Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of
others, and to protect the product and the connected equipment. These warning notices are
accompanied by a clarification of the level of caution to be observed.
Qualified Personnel: This device/system may only be set up and operated in conjunction with this
manual. Qualified personnel are only authorized to install and operate this equipment in accordance with
established safety practices and standards.
Unit Repair and Excluded Liability:
•The user is responsible for all changes and repairs made to the device by the user or the user’s
agent.
• All new components are to be provided by Siemens Milltronics Process Instruments Inc.
• Restrict repair to faulty components only.
• Do not reuse faulty components.
Warning: Cardboard shipping package provides limited humidity and moisture protection. This product
can only function properly and safely if it is correctly transported, stored, installed, set up, operated, and
maintained.
This product is intended for use in industrial areas. Operation of this equipment in a residential area
may cause interference to several frequency based communications.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2009. All Rights Reserved
This document is available in bound version and in
electronic version. We encourage users to purchase
authorized bound manuals, or to view electronic
versions as designed and authored by Siemens
Milltronics Process Instruments Inc. Siemens
Milltronics Process Instruments Inc. will not be
responsible for the contents of partial or whole
reproductions of either bound or electronic versions.
While we have verified the contents of this
manual for agreement with the instrumentation
described, variations remain possible. Thus we
cannot guarantee full agreement. The contents
of this manual are regularly reviewed and
corrections are included in subsequent editions.
Please check the website shown below for the
latest manual revisions.
We welcome all suggestions for improvement.
Technical data subject to change.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI Technical Publications European Authorized Representative
at the following address:
Technical Publications Siemens AG
Siemens Milltronics Process Instruments Inc. Industry Sector
1954 Technology Drive, P.O. Box 4225 76181 Karlsruhe
Peterborough, Ontario, Canada, K9J 7B1 Deutschland
Email: techpubs.smpi@siemens.com
•For a selection of Siemens Milltronics level measurement manuals, go to:
www. siemens.com/processautomation. Under Process Instrumentation, select
Measurement
•For a selection of Siemens Milltronics weighing manuals, go to:
www. siemens.com/processautomation. Under Weighing Technology, select
Index ..................................................................................................................................73
Table of Contents
iii
Page 6
Table o f C on t en t s
iv
Page 7
Safety Notes
Special attention must be paid to warnings and notes highlighted from the rest of the text
by grey boxes.
1
WARNING: relates to a caution symbol on the product, and means
that failure to observe the necessary precautions can result in
death, serious injury, and/or considerable material damage.
WARNING
1
: means that failure to observe the necessary
precautions can result in death, serious injury, and/or considerable
material damage.
CAUTION: means that failure to observe the necessary precautions can
result in considerable material damage.
Note:
means important information about the product or that part of the operating
manual.
Safety marking symbols
In manual On ProductDescription
Caution: refer to accompanying documents (manual) for
details.
Earth (ground) Terminal
Pointek CLS200/300
Protective Conductor Terminal
The Manual
Note: Please follow the installation and operating procedures for a quick, trouble-free
installation and to ensure the maximum accuracy and reliability of your Pointek CLS200/
300. This manual applies to the Pointek CLS200/300 Standard model only.
Pointek CLS200/300 is available in two models, standard and digital. For information on
the CLS200/300 digital model, please see manual 7ML19985JJ01.
This manual will help you set up your Pointek CLS200/300 Standard for optimum
performance.
Sections in this manual are designated as follows:
•
Pointek CLS200/300 Standard
model and to the manual
•
Specifications: standard model
•
Installation: Pointek CLS200 Standard
1.
This symbol is used when there is no corresponding caution symbol on the product.
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 1
- an introduction to Pointek CLS200/300 Standard
Page 8
•
Installation: Pointek CLS300 Standard
•
Appendix A: Technical References
•
Appendix B: Maintenance and Repairs
•
Appendix C: Product Nameplates
•
Appendix D: Hazardous Area Installation
•
Appendix E: Dimensions - CLS200
•
Appendix F: Dimensions - CLS300
•
Appendix G: Shortening the cable
We always welcome suggestions and comments about manual content, design, and
accessibility. Please direct your comments to techpubs.smpi@siemens.com.
For other Siemens Milltronics level measurement manuals, go to:
www.siemens.com/level
and look under Level Measurement.
Application Examples
The application examples used in this manual illustrate typical installations using
Pointek CLS200/300; other configurations may also apply.
Pointek CLS200/300
In all examples, substitute your own application details. If the examples do not apply to
your application, check the applicable parameter reference for the available options.
Technical Support
Support is available 24 hours a day.
To find your local Siemens Automation Office address, phone number and fax number go
to:
www.siemens.com/automation/partner
•Click on the tab Contacts by Product then drill down to find your product group
(+Process Automation > +Process Instrumentation > +Level Measuring
Instruments).
•Select the team Technical Suppo r t . Click on Next.
•Click on the appropriate continent, then select the country followed by the city.
Click on Next.
For on-line technical support go to:
www.siemens.com/automation/support-request
•Enter the device name or order number, then click on Search, and select the
appropriate product type. Click on Next.
•You will be prompted to enter a keyword describing your issue. Then either
browse the relevant documentation, or click on Next to email a detailed
description of your issue to Siemens Technical Support staff.
Page 2Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 9
Abbreviations and Identifications
Short formLong FormDescriptionUnits
CE / FM / CSA Conformitè Europèene / Factory
Mutual / Canadian Standards
Association
ε
r
ESDElectrostatic Discharge
ExExplosion Proofsafety approval
ExdFlame Proofmethod of protection
FEPFluorinated Ethylene Polymermodified polymer
FKM/FPMFluorelastomer
FFKM/FFPMPerfluoroelastomer
ISIntrinsically Safemethod of protection
LCDLiquid Crystal Display
LUILocal User Interface
μFmicro Farads10
μsmicro Seconds10
NCnormally closedrelay contact position
NOnormally openrelay contact position
pFpico Farads10
PDMProcess Device Managerconfiguration tool
PEEKPolyaryletheretherketoneorganic polymer
PPSPolyphenylene Sulfidepolymer
PTFEPolytetrafluoroethylenethermoplastic
PVDFPolyvinylidene Fluorideengineered
safety approval
relative dielectric
constant
for hazardous area
for hazardous area
-6
-6
-12
fluoropolymer
fluoropolymer
Pointek CLS200/300
Farad
Seconds
Farad
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 3
Page 10
Pointek CLS200/300 Standard
CLS200 Standard model
CLS300 Standard model
Notes:
• Pointek CLS200/300 is available in two models: the standard model, and the digital
model with integral local display. For information on the CLS200/300 Digital, please
see manual 7ML19985JJ01.
• Pointek CLS200/300 is to be used only in the manner outlined in this instruction
manual, otherwise protection provided by the equipment may be impaired.
• This product is intended for use in industrial areas. Operation of this equipment in a
residential area may cause interference to several frequency based
communications.
Pointek CLS200/300 is a versatile capacitance switch, ideal for level detection of
interfaces, solids, liquids, slurries, and foam, and for simple pump control. The switch
responds to the presence of any material with a relative dielectric constant of 1.5 or more
by detecting a change in capacitance, which is registered as a change in oscillating
Pointek CLS200/300
frequency.
The switch can be set to detect before contact or on contact with the probe. The design
of the CLS200 standard allows the instrument to operate independently of the tank wall or
pipe, so it does not require an external reference electrode for level detection in a nonconductive vessel such as concrete or plastic. The CLS300 standard requires a
connection to earth/ground for effective capacitance measurement.
The power supply is galvanically isolated and can accept voltages in the range 12 to
250 V AC/DC, depending on the application. The materials used in the probe construction
provide a high level of chemical resistance, and an excellent temperature rating on the
process wetted portion of the probe: up to 125 °C (257 °F) for the CLS200 and 400 °C
(752 °F) for the CLS300.
Page 4Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 11
Modular design and construction provide a wide choice of configurations, including rod,
cable, and sanitary versions. When used with a SensGuard protection cover, the CLS200
sensor is protected from shearing, impact, and abrasion, in tough primary processes.
