Siemens MMB3-ALD-UK Installation Instructions Manual

Page 1
Installation Instructions
Model MMB3-ALD-UK Upgrade Kit for ALD on MMB-3 Main Motherboard
OPERATION
The Model MMB3-ALD-UK Upgrade Kit provides the user with the materials to upgrade the ALD firmware on the MMB-3 main motherboard.
INSTALLATION
To upgrade the MMB-3 with new ALD firmware, remove the old U8 IC and replace it with the new U8 (P/N 161-549335) following the steps listed below.
1. Remove all connections to MMB-3, including power and battery.
CAUTION
Remove all system power before
installation, first battery and then AC.
2. Locate the IC to be upgraded on the MMB-3. (Refer to Figure 1.) The IC has a label attached to the top surface that indicates the IC number and the software revision currently installed. Make certain that the IC number on the module corresponds to the IC number in the replacement kit.
3. Note where and how the IC is positioned on the module. Refer to Figure 1 to note position of notched corner on U8.
4. Remove the old IC (U8) with the Extraction Tool provided. Do this by lifting one end of the IC slightly, then the other end. Continue this process until the IC comes free.
IMPORTANT Place the new IC in the same pin location on the socket as the one that was removed. If the IC is installed incorrectly, severe damage to the module can occur.
6. Gently place the new IC in the same pin location on the socket as the one removed.
CAUTION Be sure that the notched corner of U8 is positioned correctly. Check that the IC is properly seated in the sockets and that all the IC pins are properly aligned with the connectors.
7. Discard the old IC.
8. Re-install all connection to the MMB-3.
9. Re-install all power connections to the MMB-3.
10. Power up the system, AC first, then battery.
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-050566-0
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
Page 2
TB9
3
2
1
P3 POWER TO MOM-4 2 AMP MAX.
P2 BATTERY
TB3
4
3
2
1
TB2
4
3
2
1
TB1
4
3
2
1
DS9
DS7
MNET
GND
FAULT
P5
PROGRAMMER
5V AUX
F5
0.75 AMP
P10
1
D2300CP/MOI-7
S1
F2
BATTERY
20A
ALD-2I LOOP 2
ALD-2I LOOP 1
MNET
MNET XMIT
P4
PRINTER
LOCATION
F4
MOM-4
15 AMP
NOTCHED
CORNER
P12
1
MNET GND FAULT
DISCONNECT
EXPANSION
TB10
1
4
OF U8
3
1
2
MPS-6 MPS-12
F1
MPS-6 8 AMP
F6
BATTERY CHARGER 5 AMP
P20
ALD GND FAULT
DISCONNECT
U8
JP7JP8
P7
3
1
S7
S4
P6
MOM-4
1
P14P1
MMB-3
TB8
3
4
XNET
CB1 NAC1
CB2 NAC2
TB5
12
CZM-1
POWER
P13
1
MMB GND FAULT
DISCONNECT
DS2
DS3
ALD GND FAULT
DS5
DS6
DS4
DS8
JP2
P18
MMB GND FAULT
JP3
DS1
POLLING
U62
U80
JP6JP5
1
2
S2
TO ANN
P18
P11
UTILITY PORT
P8
1
JP1
JP4
P17
OFF ON
CZM-1 POWER
NAC 2
NAC 1
TAMPER SWITCH
SPV
TRBL
ALR
31
11
10
9
2 AMP
F3
TB6
8
7
6
5
TB7
4
3
2
1
1
P9
TB4
9
8
7
6
5
4
3
2
1
P/N 315-050566-0
Figure 1
MMB-3 Board
Loading...