Siemens NCC-2F Installation Instructions Manual

Installation Instructions
Model NCC-2F
Network Interface Card For PCI Application with Windows
OPERATION
The Model NCC-2F from Siemens Industry, Inc. (as shown in Figure 1) is a PCI-compliant network card used with the NCC, NCC WAN and Desigo CC sys­tems. The NCC-2F allows the user to interface net­worked MXL and/or XLS fire panels to Desigo CCs and/or NCCs on XNET. The NCC-2F can also provide an interface to NCC WAN components, including the HUB-4 over HNET. An NCC-2F can provide connectiv­ity to either XNET or HNET, or both XNET and HNET using 2 cards. The NCC-2F may also be used in an FVNET setup inside the VNT. This allows for interfac­ing HNET and XNET between multiple XLS systems.
The NCC-2F provides the NCC and Desigo CC with a su­pervised RS-485 network connection. The NCC-2F oper­ates in both Style 4 (Class B) and Style 7 (Class A) modes.
The module fits in any available PCI 5V compliant slot. The card is keyed so that it will only fit in an appropriate PCI slot. The module comes preinstalled in NCC and Desigo CC computers. Hardware installation instructions for the NCC­2F, when it is not factory installed, can be found in the
Physical Installation section of this document.
Controls and Indicators
The NCC-2F provides one reset switch and four LEDs that are accessible through the back of the PC it is mounted in. The reset switch (S2) is located just below TB1. Pushing the reset switch initializes the NCC-2F operation.
The LEDs are located above TB1 and are, in top to bot­tom order:
DELroloCnoitpircseD
)2SD(KOTENneerG.atadgniviecersikrowtenetacidniotsknilB
)1SD(KOTSOHneerG.timsnartotatadeta
)4SD(AHCwolleY.tcelesAlennahClaudividnietacidniot*sknilB
)5SD(BHCwolleY.tcelesBlennahClaudivi
cidniotsknilB
dnietacidniot*sknilB
.lennahctahtnotluaf7elytSasetacidni,ydaetssiDELfI*
NET OK
HOST OK
CH A
CH B
RESET
DS2
DS1
DS4
DS5
1
1 2 3 4 5
5
TB1
S2
P1
NCC-2F
P2
U4
S1
Figure 1
NCC-2F Module Board
CONFIGURATION
The NCC-2F is assigned to a standard COM port by Windows when the drivers are installed. The drivers come pre-installed in NCC and Desigo CC computers. The NCC-2F driver installations are covered in the
Driver Installation section of this document.
The COM port assigned to the NCC-2F can be viewed in the Windows Device Manager. One NCC-2F card occupies two consecutive COM ports, but only one will be available for use by the NCC-2F. On Windows XP systems, the used COM port will be the first (or lower) numbered port assigned for the NCC-2F card. On Win­dows 7 systems, the used COM port is the NCC-2F Enhanced Communications Port assigned as Port0 (seen via Properties) - and may be the lower or higher port number, depending on the computer.
The Device Manager is accessible in Windows as follows:
WINDOWS XP
Click Start >Settings >Control Panel >Administrative Tools >Computer Management >Device Manager.
Another way is to right click My Computer icon, then select Properties >Hardware >Device Manager.
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-049430-2
Siemens Canada, Ltd. 1577 North Service Road East Oakville, Ontario L6H 0H6 Canada
Figure 2 shows a sample Windows XP Device Manager view and a typical assignment of COM ports on a PC with (2) NCC-2F boards installed. The port assignments
for the NCC-2F are labeled PCI Communications Port.
Figure 2
Windows XP Device Manager View
WINDOWS 7
Open the Start menu, then click on Control Panel; this will open a new window on the Desktop, showing the Control Panel options.
The Address bar of the Control Panel window should end with the “Control Panel” location, followed by a “right-arrow”.
Click on the “right-arrow” to display the available addi­tional locations, then select All Control Panel Items, and click on it. On the updated screen, select Device Manager and click on it.
Figure 3 shows a sample Windows 7 Device Manager view and a typical assignment of COM ports on a PC with (1) NCC-2F board installed. The port assignments for the NCC-2F are labeled Enhanced Communication Port, once installed.
In these examples above, the first NCC-2F is assigned to ports COM3 and COM4, and the second NCC-2F is assigned to ports COM5 and COM6. This is the default setup, with XNET on COM3 (the first port of the first board) and HNET on COM5 (the first port of the second board).
