Siemens PMI, PMI-REM, PMI-INTL Installation Instructions Manual

Page 1
Installation Instruct ions Models PMI / PMI-REM / PMI-INTL
Person-Machine Interface
INTRODUCTION The SIEMENS Model PMI/PMI-REM/PMI-INTL is the user interface for the FireFinder-
XLS™ system. From the PMI/PMI-REM/PMI-INTL the operator can acknowledge events, control the system notification appliance circuits and reset the system. Detailed information about the nature and location of events can also be displayed.
The PMI is used as the primary user interface in CAB1, CAB2 or CAB3 enclosures. The PMI-REM is used as a remote user interface in REMBOX2 and REMBOX4 enclosures. The PMI-INTL is used as the primary or remote user interface in applications where French, Spanish
ALARM
SUPERVISORY
SECURITY
TROUBLE
....
or Portuguese is the primary language. They are identical in all other ways, and will be referred to in the remainder of this document as PMI.
POWER
ON
AUDIBLES
SILENCED
PARTIALSYSTEM DISABLED
10:32:05 04/15/01 SYSTEM STATUS: NORMAL
FireFinder-XLS
Siemens - Fire Safety
More Info
+
_
The PMI contains the site specific program as developed in Zeus. All system logic and supervision is provided by the controller in the PMI.
The PMI contains a ¼ VGA monochrome LCD, Touch Screen and LEDs for displaying system status. An audible sounds when there are unac­knowledged events on the PMI. The display is surrounded by keys that are used to control the displayed information and to navigate through
?
these screens. Keys are also provided to obtain help and to enter into the menu features of the PMI. (Refer to Figure 1.)
On the back of the PMI there are additional diagnostic displays to aid in system troubleshooting. This is also where the PMI address is set and where the connection is made to Zeus for programming. (Refer to Figure 2.)
A contrast pot is provided on the back of the PMI to adjust the LCD for
Figure 1
the best visibility.
PMI User Interface
For systems configured to provide Smoke Controk (UUKL), refer to the FireFinder XLS Control Panel System Manual, P/N 315-034853.
PRE-INSTALLATION The PMI-INTL comes with French (Canadian) labels applied to the PMI. Labels in
three additional languages are also shipped with the PMI-INTL. To apply the labels for an alternate language, first remove the French (Canadian) labels. Then select the appropriate label—either English, Spanish, or Portuguese (Brazilian), from the Power label kit, P/N 575-434249 and the Alarm label kit, P/N 575-434218. Remove the backing from the labels and apply them to the PMI. (Refer to Figure 3.) Discard the remaining labels.
P/N 315-033070-4
Siemens Building Siemens Building
Siemens Building
Siemens Building Siemens Building
TT
ecec
hnologieshnologies
T
ec
hnologies
TT
ecec
hnologieshnologies
Fire S
afetyafety
afety
afetyafety
Page 2
D19
A
C
FAIL
PMI-DAC
XNET
HNET
JP9
1
4
PMI
4218
0
1
9
2
8
3
7
4
6
5
C
S16
ADDRESS
4218C4218
0
1
9
2
8
3
7
4
6
5
C
S14
0
1
9
2
8
3
7
4
6
5
S11
ON
OPTIONS
S17
1
1
32
4
56
STATUS
U10
S2
23
10
1
S1
TP1
EARTHGND
9
10
J2
1
R61
1
JP7
2
JP5
11
5
J1
5
JP4
9
5
1
10 2
NIM-1M
RESET
CONTRAST
6
DEBUG
9
UPLOADHNET
D42
D23
D20
SCITSONGAIDIMPFONOITPIRCSED
TENH.detcetedsikrowtenTENHehtnoeruliafanehwydaetsswolgDEL
Figure 2 PMI Diagnostics
ED.ylnoesuyrotcaF
APPLY APPROPRIATE
ALARM
LABEL
(P/N 575-434218) HERE
TENX.detcetedsikrowtenTENXehtnoeruliafanehwyda
etsswolgDEL
CAD-IMP.esuerutufroF
IMP.IMPehtniseruccoeruliafrossecorpniamanehwsehsalfDEL SEHCTIWSSSERDDA .3­SNOITPO.FFOotsehctiwsrehtollateS.TENXrofNOot4hct
iwsteS
DELSUTATS siedocrorrE.noitarepolamronetacidniotthgilstnemgesgniklaW
eyalpsid
.detcetedsirorrelanretninafid
HCTIWSTESER.IMPehtezilaitini-erotsserP TOPTSARTNOC.ytilibisivtsebehtrofDCLehttsujdaotnruT TROPGUB TENH.scitsongaidkrowtenrofCPpotpalotnoitcennocTENH
DAOLPU .atadnoitarugifnocmetsysgnirre
fsnartroflootsueZotnoitcennoC
M1-MIN.esuerutufroF
SECURITY
SUPERVISORY
ALARM
TROUBLE
5-2otslaideerhtehtfohcaenosretniopehtgninrutyb352otteS
APPLY
POWER
(P/N 575-434249) HERE
Figure 3 Applying PMI-INTL Labels
Siemens Building Technologies Fire Safety
APPROPRIATE
LABEL
POWER
ON
AUDIBLES
SILENCED
PARTIALSYSTEM DISABLED
10:32:05 04/15/01 SYSTEM STATUS: NORMAL
FireFinder-XLS
Siemens - Fire Safety
....
