23
Page 30
Wiring: CLS200/300 Digital
Electrical Connection
WARNING:
• Observe the specifications of the examination certificate valid in your
country.
• Observe the laws and regulations valid in your country for electrical
installations in potentially explosive atmospheres.
• Refer to
applicable.
• Ensure that the available power supply complies with the power supply
specified on the product nameplate and specified in the examination
certificate valid in your country.
• Shipping plugs in the cable inlets must be replaced by suitable screwtype glands or dummy plugs, which are appropriately certified for
transmitters with explosion-proof protection.
• For CE installations, use a cable with a braided metallic shield (or
armoured cable where applicable).
• The lid must not be opened in wet locations while the unit is powered.
(A wet location is a location where water or another conductive fluid
may be present and is likely to increase the risk of electric shock.)
Appendix E: Hazardous Area Installation
on page 91 if
Wiring: standalone
Page 24Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
General Purpose Cable Entry: M20 (A5E03252531) and ½" NPT
(A5E03252530)
1.Strip cable and expose braided shield.
2.Feed cable through dome nut and clamping insert. Fold braided shield over clamping
insert. Make sure that braided shield overlaps the O-ring by 3/32" (2 mm) and covers
the entry 360 degrees.
3.Push clamping insert into body and tighten dome nut. Assemble into housing.
Hazardous Location Cable Entry: M20 (A5E03252528) and ½" NPT
(A5E03252527)
1.Strip the cable to suit equipment and expose armour/braid.
2.Push the cable through the diaphragm shield/armour spigot (4). Pre-fitted cable
guide (4.1) can now be discarded. The diaphragm seal can be rolled back to ease
assembly as required. Spread armour/braid over the diaphragm seal/armour spigot
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 25
Wiring: standalone
Page 32
(4) until the end of the armour/braid is up against the shoulder of the armour cone.
Position the armour clamping ring (3).
3.Place the entry (5) and position over the diaphragm seal/armour spigot (4). Move the
sub-assembly (1) and (2) up to meet the entry (5).
4.Hold the entry (5) in position with a wrench to prevent rotation. Hand tighten the
middle nut (2) to the entry (5), and turn a further 1/2 to 3/4 turn with a wrench.
Note: Support the cable to prevent it from twisting. To ease the wiring inside the
enclosure, it may be beneficial to strip the inner sheath of the cable.
5.Unscrew the middle nut (2) and visually inspect that the armour/braid has been
successfully clamped between the diaphragm seal/armour spigot and the armour
clamping ring (3). If armour/braid is not clamped, repeat assembly. (Armour/braiding
should be fitted 360 degrees around the entry.)
6.Reassemble the middle nut (2) onto the entry component (5). Tighten up the middle
nut (2) until hand tight, then using a wrench, turn the nut through 1/4 turn. Tighten
the backnut (1) to form a seal around the cable, then tighten a further full turn using
a wrench. Ensure that the middle nut (2) does not rotate when tightening the
backnut (1).
Note: The deluge seal on this gland locates on assembly and requires no further
action. Locate shroud over cable gland, if applicable.
Wiring: standalone
Page 26Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 33
Connection to screw terminals
lid clip
digital display
removable
terminal block
for Profibus PA/
power
connection
removable
terminal block
for alarm output /
solid-state switch
gland
power
cable
reed contact
r
e
d
(
+
)
b
l
a
c
k
(
–
)
o
r
a
n
g
e
(
f
)
w
h
i
t
e
w
h
i
t
e
PROFIBUS PA
alarm output
solid-state switch
test
input
sensor
Connect the power cable to
these terminals. (Polarity is
not important.)
power cable
1.Loosen the lid clip and unscrew the lid of the enclosure.
2.Unscrew and lift up the digital display. (Loosen each screw two turns before
completely loosening both, to keep the rubber retaining rings in place.)
3.Strip the cable jacket for approximately 70 mm (2.75") from the end of the power
cable, and thread the wires through the gland.
4.Connect the wires to the Profibus PA/power connection terminals shown below;
polarity is not important. The terminal can be removed and replaced to simplify
connection.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 27
Wiring: standalone
Page 34
5.If you want to use the Alarm Output, connect the wires of an optional input to the
Alarm Output terminals (polarity is not important). The terminal can be removed and
replaced to simplify connection.
6.Ground the instrument according to local regulations.
7.Tighten the gland to form a good seal.
8.Replace the Local User Interface (LUI).
9.To adjust the transmitter locally, using the keypad, go to
User Interface (LUI)
tighten the lid clip.
on page 32. After adjustment, replace the enclosure lid and
Programming via the Local
Wiring: standalone
Page 28Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 35
Local Operation: Pointek CLS200/300
The local digital display shows one of
the following:
• the measured value and associated
units
• the logical level (sensor covered/
uncovered)
• the numerical value and mode
number
• an error message and status
information.
• software revision number
1
Digital (Standalone)
•Local operation gives you access to all the functions listed in the table on page 33,
Quick Reference: operating functions using input keypad
•An extended range of functions is available only via remote operation using
PROFIBUS PA: see
PROFIBUS PA Parameters
on page 63.
Local User Interface (LUI)
You can program the transmitter using the input keypad, and view measuring results,
error messages and modes of operation on the digital display.
Input keypad
.
Operation: standalone
Three keys M, ⇑ and ⇓, are located below the display (see
User Interface (LUI)
must be closed again after programming.
on page 32). The keys are accessible when you open the lid. The lid
Programming via the Local
LCD display (local operation)
1 – Primary Reading (displays measured value, or logical level, or an error message)
2 – Auxiliary Reading (displays Units, or the Bar Graph, or Status [error code])
3 – Indicator for Write Protection / Mode number/ Simulation
4 – Down arrow indicates alarm output switch open
5 – Negative sign
6 – Up arrow indicates alarm output switch closed
7 – Communication Indicator - visible only when communications are in progress
1.
The current software revision is displayed for 1 to 2 seconds at startup on two
successive screens which are immediately followed by RUN mode display.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 29
1
Page 36
RUN mode display
sensor uncoveredsensor covered
bar graph
sensor uncoveredsensor covered
status code
error message
A status code is displayed in the auxiliary
display which indicates the type of error (see
Status
on page 55). This information is also
available via the PROFIBUS interface.
The corresponding unit is displayed in the
auxiliary reading field when Electronics
Temperature is selected in Mode 13.
Measured value display
The default startup display is the measured value display. It shows the value (in counts1)
when Sensor (Sens) has been selected in Mode 13.
Operation: standalone
Logical level display (output status)
The logical level display shows the value when the OUT parameter of the Discrete Input
Function Block is selected in Mode 13.
Error message display
If hardware or software errors occur in the transmitter, the error message appears in the
primary reading field.
Units
1.
See
Counts
Page 30Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
on page 73 for more details.
Page 37
Bar graph
Bar Graph
(representing the extent
the sensor is covered)
Falling Edge
(Switch Point 2)
Rising Edge
(Switch Point 1)
100% Application
Range setting
0% Application
Range setting
•When a lock is enabled, either Li, Lc, LA,
LL, is displayed (see
Lock
, page 71).
•When simulation (via PROFIBUS PA) is
active, Si is displayed (see
Simulation
, on
page 67).
The Bar Graph represents the extent to which the sensor is covered during normal
operation. It is displayed when one of the three following mode options is selected:
Operation: standalone
•OUT (output of the Discrete Input Function Block1)
2
•PRIM (the Primary Value of the Transducer Block
•SENS (the discrete Sensor Value of the Transducer Block
)
2
)
The 0% and 100% Application Range settings terminate the Bar Graph at each end and
are represented on the lower part of the graph. The two Switch Points (Falling Edge and
Rising Edge) are indicated as black vertical lines on the upper part of the graph; Rising
Edge is the is the point where the output state is switched on and Falling Edge is the point
where it is switched off.
Example:
Assume that a vessel is being filled and the sensor is slowly being covered. Because the
level is rising, switch point 2 (falling edge) will be passed without any change in the
output occurring. If the level continues to rise, eventually switch point 1 (rising edge) will
be reached, resulting in a state changeover.
This new state will remain unchanged until the vessel is being emptied and the probe
uncovered. If the level falls so that switch point 2 (falling edge) is passed again, the output
state will change once more.
Lock/Simulation Indicator
(In PROGRAM mode, this field displays the Mode number.)
1.
See
2.
.See
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 31
Discrete Input Function Block
Transducer Block (TB)
on page 85.
on page 85.
Page 38
PROGRAM mode display (local operation).
1 – numerical value
2 – physical unit
3 – Mode indicator
4 – Rising (or Falling) indicator
1
2
4
3
M – Mode key
⇑ – increment key
⇓ – cursor movement/accept value
The keypad consists of three input keys below the display: M, ⇑,
and ⇓. A flashing digit indicates the position of the cursor.
Operation: standalone
Programming via the Local User Interface (LUI)
Mode selection and adjustment
Note: Master Reset function and Condensed Status Setup are available only via
SIMATIC PDM
software package.
Editing non-numerical values
•To select a mode, press M (mode key).
•To select an option in a mode, press ⇑ or ⇓ to scroll forwards or backwards through
the options. Press M to select option.
•To switch to the next mode, press M again. To cycle forwards though the menu,
press M repeatedly. To move backwards through the menu, hold M and tap ⇑.
Editing numerical values:
Numerical values are always edited from the most significant digit first, and the cursor
position is indicated by a flashing digit.
•To enable Edit function and to activate the cursor press ⇑ or ⇓.
•To increment the value of the flashing digit, press ⇑.
•To move the cursor to the right press ⇓.
•After editing the least significant digit, press ⇓ once again to store the edited value.
•To switch to the next mode, press M.
Page 32Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 39
Quick Reference: operating functions using input keypad
Source of measured value: 0 = OUT (output);
1 = PRIM (primary value); 2= SENS (sensor);
3 = TMP E (electronics temperature)
Unit
Node address
(PROFIBUS only)
PROFIBUS Ident
Number
Application Range,
Lower Limit / 0%
14*Scroll up or down to select an option.
15
16Scroll up or down to select an option.
19
Enable Edit function, or
increment digit.
Enable Edit function, or
increment digit.
Move cursor to the right, or store
edited value.
Move cursor to the right, or store
edited value.
Select K, °C, °F, °R (if electronics temperature
selected in Mode 13).
Assign slave address on the PROFIBUS
network (0 to 126). Recommended setting
range 1 to 125.
Select device mode: 1 =according to profile;
or, 2 = according to profile with full device
specific support.
Adjust lower limit of application range.
Page 40
Function ModeKey functionDisplay, or explanation
Application Range,
Upper Limit / 100%
#
Ma
20
Enable Edit function, or
increment digit.
⇑ ⇓⇑ and ⇓
Move cursor to the right, or store
edited value.
Adjust upper limit of application range.
Alarm output
trigger
23*
Scroll up or down to select an option.
Select the source event to switch the alarm
output. See
(default: dIAG)
Mode 23: Alarm output trigger
, page 43.