The NCC or Desigo CC XNET (and HNET) port as­signment can be changed to agree with any port assign­ment at the time of install or update. Either board can handle XNET and either board can handle HNET. There is no difference in the boards. However, XNET and HNET are different protocols, so HNET wiring should go to the board with the COM port assigned to HNET and, likewise, XNET wiring should go to the board with the COM port assigned to XNET.
Figure 3
Windows 7 Device Manager View
PHYSICAL INSTALLATION
Remove all Windows PC power before installation.
To install the NCC-2F in a computer in which it is not factory installed, follow the steps listed below:
1. Unscrew the two knurled knobs on the rear of the NCC or Desigo CC computer (computer enclosure may have different physical characteristics.).
2. Slide the cover back an inch or so and lift it off.
3. The NCC-2F installs into any free PCI 5V compliant slot in the computer. Select a slot and remove the blank cover, keeping the screw.
4. Remove the terminal block from the NCC-2F by removing the two screws that hold it to the bracket.
5. Place the NCC-2F into the open slot so that the NCC-2F card edge extends through the opening in the back of the PC.
6. Align the NCC-2F with the card edge connector in the computer and press it firmly into place.
7. Secure the NCC-2F by installing the screw that held the blank cover. (Refer to Step 3.)
8. Replace the computer cover and tighten the knurled knobs (or equivalent).
2
9. Reattach the terminal block by sliding it onto the
O NOT US
s
NCC-2F card edge and install the two screws. This is a keyed connection and will only install one way.
10. After the NCC-2F is installed, install the NCC-2F
drivers following the instructions in the Driver Installation section of this document.
ELECTRICAL CONNECTIONS
Network (XNET)
The XNET connections are made on terminals 1-4 of the terminal block on the rear of the NCC-2F. The primary pair (or network A) is on terminals 1 and 2. The second­ary pair (or network B) is on terminals 3 and 4.
For Style 4 networks, install a 120 ohm EOLR on ter-
minals 3 and 4. See Figure 4 for wiring details.
For Style 7 networks, connect to both the primary and
secondary pairs. See Figure 4 for wiring details.
PAIR B
(OMIT FOR STYLE 4)
SUPERVISED
POWER LIM ITED
PAI R A
SUPERVISED
POWER LIMITED
DO NOT USE DO NOT USE
Network (HNET)
The HNET connections are made on terminals 1-4 of the terminal block on the rear of the second NCC-2F. The primary pair (or network A) is on terminals 1 and 2. The secondary pair (or network B) is on terminals 3 and 4. Install a 120 ohm EOLR on terminals 1 and 2, and on terminals 3 and 4.
For Style 4 networks, connect only the primary pairs.
See Figure 5 for wiring details.
For Style 7 networks, connect to both the primary and
secondary pairs. See Figure 5 for wiring details.
Network (HNET-VNT)
For Style 4 networks, connect only the primary pairs.
See Figure 6 for NCC-2F HNET-VNT connections.
For Style 7 networks, connect to both the primary and
secondary pairs. See Figure 6 for wiring details.
TO ADDITIONAL NIM-1Rs, NIM-1Ws, NCC-2Fs OR NIC- C
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
SEE NOTE 7
(MUST BE IN SAME ENCLOSURE AS THE PMI)
17 18 19 20 21 22 23 24
NIC-C
ONE SLOT OF CC-5
D
DO NOT USE
E
1 2 3 4 5
NCC-2F
LOCATED INSIDE NCC/
DESIGO CC/VNT
IF THE NCC/DESIGO CC/VNT
IS LOCATED AT THE END OF THE
XNET NETWORK, INSTALL EOLR
P/N 140-820350 ACROSS
TERMINALS 1 & 2 AND 3 & 4.
Refer to Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 315-092772 revision 6 or higher, for additional wiring information.