Pointek CLS200/300 Applications
Pointek CLS200/300 is designed for level detection and simple pump control in a variety of
applications:
•Liquids, solids (powder and granules), slurries, interface detection (for example, oil/
water), and foam detection
•Foods and pharmaceuticals
•Chemical and petrochemical
•High pressure and temperature
Pointek CLS200/300 Features
•Potted construction protects components from shock, vibration, humidity, and/or
condensation
•High chemical resistance on probes
•Level detection independent of tank wall/pipe (CLS200 only)
•Freely programmable set up covers wide range of applications/materials
•Integrated Local User Interface (LUI) for ease of use
•Rigid and cable versions available
•Operation in safety related systems for overspill in accordance with
IEC61508/61511 SIL2
•Patented Active Shield minimizes the effect of product build-up at the sensor
mounting point (CLS300 only)
Pointek CLS200/300
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 5
Page 12
Specifications: standard model
Note: Siemens Milltronics makes every attempt to ensure the accuracy of these
specifications, but reserves the right to change them at any time.
Pointek CLS200/300
Power
• supply12 to 250 V AC/DC (0 to 60 Hz)
• power consumption2W max.
Performance
• Repeatability±1% of measurement
Interface
• configuration locally, using dip switches and potentiometers
• local display 3 LED indicators
• outputrelay contact and solid-state switch
• polarity-independentyes
• failsaferelay and solid-state switch can be de-energized in
the absence of a sensor signal
Alarm Outputs
Specifications: standard
• relay1 Form C (SPDT) contact (selectable NC or NO
contact)
max. switching voltage/current (DC): 30 V DC / 5 A
max. switching voltage/current (AC): 250 V AC / 8 A
(resistive load)
• solid-state switchrated 30 V DC or peak 30 V AC, 82 mA
• time delayON/OFF alarm, selectable
1 to 60 seconds duration
• hysteresisdependent on
• failsafe operationFailsafe High or Failsafe Low
• delay timers2: Alarm ON to OFF and Alarm OFF to ON
Page 6Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
ε
: max. 2 mm (0.08”) @ εr= 1.5
r
Page 13
Mechanical
Electrode - CLS200 Standard
Model
Rod5500 mm/
Sanitary 5500 mm/
Cable30 m/
Length
(max)
216.5”
216.5”
98.4 ft
Process Con-
nections
• Threaded:
¾”, 1", or 1 ½"
BSPT (R), BSPP
(G) or NPT; 1 ¼”
NPT only
• Welded flange:
ASME: 1”, 1 ½”, 2”,
3” or 4”
DN 25, 40, 50, 80
or 100
1", 1 ½ ", 2”, 2 ½"
and 3”sanitary
clamp
• Threaded:
¾ ", 1", or 1 ½"
BSPT (R), BSPP
(G) or NPT; 1 ¼”
NPT only
• Welded flange:
ASME: 1”, 1 ½”, 2”,
3” or 4”
DN 25, 40, 50, 80
or 100
1
Extension
316L¹ stain-
less steel
316L¹ stain-
less steel
FEP (Fluori-
nated Ethyl-
ene
Polymer)
Tensile
(max)
n/a
n/a
180 kg/
400 lbs
Wetted Parts
1
stainless
•316L
steel (optional
PFA coating)
• FKM seals
(optional FFKM)
• PPS probe
(optional PVDF)
1
stainless
•316L
steel
• FKM seals
(optional FFKM)
• PPS probe
(optional PVDF)
1
stainless
•316L
steel
• FEP jacketed
cable
• FKM seals
(optional FFKM)
• PPS probe
(optional PVDF)
Specifications: standard
1.
Or 1.4404 material.
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 7
Page 14
Electrode - CLS300 Standard
Model
Rod
(19 mm/
0.75” dia.)
Length
(max)
1000 mm/40”
Process Connec-
tions
• Threaded:
¾”, 1", or 1 ½" BSPT
(R), BSPP (G) or NPT;
1 ¼” NPT only
• Welded flange:
ASME: 1”, 1 ½”, 2”, 3” or
Tensile
(max)
n/a
Wetted Parts
1
stainless steel
• 316L
• FKM seals (optional
FFKM)
• PFA lining on Active
Shield
• PEEK isolators
4”
DN 25, 40, 50, 80 or
100
Cable25000 mm/
985”
• Threaded:
1 ½" BSPT (R), BSPP
(G) or NPT; 1 ¼” NPT
only
• Welded flange:
ASME: 1 ½”, 2”, 3” or
4”
DN 40, 50, 80 or 100
1900 kg/
4188 lbs
1
stainless steel
• 316L
Active Shield and
cable weight
1
stainless steel
• 316L
cable (optional PFA
jacketed cable)
• FKM seals (optional
FFKM)
• PEEK isolators
1
High Tem-
perature
version
1000 mm/40”
• Threaded:
¾”, 1", or 1 ½" BSPT
(R), BSPP (G) or NPT;
1 ¼” NPT only
n/a
stainless steel
• 316L
• Ceramic isolators
• Welded flange:
ASME: 1”, 1 ½”, 2”, 3” or
4”
Specifications: standard
DN 25, 40, 50, 80 or
100
Page 8Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Note: The use of approved watertight conduit hubs/glands is required for Type 4 /
NEMA 4, Type 6 / NEMA 6, IP68 (outdoor applications).
Weight
Weight varies based on configuration. For example:
• compact Pointek CLS200/300, 1 kg (2.20 lb.) approx.
100 mm (4”) insertion length,
3/4” process connection
Specifications: standard
Environmental
• locationindoor/outdoor
• altitude20 00 m (6562 ft.) max.
• ambient temperature
- general applications–40 to 85 °C (–40 to +185 °F)
- in potentially explosive
atmospheresrefer to appropriate certificate
• storage temperature–40 to 85 °C (–40 to +185 °F)
• relative humiditysuitable for outdoor (Type 4 / NEMA 4 / IP68)
• installation categoryII
• pollution degree4
1.
Or 1.4404 material.
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 9
Page 16
Process
Note: Please see
and
Pointek CLS300 Standard Pressure versus Temperature Curves
• relative dielectric constant (εr)1.5 minimum
• CLS200 temperature:
- without thermal isolator –40 to 85 °C (–40 to 185 °F)
- with thermal isolator–40 to 125 °C (–40 to 257 °F)
• CLS200 pressure (vessel):
- rod version–1 to 25 bar g/–14.6 to 365 psi g (nominal)
- cable version–1 to 10 bar g/–14.6 to 150 psi g (nominal)
- sliding coupling version–1 to 10 bar g/–14.6 to 150 psi g (nominal)
• CLS300 temperature:
- rod/cable version –40 to 85°C (–40 to 185°F)
without thermal isolator
- rod/cable version –40 to 200°C (–40 to 392 °F)
with thermal isolator
- high temperature version –40 to 400 °C (–40 to 752 °F)
• CLS300 pressure (vessel): –1 to 35 bar g/–14.6 to 511 psi g (nominal)
Pointek CLS200 Standard Pressure versus Temperature Curves
1
2
Approvals (verify against product nameplate)
CLS200
on page 35.
Specifications: standard
• General Purpose CSA, FM, CE, C-TICK
• Dust Ignition Proof ATEX II 1/2 D T100°C
• Dust Ignition Proof CSA/FM Class II, Div. 1, Gr. E, F, G
with IS ProbeCSA/FM Class III T4
• Explosion Proof Enclosure CSA/FM Class I, Div. 1, Gr. A, B, C, D
with IS ProbeCSA/FM Class II, Div. 1 Gr. E, F, G
CSA/FM Class III T4
• Flame Proof EnclosureATEX II 1/2 G EEx d[ia] IIC T6 to T4
with IS ProbeATEX II 1/2 D T100°C
• Marine Lloyds Register of Shipping, Categories ENV1,
ENV2 and ENV5
• Overfill ProtectionWHG (Germany)
• Others SIL/IEC61508 Declaration of Conformity
[SIL-2(overspill)]
Pattern Approval (China)
1.
at process connection
2.
at process connection
Page 10Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 17
CLS300
• General Purpose CSA, FM, CE, C-TICK
• Dust Ignition Proof CSA/FM Class II, Div. 1, Gr. E, F, G
with IS ProbeCSA/FM Class III T4
ATEX II 1/2 D T100°C
• Explosion Proof CSA/FM Class I, Div. 1, Gr. A, B, C, D
with IS ProbeCSA/FM Class II, Div. 1, Gr. E, F, G
CSA/FM Class III T4
• Flame Proof EnclosureATEX II 1/2G EEx d[ia] IIC T6 to T1
with IS ProbeATEX II 1/2 D T100°C
• Marine Lloyds Register of Shipping, Categories ENV1,
ENV2 and ENV5
• Overfill ProtectionWHG (Germany)
• OthersSIL/IEC61508 Declaration of Conformity
[SIL-2(overspill)],
Pattern Approval (China)
Specifications: standard
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 11
Page 18
Installation: Pointek CLS200 Standard
High level alarmLow level alarm
normal process
level
normal process
level
vertical
horizontal
Notes:
• Installation shall only be performed by qualified personnel and in accordance with
local governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
• The housing may only be opened for maintenance, local operation, or electrical
installation.