Set contact functionality in case of event:
Contact type24*
Scroll up or down to select an option.
(logical inversion of alarm output switch)
- Make contact (CLOSE)/ Break contact (OPEn)
Switch Point 1
(Rising Edge)
25
OFF to ON
Switch Point 2
(Falling Edge)
26
ON to OFF
Local Status Text27*
a.
In Modes indicated by an asterisk (*), press M to store a selection. In other Modes, press to store numerical values.
b.
If L appears in the Mode indicator field of the display, the HW Write Protection is activated.
c.
If LA, LL, Lc or Li appears in the Mode indicator field of the display after releasing the HW Write Protection, there is an additional block on local operation via
Lock
the bus.
, on page 71 explains how to release this using SIMATIC PDM. In measuring mode, if neither L, LA, LL, Lc or Li, appears in the Mode indicator dis-
Enable Edit function, or
increment digit.
Enable Edit function, or
increment digit.
Scroll up or down to select an option.
Move cursor to the right, or store
edited value.
Move cursor to the right, or store
edited value.
Set % of range at which switch will change
from OFF to ON.
Set % of range at which switch will change
from ON to OFF.
Select presentation of status text. See
27: Local Status Text (default: U_075)
play field, local operation is possible.
Mode
, page 46.
Page 41
Status codes
Every measured value which can be displayed is given a status to identify its quality. If it
is classified as Bad or Uncertain the text Error alternates with the measured value in the
display and the status code alternates with the unit or Bar Graph.
If the status is Bad or Uncertain, either a status code or a status message is displayed in
the auxiliary display. If the selection for Local Status text is numeric a numeric code will
be displayed. If a language is selected, a text message will be displayed. (For details see
Mode 27: Local Status Text (default: U_075)
The status display has priority, and neither the physical unit nor the Bar Graph is visible if
the status is Bad or Uncertain.
Examples:
LUI Status CodeQualityError
Bar graph displayedGood
G_164GoodMaintenance required
U_075UncertainSubstitute value - Constant output
B_016BadSensor failure
on page 46).
Operation: standalone
The status codes can be found in
Status
on page 55.
Error messages
In the case of exceptional events, error messages can appear during local operation and
are displayed for around 10 seconds after the occurrence of the error.
as the device is exchanging data
with master class 1
F_003Change of PROFIBUS Ident Number
not possible as the device is
exchanging data with master class 1
F_004Value too large to fit in LCD display
(>99999 or <-99999)
F_008Local adjustment of parameters
blocked by SIMATIC PDM
End communication with master
class 1
End communication with master
class 1
Change display value units
Enable “Local operation” with
SIMATIC PDM
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 35
Page 42
Mode 2: Sensor test (default: OFF)
Note: Sensor Test should only be initiated when the process value is stable. A
dramatic change of level in the vessel could cause a sensor failure message.
The Sensor Test checks the circuitry including the sensor, the signal path from the sensor
to the transmitter, and the transmitter itself. While the sensor test is active, the sensor
value increases by a specific offset. This is verified by the electronics.
Operation: standalone
There are three methods of activating a sensor test:
•locally, using the keypad
•locally, using a magnet
•remotely, via PROFIBUS PA
Keypad activated sensor test
•Select Mode 2.
•Press ⇑ or ⇓ to start the test.
•After a few seconds, the display shows GOOd or FAILd.
•Press M to exit.
Magnet-activated sensor test
To carry out a test without opening the lid or entering Mode 2, use a magnet.
•Bring the magnet close to the test area indicated on the
housing.
•The sensor test starts, and finishes automatically after 10
seconds.
•The auxiliary reading displays either SENSOR TEST
SUCCESSFUL, or SENSOR TEST FAILED, as rolling text.
1
Sensor test using PROFIBUS PA
•Please see
Sensor Test
on page 72 for details.
Note: Output state does not change when sensor test is initiated.
1.
Test magnet is supplied with the instrument.
Page 36Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 43
Mode 4: Rise Time (default: 0.0 s)
Rise Time is a delay setting which adjusts the response time of the signal1 to the sensor
becoming covered (Rising Edge). It affects the Primary Value of the Transducer Block.
Possible values range from 0.0 to 100.0 s, in 0.1 s intervals.
This symbol to the left of the numerical value on the display indicates a Rise Time
setting.
To set Rise Time:
•Select Mode 4.
•Press ⇑ or ⇓ to open Edit Mode.
•Press ⇑ to adjust the value digit by digit.
•Press ⇓ to save the value.
•Press M to exit.
Mode 5: Fall Time (default: 0.0 s)
Fall Time is a delay setting which adjusts the response time of the signal1 to the sensor
becoming uncovered (Falling Edge). It affects the Primary Value of the Transducer Block.
Possible values range from 0.0 to 100.0 s, in 0.1 s intervals.
This symbol to the left of the numerical value on the display indicates a Fall Time
setting.
To set Fall Time:
Operation: standalone
•Select Mode 5.
•Press ⇑ or ⇓ to open Edit Mode.
•Press ⇑ to adjust the value digit by digit.
•Press ⇓ to save the value.
•Press M to exit.
1.
The bar graph, and numerical value in counts, continue to respond instantaneously to
changes in level.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 37
Note: When HW Write Protection is enabled, L appears in the Mode display field, in
normal measuring mode.
Protects parameters from unintentional modification. This prevents parameter changes
both locally via the keypad and remotely via SIMATIC PDM. The parameters are still
readable.
Operation: standalone
To enable HW Write Protection:
•Select Mode 10.
•Press ⇑ or ⇓ to activate keylock and to disable operation: L appears in the
numerical value field.
•Press M to exit.
To disable HW Write Protection
•Select Mode 10.
•Hold ⇑ and ⇓ simultaneously for more than 5 seconds: L disappears from the
numerical value field.
•Press M to exit.
Mode 13: Display Source (default: 0)
Determines which value will be displayed.
To select the display source from the options shown in the table below:
•Select Mode 13.
•Press ⇑ or ⇓ to select the value for the desired source.
•Press M to save the selection and exit
You can assign the physical unit in Mode 14, if Electronics Temperature is selected as the
display source.
Display SourceValue
From Discrete Input
Function Block: OUT
From Transducer Block:
Primary Value
From Transducer Block:
Sensor Value
From Transducer Block:
electronics temperature:
Electronics temperature
Page 38Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Auxiliary
Reading
0OUTnoneBar graph and
1PRIMnoneBar graph and
2SENSnoneBar graph and
3TMP EK, °C, °F, or °RTemperature in
Units
Displayed
Value
ON or OFF
ON or OFF
counts value
units
Page 45
Mode 14: Unit (default: °C)
Note: Mode 14 becomes available only after Electronics Temperature is selected in
Mode 13.
If Electronics Temperature is selected as the display source in Mode 13, you can change
the corresponding physical unit by selecting one of the following options:
Physical UnitDisplay
KK
°C°C
°F°F
°R°R
To set the physical unit:
•Select Mode 14: the primary reading field displays Unit, and the physical unit
appears in the auxiliary reading field.
•Press ⇑ or ⇓ to select the desired physical unit.
•Press M to save the selection and exit
Mode 15: Node address1 (default: 126)
Sets the node address of the device on PROFIBUS. The permitted range is from 0 to 126.
We recommend setting the range between 1 and 125.
To set the PROFIBUS node address:
Operation: standalone
•Select Mode 15. The current node address is shown in the primary reading field.
•Press ⇑ or ⇓ to open Edit mode.
•Enter the node address in the permitted range: press ⇑ to change the value of
each digit, and press ⇓ to move the cursor to the next digit.
•Press ⇓ after editing the least significant digit, to terminate the procedure and to
save the value.
•Press M to exit.
Note:
• While the device is in cyclic data exchange with a class 1 Master, it is not possible
to change the address. Abort the cyclic communication to change the address.
• Ensure that you set a unique node address to the device. Otherwise, the devices
with the same addresses will cause confusion on the bus.
1.
Applies to PROFIBUS PA applications only. If in standalone application (no network), leave
the node address at the default value.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 39
Page 46
Mode 16: PROFIBUS Ident Number1 (default: 1)
Determines which of two device operating modes to select. Pointek CLS200/300 Digital
recognizes two operating modes in relation to the DP Master:
ModeDescription
Operation: standalone
0Conforms to profile
version 3.0 Class B
device with no
Generic: can substitute transmitters conforming to
PROFIBUS PA profile 3.0, one Discrete Input
Function Block.
extensions.
1Conforms to profile
version 3.0 Class B
device with
Device-Specific: full functional range of
Pointek CLS200/300 with Discrete Input Function
Block.
extensions.
To set the device operating mode:
•Select Mode 16. The current device operating Mode (0 or 1) appears in the
primary reading field.
•Press ⇑ or ⇓ to select the desired operating mode.
•Press M to save the selection and exit.
Mode 19: 0% Application Range setting
This point corresponds to the left limit of the bar graph in the digital display.
CLS200 0% Application Range setting
To adjust the 0% Application Range setting for CLS200:
1.Install the device in the process.
2.Use the M button to navigate to Mode 19.
3.Set up the process to provide the recommended condition for your process from the
table below:
ApplicationMaterialSetup conditions
General
Demanding
Interface
detection
1.
Applies to PROFIBUS PA applications only. If in standalone application (no network), leave
the node address at the default value.
Page 40Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
•dry solids
• low viscosity liquids
• hygroscopic / wet solids
• high viscosity and high
conductivity liquids
• liquid A / liquid B
• foam / liquid
sensor uncovered;
min. 100 mm (4") free space all around
sensor immersed then uncovered; but
retaining max. possible material buildup
sensor immersed in the material with
the lowest dielectric constant
Page 47
4.Press ⇑ or ⇓. The display switches to the current measured sensor value in counts.
Record the count value.
5.Press ⇑ or ⇓ to enter Edit Mode; the sensor value is frozen and ready for editing.
6.Set the sensor value to approximately 300 counts below the value obtained in step 4.
Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor to the next
digit.
7.After editing the least significant digit (or leaving it unchanged), press ⇓ to terminate
the procedure and save the new value. The display now shows the new value for
the 0% Application Range setting.
8.Press M to exit.
CLS300 0% Application Range setting
To adjust the 0% Application Range setting for CLS300:
1.Install the device in the process.
2.Use the M button to navigate to Mode 19.
3.Set up the process to provide the recommended condition for your process from the
table below:
ApplicationMaterialSetup conditions
Material in tank should be at the lowest
point it could reach during the normal
process.
General
•dry solids
• low viscosity liquids
Operation: standalone
Material in tank should be at the lowest
point it could reach during the normal
process. The sensor should have the
minimum possible material build up.
Material in tank should be at the lowest
point it could reach during the normal
process.
Demanding
Interface
detection
• hygroscopic / wet solids
• high viscosity and high
conductivity liquids
• liquid A / liquid B
• foam / liquid
4.Press ⇑ or ⇓. The display switches to the current measured sensor value in counts.
Record the count value.
