OPERATION
The Model MPS-6 from Siemens Industry, Inc. is a fully supervised power supply that provides the MXL System with primary 24 VDC power. It is rated at 6.5 amps and is unfiltered and unregulated. The MPS-6 supplies the MXL Control Panel or PSR-1 and its expansion modules with the power required for normal operation. The module incorporates a 2 amp resettable circuitbreaker on the primary input and includes a built-in AC line filter for surge and noise suppression. The MPS-6 mounts in an MXL enclo­sure backbox.
INSTALLATION
Always remove power before installation.
The installation kit for the MPS-6 includes the following:
Four #10 nuts Two #10 lockwashers Two #10 flat washers Two ¼" nuts One 14 gauge green ground strap
The MPS-6 is designed to operate from a 120 VAC, 60 Hz power source. Use a separate or dedicated circuitbreaker. Wire in accordance with local codes and Article 760 of the NEC, NFPA 70, latest edition.
Run the earth ground from a suitable source to the MPS-6. Check local requirements. Conduit is not
an acceptable conductor.
1. Make sure that the dedicated circuitbreaker for the MPS-6 is turned off at the mains.
2. Place the mounting bracket for the MPS-6 over the two studs provided in the enclosure. (Refer to Figure 1.)
3. Secure the MPS-6 to the enclosure by slipping the flat washers, then the lockwashers, and finally the nuts over the two studs. Tighten them securely.
4. Connect the AC mains to the MPS-6:
Terminal
Black (hot) 1 White (neutral) 2 Green (earth ground) 3
5. Install the 14 gauge green ground strap spade lug side to Terminal 3 (green, earth ground) of the MPS-6. Secure the ring lug side of the ground strap to the nearest available stud in the enclo­sure. The stud size may vary depending on the actual system modules and enclosure used. Because the stud may be either a #10 thread or ¼" thread, nuts for both have been provided. The ground strap provided is long enough for all applications and the ring lug is good for both #10 and ¼" studs. If possible, install the ring lug under one of the lock-washers and nuts which secure the MPS-6 itself.
6. When used with a PSR-1: Connect the 3-wire cable coming from the MPS-6 to the PSR at P12.
When used with an MMB-1/-2/-3 or SMB-1/2:
Connect the 3-wire cable coming from the MPS-6 to the MMB-1/-2/-3 or the SMB-1/2 at P1.
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-090334-8
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
Page 2
Figure 1
MPS-6 in MXL Enclosure
POWER CABLE TO: MMB-1/-2/-3, P1 SMB-1/-2, P1 PSR-1, P12
P/N 315-090334-8
Figure 2
Front of MPS-6