• Before installing the instrument, verify that the environment complies with any
restrictions specified on the product nameplate.
Location
Recommended:
•Provide a sun shield to protect the transmitter from direct heat radiation.
Precautions:
•Avoid mounting Pointek CLS200 in locations subject to strong vibrations in the
vicinity, whenever possible.
•Do not exceed the permissible ambient temperature limits (see
page 9 for details).
Environmental
on
Mounting
CLS200 Installation
Page 12Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Pointek CLS200 (compact threaded probe shown )
For high level alarm (level exceeds normal process level):
•normally mounted into the vessel top, or
•mounted through the tank wall at the detection level
For low level alarm (level drops below normal process level):
•mounted through the tank wall at the detection level
Page 19
Pointek CLS200 typical configuration with extensions:
Angle
High level alarmLow level alarm
normal process
level
normal process
level
50 mm (2") min
50 mm
(2")
min
In nozzle
Close to tank walls
> 100mm
(4") Ø
50 mm (2")
minimum
For high or low level alarm:
•designed for top mounting. The probe suspends vertically so that it reaches into
the process at the desired detection level (high or low detection alarm).
Mounting Restrictions
Note:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 100 mm (4") between them, to prevent
interference.
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 13
CLS200 Installation
Page 20
CLS200 Dimensions
Sensors must be at least 100 mm (4") apart.
Side View
100 mm
(4") min
100 mm
(4") min
100 mm
(4") min
End View
Mount diagonally if space is restricted
Multiple Units
Dimensions for all versions of the Pointek CLS200 Standard can be found in
Dimensions - CLS200
starting on page 47.
CLS200 Installation
Page 14Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Appendix E:
Page 21
Process Cautions
Cautions:
• The maximum allowable torque on a horizontally installed rod is 15 Nm.
• Keep unit out of path of falling material, or protect probe from falling material.
Caution: Tensile load must not exceed
probe or vessel rating (See
Tensile
(max)
on page 7.).
Caution: Avoid areas where material build up
occurs.
50 mm
(2") min
Caution: Consider material surface
configuration when installing unit.
CLS200 Installation
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 15
Page 22
Installation: Pointek CLS300 Standard
High level alarmLow level alarm
normal process
level
normal process
level
detection level
vertical
horizontal
Notes:
• Installation shall only be performed by qualified personnel and in accordance with
local governing regulations.
• This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
• The housing may only be opened for maintenance, local operation, or electrical
installation.
• Before installing the instrument, verify that the environment complies with any
restrictions specified on the product nameplate.
Location
Recommended:
•Provide a sun shield to protect the transmitter from direct heat radiation.
Precautions:
•Avoid mounting Pointek CLS300 Standard in locations subject to strong vibrations in
the vicinity, whenever possible.
•Do not exceed the permissible ambient temperature limits (see
page 9 for details).
Environmental
on
Mounting
Pointek CLS300 typical configuration:
For high level alarm (level exceeds normal process level):
•normally mounted into the vessel top, or
CLS300 Installation
Page 16Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
•mounted through the tank wall at the detection level
For low level alarm (level drops below normal process level):
•mounted through the tank wall at the detection level
Page 23
Angled mounting
Angle
500 mm
(20") min
500 mm
(20") min
500 mm
(20") min
Side View
(section)
Multiple Units
End View
Sensors must be 500 mm (20") apart.
Mount diagonally if space is restricted.
Pointek CLS300 cable version:
The cable version is designed for top mounting. The cable suspends vertically so that it
reaches into the process at the desired detection level (high or low detection alarm).
Mounting Restrictions
Note:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 500 mm (20") between them, to prevent
interference.
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 17
CLS300 Installation
Page 24
Process Cautions
Wall Restriction
50 mm
(2") min
50 mm
(2") min
• The maximum
allowable torque on a
horizontally installed
rod is 15 Nm.
• Keep unit out of path
of falling material, or
protect probe from
falling material.
• Consider material
surface configuration
when installing unit.
• Tensile load must not
exceed probe or
vessel rating.
500 mm
(20") min
CLS300 Installation
Page 18Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 25
Note: Buildup of material in Active Shield area does not affect switch operation.
CLS300 Dimensions
Dimensions for all versions of the Pointek CLS300 Standard can be found in
Dimensions - CLS300
starting on page 55.
Appendix F:
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 19
CLS300 Installation
Page 26
Wiring: Pointek CLS200/300 standard
WARNING: All field wiring must have insulation suitable for at least
250 V.
Notes:
Wiring: standard
•Only qualified personnel are authorized to install and operate this equipment in
accordance with established safety practices and standards.
•The Protective Earth Terminal indicated by must be connected to reliable
ground.
•All wiring must be done by qualified personnel in accordance with all governing
regulations.
•The equipment must be protected by a 15A fuse or circuit breaker in the building
installation.
•A circuit breaker or switch in the building installation, marked as a disconnect
switch, shall be in close proximity to the equipment and within easy reach of the
operator.
•Use shielded twisted pair cable, wire gauge 20 AWG to 14 AWG (0.5 mm
2.0 mm2).
•Maximum working voltage between adjacent relay contacts is 250 V.
•Relay contact terminals are for use with equipment which has no accessible live
parts and wiring which has insulation suitable for at least 250 V.
1.Loosen the lid clip and remove the lid to access the connectors and electronics. (For
quick reference, the diagram on the next page can also be found on the underside of
the lid, together with a guide to switch function).
2.Strip the cable jacket for approximately 70 mm (2.75") from the end of the cable, and
thread the wires through the gland.
3.Connect the wires to the terminals (polarity is not important).
4.Ground the instrument according to local regulations.
5.Tighten the gland to form a good seal.
6.If you wish to carry out a function test, follow the test procedures on page 23.
2
to
Page 20Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Page 27
Note: Switch and potentiometer settings are for illustration purposes only.
relay contact:
8 A @ 250 V AC, 2000 VA
5 A @ 30 V DC, 150 W
solid state switch:
30 V DC/30 V AC (peak),
82 mA max.
power supply
12 to 250 V AC/DC
power on
sensor
status
output
status
delay
sensor
switch bank
trip
point
red
black
white
The relay is shown in a de-energized/unpowered state.
K2 contact ratings:
•max. switching voltage/current (DC): 30 V DC / 5 A
•max. switching voltage/current (AC): 250 V AC / 8 A
•max. switching capacity: 150 W / 2000 VA
NCNO
COM
32 1
K2
Solid-state switch to customer's control or instrumentation device.
The switch is shown in de-energized/unpowered state.
K3 contact ratings:
•Maximum Voltage: 30 V DC or peak AC
•Maximum Current: 82 mA
•Non-polarized
2
1
K3
Relay Output Connection
Wiring: standard
Solid-state Switch
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 21
Page 28
Diode Protection
customer-supplied
diode protection
relay coil
customer-supplied
diode protection
relay coil
12
3
K4
12 to 250 V AC/DC
Connect protective earth wire to terminal provided in housing and marked with
When driving an external relay with either the solid-state switch and/or relay outputs
using DC power, protection diodes must be connected in the correct polarity across the
relay coil to prevent possible switch/relay damage resulting from inductive spikes
generated by the relay coil.
Wiring: standard
Power Connection
Nominal24 V DC48 V DC
V DC22 to 26 V46 to 50 V
R120 Ω234 Ω
Page 22Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Page 29
Functionality Test
1
2
34
5
switches shown in
OFF position
1122334 5
trip point
sensor
status
(yellow)
output
status
(red)
delay
O
F
F
/ROCKER DOWN
P2
P1
switch bank
L2
L1
L3
power
(green)
To test the basic functionality of the probe and potentiometers:
Preparation
1.Ensure green power light L3 is on.
2.Turn the delay potentiometer P1 and the trip point potentiometer P2 fully counterclockwise (minimum delay and minimum sensitivity respectively).