NOTES:
1. No EOLR required for NIC-C.
2. The screw terminals can accommodate one 12-24AWG or two 16­24AWG.
3. From the NCC-2F to NIM-1R, NIM-1W or NCC-2F: 80 Ohms max. per pair. Unshielded twisted pair - .5μF line to line Shielded twisted pair - .3μF line to line, .4μF line to shield
NCC-2F XNET Connections
NOTE:
Figure 4
2
1
4
3
MOM-4
TB3 OR TB4
NIM-1R / NIM-1W
4. From the NCC-2F to NIC-C: 2000 feet (33.8 ohms) max. per pair between CC-5s/CC-2s. Unshielded twisted pair .25μF max. line to line Shielded twisted pair .15μF max. line to line .2μF max. line to shield
5. Use twisted pair or twisted shielded pair.
6. Terminate shields at one end only.
7. Power limited to NFPA 70 per NEC 760.
8. CC-5 terminals 9 - 14 are not connected and can be used to tie shields together.
9. Positive or negative ground fault detected at 7-8 of the NIC-C.
10. Each pair independently supervised.
11. Maximum voltage 8V P-P.
12. Maximum current 75mA during message transmission.
<10K ohms on pins 3-4,
3
NOTES:
1. The screw terminals can accommodate one 12-24AWG or two16-24AWG.
2. From the NCC-2F to NIC-C: 2000 feet (33.8 ohms) max. per pair between CC-5s/CC-2s. Unshielded twisted pair .25μF max. line to line Shielded twisted pair .15μF max. line to line .2μF max. line to shield
3. Use twisted pair or twisted shielded pair.
4. Terminate shields at one and only one NIC-C.
5. Power limited to NFPA 70 per NEC 760.
6. Maximum voltage 8V P-P.
7. Maximum current 75mA during message transmission.
8. Each pair independently supervised.
9. Positive or negative ground fault detected at <10K ohms on pins 1-2, 3-4, 5-6, 7-8 of the NIC-C.
* EOLR 120 OHMS, 1/2W, 5%
P/N 140-820350
TB1
*
5
*
34
2
1
NETWORK A (PRIMARY) SUPERVISED
NCC-2F
Figure 5
NCC-2F HNET Connections
NETWORK B (SECONDARY) SUPERVISED OMIT THIS PAIR FOR STYLE 4
12345678
910111213141516
NIC-C
ONE SLOT OF CC-5
NETWORK A (PRIMARY) SUPERVISED
* EOLR 120 OHMS, 1/2W, 5%
P/N 140-820350
*
*
TB1
5
NCC-2F
NETWORK A
(PRIMARY)
SUPERVISED
34
2
1
12345678
910111213141516
NOTES:
1. The screw terminals can accommodate one 12-24AWG or two16-24AWG.
2. From the NCC-2F to NIC-C:
ONE SLOT OF CC-5/CC-2
17 18 19 20 21 22 23 24
2000 feet (33.8 ohms) max. per pair between CC-5s/CC-2s. Unshielded twisted pair .25μF max. line to line Shielded twisted pair .15μF max. line to line .2μF max. line to shield
3. Use twisted pair or twisted shielded pair.
4. Terminate shields at one and only one NIC-C.
5. Power limited to NFPA 70 per NEC 760.
6. Maximum voltage 8V P-P.
7. Maximum current 75mA during message transmission.
8. Each pair independently supervised.
9. Positive or negative ground fault detected at
<10K ohms on pins 1-2, 3-
4, 5-6, 7-8 of the NIC-C.
10. For Style 4, remove jumper P2 on all NIC-Cs except on the NIC-C that is connected to the NCC-2F card. For Style 7, remove jumpers P2 and P4 on all NIC-Cs except on the NIC-C that is connected to the NCC-2F card.
SEE NOTE 7
FIRST NIC-C
DO NOT USE
DO NOT USE
NETWORK B
(SECONDARY)
SUPERVISED
OMIT THIS PAIR
FOR STYLE 4
NETWORK A (PRIMARY) SUPERVISED
DO NOT USE
12345678
910111213141516
SEE NOTE 7
ONE SLOT OF CC-5/CC-2
17 18 19 20 21 22 23 24
DO NOT USE
DO NOT USE
DO NOT USE
* EOLR 120 OHMS, 1/2W, 5%
P/N 140-820350
SEE NOTE 7
*
DO NOT USEDO NOT USE
DO NOT USE
*
12345678
910111213141516
LAST NIC-C
ONE SLOT OF CC-5/CC-2
17 18 19 20 21 22 23 24
DO NOT USE
Figure 6
NCC-2F-HNET-VNT Wiring on FCC Only
4
Loading...
+ 8 hidden pages