More Info
+
_
?
P/N 315-033070-42
Page 3
INSTALLATION
INNER DOOR
Remove ELECTRICAL POWER prior to installing the PMI/PMI-REM/PMI-INTL in the enclosure.
Remove the PMI from its anti static bag. Set the three-digit network address using the 10-position rotary switches located on the back of the PMI. For HNET, set the PMI/PMI­REM/PMI-INTL to 253. Make sure that the PMI is configured at this address in the Zeus physical view.
When the PMI is used with XNET, the three-digit network address switch is used to set the XNET node address. In order to configure the PMI for XNET operation, first set position 4 of the options switch, S17, to ON. (Refer to Figure 2 for the location of the options switch.) Next set the XNET node address that has assigned in Zeus on the network address switches. Be sure to set all leading zeros. For example, Node 2 is set at 002. The MNET address of the PMI is automatically set to 253 when position 4 of S17 is in the ON position.
Note the location of the contrast pot. Although the PMI comes from the factory with the LCD contrast adjusted, this adjustment may not be proper for the viewing angle of the LCD once it is installed in the enclosure. If the contrast appears poor with the system powered, open the inner door and locate the contrast pot on the lower edge of the PMI printed circuit board. Adjust this pot until the LCD contrast is acceptable.
The PMI/PMI-INTL mounts to the rear of the inner door in the CAB-1, CAB-2 or CAB-3 enclosures. The PMI-REM/PMI-INTL mounts to the rear of the inner door in the REMBOX2 or REMBOX4 enclosures. Select the location of the PMI. They can be mounted either in the center or on the left side of the
PMI
inner door, when viewed from the outside of the enclosure. Place the PMI onto the inner door from the rear, over the four mounting studs in the desired location. Secure the PMI to the inner door with the four nuts provided. (Refer to Figure 4.)
Figure 4 Mounting The PMI/PMI-REMPMI-INTL To The Rear Of The Inner Door
The PMI-INTL also connects to the RNI, however it is shipped with a 40 inch long 60 wire cable, P/N 555-133743.
Make sure that all cables snap fully into their connectors and close the locking levers over the top of each cable connector. Secure the cable in the back box using cable ties and the tie down points in the enclosure. The cable must have sufficient slack to allow the inner door to open fully without putting stress on the cable.
Siemens Building Technologies Fire Safety
A 40 inch long 60 wire cable, P/N 555-133743, connects the PMI/PMI-INTL to the CC-5. The CC-5 is located in the back of the enclosure on the left hand side. Connect one end of the cable to JP3 on the PMI. JP3 is marked with “CC-5” on the PMI/PMI-INTL printed circuit board. Connect the other end of the cable to P1 on the CC-5. (Refer to Figure 5.)
A 24 inch long 60 wire cable, P/N 555-133998, connects the PMI-REM to the RNI. The RNI is located in the back of the enclosure on the top left hand side. Connect one end of the
cable to JP3 on the PMI-REM. JP3 is marked with “CC-5” on the PMI-REM printed circuit board. Connect the other end of the cable to P2 on the RNI. (Refer to Figure 6.)
P/N 315-033070-43
Page 4
Figure 5 Connecting The PMI/PMI-INTL To The CC-5
Figure 6
Connecting The PMI-REM/PMI-INTL To The RNI
OPERATION In the normal standby condition the PMI displays the site specific custom message,
the time and date, and a synopsis of the system status.
When an event occurs in the system, the display enters the Alert mode. The event is displayed, the local audible sounds and the appropriate LED blinks. If the event caused notification appliances to sound the Audibles On indicator lights. At the bottom of the screen an acknowledge button is displayed. Pressing this button acknowledges the event and silences the local audible. Once all events are acknowl­edged a reset button becomes available in the lower right side of the display. If notification appliances were active, two additional buttons appear at the bottom of the screen. These allow the operator to silence or unsilence the notification appli­ances. When the notification appliances are silenced the Audibles Silenced LED lights. The system can only be reset with the notification appliances silenced.
If more events are present in the system than can be displayed on a single screen a scroll bar appears to the right of the event list. Pressing the up and down navigation buttons to the right of the LCD allows the operator to move through the list. The selected event is highlighted in the display. Pressing the More Info button will display a screen showing details relating to the selected event. Other buttons also appear at the bottom of this screen. There is an expanded text message available and a selec­tion to show all of the devices associated with the event that are active. The operator can return to the previous screen by pressing the ESC (-) button, which is adjacent to the More Info button. (For more detail on PMI operation, refer to the FireFinder-XLS Manual, P/N 315-033744.)
ELECTRICAL RATINGS
For CE applications in Cerberus E100 systems refer to
Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN P/N 315-033070-4
tnerruCenalPkcaBV42Am032
tnerruCV42lanimreTwercS0
tnerruCenalPkcaBV2.60
tnerruCybdnatSV42Am032
Siemens Gebäudesicherheit
GmbH & Co. oHG D-80930 München