3.Set dip switches S1 to S4 OFF (full potentiometer control activated).
4.Set switch S5 ON (high sensitivity).
Test Procedures
Test the sensitivity of the sensor:
•Slowly turn the trip point potentiometer P2 clockwise until the yellow sensor status
light L1 glows. Shortly afterwards, the red output status light L3 will glow. This
concludes the sensitivity test.
Wiring: standard
Test the delay :
1.Turn the trip point potentiometer P2 fully counterclockwise (minimum sensitivity).
2.Turn the delay potentiometer P1 about 1/8 turn clockwise (delay set point).
3.Slowly turn the trip point potentiometer P2 clockwise until the yellow sensor status
light L1 glows. After an appropriate delay the red output status light L3 will glow.
This concludes the delay test.
Test the switch function:
1.Turn the delay potentiometer P1 and trip point potentiometer P2 fully counter clockwise (minimum delay and sensitivity respectively).
2.Slowly turn the trip point potentiometer P2 clockwise until the yellow sensor status
light glows.
3.Slightly turn the trip point potentiometer P2 counterclockwise until the yellow sensor
status light just stops glowing. Grasp the probe with your hand. The yellow sensor
status light L1 will glow, indicating switch function. After an appropriate delay the
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 23
red output status light L3 will glow. This concludes the switch function test.
Page 30
Operation: Pointek CLS200/300 standard
1
2
34
5
switches shown in
OFF position
1122334 5
trip point
sensor
status
(yellow)
output
status
(red)
delay
O
F
F
/ROCKER DOWN
P2
P1
switch bank
L2
L1
L3
power
(green)
model
User Interface
•A switch bank of five dip switches allows you to control the settings for Pointek CLS 200
(standard model).
•Three LEDs (L2, L1, and L3) indicate output status, sensor status, and power ON or
OFF.
•Two potentiometers (P1 and P2) adjust the alarm delay and trip point settings.
Operation: standard
Indicators
Three LEDs (L1, L2, and L3) indicate power status, sensor status, and alarm output status:
LED
status
sensor contacting, or very close to, process
Lit
material
(material capacitance greater than setpoint for P2)
sensor not contacting process material
Unlit
(material capacitance less than setpoint for P2)
Page 24Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Sensor status:
L1 (yellow)
Output status:
L2 (red)
alarm OFF
(relay energized/
switch closed)
alarm ON
(relay de-energized/
switch open)
Power status:
L3 (green)
power
ON
no power
Page 31
32
K2K3
L2
12 1
(unlit)
relay switch
32
K2K3
121
L2
(lit)
relay switch
32
K2K3
L2
12 1
(lit)
relay switch
32
K2K3
L2
121
(unlit)
relay switch
Alarm Output
The relay and solid-state switch are connected, and provide the alarm output:
Relay Solid-state switch Output status/Red LED
Alarm OFF energizedclosedlit
Alarm ONde-energizedopenunlit
Alarm Output Status
There are two alarm options:
ProbeRelay
Low
Alarm
High
Alarm
a.
The manual assumes that the pump should be turned off in the event of a failure. If
uncovered
(level too low)
covered
(level too high)
de-energized
de-energized
Solid-state
switch
a
open
a
open
Output status/
Red LED
unlit
unlit
this is not the case in your process, please see the relay schematic below, and make
the appropriate connections to suit your application.
Failsafe
The Failsafe function controls the response of Pointek CLS200/300 to a fault so that the
process will be put into a safe mode of operation. (See
Fault Signaling
on page 70 for
further details). Failsafe and Alarm mode are interconnected:
•High Alarm/Failsafe High
•Low Alarm/Failsafe Low
Relay and solid-state switch functionality
Alarm
Mode
Failsafe
High
Dip
Switch
S3
ON
Covered ProbeUncovered Probe
Operation: standard
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 25
Failsafe
Low
S3
OFF
Page 32
Switch Bank
1
2
34
5
Dip switches shown in OFF
(open) position.
delay: alarm deactivation
delay: alarm activation
failsafe/alarm
test delay settings
sensitivity (High or Low gain)
O
F
F
/ROCKER DOWN
4 dip switches (S1, S2, S3, and S5) control settings for the alarm output. The fifth dip
switch (S4) is used only to test the delay settings.
Failsafe/Alarm Setting: S3
•When Failsafe switch S3 is ON, it inverts the relay function, and the functioning of
Use the delay function to slow the response, and compensate for turbulence or false
readings.
•Delay potentiometer P1 can be adjusted to set a delay time from 1 to 60 seconds.
•Two separate delay settings are controlled by S1 and S2:
- for alarm activation (alarm ON)
- for alarm de-activation (alarm OFF)
•When switches are OFF (open) the delay is enabled.
•The position of Failsafe switch S3 determines how S1 and S2 function.
S3-ON High alarm/
overfill protection
S3-
Low alarm/dry run
OFF
Page 26Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
protection
S1-ON disables delay of alarm de-activation (alarm OFF)
S2-ON disables delay of alarm activation (alarm ON)
S1-ON disables delay of alarm activation (alarm ON)
S2-ON disables delay of alarm de-activation (alarm OFF)
Page 33
Sensitivity setting (high or low): S5
S5-ON High sensitivityUse this setting for measuring dry solids or non-
conductive liquids.
S5-OFF Low sensitivityUse this setting for measuring conductive liquids, or
viscous conductive solids that can build up on the sensor.
Test settings: S4
•When S4 is set to ON, it inverts the signal, allowing you to test the delay settings
from P1, or to verify that S1 and S2 are in the correct position.
S4-ON Enable testObserve the response of the output status and sensor
status LEDs to verify the delay interval set by
potentiometer P1.
S4-OFF Normal operation
Setup
WARNING: It is essential to check settings during the process itself,
and confirm that they are correct, before regular operation
commences.
Initial setup can be carried out prior to mounting into the process, but it is extremely
important to calibrate the unit and adjust the sensitivity on the product itself.
For a simple application, set Pointek CLS200/300 to Low alarm/no delays:
•turn P1 fully counter-clockwise (no delay interval)
•set dip switches S1, S2 and S5 to ON, S3 and S4 to OFF
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 27
• default setting
• for dry solids or non-conductive liquids
Page 34
Start Up
1122334 5
1
2
34
5
switches
trip
point
power
(green)
sensor
status
(yellow)
output
status
(red)
delay
Switches shown in OFF position.
P1
P2
L2
L1
L3
delay: alarm deactivation
delay: alarm activation
1
failsafe/alarm
1
test delay settings
sensitivity (High or
Low gain)
O
F
F
/ROCKER DOWN
After Pointek CLS200/300 is properly mounted and the switch bank is set up, apply power
to the unit. The green LED (L3) glows, indicating the unit is powered and operational.
Setpoint Adjustment.
Operation: standard
Use the potentiometers P1 and P2 to adjust the alarm setpoints. Follow the setup
procedure for the application that most closely describes your operation:
ApplicationMaterialSetup conditionsS5
General
Demanding
Interface
detection
1
•dry solids
• low viscosity liquids
• hygroscopic / wet solids
• high viscosity and high
conductivity liquids
• liquid A / liquid B
• foam / liquid
sensor uncovered;
min. 100 mm (4") free space all around
sensor immersed then uncovered; but
retaining max. possible material buildup
immerse sensor in whichever material
has lowest dielectric constant
ON
(high)
OFF
(low)
OFF
(low)
General applications (Failsafe Low, no delay)
Preparation
•Ensure that L3 (green) is lit.
•Turn the trip point and delay potentiometers P1 and P2 fully counterclockwise (to
minimum).
•Set dip switches S1 to S4 to OFF, and S5 to ON (high sensitivity)
Configuration
1.With sensor uncovered and a minimum 100 mm (4") free space all around, turn the
trip point potentiometer P2 clockwise until L1 (yellow) glows.
2.Turn P2 back (counterclockwise) until L1 stops glowing.
1.
When S3 is set to ON, it inverts the relay function, and the functioning of S1 and S2.
Page 28Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 35
Demanding applications (Failsafe Low, no delay, sensitivity adjusted for viscous, con-
ductive material)
Preparation
•Ensure that L3 (green) is lit.
•Turn the delay potentiometer P1 fully counterclockwise (to minimum).
•Turn trip point potentiometer P2 fully clockwise (to maximum).
•Set dip switches S1 to S4 to OFF (full potentiometer control).