5.Press ⇑ or ⇓ to enter Edit mode; the sensor value is frozen and ready for editing.
6.Set the sensor value to 95% of the value obtained in step 4 (0.95 x counts). Press ⇑ to
edit the value of each digit, and press ⇓ to move the cursor to the next digit.
7.After editing the least significant digit (or leaving it unchanged), press ⇓ to terminate
the procedure and save the new value. The display now shows the new value for
the 0% Application Range setting.
8.Press M to exit.
Mode 20: 100% Application Range setting
This point corresponds to the right limit of the bar graph in the digital display.
CLS200 100% Application Range setting
To adjust the 100% Application Range setting for CLS200:
1.Install the device in the process.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 41
Page 48
2.Use the M button to navigate to Mode 20.
3.Set up the process to provide the recommended condition for your process from the
table below:
ApplicationMaterialSetup conditions
Operation: standalone
General
Demanding
Interface
detection
•dry solids
• low viscosity liquids
• hygroscopic / wet solids
• high viscosity and high
conductivity liquids
• liquid A / liquid B
• foam / liquid
sensor fully covered
sensor fully covered
sensor immersed in the material with
the highest dielectric constant
4.Press ⇑ or ⇓. The display switches to the current measured sensor value in counts.
Record the count value.
5.Press ⇑ or ⇓ to enter Edit Mode; the sensor value is frozen and ready for editing.
6.Set the sensor value to approximately 1000 counts above the obtained in step 4.
Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor to the next
digit.
7.After editing the least significant digit (or leaving it unchanged), press ⇓ to terminate
the procedure and save the new value. The display now shows the new value for
the 100% Application Range setting.
8.Press M to exit.
CLS300 100% Application Range setting
To adjust the 100% Application Range setting for CLS300:
1.Install the device in the process.
2.Use the M button to navigate to Mode 20.
3.Set up the process to provide the recommended condition for your process from the
table below:
ApplicationMaterialSetup conditions
Material in tank should be at the highest
point it could reach during the normal
process.
Material in tank should be at the highest
point it could reach during the normal
process.
Sensor immersed in the material with
the highest dielectric constant
General
Demanding
Interface
detection
•dry solids
• low viscosity liquids
• hygroscopic / wet solids
• high viscosity and high
conductivity liquids
• liquid A / liquid B
• foam / liquid
4.Press ⇑ or ⇓. The display switches to the current measured sensor value in counts.
Record the count value.
5.Press ⇑ or ⇓ to enter Edit mode; the sensor value is frozen and ready for editing.
6.Set the sensor value to 105% of the value obtained in step 4 (1.05 x counts). Press ⇑
to edit the value of each digit, and press ⇓ to move the cursor to the next digit.
Page 42Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 49
7.After editing the least significant digit (or leaving it unchanged), press ⇓ to terminate
the procedure and save the new value. The display now shows the new value for
the 100% Application Range setting.
8.Press M to exit.
Mode 23: Alarm output trigger (default: dIAG)
The alarm output (solid-state switch) can be forced to switch for one of several reasons.
The table below lists the possible triggers:
Operation: standalone
Selection
message
OFFDeactivated
dIAGDiagnosis
OUt_dOutput Value
ALErtDiagnostic
Tr ig g er
description
(diagnostic
interrupt)
(process
interrupt)
Alarm Limit
exceeded
CauseRemark
Sensor Value above sensor
range
Sensor Value below sensor
range
Electronics temperature
above nominal range
Electronics temperature
below nominal range
Memory check of RAM,
ROM, EEPROM not passed
(test running in background)
Logical Level
(OUT parameter)
Sensor Value higher than
Diagnostic Alarm upper limit.
Affected by Application
Range, upper and lower
limits; Rise Time; Fall
Time; and Inversion
Diagnostic Alarm Limits
are set with SIMATIC
PDM
To select the trigger which will force the alarm output to switch:
•Select Mode 23. The current selection (OFF, dIAG, Out_d, or ALErt) appears in
the primary reading field.
•Press ⇑ or ⇓ until the desired selection message appears.
•Press M to save and exit.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 43
Page 50
Mode 24: Contact type (default: CLOSE)
The solid state switch alarm output can function in one of two ways:
•Make contact (close)
•Break contact (open)
To select the contact type.
Operation: standalone
•Select Mode 24. The current contact type (OPEn or CLOSE) appears in the
primary reading field.
•Press ⇑ or ⇓ to select the desired contact type.
•Press M to save and exit.
WARNING: If you change this parameter, the position of the switch
changes immediately. Adapted applications or devices can react
unintentionally.
Note: This
Discrete Input Function Block, which can only be set remotely.
adjustment is independent of the Inversion Output parameter of the
Mode 25: Switch Point Off to On/Switch Point 1/Rising Edge
(default: 55%)
Note: Initial setup can be carried out prior to mounting into the process, but it is
extremely important to calibrate the unit and adjust the sensitivity on the product itself.
Allows you to adjust the switch behavior by setting the percentage of the Application
Range (defined in Mode 19 and Mode 20) at which point the logical switch will change
from Off to On.
This symbol appears to the left of the numerical value to indicate a Rising Edge value.
Switch Point 1 must have a value greater than or equal to the value for Switch Point 2. If
you enter a lower value, Switch Point 2 will be adjusted to the same value.
The permitted range is limited by the distance of the Switch Point to the next Measuring
Limit.
To view the current setting for Switch Point 1:
•Select Mode 25.
•The current setting appears in the primary reading field as a percent of the
Application range (0 to 100%).
•Press M to exit, or:
To adjust the setting:
•Press ⇑ or ⇓.
•The display switches to the current measured Sensor Value as a percent of the
Application Range (0 to 100%).
•Press ⇑ or ⇓ to open Edit mode: the Sensor value is frozen.
•Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor to the
next digit.
Page 44Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 51
•After editing or leaving the least significant digit unchanged, press ⇓ to
terminate procedure and save the new value.
•You see the new setting for Switch Point 1.
•Repeat the process, or press M to exit.
Mode 26: Switch Point On to Off/ Falling Edge (default: 45%)
Note: Initial setup can be carried out prior to mounting into the process, but it is
extremely important to calibrate the unit and adjust the sensitivity on the product itself.
Allows you to adjust the switch behavior by setting the percentage of the Application
Range (defined in Mode 19 and Mode 20) at which point the logical switch will change
from ON to OFF.
This symbol appears to the left of the numerical value to indicate a Falling Edge
value.
Switch Point 2 must have a value less than or equal to the value for Switch Point 1. If you
enter a higher value, Switch Point 1 will be adjusted to the same value.
To view the current setting for Switch Point 2:
•Select Mode 26.
•The current setting appears in the primary reading field as a percent of the
Application Range (0 to 100%).
•Press M to exit, or:
To adjust the setting:
•Press ⇑ or ⇓.
•The display switches to the current measured Sensor Value as a percent of the
Application Range (0 to 100%).
•Press ⇑ or ⇓ to open Edit mode: the Sensor value is frozen.
•Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor to the
next digit.
•After editing or leaving the least significant digit unchanged, press ⇓ to
terminate procedure and save the new value.
•You see the new setting for Switch Point 2.
•Repeat the process, or press M to exit.
Operation: standalone
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 45
Page 52
Mode 27: Local Status Text (default: U_075)
Sets the format for representing Sensor Status. The default setting is a numeric format:
one letter followed by an underscore and a decimal figure representing the status code
(e.g. U_075).
You can select between the numeric format described above, or text as English, German,
French, Spanish, or Italian strings. The strings are represented as rolling text.
Operation: standalone
Language formatDisplay message
numericU_075
ItalianItALI
SpanishESPAn
FrenchFrAnC
GermandEUtS
EnglishEnGLI
To select the status format:
•Select Mode 27.
•The current setting is shown in the primary reading field.
•Press ⇑ or ⇓ to select a new format.
•Press M to save and exit.
CLS200 Digital Switching Point Setup
Use the following procedure to set up the switch point for the CLS200 Digital model.
1.Set the 0% Application Range Setting (Mode 19):
a. Install the device in the process.
b. Use the M button to navigate to Mode 19.
c. Set up the process to provide the recommended condition for your process from
the table below:
ApplicationMaterialSetup conditions
General
Demanding
Interface
detection
•dry solids
• low viscosity liquids
• hygroscopic / wet solids
• high viscosity and high
conductivity liquids
• liquid A / liquid B
• foam / liquid
sensor uncovered;
min. 100 mm (4") free space all around
sensor immersed then uncovered; but
retaining max. possible material buildup
sensor immersed in the material with
the lowest dielectric constant
d. Press ⇑ or ⇓. The display switches to the current measured sensor value in
counts.
e. Press ⇑ or ⇓ to enter Edit Mode; the sensor value is frozen and ready for editing.
Page 46Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 53
f. Set the sensor value to approximately 300 counts below the value of the current
reading. Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor
to the next digit.
g. After editing the least significant digit (or leaving it unchanged), press ⇓ to
terminate the procedure and save the new value. The display now shows the
new value for the 0% Application Range setting.
h. Press M to exit.
2.Set the 100% Application Range setting (Mode 20):
a. Install the device in the process.
b. Use the M button to navigate to Mode 20.
c. Set up the process to provide the recommended condition for your process from
the table below:
ApplicationMaterialSetup conditions
Operation: standalone
General
Demanding
Interface
detection
•dry solids
• low viscosity liquids
• hygroscopic / wet solids
• high viscosity and high
conductivity liquids
• liquid A / liquid B
• foam / liquid
sensor fully covered
sensor fully covered
sensor immersed in the material with
the highest dielectric constant
d. Press ⇑ or ⇓. The display switches to the current measured sensor value in
counts.
e. Press ⇑ or ⇓ to enter Edit Mode; the sensor value is frozen and ready for editing.
f. Set the sensor value to approximately 1000 counts above the value of the
current reading. Press ⇑ to edit the value of each digit, and press ⇓ to move the
cursor to the next digit.
g. After editing the least significant digit (or leaving it unchanged), press ⇓ to
terminate the procedure and save the new value. The display now shows the
new value for the 100% Application Range setting.
h. Press M to exit.
3.Adjust the Off to On switch point (Mode 25):
a. Use the M button to navigate to Mode 25.
b. Set the value to 55% as a starting point.
4.Adjust the On to Off switch point (Mode 26):
a. Use the M button to navigate to Mode 26.
b. Set the value to 45% as a starting point.
Note: A minimum hysteresis (difference between the Off to On switch point and the
On to Off switch point) of 10% must be maintained for reliable operation. In some
situations it may be desirable to increase the hysteresis between the two switch points
to prevent false tripping (e.g. turbulence in the process).
5.Adjust the other parameters of the device as desired.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 47
Page 54
CLS300 Digital Switching Point Setup
Use the following procedure to set up the switch point for the CLS300 Digital model.
1.Set the 0% Application Range Setting (Mode 19):
a. Install the device in the process.
b. Use the M button to navigate to Mode 19.
c. Set up the process to provide the recommended condition for your process from
Operation: standalone
the table below:
ApplicationMaterialSetup conditions
Material in tank should be at the lowest
point it could reach during the normal
process.
