Network Interface Card
For PCI Application with Windows
OPERATION
The Model NCC-2F from Siemens Industry, Inc. (as
shown in Figure 1) is a PCI-compliant network card
used with the NCC, NCC WAN and Desigo CC systems. The NCC-2F allows the user to interface networked MXL and/or XLS fire panels to Desigo CCs
and/or NCCs on XNET. The NCC-2F can also provide
an interface to NCC WAN components, including the
HUB-4 over HNET. An NCC-2F can provide connectivity to either XNET or HNET, or both XNET and HNET
using 2 cards. The NCC-2F may also be used in an
FVNET setup inside the VNT. This allows for interfacing HNET and XNET between multiple XLS systems.
The NCC-2F provides the NCC and Desigo CC with a supervised RS-485 network connection. The NCC-2F operates in both Style 4 (Class B) and Style 7 (Class A) modes.
The module fits in any available PCI 5V compliant slot. The
card is keyed so that it will only fit in an appropriate PCI slot.
The module comes preinstalled in NCC and Desigo CC
computers. Hardware installation instructions for the NCC2F, when it is not factory installed, can be found in the
Physical Installation section of this document.
Controls and Indicators
The NCC-2F provides one reset switch and four LEDs that
are accessible through the back of the PC it is mounted
in. The reset switch (S2) is located just below TB1.
Pushing the reset switch initializes the NCC-2F operation.
The LEDs are located above TB1 and are, in top to bottom order:
The NCC-2F is assigned to a standard COM port by
Windows when the drivers are installed. The drivers
come pre-installed in NCC and Desigo CC computers.
The NCC-2F driver installations are covered in the
Driver Installation section of this document.
The COM port assigned to the NCC-2F can be viewed
in the Windows Device Manager. One NCC-2F card
occupies two consecutive COM ports, but only one will
be available for use by the NCC-2F. On Windows XP
systems, the used COM port will be the first (or lower)
numbered port assigned for the NCC-2F card. On Windows 7 systems, the used COM port is the NCC-2F
Enhanced Communications Port assigned as Port0
(seen via Properties) - and may be the lower or higher
port number, depending on the computer.
The Device Manager is accessible in Windows as follows:
Another way is to right click My Computer icon, then
select Properties >Hardware >Device Manager.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-049430-2
Siemens Canada, Ltd.
1577 North Service Road East
Oakville, Ontario
L6H 0H6 Canada
Figure 2 shows a sample Windows XP Device Manager
view and a typical assignment of COM ports on a PC
with (2) NCC-2F boards installed. The port assignments
for the NCC-2F are labeled PCI Communications Port.
Figure 2
Windows XP Device Manager View
WINDOWS 7
Open the Start menu, then click on Control Panel; this
will open a new window on the Desktop, showing the
Control Panel options.
The Address bar of the Control Panel window should
end with the “Control Panel” location, followed by a
“right-arrow”.
Click on the “right-arrow” to display the available additional locations, then select All Control Panel Items,
and click on it. On the updated screen, select Device
Manager and click on it.
Figure 3 shows a sample Windows 7 Device Manager
view and a typical assignment of COM ports on a PC
with (1) NCC-2F board installed. The port assignments
for the NCC-2F are labeled Enhanced Communication
Port, once installed.
In these examples above, the first NCC-2F is assigned
to ports COM3 and COM4, and the second NCC-2F is
assigned to ports COM5 and COM6. This is the default
setup, with XNET on COM3 (the first port of the first
board) and HNET on COM5 (the first port of the second
board).
The NCC or Desigo CC XNET (and HNET) port assignment can be changed to agree with any port assignment at the time of install or update. Either board can
handle XNET and either board can handle HNET. There
is no difference in the boards. However, XNET and
HNET are different protocols, so HNET wiring should
go to the board with the COM port assigned to HNET
and, likewise, XNET wiring should go to the board with
the COM port assigned to XNET.
Figure 3
Windows 7 Device Manager View
PHYSICAL INSTALLATION
Remove all Windows PC power before installation.