•Set S5 to OFF (low sensitivity).
Configuration
1.Adjust the material level of the process so that the sensor is immersed: L1 (yellow)
should glow. If L1 does not glow, reset S5 to ON (high sensitivity) The appropriate
position of S5 depends on the dielectric properties of the material).
2.Adjust the material level of the process so that the sensor is uncovered, but retains
as much buildup of material as possible on the sensor.
3.Adjust trip point P2 counterclockwise until L1 stops glowing. To get the true feel for
the correct position, adjust P2 clockwise then counterclockwise several times to
ensure that L1 stops glowing. (This adjustment is very sensitive, and we recommend
repeating this exercise to finetune P2, until a very small adjustment causes L1 to
stop glowing.)
Interface detection (Failsafe Low, no delay, sensitivity adjusted to detect an inter-
•Turn trip point potentiometer P2 fully clockwise (to maximum).
•Set dip switches S1 to S4 to OFF (full potentiometer control).
•Set S5 to OFF (low sensitivity).
Configuration
1.Immerse the sensor in the material that has the lowest dielectric constant. L1 (yellow) should glow. If not, reset S5 to ON (high sensitivity).
2.Adjust P2 counterclockwise until L1 stops glowing.
3.Immerse the sensor in the material that has the highest dielectric constant. L1
should glow.
Delay alarm output
If you want to slow the Pointek CLS200/300 response, to compensate for turbulence or
false readings, set a delay interval using potentiometer P1, and set S1 and/or S2 to OFF, to
enable the delay for either alarm activation, alarm de-activation, or both.
If an immediate alarm output is critical, set the appropriate switch to ON, to disable the
delay.
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 29
Page 36
The functioning of S1 and S2 depends on the alarm setting:
Operation: standard
High alarm/
overfill protection
Low alarm/
dry run protection
To test the delay function, follow the test procedure on page 23.
S1-ON disables delay of alarm de-activation (alarm OFF)
S2-ON disables delay of alarm activation (alarm ON)
S1-ON disables delay of alarm activation (alarm ON)
S2-ON disables delay of alarm de-activation (alarm OFF)
Operation
After completing the setup, replace the lid and secure the lid clip. Pointek CLS200/300
standard model is now ready to operate.
Page 30Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 37
Troubleshooting: Pointek CLS200/300
standard model
SymptomObservationAction
No Alarm Response L3 (green) off.Check power supply voltage.
Alarm doesn't
switch when sensor
is uncovered.
Alarm doesn't
switch on when
sensor is covered.
L1 (yellow) doesn't respond
when sensor is uncovered.
L1 (yellow) responds when
sensor is uncovered.
L1 (yellow) doesn't respond
when sensor is covered.
L1 (yellow) responds when
sensor is covered.
L1 (yellow) flashes when
material level approaches the
alarm setpoint.
Check sensitivity switch S5.
Check that relay changes
state when S3 is toggled ON
and OFF.
Check sensitivity switch S5.
Troubleshooting: standard
Check that relay changes
state when S3 is toggled ON
and OFF.
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 31
Page 38
Appendix A: Technical References
dielectric = contents plus insulation (non-conductive contents)
dielectric = insulation (conductive contents)
(insulation)
p ro b e
sleeve
internal
vessel
wall
probe
dia. (d)
internal vessel dia. (D)
Operating Principles
In capacitance measurement1 inside a vessel or silo, the environment (typically, the
vessel wall) acts as the reference electrode of a variable capacitor, and the probe
supplies the measurement electrode. The dielectric
(air, vapor, liquid, solid, or a combination) and, if the measurement electrode is insulated,
the insulating layer.
The capacitance when the probe is uncovered (capacitance in air) will be different from
the capacitance when the probe is covered (for example, capacitance in water). If the
product is two immiscible liquids with different relative dielectric constants, (for example,
oil and water) the capacitance will change at the interface between the two liquids.
2
is composed of the vessel contents
High Frequency Oscillator
The Pointek CLS200/300 probe is equipped with a high frequency oscillator which
responds to the capacitance. The inverse of frequency is proportional to the capacitance.
A small change in capacitance results in a large change in frequency which is easy to
detect, resulting in high resolution and accuracy.
A: Technical References
Detection Range
The functional detection range depends on the relative dielectric constant of the material
monitored. The detection range will be shorter when the material has a lower relative
dielectric constant, and longer when it has a higher relative dielectric constant.
1.
For definitions relating to capacitance, see the glossary, page 71
2.
The relative dielectric constant of air (vacuum) is 1: all other materials have a higher value.
Page 32Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Page 39
See
R = Ca1 + Ca
2
Ca1 + Ca2 + Cm1 + Cm
2
Measuring
Circuit
R = Ratio between initial
capacitance and total
capacitance
Ca
1
= Initial capacitance of the
CLS200
Ca
2
= Initial capacitance (air)
between the probe and the
installation
Cm
1
= Capacitance increase of the
CLS200 caused by product
replacing air
Cm
2
= Capacitance increase
between the probe and the
installation caused by
product replacing air.
Ca
2
Cm
2
Cm
1
Ca
1
Specifications: standard model
, page 6, for performance information; also check the
product nameplate on the enclosure, for details of your particular instrument.
The Pointek CLS200 electrode
The Pointek CLS200 electrode is the primary sensor of the system. It supplies the
electrical capacitance value. The reference is the environment at the time of setup.
The design of the Pointek CLS200 probe makes it very sensitive to changes in
capacitance in the immediate vicinity of the antenna tip.
The initial capacitance of the CLS200 itself makes it possible to operate the CLS200 in a
plastic tank where the Ca
grounded metal tank will reduce the effects of external influences on the sensor.
The sensor can be set to detect either the change in capacitance as the product level
approaches the antenna tip, or the change when the probe becomes covered.
and Cm2 terms would disappear. However, a properly
2
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 33
A: Technical References
Page 40
The Pointek CLS300 electrode
Measuring
Circuit
Measuring
Circuit
Conventional Capacitance
Measurement
Pointek CLS300 with
Active Shield
C1
C2
C3
R = (C1 + C2 + C3) + Ca
(C1 + C2 + C3) + Ca + Cm
R = Ca
Ca + Cm
Ca
Ca
Cm
Cm
R = Ratio between initial
capacitance and total
capacitance
Ca = Initial capacitance (air)
Cm = Capacitance Increase
(product)
C1 = Capacitance connection
point
C2 = Capacitance connection
cable
C3 = Capacitance Process
connection (includes active
part)
The Pointek CLS300 electrode is the primary sensor of the system. It supplies the
electrical capacitance value.
The Pointek CLS300 patented Active Shield Technology electrically isolates the
measurement section and reduces the effect of any non-measurement capacitance on
the measurement capacitance. (Capacitance changes could result from uncontrolled
variations occurring in the connection cable, process connection, and non-active parts of
the probe.) This gives a better ratio of initial capacitance to total capacitance, resulting in
higher accuracy.
.
The measurement is further protected from interference by a buffer, which applies the
frequency signal from the measurement section to the Active Shield section. This effectively
A: Technical References
eliminates any electrical potential difference between the shield and the measurement
section and prevents additional changes in capacitance occurring, especially when
material builds up at the probe entrance to the tank.
Page 34Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Page 41
The relative lengths of the measurement section and Active Shield section can be
frequency (f) ≈K
capacitance (C)
Active
Shield
active
measurement
section
100%
0%
Poi nte k
CLS300
buffer
empty
tank
full
tank
atmospheric
P = permitted operating pressure
T = permitted operating temperature
specified to suit a particular application. If the measured range will be short relative to
the total length of the electrode, specify a short measurement section. This increases the
achievable resolution of the measurement, since any change in level will be greater
relative to the length of the measurement section.
The powder-coated aluminum enclosure provides reliable operation in environments with
dust, moisture, and high-frequency interference.
Pointek CLS200 Standard Pressure versus
Temperature Curves
CLS200 compact and extended rod versions, threaded
A: Technical References
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 35
Page 42
CLS200 cable version, threaded
atmospheric
P = permitted operating pressure
T = permitted operating temperature
atmospheric
P = permitted operating pressure
T = permitted operating temperature
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable fl ange class for the shaded area below.
CLS200 sanitary compact and extended rod versions
CLS200 compact and extended rod, ASME welded flange
A: Technical References
Page 36Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Page 43
CLS200 cable, ASME welded flange
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable fl ange class for the shaded area below.