General
•dry solids
• low viscosity liquids
Material in tank should be at the lowest
point it could reach during the normal
process. The sensor should have the
minimum possible material build up.
Material in tank should be at the lowest
point it could reach during the normal
process.
Demanding
Interface
detection
• hygroscopic / wet solids
• high viscosity and high
conductivity liquids
• liquid A / liquid B
• foam / liquid
d. Press ⇑ or ⇓. The display switches to the current measured sensor value in
counts. Record the count value.
e. Press ⇑ or ⇓ to enter Edit mode; the sensor value is frozen and ready for editing.
f. Set the sensor value to 95% of the value obtained in step 1d (0.95 x counts).
Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor to the next
digit.
g. After editing the least significant digit (or leaving it unchanged), press ⇓ to
terminate the procedure and save the new value. The display now shows the
new value for the 0% Application Range setting.
h. Press M to exit.
2.Set the 100% Application Range setting (Mode 20):
a. Install the device in the process.
b. Use the M button to navigate to Mode 20.
c. Set up the process to provide the recommended condition for your process from
the table below:
ApplicationMaterialSetup conditions
Material in tank should be at the highest
point it could reach during the normal
process.
General
•dry solids
• low viscosity liquids
Demanding
Interface
detection
• hygroscopic / wet solids
• high viscosity and high
conductivity liquids
• liquid A / liquid B
• foam / liquid
Material in tank should be at the highest
point it could reach during the normal
process.
Sensor immersed in the material with
the highest dielectric constant
Page 48Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 55
d. Press ⇑ or ⇓. The display switches to the current measured sensor value in
counts. Record the count value.
e. Press ⇑ or ⇓ to enter Edit mode; the sensor value is frozen and ready for editing.
f. Set the sensor value to 105% of the value obtained in step 2d (1.05 x counts).
Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor to the next
digit.
g. After editing the least significant digit (or leaving it unchanged), press ⇓ to
terminate the procedure and save the new value. The display now shows the
new value for the 100% Application Range setting.
h. Press M to exit.
3.Determine the switch point:
a. Bring the process material to the desired switching level in the process.
b. Record the count value displayed on the device.
c. Calculate the trip point as a percent of process range:
Operation: standalone
trip point (%) =
4.Adjust the Off to On switch point (Mode 25):
a. Use the M button to navigate to Mode 25.
b. Set the value to 5% above the trip point percentage calculated in step 3c as a
starting point.
5.Adjust the On to Off switch point (Mode 26):
a. Use the M button to navigate to Mode 26.
b. Set the value to 5% below the trip point percentage calculated in step 3c as a
starting point.
(counts recorded in step 3b – M19)
(M20 – M19)
x 100
Notes:
• A hysteresis (difference between the Off to On switch point and the On to Off switch
point) of 10% is used as an example of a typical setup. In some situations it may be
desirable to increase the hysteresis between the two switch points to prevent false
tripping (e.g. turbulence in the process).
• All parameters should be set up to account for a possible deviation of ±1% of the
actual measurement under reference conditions.
6.Adjust the other parameters of the device as desired.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 49
Page 56
Wiring: connecting CLS200/300 Digital
to a PROFIBUS PA network
Electrical Connection
WARNING:
• Observe the specifications of the examination certificate valid in your
country.
• Observe the laws and regulations valid in your country for electrical
installations in potentially explosive atmospheres.
• Refer to
applicable.
• Ensure that the available power supply complies with the power supply
Wiring: PROFIBUS PA
specified on the product nameplate and specified in the examination
certificate valid in your country.
• Shipping plugs in the cable inlets must be replaced by suitable screwtype glands or dummy plugs, which are appropriately certified for
transmitters with explosion-proof protection.
• The lid must not be opened in wet locations while the unit is powered.
(A wet location is a location where water or another conductive fluid
may be present and is likely to increase the risk of electric shock.)
Notes:
• Lay PROFIBUS PA cable separately from power cable with voltages greater than
60 V.
• Avoid locating Pointek CLS200/300 Digital near large electrical equipment wherever
possible.
• Connect the cable shield to earth (for example, to the housing by means of a
metallic screwed gland).
Appendix E: Hazardous Area Installation
on page 91 if
Page 50Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 57
PROFIBUS PA connection to screw terminals
lid clip
digital display
removable
terminal
block for
PROFIBUS
PA/ po w e r
connection
(polarity not
important)
removable
terminal block
for alarm output /
solid-state switch
gland
reed contact
r
e
d
(
+
)
b
l
a
c
k
(
–
)
o
r
a
n
g
e
(
f
)
w
h
i
t
e
w
h
i
t
e
PROFIBUS PA
alarm output
solid-state switch
test
input
sensor
1.Loosen the lid clip and unscrew the lid of the enclosure.
2.Unscrew and lift up the digital display. (Loosen each screw two turns before
completely loosening both, to keep the rubber retaining rings in place.)
3.Strip the cable jacket for approximately 70 mm (2.75") from the end of the cable, and
thread the wires through the gland.
4.Connect the PROFIBUS PA wires to the terminals shown below (polarity is not
important). The terminal block can be removed and replaced to simplify connection.
5.If you want to use the Alarm Output, connect the wires of an optional input to the
Alarm Output terminals (polarity is not important). The terminal can be removed and
replaced to simplify connection.
6.Ground the instrument according to local regulations.
7.Tighten the gland to form a good seal.
8.Replace the digital display.
9.If you want to adjust the transmitter locally using the keypad, go to
the Local User Interface (LUI)
.
on page 32: if not, replace the enclosure lid.
Programming via
Wiring: PROFIBUS PA
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 51
Page 58
PROFIBUS PA connection via M12 plug
M12 plug
(device side)
M12 receptacle
(cable side)
digital display
lid
lid clip
thread M12 x 1
positioning lug
positioning
nut
PIN PROFIBUS PA
1PA+
2not connected
3PA–
4shield, connected to ground
1
1
2
4
3
21
3
4
Front view of pin insert
and pins
Front view of sleeve
insert and sleeves
PIN PROFIBUS PA
1PA+
2not connected
3PA–
4shield, connected to ground
1
Pin assignment: device side Pin assignment: cable side
Front view of sleeve
insert and sleeves
If an M12 connector is used, an M12 receptacle will be required to complete the bus
connection to PROFIBUS PA.
Wiring: PROFIBUS PA
Follow the instructions accompanying the female receptacle. The pin assignment is
shown below.
1
Page 52Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
1.
Although the PROFIBUS PA recommendation is usually to ground the shield on both the device
side and the cable side (to avoid interference), in some cases, it may be preferable to ground one
side only, to avoid ground loops.
This is particularly important if the device is mounted on cathodically protected tanks.
Page 59
Remote Operation via PROFIBUS PA
Note: The following instructions assume that the user is familiar with PROFIBUS PA.
PROFIBUS PA is an open industrial protocol. Full details about PROFIBUS PA can be
obtained from PROFIBUS International at www.profibus.com
Pointek CLS200/300 Digital is a Class B, Profile Version 3.01, PA device. It supports Class 1
Master for cyclic and acyclic data exchange, and Class 2 for acyclic services: (see
versus Acyclic Data
You will need a software package to configure Pointek CLS200/300. We recommend
SIMATIC Process Device Manager (PDM) by Siemens. (You can find more information at
www.siemens.com/processinstrumentation
products drop-down list on the right hand side.)
SIMATIC PDM
SIMATIC PDM is a software package used to commission and maintain Pointek CLS200/
300 and other process devices.
SIMATIC PDM monitors the process values, alarms and status signals of the device and
allows you to display, compare, adjust, verify, and simulate process device data.
Electronic Device Description (EDD)
In order to use SIMATIC PDM with PROFIBUS PA, you will need the Device Description
for Pointek CLS200/300 which will be included with new versions of PDM. You can locate
the Device Description in Device Catalog, under Sensors/Level/Capacitive/Siemens
Milltronics. If you do not see Pointek CLS200/300 under Siemens Milltronics, you can
download it from the Pointek CLS200 or CLS300 product page of our web site. Go to:
http://pia.khe.siemens.com/index.asp?Nr=4924 andclick on Downloads. After
downloading the DD file, you need to open PDM and click Options/Manage Device
Catalog.
on page 54 for details).
. Select SIMATIC PDM from the Quick links to
Cyclic
Remote Operation: PA
Configuration
To configure a PROFIBUS Class 1 Master (for example, a PLC), you will need a GSD file.
The GSD file
The GSD file can be downloaded from either the Pointek CLS200 or CLS300 product pages
on our web site: www.siemens.com/level
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 53
, under Downloads.
Page 60
Setting the PROFIBUS address
When your instrument is shipped, the PROFIBUS PA address is set to 126. You can set it
locally (see
using a parameterization tool such as SIMATIC PDM or HW-Config.
When cyclic data transfer with a Class 1 Master is in process, the address can only be
changed via the bus.
Mode 15: Node address (default: 126)
, on page 39) or remotely via the bus,
Bus address (Device Address)
Range: 0 to 126 (recommended setting
Values
between 1 and 125)
Pre-set: 126
Bus Termination
Note: PROFIBUS PA MUST be terminated at both extreme ends of the cable for it to
work properly. Please refer to the PROFIBUS PA User and Installation Guidelines (order
number 2.092), available from www.profibus.com
Power Demands
To determine how many devices can be connected to a bus line, calculate the combined
maximum current consumption of all the connected devices (12.5 mA for Pointek CLS200/
300). Allow a current reserve for safety.
Cyclic versus Acyclic Data
When data is requested from a device via PROFIBUS PA, there are two data transfer
Remote Operation: PA
methods. Cyclic data is requested and provided at every bus scan: acyclic data is
requested and provided as needed.
•Input and output information is always requested at every bus scan and is set up as
cyclic data.
•Configuration and maintenance information is needed infrequently, and is set up as
acyclic data.
Acyclic Data Transmission
Pointek CLS200/300 supports up to four simultaneous connections by a Class 2 Master
(C2 connection). It supports one connection by a Class 1 Master (C1 connection).
Cyclic Data Transmission
Cyclic data transmission transfers the user data relevant for process automation
between the Class 1 Master (control or automation system) and the transmitter.
When you configure Pointek CLS200/300 on the PROFIBUS PA bus, there is one slot
available for modules, and the Level Status module is automatically inserted.
Page 54Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 61
Transmission of user data via PROFIBUS PA
The user data is continuously updated by the cyclic service of PROFIBUS PA. The user
data is the OUT parameter of the Discrete Input Function Block and is composed of the
Logical Level and Status bytes.
The 2 bytes must be read consistently1, in a contiguous chunk: they must not be read byte
by byte, and must not suffer an interrupt. If you are using an S7-300 / 400, you will need to
use SFC14 DPRD_DAT: Read Consistent Data of a Standard PD Slave.
ByteOut
Byte 1Logical Level
Byte 2
a.
If Condensed status is turned on (default), then the condensed status
appears here.