To install the NCC-2F in a computer in which it is not
factory installed, follow the steps listed below:
1. Unscrew the two knurled knobs on the rear of the
NCC or Desigo CC computer (computer enclosure
may have different physical characteristics.).
2. Slide the cover back an inch or so and lift it off.
3. The NCC-2F installs into any free PCI 5V compliant
slot in the computer. Select a slot and remove the
blank cover, keeping the screw.
4. Remove the terminal block from the NCC-2F by
removing the two screws that hold it to the bracket.
5. Place the NCC-2F into the open slot so that the
NCC-2F card edge extends through the opening in
the back of the PC.
6. Align the NCC-2F with the card edge connector in
the computer and press it firmly into place.
7. Secure the NCC-2F by installing the screw that
held the blank cover. (Refer to Step 3.)
8. Replace the computer cover and tighten the
knurled knobs (or equivalent).
2
9. Reattach the terminal block by sliding it onto the
O NOT US
s
NCC-2F card edge and install the two screws. This
is a keyed connection and will only install one way.
10. After the NCC-2F is installed, install the NCC-2F
drivers following the instructions in the DriverInstallation section of this document.
ELECTRICAL CONNECTIONS
Network (XNET)
The XNET connections are made on terminals 1-4 of the
terminal block on the rear of the NCC-2F. The primary
pair (or network A) is on terminals 1 and 2. The secondary pair (or network B) is on terminals 3 and 4.
For Style 4networks, install a 120 ohm EOLR on ter-
minals 3 and 4. See Figure 4 for wiring details.
For Style 7 networks, connect to both the primary and
secondary pairs. See Figure 4 for wiring details.
PAIR B
(OMIT FOR STYLE 4)
SUPERVISED
POWER LIM ITED
PAI R A
SUPERVISED
POWER LIMITED
DO NOT USEDO NOT USE
Network (HNET)
The HNET connections are made on terminals 1-4 of the
terminal block on the rear of the second NCC-2F. The
primary pair (or network A) is on terminals 1 and 2. The
secondary pair (or network B) is on terminals 3 and 4.
Install a 120 ohm EOLR on terminals 1 and 2, and on
terminals 3 and 4.
For Style 4networks, connect only the primary pairs.
See Figure 5 for wiring details.
For Style 7 networks, connect to both the primary and
secondary pairs. See Figure 5 for wiring details.
Network (HNET-VNT)
For Style 4 networks, connect only the primary pairs.
See Figure 6 for NCC-2F HNET-VNT connections.
For Style 7 networks, connect to both the primary and
secondary pairs. See Figure 6 for wiring details.
TO ADDITIONAL
NIM-1Rs, NIM-1Ws,
NCC-2Fs OR NIC- C
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
SEE NOTE 7
(MUST BE IN SAME ENCLOSURE AS THE PMI)
17 18 19 20 21 22 23 24
NIC-C
ONE SLOT OF CC-5
D
DO NOT USE
E
1 2 3 4 5
NCC-2F
LOCATED INSIDE NCC/
DESIGO CC/VNT
IF THE NCC/DESIGO CC/VNT
IS LOCATED AT THE END OF THE
XNET NETWORK, INSTALL EOLR
P/N 140-820350 ACROSS
TERMINALS 1 & 2 AND 3 & 4.
Refer to Wiring Specification for MXL, MXL-IQ
and MXLV Systems, P/N 315-092772 revision
6 or higher, for additional wiring information.
NOTES:
1.No EOLR required for NIC-C.
2.The screw terminals can accommodate one 12-24AWG or two 1624AWG.
3.From the NCC-2F to NIM-1R, NIM-1W or NCC-2F:
80 Ohms max. per pair.
Unshielded twisted pair - .5μF line to line
Shielded twisted pair - .3μF line to line, .4μF line to shield
NCC-2F XNET Connections
NOTE:
Figure 4
2
1
4
3
MOM-4
TB3 OR TB4
NIM-1R / NIM-1W
4.From the NCC-2F to NIC-C:
2000 feet (33.8 ohms) max. per pair between CC-5s/CC-2s.