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable fl ange class for the shaded area below.
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable fl ange class for the shaded area below.
CLS200 compact and extended rod, EN welded flange
CLS200 cable, EN welded flange
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 37
A: Technical References
Page 44
Pointek CLS300 Standard Pressure versus
atmospheric
P = permitted operating pressure
T = permitted operating temperature
Example: Permitted operating pressure = 30 bar
(435 psi) at 75 °C
atmospheric
P = permitted operating pressure
T = permitted operating temperature
Temperature Curves
CLS300 standard, extended rod and cable versions,
threaded
CLS300 high temperature rod version, threaded
A: Technical References
Page 38Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Page 45
CLS300 standard, extended rod and cable versions,
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable flange cl ass for the shaded area below.
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable flange cl ass for the shaded area below.
ASME welded flange
CLS300 high temperature rod version, ASME welded
flange
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 39
A: Technical References
Page 46
CLS300 standard, extended rod and cable versions, EN
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable flange cl ass for the shaded area below.
atmospheric
P = permitted operating pressure
T = permitted operating temperature
1) The curve denote the minimum allowable flange cl ass for the shaded area below.
welded flange
CLS300 high temperature rod version, EN welded flange
A: Technical References
Page 40Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Page 47
Appendix B: Maintenance and Repairs
Pointek CLS200/300 requires no maintenance or cleaning.
Unit Repair and Excluded Liability
All changes and repairs must be done by qualified personnel, and applicable safety
regulations must be followed. Please note the following:
•The user is responsible for all changes and repairs made to the device.
•All new components must be provided by Siemens Milltronics Process
Instruments Inc.
•Restrict repair to faulty components only.
•Do not re-use faulty components.
7ML19985JH01Pointek CLS200/30 0 Standard – INSTRUCTION MANUAL Page 41
B: Maintenance / Repairs
Page 48
Appendix C: Product Nameplates
Note: Information in boxes 1 through 7 changes based on customer order.
Pointek CLS200
C: Approvals
Page 42Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 49
Pointek CLS300
C: Approvals
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 43
Page 50
Appendix D: Hazardous Area Installation
WARNINGS:
• Turn off power before servicing any device.
• Please check the ambient and operating temperatures under
Environmental
configuration you are about to use or install.
• In potentially explosive atmospheres:
- open the enclosure only when Pointek CLS200/300 is not
energized.
- if a transmitter is to be used as category 1/2 equipment, please
check the product nameplate, and see
Nameplates
Note:
The transmitter is in operation when the power supply is switched on.
D: Hazerdous areas
Instructions specific to hazardous area
installations
(Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6)
The following instructions apply to equipment covered by certificate number KEMA
00ATEX2039X and KEMA 00ATEX2040X:
1.For use and assembly, refer to the main instructions.
2.The equipment is certified for use as Category 1/2G, 1/2D. Refer to appropriate
certificate.
3.Refer to appropriate certificate for application in specific hazardous environment.
4.Refer to appropriate certificate for ambient temperature range.
5.The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6.Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and
EN 60079-17 in Europe).
7.Repair of this equipment shall be carried out by suitably trained personnel in
accordance with the applicable code of practice (e.g. EN 60079-19 within Europe).
8.Components to be incorporated into or used as replacements in the equipment shall
be fitted by suitably trained personnel in accordance with the manufacturer's
documentation.
9.The certificate numbers have an 'X' suffix, which indicates that special conditions
for safe use apply. Those installing or inspecting this equipment must have access
to the certificates.
10. If the equipment is likely to come into contact with aggressive substances, then it is
the responsibility of the user to take suitable precautions that prevent it from being
adversely affected, thus ensuring that the type of protection is not compromised.
on page 9, and
Process
on page 10 for the specific
Appendix C: Product
, page 42 onwards, to verify the protection type.
Aggressive substances: e.g. acidic liquids or gases that may attack metals, or
solvents that may affect polymeric materials.
Page 44Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Page 51
Suitable precautions: e.g. establishing from the material's data sheet that it is
resistant to specific chemicals.
Note: Please see www.siemens.com/pointek for the latest approval certificates.
Operating the CLS200 Flameproof / Explosion Proof configuration in
hazardous areas
ATEX
Maximum permissible ambient temperature range in potentially explosive
atmospheres:
For category II 1 G:
–20 ºC to maximum +60 °C (–4 ºF to maximum +140 ºF )
For category II 2 G:
–40 °C to maximum +85 °C (–40 °F to maximum +185 °F): T4
–40 °C to maximum +85 °C (–40 °F to maximum +185 °F): T5
–40 °C to maximum +70 °C (–40 °F to maximum +158 °F): T6
•Maximum permissible process temperature range in potentially explosive
atmospheres:
For category II 1 G:
–20 ºC to maximum +60 °C (–4 ºF to maximum +140 ºF )
For category II 2 G:
–40 °C to maximum +125 °C (–40 °F to maximum +257 °F): T4
–40 °C to maximum +95 °C (–40 °F to maximum +203 °F): T5
–40 °C to maximum +80 °C (–40 °F to maximum +176 °F): T6
D: Hazardous areas
CSA/FM
•Maximum permissible ambient temperature range in potentially explosive
atmospheres:
–40 °C to maximum +85 °C (–40 ºF to maximum +185 ºF ): T4
•Maximum permissible process temperature range in potentially explosive
atmospheres:
–40 °C to maximum +125 °C (–40 ºF to maximum +257 ºF )
Operating the CLS300 Flameproof / explosion proof configuration in
hazardous areas
ATEX
Maximum permissible ambient temperature range in potentially explosive
atmospheres:
For category II 1 G:
–20 ºC to maximum +60 ºC (–4 ºF to maximum +140 ºF)
For category II 1 G:
–40 ºC to maximum +85 ºC (–40 ºF to maximum +185 ºF): T1
–40 ºC to maximum +85 ºC (–40 ºF to maximum +185 ºF): T2
–40 ºC to maximum +85 ºC (–40 ºF to maximum +185 ºF): T3
–40 ºC to maximum +85 ºC (–40 ºF to maximum +185 ºF): T4
–40 ºC to maximum +85 ºC (–40 ºF to maximum +185 ºF): T5
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 45
Page 52
D: Hazerdous areas
–40 ºC to maximum +70 ºC (–40 ºF to maximum +158 ºF): T6
•Maximum permissible process temperature range in potentially explosive
atmospheres:
For category II 1 G:
–20 ºC to maximum +60 ºC (–4 ºF to maximum +140 ºF)
For category II 2 G:
–40 ºC to maximum +400 ºC (–40 ºF to maximum +752 ºF): T1
–40 ºC to maximum +300 ºC (–40 ºF to maximum +572 ºF): T2
–40 ºC to maximum +200 ºC (–40 ºF to maximum +392 ºF): T3
–40 ºC to maximum +135 ºC (–40 ºF to maximum +275 ºF): T4
–40 ºC to maximum +100 ºC (–40 ºF to maximum +212 ºF): T5
–40 ºC to maximum +80 ºC (–40 ºF to maximum +176 ºF): T6
CSA/FM
•Maximum permissible ambient temperature range in potentially explosive
atmospheres:
–40 °C to maximum +85 °C (–40 ºF to maximum +185 ºF ): T4
•Maximum permissible process temperature range in potentially explosive
atmospheres:
–40 °C to maximum +200 °C (–40 ºF to maximum+ 392 ºF )
–40 °C to maximum +400 °C (–40 ºF to maximum +752 ºF ):
high temperature version
Page 46Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Page 53
Appendix E: Dimensions - CLS200
2 cable entries
½" NPT or M20x1.5
M20: 135 mm (5.32")
½" NPT: 150 mm (5.91")
thermal
isolator
150 mm
(5.91")
272 mm
(10.83")
120 mm
(4.7")
22 mm
(0.87")
PPS or optional
PVDF probe
electronics/
enclosure
Enclosure, threaded process connection
H: CLS200 Dimensions
Compact Version, threaded
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 47
Page 54
Extended Rod Version, threaded
316L stainless steel
extension
Ø 20 mm (0.79")
PPS or optional
PVDF probe
84 mm
(3.3")
Y01 (insertion length)
Min. insertion length = 200 mm (7.87")
Max. insertion length = 5500 mm (216")
98 mm
(3.80")
316L stainless steel
sanitary process connection
PPS or optional
PVDF probe
Sanitary Compact Version
H: CLS200 Dimensions
Page 48 Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 55
Sanitary Extended Version
316L stainless steel
sanitary process connection
316L stainless steel
extension
Ø 24 mm
(0.95")
PPS or optional
PVDF probe
98 mm
(3.80")
Y01 (insertion length)
Min. insertion length = 110 mm (4.3")
Max. insertion length = 5500 mm (216")
H: CLS200 Dimensions
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 49
Page 56
Sliding Coupling Version, threaded
316L stainless steel
sliding coupling
Ø 20 mm (0.79")
PPS or optional
PVDF probe
Y01
(insertion length)
min. 215 mm
(8.46")
84 mm
(3.3")
Min. insertion length = 350 mm (13.82")
Max. insertion length = 5500 mm (216")
H: CLS200 Dimensions
Page 50 Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 57
Extended Cable Version, threaded
FEP insulated cable
Ø 6 mm (0.3")
316L stainless steel
sensor weight
Ø 20 mm (0.79")
PPS or optional
PVDF probe
Y01
(insertion length)
84 mm
(3.3")
Min. insertion length = 500 mm (19.69")
Max. insertion length = 35000 mm (1378")
Applicable for liquids and solids applications.