Status
a
Logical Level
The Logical Level indicates the level of the material.
InversionSensor StatusLogical Level
OFFuncovered= 0 (zero)
OFFcovered= 1
Status
Status provides information via the status byte, on the usability of the measured value in
the PLC/DCS
process alarms).
2
, the device status, and additional process information (for example,
Remote Operation: PA
Status Byte
The status byte is a standardized code returned by a PROFIBUS slave on every bus scan,
along with the main process variable (output of the Analog Input Function Block).
•The status code indicates whether the process variable is valid or not.
•It also indicates other process-related information.
Status Codes
The codes for the Status bytes are listed in the following tables. Possible causes for an
error are shown, along with measures to correct it.
If the language selected for the display is numeric, a status code will be displayed. If any
other language has been selected, a status description will be displayed
Note: For more detail, please consult the PROFIBUS PA User and Installation
Guideline (order number 2.092), available for download from www.profibus.com.
1.
Consistent in this context means all-at-one-time.
2.
Programmable Logic Controller/Distributed Control System
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 55
.
Page 62
Status Codes for Good Quality
Digital
Hex
display
80---GoodNormal operation---
84G_132
8DG_141
8EG_142
A4G_164
a.
Set via PROFIBUS PA, in counts (see
PDM displayPossible Cause
A parameter relevant for the
Good;
Active block alarm
The function block is put out of
order with a target mode
command. A parameterized
safety value is supplied.
Corrective
Measure
Note to the control
system
Check installation
and sensor
a
adjustment.
Check installation
and sensor
a
adjustment.
Maintenance work,
electronics
servicing, or sensor
servicing, is
required.
Corrective
Measure
Replace the
electronics.
Check sensor
Check sensor
For normal
operation, reset
the target mode to
“AUTO”.
Page 56Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 63
Digital
Hex
display
40U_064Uncertain
47U_071
4BU_075
4FU_079
50U_080
PDM displayPossible CauseCorrective Measure
Uncertain,
Last usable value,
Value constant
Uncertain,
Substitute value,
Value constant
Uncertain,
initial value,
Value constant
Uncertain,
Value inaccurate
Status Codes for Uncertain Quality
Sensor test in progress;
no error detected.
“Fail Safe” input condition
is met; the parameterized
safety setting is set to
“keep last valid value”.
Value is not an automatic
measured value. This
identifies a parameterized,
static substitute value or a
preset value.
After run-up, an initial value
is entered in the device
memory.
Unreliable operating
parameters or
maintenance alarm
To return to normal
operation, deactivate
sensor test.
Consult the log of
measured data.
Consult the log of
measured data.
Reject the value in the
user program.
Check the operating
parameters, e.g. the
permitted ambient
temperature. Immediate
maintenance work
required.
Remote Operation: PA
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 57
Page 64
Diagnostics
In addition to information on the usability of the measured value, Pointek CLS200/300 can
actively report information on its own status. Diagnostics are important information, which an
automation system can use to introduce remedial measures.
Standard PROFIBUS DP mechanisms are used to transport diagnostic information and actively
report it to the Class 1 Master. For this, PROFIBUS DP provides a protocol to transmit
information ranked higher than user data to the Class 1 Master.
The content of the “Device status” parameter from the physical block is reported and, in
addition, information on whether a change of status has occurred (event arrived/ event gone).
The diagnostic object consists of 10 bytes (4 bytes standard diagnostics and 6 bytes Extended
diagnostics).
Standard diagnostics
Diagnostic Messages
Remote Operation: PA
ByteBit
0--1--2---
3
Byte 0
4Memory error
5
6--7---
Meaning when
value = 1
Electronics
temperature is too
high
Measurement
failure
Possible Cause
The temperature of the
measuring transducer
electronics (which is monitored
by the measuring transducer)
exceeds 85°C.
An error has been found.
(During operation, the memories
are constantly checked for
check sum errors and read/
write errors.)
Either the sensor has failed, or
the sensor limits are being
exceeded.
Corrective
Measure
Reduce the ambient
temperature to within
the permissible range
Replace the
electronics.
Have the sensor
checked by the
service department.
Page 58Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 65
ByteBit
0--1--2---
3
4
5
Byte 1
6---
7
0
Diagnostic Messages (cont’d)
Meaning when
value = 1
Restart (goes to 0
after 10 s)
b
Coldstart
0 after 10 s)
Maintenance
required
Ident Number
violation
Maintenance
alarm
(goes to
Possible Cause
The supply current has been fed
to the device; or a warm start
has been triggered using
SIMATIC PDM; or the internal
watchdog has expired.
The device has been reset to its
factory settings.
A service interval has expired.
You have changed the
parameter PROFIBUS Ident
Number during cyclic operation.
The device is reporting the
violation of the Ident number
and showing you a preliminary
failure warning. In the case of a
warm restart, the device will no
longer participate in cyclical
communication of reference
data without a change in the
system configuration.
Device requires maintenance
a
Corrective
Measure
Check the cabling
and the power unit
Service the device,
and reset the
messages using
SIMATIC PDM.
Adjust the
configuration data
(change of GSD), so
that it is consistent
with the Ident number
set in the device.
Maintenance action
required
Remote Operation: PA
1
Byte 2
2Function check
3
Byte 3 7
a.
With a warm start, the volatile data is preserved.
b.
With a cold start, all volatile data is lost.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 59
Maintenance
demanded
Invalid process
conditions
Extended
diagnostics
available
Device requires immediate
maintenance or a failure will
occur.
Page 66
Extended diagnostics
Extended Diagnostic Messages
MeaningCorrective ActionByte Bit
Electronic temperature exceeds
permissible range
Bring temperature of electronics module
to within allowed range
0
Sensor value exceeds
diagnostic alarm limits
Calibration timer,
unacknowledged alarm
Calibration timer,
unacknowledged warning
Service timer, unacknowledged
alarm
Service timer, unacknowledged
warning
Sensor value exceeds sensor
limits
Sensor Test Running
Memory checksum errorDevice is defective; replace unit
Sensor test failedSensor is defective; replace sensor2
Remote Operation: PA
Sensor value simulation
Simulation: Electronic
temperature
Simulation: Digital input in
simulation
Either adjust diagnostic alarm limits or
remove cause of out of range sensor value
Perform calibration and timer will
automatically be reset
Perform service and reset timer using
SIMATIC PDM
Perform service on sensor or replace unit
Wait for sensor test to finish, then remove
test magnet from device housing
To return to normal operation, disable the
simulation with SIMATIC PDM
To return to normal operation, disable the
simulation with SIMATIC PDM
To return to normal operation, disable the
simulation with SIMATIC PDM
2
3
0
4
5
6
6
2
7
1
3
4
3
5
To return to normal operation, disable the
Digital Input in Manual mode
Simulation: Diagnosis
simulation with SIMATIC PDM; reset the
block mode of the Digital Input Function
Block
To return to normal operation, disable the
simulation with SIMATIC PDM
6
7
Note: The instrument status can be simulated using SIMATIC PDM. This allows you to test
the reaction of the automation system to errors.
Page 60Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 67
Self tests
Pointek CLS200/300 carries out the following self tests:
Self Tests
Self test
function
Measure the
electronics
temperature
RAM test
Code test
Sensor test
Check
service
timers
Watchdog
trigger
a.
A walking one and zero is a method of checking each bit in each location of volatile
memory.
AlgorithmFrequency
If electronics temperature
exceeds 85 °C
Writing and verifying every
cell with a byte (walking one
and walking zero
defect cells and crosstalk
Summarizing the bytes and
comparison with a
checksum
If measurement returns a
value outside the sensor
range determined by
Measuring Limits
If a service timer reaches
the parameterized warning
or alarm limit
The program must pass
specific checkpoints. If all
checkpoints are not passed
within a specific time, the
watchdog timer expires and
a restart will be carried out
a
) to detect
Every
measurement
cycle/ 60 ms
45 sMemory error
45 sMemory error
every
measurement
cycle/ 60 ms
60 ms
2 sRestart
Diagnostic
error
message
Electronics
temperature
too high
Measurement
failure
Maintenance
required
Corrective
measure
Reduce ambient
temperature to
within
permissible
range
Replace the
electronics.
Replace
electronics and,
if necessary,
measuring cell.
Have sensor
checked by
service
department.
Carry out
servicing and
reset messages
using SIMATIC
PDM.
Check cabling
and power unit
to ensure the
power supply to
Pointek CLS20 0 /
300
Remote Operation: PA
Values of the DIAGNOSIS bit:
0 = not set
1 = set
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 61
Page 68
Configuration Example
To configure and use PROFIBUS PA with an S7-300/ 400 PLC
1.If Pointek CLS200/300 is not listed in the STEP 7 device catalog, you can download
the DeviceInstall file from the Siemens Milltronics Web site and run it from your
computer. Go to http://pia.khe.siemens.com/index.asp?Nr=4924 and click
Downloads.
2.Add the Pointek CLS200/300 "rack": click and drag the Pointek CLS200/300 folder from
the hardware catalog.
3.Fill the rack with desired modules, by dragging and dropping them from the
hardware catalog.
4.After configuring PROFIBUS PA in steps 2 and 3, download it to the PLC.
Add code to the PLC program to read data consistently using the SFC14.
Remote Operation: PA
Page 62Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 69
PROFIBUS PA Parameters
WARNING: It is essential to check settings during the process itself,
and confirm that they are correct, before regular operation commences.
The full range of Pointek CLS200/300 functions is available only via remote operation
using PROFIBUS PA.
To use PROFIBUS PA, you will need a PC configuration tool: we recommend
SIMATIC PDM. For more information see
SIMATIC PDM
Measured Values
In measuring operations, measured values such as the logical level are provided via
PROFIBUS PA. They can be viewed via PROFIBUS PA, and on the LCD display.
To view values via PROFIBUS PA open the menu View – Display, and select one of the
following tabs:
Output Output value On (covered) or Off (uncovered)
TB² Discrete Input Part 2 Discrete Sensor Value On (covered) or Off
TB² Discrete Input Part 1Sensor value represented in counts
1
2
Measured value sourceDescription
(uncovered) as well as Primary Value (On or Off)
a dynamic representation of level as a
percentage of the application range.
on 53.
1
as well as
Electronics TemperatureInternal temperature of the electronics.
For instructions on selecting the display source for the LCD, see
operation
2
1.
2
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 63
on page 72.
For more detail see
TB - Transducer Block
Counts
on page 73.
Display Source for local
Parameters: PA
Page 70
Functions
value
column
The device menu gives you access to the following functions:
•Upload from/Download to the device
•Set Address
•Master Reset
•Write Locking
•Sensor Test
•Simulation
•Condensed Status Setup
Changing parameter settings
Note: Initial setup can be carried out prior to mounting into the process, but it is
extremely important to calibrate the unit and adjust the sensitivity on the product itself.
•First launch SIMATIC PDM, connect to Pointek CLS200/300, and upload data from
the device (the status fields change to Loaded).
•Adjust parameter values in the parameter value field.