Unshielded twisted pair
.25μF max. line to line
Shielded twisted pair
.15μF max. line to line
.2μF max. line to shield
5.Use twisted pair or twisted shielded pair.
6.Terminate shields at one end only.
7.Power limited to NFPA 70 per NEC 760.
8.CC-5 terminals 9 - 14 are not connected and can be used to tie shields
together.
9.Positive or negative ground fault detected at
7-8 of the NIC-C.
10. Each pair independently supervised.
11. Maximum voltage 8V P-P.
12. Maximum current 75mA during message transmission.
<10K ohms on pins 3-4,
3
NOTES:
1. The screw terminals can accommodate one
12-24AWG or two16-24AWG.
2. From the NCC-2F to NIC-C:
2000 feet (33.8 ohms) max. per pair between
CC-5s/CC-2s.
Unshielded twisted pair
.25μF max. line to line
Shielded twisted pair
.15μF max. line to line
.2μF max. line to shield
3. Use twisted pair or twisted shielded pair.
4. Terminate shields at one and only one NIC-C.
5. Power limited to NFPA 70 per NEC 760.
6. Maximum voltage 8V P-P.
7. Maximum current 75mA during message
transmission.
8. Each pair independently supervised.
9. Positive or negative ground fault detected at
<10K ohms on pins 1-2, 3-4, 5-6, 7-8 of the
NIC-C.
* EOLR 120 OHMS, 1/2W, 5%
P/N 140-820350
TB1
*
5
*
34
2
1
NETWORK A
(PRIMARY)
SUPERVISED
NCC-2F
Figure 5
NCC-2F HNET Connections
NETWORK B
(SECONDARY)
SUPERVISED
OMIT THIS PAIR
FOR STYLE 4
12345678
910111213141516
NIC-C
ONE SLOT OF CC-5
NETWORK A
(PRIMARY)
SUPERVISED
* EOLR 120 OHMS, 1/2W, 5%
P/N 140-820350
*
*
TB1
5
NCC-2F
NETWORK A
(PRIMARY)
SUPERVISED
34
2
1
12345678
910111213141516
NOTES:
1. The screw terminals can
accommodate one 12-24AWG
or two16-24AWG.
2. From the NCC-2F to NIC-C:
ONE SLOT OF CC-5/CC-2
17 18 19 20 21 22 23 24
2000 feet (33.8 ohms) max.
per pair between CC-5s/CC-2s.
Unshielded twisted pair
.25μF max. line to line
Shielded twisted pair
.15μF max. line to line
.2μF max. line to shield
3. Use twisted pair or twisted shielded pair.
4. Terminate shields at one and only one NIC-C.
5. Power limited to NFPA 70 per NEC 760.
6. Maximum voltage 8V P-P.
7. Maximum current 75mA during message transmission.
8. Each pair independently supervised.
9. Positive or negative ground fault detected at
<10K ohms on pins 1-2, 3-
4, 5-6, 7-8 of the NIC-C.
10. For Style 4, remove jumper P2 on all NIC-Cs except on the NIC-C that is
connected to the NCC-2F card. For Style 7, remove jumpers P2 and P4 on
all NIC-Cs except on the NIC-C that is connected to the NCC-2F card.
SEE NOTE 7
FIRST NIC-C
DO NOT USE
DO NOT USE
NETWORK B
(SECONDARY)
SUPERVISED
OMIT THIS PAIR
FOR STYLE 4
NETWORK A
(PRIMARY)
SUPERVISED
DO NOT USE
12345678
910111213141516
SEE NOTE 7
ONE SLOT OF CC-5/CC-2
17 18 19 20 21 22 23 24
DO NOT USE
DO NOT USE
DO NOT USE
* EOLR 120 OHMS, 1/2W, 5%
P/N 140-820350
SEE NOTE 7
*
DO NOT USEDO NOT USE
DO NOT USE
*
12345678
910111213141516
LAST NIC-C
ONE SLOT OF CC-5/CC-2
17 18 19 20 21 22 23 24
DO NOT USE
Figure 6
NCC-2F-HNET-VNT Wiring on FCC Only
4
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.