Cable can be shortened on site.
H: CLS200 Dimensions
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 51
Page 58
CLS200 - Flanged Process Connections
2 cable entries
½" NPT or M20x1.5
M20: 135 mm (5.32")
½" NPT: 150 mm (5.91")
thermal isolator
165 mm
(6.50")
290 mm
(11.42")
Flange Facing Table
H: CLS200 Dimensions
Flange Facing (raised face)
Flange ClassFacing thickness
ASME150/3002 mm (0.08")
ASME600/9007 mm (0.28")
PN16/402 mm (0.08")
Page 52 Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 59
Compact Version, welded flange
PPS or optional
PVDF probe
98 mm
(3.8")
electronics/
enclosure
316L stainless steel
extension
Ø 20 mm
(0.79")
PPS or optional
PVDF probe
84 mm
(3.3")
Y01 (insertion length)
Min. insertion length = 200 mm (7.87")
Max. insertion length = 5500 mm (216")
Extended Rod Version, welded flange
H: CLS200 Dimensions
7ML19985JH01 Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 53
Page 60
Extended Cable Version, welded flange
FEP insulated cable
Ø 6 mm (0.3")
316L stainless steel
sensor weight
Ø 20 mm (0.79")
PPS or optional
PVDF probe
Y01
(insertion length)
84 mm
(3.3")
Applicable for liquids and solids applications.
Cable can be shortened on site.
Min. insertion length = 500 mm (19.69")
Max. insertion length = 30000 mm (1181")
H: CLS200 Dimensions
Page 54 Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 61
Appendix F: Dimensions - CLS300
2 cable entries
½" NPT or M20x1.5
M20: 135 mm (5.32")
½" NPT: 150 mm (5.91")
thermal isolator
165 mm
(6.50")
290 mm
(11.42")
Threaded Processs Connection
7ML19985JH01 Pointek CL200/300 Standard – INSTRUCTION MANUALPage 55
F: CLS300 Dimensions
Page 62
Rod Version, threaded
lid
lid clip
electronics/
enclosure
20 mm
(0.79")
Y02
1
measuring
length
Y01 (insertion length)
min = 350 mm (14")
max. = 1000 mm (39.37")
probe
Ø 19 mm (0.75")
1
Extended Active Shield (Y02):
standard length 125 mm (4.92")
Optional Active Shield lengths:
250 mm (9.84") or 400 mm (15.75"
F: CLS300 Dimensions
Page 56 Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 63
High Temperature Rod Version, threaded
Ceramic insulator(s)
Thermal isolator
Ø 19 mm (0.75")
probe
Y01 (insertion length)
min. = 350 mm (14")
max. = 1000 mm (39")
Y02
1
1
Extended Active Shield (Y02):
standard length 125 mm (4.92")
Optional Active Shield lengths:
250 mm (9.84") or 400 mm (15.75")
measuring
length
7ML19985JH01 Pointek CL200/300 Standard – INSTRUCTION MANUALPage 57
F: CLS300 Dimensions
Page 64
Non-insulated Cable Version, threaded
Ø 32 mm (1.26")
stainless steel
cable
Y01 (insertion length)
min. = 1000 mm (40")
max. = 25000 mm (984")
Y02
1
1
Extended Active Shield (Y02):
standard length 125 mm (4.92")
Optional Active Shield lengths:
250 mm (9.84") or 400 mm (15.75")
measuring
length
Ø 6 mm (0.24")
stainless steel
weight
250 mm
(9.84")
F: CLS300 Dimensions
Page 58 Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 65
Insulated Cable Version, threaded
Ø 32 mm (1.26")
PFA
insulated cable
Y01 (insertion length)
min. = 100 0 mm (40")
max. = 25000 mm (984")
Y02
1
1
Extended Active Shield (Y02):
standard length 125 mm (4.92")
Optional Active Shield lengths:
250 mm (9.84") or 400 mm (15.75")
measuring
length
Ø 10 mm (0.35")
stainless steel weight
250 mm
(9.84")
7ML19985JH01 Pointek CL200/300 Standard – INSTRUCTION MANUALPage 59
F: CLS300 Dimensions
Page 66
CLS300 - Flanged Process Connections
2 cable entries
½" NPT or M20x1.5
M20: 135 mm (5.32")
½" NPT: 150 mm (5.91")
thermal isolator
165 mm
(6.50")
290 mm
(11.42")
Flange Facing Table
ASME150/3002 mm (0.08")
ASME600/9007 mm (0.28")
PN16/402 mm (0.08")
F: CLS300 Dimensions
Page 60 Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Flange Facing (raised face)
Flange ClassFacing thickness
Page 67
Y01 (insertion length)
min. = 250 mm (9.8")
max. = 1000 mm (39.37")
measuring
length
Active
Shield
Ø 19 mm (0.75")
probe
electronics/
enclosure
lid
lid clip
Rod Version, welded flange
7ML19985JH01 Pointek CL200/300 Standard – INSTRUCTION MANUALPage 61
F: CLS300 Dimensions
Page 68
High Temperature Rod Version, welded flange
Y01 (insertion length)
min. = 250 mm (9.8")
max. = 1000 mm (39.37")
measuring
length
Y02
1
Ø 19 mm (0.75")
probe
Ceramic insulator(s)
Thermal isolator
1
Extended Active Shield (Y02):
standard length 105 mm (4.13")
Optional Active Shield lengths:
230 mm (9.06") or 380 mm (14.96")
F: CLS300 Dimensions
Page 62 Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 69
Non-insulated Cable Version, welded flange
Y012 (insertion length)
min. = 1000 mm (39.37")
max. = 2500 0 mm (984")
measuring
length
Y02
1
Ø 32 mm (1.26")
stainless steel
cable
Ø 6 mm (0.24")
stainless steel
weight
1
Extended Active Shield (Y02):
standard length 105 mm (4.13")
Optional Active Shield lengths:
230 mm (9.06") or 380 mm (14.96")
2
Insertion length does not include
any raised face/gasket face
dimension (see the
Flange Facing
Ta bl e
on page 60).
250 mm
(9.84")
7ML19985JH01 Pointek CL200/300 Standard – INSTRUCTION MANUALPage 63
F: CLS300 Dimensions
Page 70
Insulated Cable Version, welded flange
Ø 32 mm (1.26")
PFA
insulated cable
Y012 (insertion length)
min. = 1000 mm (39.37")
max. = 25000 mm (984")
Y02
1
Notes:
1
Extended Active Shield (Y02): standard
length 105 mm (4.13")
Optional Active Shield lengths:
230 mm (9.06") or 380 mm (14.96")
2
Insertion length does not include any
raised face/gasket face dimension (see
Flange Facing Table
on page 60).
measuring
length
Ø 10 mm (0.35")
stainless steel
weight
250 mm
(9.84")
F: CLS300 Dimensions
Page 64 Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01
Page 71
Appendix G: Shortening the cable
actual
length
excess
length
required
length
cable gland
compression nut
probe, lower
assembly
probe sleeve
Pointek CLS200 Standard, Cable Version
CAUTION: Possible only with the general purpose configuration; please verify against
product nameplate.
Preparation
Determine the required cable length, and subtract that amount from the actual length, to
find the excess length to cut off.