•After adjusting the value, press Enter (the status fields read Changed).
•When you have completed the adjustments, open the menu Device – Download
data to Device then go to File – Save to save parameter settings offline (the status
fields are cleared).
Parameters: PA
Page 64Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 71
Filling level status:
Adjust 0 % application range setting
The lower limit of the application range (0%) corresponds to the left limit of the bar graph
in the digital display.
For reliable and accurate detection of the process material, select the example in the
table below that most closely resembles your application, and follow the setup
procedure.
ApplicationMaterialSetup procedure
General
applications
Demanding
applications
Interface
detection
1.Follow the setup procedure that most closely resembles your application.
2.Open the menu View – Display and select the tab Transducer Block: Discrete Input
(Part 1). Make a note of the Sensor_Value (digits)
3.Close Display window, and enter the sensor value (recorded in the previous step) to
the Value field:
> Input > Transducer Block: Discrete Input > Range of Application> 0%.
Press Enter: the status field reads Changed.
dry solids
low viscosity liquids
hygroscopic / wet solids
high viscosity and high
conductivity liquids
liquid A / liquid B
foam / liquid
Sensor uncovered and a minimum of
100 mm (4") free space all around
Sensor immersed and then uncovered,
but retaining as much build up of
material as possible on the sensor.
Immerse the sensor in the material that
has the lowest relative dielectric
constant.
Parameters: PA
4.If no more settings need adjusting, download the data to the device and save the
parameter settings offline (the status fields go blank). Otherwise, continue to adjust
other parameters as required.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 65
Page 72
Adjust 100 % application range setting
Adjusts the upper limit of the application range (100%). This point corresponds to the right
limit of the bar graph in the digital display.
For reliable and accurate detection of the process material, select the example in the
table on page 66 that most closely resembles your application, and follow the setup
procedure.
ApplicationMaterialSetup procedure
General
applications
Demanding
applications
Interface detectionliquid A / liquid B
1.Follow the setup procedure that most closely resembles your application.
2.Open the menu View – Display and select the tab Trans duc er Block: Discrete Input
(Part 1). Make a note of the Sensor_Value (digits)
3.Close Display window, and copy the sensor value to the parameter view field:
> Input > Transducer Block: Discrete Input > Range of Application > 100%.
Press Enter: the status field reads Changed.
4.If no more settings need adjusting, download the data to the device and save the
parameter settings offline (the status field goes blank). Otherwise, continue to
adjust other parameters as required.
dry solids
low viscosity liquids
hygroscopic / wet solids
high viscosity and high
conductivity liquids
foam / liquid
Sensor fully covered
Sensor fully covered
Immerse the sensor in the
material that has the highest
relative dielectric constant.
Inversion
When Inversion Output = On, the level status undergoes a logical inversion. If you want to
invert the logic of the level status:
•Go to Output > Function Block: Discrete Input > Inversion Output > Off or On
•Press Enter: the status field reads Changed
Delay
Parameters: PA
You can adjust the timing behavior of the transmitter using two independent delay times.
•Rise Time (Off to On) determines the delay of the signal flow from the moment the
sensor becomes covered until the Primary Value is set.
•Fall Time (On to Off) determines the delay of the signal flow from the moment the
sensor becomes uncovered until the Primary Value is reset.
The delay timers have a range of values from 0.0 to 100.0 seconds.
•Go to Input > Transducer Block: Discrete Input > Delay > Rise Time (Off to On) and
set the value from 0 to 100 seconds.
•Go to Fall Time (On to Off), and set the value from 0 to 100 seconds.
Page 66Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 73
•Press Enter: the status field reads Changed.
Note: If the sensor status changes before the delay interval is complete, the timer is
reset to its initial value and restarted.
Failsafe Mode
If the Transducer Block delivers a measured value accompanied by a status message
classifying the quality as bad (for example Bad, sensor failure), the Discrete Input
Function Block can react with one of three possible preset options.
Failsafe ModeDescription
The default value is used as the
output value.
Store the last valid output value. The last valid output value is output (status code
The predefined preset safety value is output
(status code U_075).
U_071).
The calculated output value is
incorrect.
Set the fault behavior in the Discrete Input Function Block:
•Go to Output > Function Block: Discrete Input > Fail Safe Mode > Fail Safe Mode
and select one of the 3 options.
•Press Enter: the status field reads Changed
You can use SIMATIC PDM to determine the fault location by looking at the Input and
Sensor Values of the Transducer Block.
The bad output value is accompanied by the
status which the Transducer Block assigns to it
(B_0xx).
Simulation
Simulation functions are helpful when you are installing the transmitter.
•You can create process values without recording actual values.
•You can use the full range of values of the simulated process values.
•You can simulate errors.
The LCD displays Si in the Mode display when Simulation is activated.
Output simulation
Output simulation allows you to provide process values for the cyclic class 1 Master, to
test how the automation program processes those values.
Carry out the following settings:
1.Open the Device Menu Simulation.
2.Select the register Output.
3.Set the target mode to MAN (manual).
4.Enter the desired output value, the quality and the status.
Parameters: PA
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 67
Page 74
5.Transfer the settings to the device.
Val ue
Time
step
length
start
end
Number of
steps
6.You can view the output behavior, for example with SIMATIC PDM (open the View
Menu Display).
7.To return to normal operation, reset the target mode to AUTO and press Transfer.
Input (Primary Value) simulation
Input Value simulation allows you to test the effects on the Primary Variable of your
preset inversion and failsafe settings, and see how the output value is affected.
Carry out the following settings:
1.Open the Device Menu Simulation
2.Select the register Input.
3.Set the simulation mode to Enabled.
4.Enter the desired input value, the quality and the status.
5.Transfer the settings to the device.
6.You can view the output behavior, for example with SIMATIC PDM (open the View
Menu Display).
7.To return to normal operation, reset the simulation mode to Disabled and press
Trans fer.
Sensor Value Simulation
By simulating the Sensor Value as a fixed value or as a parameterizable slope, you can
test:
•the reaction to the Measuring Limits being exceeded
•the logic switch behavior
•the behavior of the delay timers
With a parameterizable slope you can make the simulation value dynamic. It runs from a
starting value to an end value in a step function, dwelling on each step for the preset
period of time. At the end value the direction is reversed.
Parameterizable slope
Parameters: PA
Page 68Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 75
Carry out the following settings:
1.Open the Device Menu Simulation.
2.Select the register Sensor Value.
3.Set Simulation Sensor Value, then set the parameters:
•for simulation mode fixed, enter a Sensor Value
•for simulation mode ramp, adjust the ramp parameters
4.Transfer the settings to the device.
5.You can view the behavior of the Sensor Value Discrete, the Input (Primary) Value,
and the Output, in SIMATIC PDM (open the View Menu Display, and select the
register Transducer Block: Discrete Input Part I).
6.To return to normal operation, turn off Simulation Sensor Value and press Trans fer.
Electronics temperature Simulation
By simulating the electronics temperature, you can test the effect of excessive
temperatures on the measuring results:
1.Open the Device Menu Simulation
2.Select the register Electronics Temperature.
3.Set Simulation Electronic Temperature, then set the parameters:
•either enter a fixed value for Electronics Temperature fixed
•or adjust the ramp parameters for Electronic Temperature ramp
4.Transfer the settings to the device.
5.You can view the reaction in the status of the measured values (input and secondary
variables), and the output, using SIMATIC PDM (open the View Menu Display and
select the appropriate register).
6.To return to normal operation, turn off Simulation Electronic Temperature and press
Trans fer.
Drag indicators (Peak indicators)
Two pairs of drag indicators allow you to monitor the negative and positive peak values
for the measured values Sensor Value and Electronics Temperature.
•Open the View Menu Drag Indicators.
•To reset the peaks to the actual measured value, click the appropriate Reset button.
•Press Enter: the status field reads Changed
Operating hours
An operating hours meter for the electronics is activated when the transmitter is first
started.
•Open the View Menu Operating hours.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 69
Parameters: PA
Page 76
Switch Point adjustment
There are two switch points:
•Switch point 1 (Off to On)
•Switch point 2 (On to Off)
To adjust the switch behavior, set the percentage of the application range
the logic switch will change from OFF to ON, or from ON to OFF.
•The application range must be defined first (see
: and
setting
setup procedure follows the guidelines for the application which most
resembles your operation).
•Open the menu View–Display, and select the register Transducer Block:
Discrete Input, to view the actual Sensor Value, the Sensor Value Discrete, the
actual valid Switch Point and Hysteresis
•Edit the value of Switch Point 1 in the “Switch Point” field.
•Edit the value of Switch Point 2 to adjust the Hysteresis
•Click on Transmit.
•Track the effect of the adjustment by looking at the Sensor Value Discrete.
Adjust 100 % application range setting
Adjust 0 % application range
on page 66. Ensure your
1
Device Reset
To reset the device, open the Device Menu Master Reset. The three reset options are:
•Factory reset (Restart/cold startup)
•Warm start (new start-up)
•Resetting the PROFIBUS address to 126
at which point
Factory Reset (Restart/cold startup)
If Pointek CLS200/300 has been adjusted to such an extent that it can no longer fulfil its
measuring tasks, you can use Factory Reset to recreate the delivery status. It resets most
parameters to the factory setting.
During a Factory Reset, a check mark appears against the diagnostic message Restart
(cold startup) carried out for about ten seconds, and the LCD displays UPDATE ALERT, as
rolling text in the auxiliary reading field.
Warm start (new start-up)
Parameters: PA
A Warm start (new start-up) disconnects Pointek CLS200/300, and restarts it.
Communication is interrupted and re-established.
You will need this function if, for example, during communication with a cyclic Master, the
PROFIBUS address has been changed.
During a Warm start, a check mark appears against the diagnostic message New startup (warm startup) carried out for a few seconds. As long as there is no measured value
result, the automation or control system records the status Uncertain, initial value, Value
constant.
1.
The application range is defined by the 0% and 100% settings (see page 65).
Page 70Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 77
Resetting the PROFIBUS address to 126
If no other device in your system has the preset address 126, you can extend the
PROFIBUS PA line during operation of the automation or control system, with an
additional Pointek CLS200/300 with the address 126. The only requirement is to change
the address of the new integrated device to another value lower than 126.
If you remove a Pointek CLS200/300 from the PROFIBUS channel, you should use this
function to reset its address to 126 so that, if required, it can be reintegrated into this or
another system.
Lock
Secures Pointek CLS200/300 from changes.
Lock Options
Parameter
name
HW Write
Protection
Parameter changes using SIMATIC
PDM, and settings via local operation,
are both disabled. Independent of the
other lock functions.
EffectTurn on /o f f
Keypad
Mode 10
Digital
display
L
Write lockingPrevents parameter changes via the
bus. Local operation is possible.
Local
Operation
You can also combine the locking functions
If local operation is disabled, no
access is possible using the keypad.
Independently of this parameter, local
operation is automatically enabled 30
s after a communication failure. Once
communication has been reestablished, the parameter Local
Operation in the device is reset to the
original setting.