For example: 10 m (actual length) minus 9 m (required length) = 1 m (excess)
Steps
1.Unscrew the cable gland compression nut to relieve the sealing cone and release
the cable.
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 65
G: Cable Modifications
Page 72
2.Unscrew the probe sleeve from the lower assembly using two 17 mm (0.67")
flat
surface
flat
surface
lower
wrench
tension block
9.5 mm (0.37") heat
shrink insulation
steel spacer
lead
cable core
wrenches across the flat surfaces, as shown below.
a. Place two wrenches on the flat surfaces of the
probe as shown: hold the probe sleeve still, and turn the
lower wrench counter-clockwise to loosen the probe
lower assembly.
b. Remove the lower assembly by turning the threaded
electrode end counter-clockwise: this exposes the three
leads, the tension block, and the steel spacer.
3.Remove the heat shrink insulation covering the solder connections.
G: Cable Modifications
4.Unsolder the connections.
Note: Do not cut the connections to the probe leads, as this can render them too short
to work with later.
5.Remove the tension block, and save it for re-use in step 7.
6.Calculate the excess cable, then add back an allowance of 75 mm (3") for making the
connections:
For example, 1000 mm = excess
less 75 mm
925 mm= excess cable to be removed
7.Cut off the excess cable.
Page 66Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
= allowance for connections
Page 73
Caution: To prevent wires from being pulled through the cable bundle, secure each
40 mm
(1.57")
core
tension
block
steel
spacer
wire close to where the outer black jacket stops prior to stripping cable insulation from
it.
8.Remove approximately 75 mm (3") of cable jacket, shield, and filler strands.
9.Cut off the excess cable core, making sure the cut is clean and square
10. Replace the steel spacer and tension block, then shorten the leads to approximately
40 mm (1.6").
11. Prepare the leads for soldering, and if heat shrink is used to insulate splices,
remember to slip on the heat shrink before soldering the leads.
12. Make the solder connections and position the heat shrink to completely insulate
each solder connection before shrinking it.
13. Remove any excess cable core, if necessary.
14. Apply PTFE type tape/sealant to all threads.
15. Add a pre-twist to the wires before screwing the probe sleeve and lower probe
assembly together: hold the probe sleeve still, and gently turn the lower probe
assembly counter-clockwise about 5 full turns. This avoids the wires being broken
when the probe and probe sleeve are assembled.
16. Screw the lower probe assembly clockwise into the probe sleeve, and tighten it with
a 17 mm (0.67") wrench.
17. Check that the instrument is operating correctly, using the test procedure on
page 23.
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUAL Page 67
G: Cable Modifications
Page 74
Pointek CLS300 Standard, Cable Version
cable
weight
Caution: When shortening a PFA cable, be sure to take extra care not to damage the
PFA coating.
Methods
1.An angle grinder (preferably with a disc suitable for stainless steel)
or
2.Wire cutters (suitable for piano cable
Procedure
1.Loosen the three set screws and pull weight from the cable.
2.Grind/cut the cable to the required length, and then remove rough edges from the
cable.
3.Ensure that cable strands are properly seated in the lay of the cable (i.e. no wire
strands sticking outside the normal cable profile). Make sure ALL strands are
properly seated before continuing the assembly.
4.Push the weight onto the cable while simultaneously rotating it counter-clockwise
around the cable. Make sure that no cable strands are pushed out of their position
in the cable and that the cable is fully inserted.
5.Re-fasten the weight by tightening the three set screws.
Ø 6 to 9 mm).
G: Cable Modifications
Page 68Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Page 75
Appendix H: Application for Pointek
CLS200/300 Standard
Level Detection
Note:
• For a more detailed explanation, please see
• For more detailed instructions on setting the dip switches and potentiometers,
please see
The difference in capacitance between a covered probe and an uncovered probe (for
example, between a probe in water and a probe in air), is used to detect level, and to
protect the process from a level that is either too high or too low.
The trip point is set by potentiometer P2. This determines how large the difference in
capacitance needs to be before the output is switched. Dip switch 5 allows you to adjust
the sensitivity. The sensitive electronics can be set to detect the change in capacitance
either as the level approaches the probe tip, or when the probe is covered.
Operation: Pointek CLS200/300 standard model
Alarm Signaling
Relay and Solid-state Switch
The relay and solid-state switch are interlinked: when the change in capacitance is
greater than the setting at the trip point, the output switches. (For a diagram illustrating
the relay and solid-state switch contacts, see page 25.)
Operating Principles
from page 24 onwards.
on page 32.
Appendix H: Application
RelayRed LEDSolid-state switchAlarm state
EnergizedOnClosedOFF
De-energizedOffOpenON
Alarm settings
The alarm can be set to protect the process from a level that is either too high or too low.
Overfill Protection =
Failsafe High
alarm state
normal state
•high alarm:alarm ON/switch open when level is higher than the set point
(probe becomes covered
•low alarm:alarm ON/switch open when level is below the set point (probe
becomes uncovered)
The setting is selected by turning dip switch 3 on or off.
1.
Or, if the trip point is set to detect the approaching level, when that trip point is reached.
Page 69Pointek CLS200/300 Standard – INSTRUCTION MANUAL 7ML19985JH01
Dry Run Protection =
normal state
alarm state
1
)
Failsafe Low
Page 76
Fault Signaling
The Failsafe function puts the process into a safe mode of operation in the event of a fault
or failure (such as a loss of power). When the Pointek CLS200/300 standard model
responds to a failure, the output switches according to the Failsafe setting
two Failsafe options:
Appendix H: Application
Note: The following examples assume that the pump should be turned off in the event
of a failure. If this is not the case in your process, please see the relay diagram on
page 25, and make the appropriate connections to suit your application.
Failsafe High is used in applications where Pointek CLS200/300 is set to turn off a pump
when the level becomes too high (probe covered, or level too close to probe). When
Failsafe High is selected, the device will respond to a failure (regardless of the true level)
as if it were a high level alarm (alarm ON/solid-state switch open). The pump will stop,
preventing an overfill.
Failsafe Low is used in applications where CLS200/300 is set to turn off a pump when the
level becomes too low (probe uncovered). When Failsafe Low is selected, CLS200/30 0 will
respond to a failure (regardless of the true level) as if it were a low level (alarm ON/solidstate switch open). The pump will stop, preventing the pump from running dry.
7ML19985JH01Pointek CLS200/300 Standard – INSTRUCTION MANUALPage 70
Page 77
Glossary
capacitance: the property of a system of conductors and dielectrics that permits the storage of
electricity when potential differences exist between the conductors. Its value is
expressed as the ratio of a quantity of electricity to a potential difference, and the unit is a
Farad.
capacitor: a device in a circuit that has the potential to store an electric charge. Typically a
capacitor has 2 conductors or electrodes separated by a layer of a nonconducting
material called a dielectric. With the conductors on opposite sides of the dielectric layer
oppositely charged by a source of voltage, the electrical energy of the charged system is
stored in the polarized dielectric.
derating: to decrease a rating suitable for normal conditions according to guidelines specified
for different conditions.
Glossary
dielectric: a nonconductor of electric current.
relative dielectric constant: the ability of a dielectric to store electrical potential energy under
the influence of an electric field. This is measured by the ratio of the capacitance of a
condenser with the material as dielectric to its capacitance with vacuum as dielectric.
The value is given relative to a vacuum /dry air: the relative dielectric constant of air is 1
immiscible: incapable of mixing or attaining homogeneity.
implicit: for example in “the units are implicit in pF”, the units are implied, or assumed to be pF,
because there is no other option.
miscible: capable of being mixed.
repeatability: the closeness of agreement among repeated measurements of the same
variable under the same conditions.
saturation: a condition in which any further change of input no longer results in a change of
output. For example, “the loop-current will saturate to 3.8 or 20.5 if the level exceeds the
Range settings”.
solid-state device: a device whose function is performed by semi-conductors or the use of
otherwise completely static components such as resistors and capacitors.
stilling-well: a grounded metal tube with openings.
1
1
.
1.
Many conductive liquids/electrolytes exhibit dielectric properties; the relative
dielectric constant of water is 80.
7ML19985JH01Pointek CLS200/30 0 Standard – INSTRUCTION MANUALPage 71
Page 78
Glossary
Notes
Page 72Pointek CLS200/300 Standard – INSTRUCTION MANUAL7ML19985JH01