SIMATIC PDM
Online dialog:
Write locking
SIMATIC PDM
Local
Operation
HW Write ProtectionWrite lockingLocal Operation
OffOffenabled
OnOn or Offenabled or disabledL
OffOffdisabledLA
OffOndisabledLL
OffOnenabledLc
Lc
LA
Parameters: PA
Digital
display
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 71
Page 78
Sensor Test
sensor uncovered
sensor covered
Logical level displayMeasured value display
communications
character
down arrow
indicates solidstate switch
open
up arrow
indicates solidstate switch
closed
communications
character
Open the Device Menu to find and activate the Sensor Test via PDM, and to see the
results (test successful, or test failed).
Display Source for local operation
You can select one of four options for the value to be displayed on the LCD:
•Output value
•Primary Value
•Sensor Value
•Electronics Temperature.
Go to Local Display and Operation > Display Source and select from the pull-down tab.
The measured value display shows the value (in counts) when Sensor value is selected.
The logical level display shows the value On or Off when Output value is selected. When
communication with a master is in progress, this is indicated by the communication
character o on the digital display. (For more details see
RUN mode display
on page 30.)
Parameters: PA
Page 72Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 79
Appendix A: Technical References
dielectric = contents plus insulation (non-conductive contents)
dielectric = insulation (conductive contents)
(insulation)
p ro b e
sleeve
internal
vessel
wall
probe
dia. (d)
internal vessel dia. (D)
Operating Principles
In capacitance measurement1 inside a vessel or silo, the environment (typically, the
vessel wall) acts as the reference electrode of a variable capacitor, and the probe
supplies the measurement electrode. The dielectric
(air, vapor, liquid, solid, or a combination) and, if the measurement electrode is insulated,
the insulating layer.
The capacitance when the probe is uncovered (capacitance in air) will be different from
the capacitance when the probe is covered (for example, capacitance in water). If the
product is two immiscible liquids with different relative dielectric constants, (for example,
oil and water) the capacitance will change at the interface between the two liquids.
2
is composed of the vessel contents
High Frequency Oscillator
The Pointek CLS200/300 probe is equipped with a high frequency oscillator which
responds to the capacitance. The inverse of frequency is proportional to the capacitance.
A small change in capacitance results in a large change in frequency which is easy to
detect, resulting in high resolution and accuracy.
Counts
Frequency is always represented in ’counts’, a dimensionless, uncalibrated value
generated from the inverse of frequency. The measured value is displayed in counts. (If
you are using PROFIBUS PA, you can set the measuring limits, in counts.)
1.
For definitions relating to capacitance, see the glossary, page 117
2.
The relative dielectric constant of air (vacuum) is 1: all other materials have a higher value.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 73
A: Technical References
Page 80
Detection Range
R = Ca1 + Ca
2
Ca1 + Ca2 + Cm1 + Cm
2
Measuring
Circuit
R = Ratio between initial
capacitance and total
capacitance
Ca
1
= Initial capacitance of the
CLS200
Ca
2
= Initial capacitance (air)
between the probe and the
installation
Cm
1
= Capacitance increase of the
CLS200 caused by product
replacing air
Cm
2
= Capacitance increase
between the probe and the
installation caused by
product replacing air.
Ca
2
Cm
2
Cm
1
Ca
1
The functional detection range depends on the relative dielectric constant of the material
monitored. The detection range will be shorter when the material has a lower relative
dielectric constant, and longer when it has a higher relative dielectric constant.
Specifications
See
, page 8, for performance information; also check the product
nameplate on the enclosure, for details of your particular instrument.
The Pointek CLS200 electrode
The Pointek CLS200 electrode is the primary sensor of the system. It supplies the
electrical capacitance value. The reference is the environment at the time of setup.
The design of the Pointek CLS200 probe makes it very sensitive to changes in
capacitance in the immediate vicinity of the antenna tip.
The initial capacitance of the CLS200 itself makes it possible to operate the CLS200 in a
plastic tank where the Ca
grounded metal tank will reduce the effects of external influences on the sensor.
The sensor can be set to detect either the change in capacitance as the product level
approaches the antenna tip, or the change when the probe becomes covered.
and Cm2 terms would disappear. However, a properly
2
A: Technical References
Page 74Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 81
The Pointek CLS300 electrode
Measuring
Circuit
Measuring
Circuit
Conventional Capacitance
Measurement
Pointek CLS300 with
Active Shield
C1
C2
C3
R = (C1 + C2 + C3) + Ca
(C1 + C2 + C3) + Ca + Cm
R = Ca
Ca + Cm
Ca
Ca
Cm
Cm
R = Ratio between initial
capacitance and total
capacitance
Ca = Initial capacitance (air)
Cm = Capacitance Increase
(product)
C1 = Capacitance connection
point
C2 = Capacitance connection
cable
C3 = Capacitance Process
connection (includes active
part)
The Pointek CLS300 electrode is the primary sensor of the system. It supplies the
electrical capacitance value.
The Pointek CLS300 patented Active Shield Technology electrically isolates the
measurement section and reduces the effect of any non-measurement capacitance on
the measurement capacitance. (Capacitance changes could result from uncontrolled
variations occurring in the connection cable, process connection, and non-active parts of
the probe.) This gives a better ratio of initial capacitance to total capacitance, resulting in
higher accuracy
.
The measurement is further protected from interference by a buffer, which applies the
frequency signal from the measurement section to the Active Shield section. This effectively
eliminates any electrical potential difference between the shield and the measurement
section and prevents additional changes in capacitance occurring, especially when
material builds up at the probe entrance to the tank.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 75
A: Technical References
Page 82
The relative lengths of the measurement section and Active Shield section can be
frequency (f) ≈K
capacitance (C)
Active
Shield
active
measurement
section
100%
0%
Poi nte k
CLS300
buffer
empty
tank
full
tank
specified to suit a particular application. If the measured range will be short relative to
the total length of the electrode, specify a short measurement section. This increases the
achievable resolution of the measurement, since any change in level will be greater
relative to the length of the measurement section.
The powder-coated aluminum enclosure provides reliable operation in environments with
dust, moisture, and high-frequency interference.
Sensor Test
You can initialize a sensor test by activating the reed contact with a magnet1 from outside
the housing. For details, see
Magnet-activated sensor test
, on page 36.
1.
A test magnet will be supplied with the instrument.
A: Technical References
Page 76Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 83
PROFIBUS PA electronics: mode of operation
1Sensor
2Isolation
3 Micro controller
4 PROFIBUS PA interface
5 Non-volatile memory
6 Digital display
7 Keyboard for local operation
8Reed relay
9Isolation
10 Alarm Output Solid-state Switch
Sensor
μC
EEPROM
PROFIBUS PA
interface
PROFIBUS PA
1
2
3
4
5
6
7
8
9
10
The process variable to be measured is generally referred to as the input variable.
The input variable provided by the sensor is an isolated digital frequency signal. This is
evaluated in a microprocessor and made available via PROFIBUS PA. The data for
transmitter parameterization is stored in non-volatile memory.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 77
A: Technical References
Page 84
Pointek CLS200 Digital Pressure versus
atmospheric
P = permitted operating pressure
T = permitted operating temperature
atmospheric
P = permitted operating pressure
T = permitted operating temperature
atmospheric
P = permitted operating pressure
T = permitted operating temperature
Temperature Curves
CLS200 compact and extended rod versions, threaded
CLS200 cable version, threaded
CLS200 sanitary compact and extended rod versions
A: Technical References
Page 78Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 85
CLS200 compact and extended rod, ASME welded flange
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable fl ange class for the shaded area below.
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable fl ange class for the shaded area below.
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable fl ange class for the shaded area below.
CLS200 cable, ASME welded flange
CLS200 compact and extended rod, EN welded flange
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 79
A: Technical References
Page 86
CLS200 cable, EN welded flange
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable fl ange class for the shaded area below.
atmospheric
P = permitted operating pressure
T = permitted operating temperature
Example: Permitted operating pressure = 30 bar
(435 psi) at 75 °C
atmospheric
P = permitted operating pressure
T = permitted operating temperature
Pointek CLS300 Digital Pressure versus
Temperature Curves
CLS300 standard, extended rod and cable versions,
threaded
CLS300 high temperature rod version, threaded
A: Technical References
Page 80Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 87
CLS300 standard, extended rod and cable versions,
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable flange cl ass for the shaded area below.
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable flange cl ass for the shaded area below.
ASME welded flange
CLS300 high temperature rod version, ASME welded
flange
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 81
A: Technical References
Page 88
CLS300 standard, extended rod and cable versions, EN
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable flange cl ass for the shaded area below.
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable flange cl ass for the shaded area below.
welded flange
CLS300 high temperature rod version, EN welded flange
A: Technical References
Page 82Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 89
Appendix B: Maintenance and Repairs
Pointek CLS200/300 requires no maintenance or cleaning.
Unit Repair and Excluded Liability
All changes and repairs must be done by qualified personnel, and applicable safety
regulations must be followed. Please note the following:
•The user is responsible for all changes and repairs made to the device.
•All new components must be provided by Siemens Milltronics Process
Instruments Inc.
•Restrict repair to faulty components only.
•Do not re-use faulty components.
B: Maintenance / Repairs
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 83
Page 90
Appendix C: Profile structure – Pointek
1Sensor
2Isolation
3 Micro controller
4 PROFIBUS PA interface
5 Non-volatile memory
6 Digital display
7 Keyboard for local operation
8Reed relay
9Isolation
10 Alarm Output Solid-state Switch
Sensor
μC
EEPROM
PROFIBUS PA
interface
PROFIBUS PA
1
2
3
4
5
6
7
8
9
10
CLS200/300 (PROFIBUS PA)
PROFIBUS PA electronics: mode of operation
The process variable to be measured is generally referred to as the input variable.
The input variable provided by the sensor is an isolated digital frequency signal. This is
evaluated in a microprocessor and made available via PROFIBUS PA. The data for
transmitter parameterization is stored in non-volatile memory.
C: Profile structure
Page 84Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 91
Block model for recording and processing
level
electronics
temperature
sensor
sensor
Transducer Block
Discrete input
function block
PROFIBUS PA
measured values
The functions of the device are divided into blocks for different areas of responsibility.
They can be parameterized by acyclic data transfer via PDM
Block connection diagram for recording and processing measured values
Transducer Block (TB)
The Transducer Block carries out adjustments to the sensor. Its output value (Primary
Value) is the status of the switch that indicates whether the sensor is covered by the
medium or not.
The Transducer Block also carries out the required temperature measurement functions
and monitors the permitted temperature limits.
C: Profile structure
Discrete Input Function Block
In the Discrete Input Function Block, the Primary Value is processed further and is
adjusted to the automation task: that is, it looks after conversion, and
operations.
The output of this block supplies the measured value and the associated status
information to PROFIBUS PA.
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 85
Page 92
Parameters for local digital display
sensor
Sensor Value
%
Sensor Value discretePrimary Value
sensor
technology
logical switch
behavior
delay
Application
Range,
Lower Limit
Mode 19
Application
Range,
Upper Limit
Mode 20
Rise Time
Mode 4
Switch
Point 1
(Rising
Edge)
Mode 25
Switch
Point 2
(Falling
Edge)
Mode 26
Fall Time
Mode 5
Time
Time
0
0
1
1
The values of the following parameters from the measuring and function blocks can be
presented on the digital display. One of the options shown below must be selected in
Mode 13: Display Source (default: 0)
BlockParameterCan be displayed locally
Transducer Block Primary Valueyes
: see page 38.
Sensor Value discreteno
Sensor Valueyes
Transducer Block Electronics
temperature
Discrete Input Function BlockOutputyes
C: Profile structure
Description of the blocks
Transducer Block
The figure below shows the signal flow of measured values from the sensor through the
Transducer Block into the output value (Primary Value). The parameters of the individual
functions (switch behavior and delay) can be changed via acyclic access (SIMATIC
PDM).
Transducer Block function groups
Electronic temperature yes
Page 86Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 93
How it works:
The frequency value (represented in ’counts’1) is checked to see if it is within its
measuring limits. If the limit is exceeded, this results in a Bad status and the error
message Failure in measurement. The frequency value is stored in Sensor Value.
The analog signal from the sensor is transformed into a discrete signal which controls the
behavior of the switch point. The switch point is provided with a hysteresis.
A delay function provides the discrete signal with individual delay times for rising and
falling delay (Rise Time and Fall Time). The delay function acts as a filter that, for
example, compensates for a medium with an agitated surface. The result of this
smoothed signal is the Primary Value.
Electronics temperature
The Transducer Block also monitors the internal temperature of the device electronics. If
the temperature exceeds permitted limits, it does not change the sensor value, but it does
change the status. Permitted limits correspond to those of the permitted ambient
temperature for the electronics components. Temperatures in excess of these limits may
damage the components or cause them to become unstable.
If a temperature limit is exceeded, the status changes to GOOD – Active Critical Alarm –
Limit Overflow/Underflow. The status of the Sensor Value, the Sensor Value discrete, and
the Primary Value in the Transducer Block Discrete input, receive the status UNCERTAIN
– Value inaccurate. This action is accompanied by a PROFIBUS diagnostic message
Electronics temperature too high.
2
Drag indicators
occurred.
allow you to check the maximum and minimum temperatures that have
C: Profile structure
1.
See
Counts
2.
See
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 87
on page 73 for more detail.
Drag indicators (Peak indicators)
on page 69 for more detail.
Page 94
Discrete Input Function Block
Inversion
Fail
Safe
Logic
PROFIBUS
Cyclic Data
MAN
O/S
AUTO
Simulation
Val ue;
status
Simulation
Enable
Primar y Value
from
Tra nsdu cer
Block
1
OUT
via
PDM
via
PDM
The figure below shows how measured values are processed within the Discrete Input
Function Block.
Discrete Input Function Block function groups
C: Profile structure
How it works
The Discrete Input Function Block allows you to control modifications to the output value
(PROFIBUS cyclic data):
•Select Inversion ON or OFF: when ON, the Primary Value from the Transducer Block,
or a simulation value given by the simulation switch, will be inverted.
•Select Failsafe behavior options: if the status of the Primary Value or Simulation
Value is bad, the fault logic can output either the last usable measured value (Mode
22 = LUv), a given substitute value (0 or 1), or the last usable measure value with the
status Bad, sensor failure.
Page 88Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 95
Appendix D: Product Nameplates
Note: Information in boxes 1 through 7 changes based on customer order.
Pointek CLS200
D: Approvals
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 89
Page 96
Pointek CLS300
D: Approvals
Page 90Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 97
Appendix E: Hazardous Area Installation
WARNINGS:
• Turn off power before servicing any device.
• Please check the ambient and operating temperatures under
Environmental
configuration you are about to use or install.
• For intrinsically safe circuits, only certified current measuring devices
compatible with the transmitter may be used.
• In potentially explosive atmospheres:
- open the enclosure only when Pointek CLS200/300 is not
energized.
- if a transmitter is to be used as category 1/2 equipment, please
check the product nameplate, and see
Nameplates
• For intrinsically safe CLS200/300 models, power must be supplied from
an Intrinsically Safe power source, otherwise protection is no longer
guaranteed.
Note:
The transmitter is in operation when the power supply is switched on.
Instructions specific to hazardous area
on page 12, and
Process
on page 12 for the specific
Appendix D: Product
, page 89 onwards, to verify the protection type.
installations
(Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6)
The following instructions apply to equipment covered by certificate number KEMA
03ATEX1007X , KEMA 03ATEX1008X, KEMA 03ATEX1010X, KEMA 00ATEX2039X and KEMA
00ATEX2040X:
1.For use and assembly, refer to the main instructions.
2. The equipment is certified for use as Category 1G, 1/2G, 3G, 1/2D, 2D. Refer to appropriate
certificate.
3. Refer to appropriate certificate for application in specific hazardous environment.
4. Refer to appropriate certificate for ambient temperature range.
5. The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6. Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and EN 6007917 in Europe).
7. Repair of this equipment shall be carried out by suitably trained personnel in accordance
with the applicable code of practice (e.g. EN 60079-19 within Europe).
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 91
E: Hazardous areas
Page 98
8. Components to be incorporated into or used as replacements in the equipment shall be
fitted by suitably trained personnel in accordance with the manufacturer's
documentation.
9. The certificate numbers have an 'X' suffix, which indicates that special conditions for
safe use apply. Those installing or inspecting this equipment must have access to the
certificates.
10. If the equipment is likely to come into contact with aggressive substances, then it is the
responsibility of the user to take suitable precautions that prevent it from being adversely
affected, thus ensuring that the type of protection is not compromised.
Aggressive substances: e.g. acidic liquids or gases that may attack metals, or solvents
that may affect polymeric materials.
Suitable precautions: e.g. establishing from the material's data sheet that it is resistant to
specific chemicals.
Note: Please see www.siemens.com/pointek for the latest approval certificates.
Operating the CLS200 Intrinsically Safe
configuration in hazardous areas
ATEX
•Maximum permissible ambient temperature range in potentially explosive
atmospheres:
–40 °C to maximum +85 °C (–40 °F to maximum +185 °F ): T4
–40 °C to maximum +40 °C (–40 °F to maximum +104 °F): T6
•Maximum permissible process temperature range in potentially explosive
atmospheres:
–40 °C to maximum +125 °C (–40 ºF to maximum +257 ºF )
CSA/FM
•Installation shall be done according to drawing A5E01175715
(www.siemens.com/pointek).
•Maximum permissible ambient temperature range in potentially explosive
atmospheres:
–40 °C to maximum +85 °C (–40 ºF to maximum +185 ºF ): T4
E: Hazerdous areas
–40 °C to maximum +40 °C (–40 °F to maximum +104 °F): T6
•Maximum permissible process temperature range in potentially explosive
atmospheres:
–40 °C to maximum +125 °C (–40 ºF to maximum +257 ºF )
Page 92Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Page 99
Operating the CLS200 Flameproof / Explosion Proof
configuration in hazardous areas
ATEX
•Maximum permissible ambient temperature range in potentially explosive
atmospheres:
–40 °C to maximum +85 °C (–40 °F to maximum +185 °F): T4
–40 °C to maximum +85 °C (–40 °F to maximum +185 °F): T5
–40 °C to maximum +70 °C (–40 °F to maximum +158 °F): T6
•Maximum permissible process temperature range in potentially explosive
atmospheres:
For category II 1 G:
–20 ºC to maximum +60 °C (–4 ºF to maximum +140 ºF )
For category II 2 G:
–40 °C to maximum +125 °C (–40 °F to maximum +257 °F): T4
–40 °C to maximum +95 °C (–40 °F to maximum +203 °F): T5
–40 °C to maximum +80 °C (–40 °F to maximum +176 °F): T6
CSA/FM
•Maximum permissible ambient temperature range in potentially explosive
atmospheres:
–40 °C to maximum +85 °C (–40 ºF to maximum +185 ºF ): T4
–40 °C to maximum +40 °C (–40 °F to maximum +104 °F): T6
•Maximum permissible process temperature range in potentially explosive
atmospheres:
–40 °C to maximum +125 °C (–40 ºF to maximum +257 ºF )
Operating the CLS300 Intrinsically Safe
configuration in hazardous areas
ATEX
•Maximum permissible ambient temperature range in potentially explosive
atmospheres:
–40 °C to maximum +85 °C (–40 ºF to maximum +185ºF ): T4
–40 °C to maximum +40 °C (–40 °F to maximum +104 °F): T6
•Maximum permissible process temperature range in potentially explosive
atmospheres:
–40 °C to maximum +200 °C (–40 ºF to maximum +392 ºF )
–40 °C to maximum +400 °C (–40 ºF to maximum +752 ºF ):
high temperature version
CSA/FM
•Installation shall be done according to drawing A5E01175715
(www.siemens.com/pointek).
7ML19985JJ03Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS Page 93
E: Hazardous areas
Page 100
•Maximum permissible ambient temperature range in potentially explosive
atmospheres:
–40 °C to maximum +85 °C (–40 ºF to maximum 185 ºF ): T4
–40 °C to maximum +40 °C (–40 °F to maximum 104 °F): T6
•Maximum permissible process temperature range in potentially explosive
atmospheres:
–40 °C to maximum +200 °C (–40 ºF to maximum +392 ºF )
–40 °C to maximum +400 °C (–40 ºF to maximum +752 ºF ):
high temperature version
Operating the CLS300 Flameproof / explosion proof
configuration in hazardous areas
ATEX
•Maximum permissible ambient temperature range in potentially explosive
atmospheres:
–40 °C to maximum +85 °C (–40 °F to maximum +185 °F): T4
–40 °C to maximum +85 °C (–40 °F to maximum +185 °F): T5
–40 °C to maximum +70 °C (–40 °F to maximum +158 °F): T6
•Maximum permissible process temperature range in potentially explosive
atmospheres:
For category II 1 G:
–20 ºC to maximum +60 °C (–4 ºF to maximum +140 ºF )
For category II 2 G:
–40 °C to maximum +135 °C (–40 °F to maximum +275 °F): T4
–40 °C to maximum +100 °C (–40 °F to maximum +212 °F): T5
–40 °C to maximum +80 °C (–40 °F to maximum +176 °F): T6
CSA/FM
•Maximum permissible ambient temperature range in potentially explosive
atmospheres:
–40 °C to maximum +85 °C (–40 ºF to maximum +185 ºF ): T4
–40 °C to maximum +40 °C (–40 °F to maximum +104 °F): T6
•Maximum permissible process temperature range in potentially explosive
atmospheres:
–40 °C to maximum +200 °C (–40 ºF to maximum+ 392 ºF )
E: Hazerdous areas
–40 °C to maximum +400 °C (–40 ºF to maximum +752 ºF ):
high temperature version
Page 94Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS7ML19985JJ03
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.