Siemens MMB-3 Installation Instructions Manual

Page 1
Installation Instructions
Model MMB-3 Main Control Board
OPERATION
The Model MMB-3 board from Siemens Industry, Inc., in each MXL System controls operations and monitors input device identity, network communication, and operator commands that are entered through the MKB Annunciator/ Key­board. The MMB-3 also provides two analog loop driver circuits. Each ALD-2I loop can be used as Class B or Class A and can monitor and control up to 60 intelligent devices as well as program­mable device relays. The MMB-3 module can be programmed and upgraded in the field. It is equipped with two programmable Class B (Style Y) or Class A (Style Z) notification appliance circuits. Each circuit can activate up to 1.5 amps of audible or visual notification appliances. The MMB-3 has a user-defined Style 4 or Style 7 MNET communication port.
The module also has auxiliary relays for the external monitoring of Common System Alarm, Common System Trouble, and Common Supervi­sory conditions. The Common Supervisory relay is user programmable.
The MMB-3 includes a built-in battery charger and transfer circuit. The charger is microproces­sor controlled and incorporates a brownout circuit that switches the System to standby batteries during the loss or reduction of the primary source AC.
The System can display the real time battery voltage, the AC voltage, and the charger current on the MKB display. It also has a 1 amp, 24 VDC output that powers CZM-1/-1B6 modules.
For additional information on the MXL/MXLV System, refer to the MXL/MXLVManual, P/N 315-092036.
INSTALLATION
Remove all system power before installation, first battery and then AC. (To power up, connect
the AC first, then the battery.)
Installing the MMB-3 Board
Unpack the MMB-3. Inspect the module, looking for such things as integrated circuits (ICs) not firmly seated in their sockets, bent IC pins, connectors not properly installed, dirt, packing material on the board, etc.
The MMB-3 includes the following installation kits:
tiKelbaC3-BMM )530946-545N/P(
stun01#ruoF
stnetnoCroFdesU
To install the MMB-3:
1. Place the MMB-3 with the mounting bracket over the four standoffs on the MBR-MP mounting plate in the upper left portion of the backbox (See Figure 1).
seilbmessarotsisereerhT
eriwhtiwelbacyrettaB
tiKerawdraH3-BMM
)630946-545N/P(
kcolblanimretwercselbavomernoitisop-3enO
9BT skcolblanimretwercselbavomernoitisop-4xiS kcolblanimretwercselbavomernoitisop-9enO
4BT
7,6,5,3,2,1BT
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-048860-7
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
Page 2
Figure 1
BACKBOX
MBR-MP
MMB-3
Installing the MMB-3
DO NOT USE
_
+
_ _
+ +
_ _
+ +
TB9
3
2
1
P3 POWER TO MOM-4 2 AMP MAX.
P2 BATTERY
TB3
4
3
2
1
TB2
4
3
2
1
TB1
4
3
2
1
DS9
DS7
MNET
GND
FAULT
P5
PROGRAMMER
5V AUX
F5
0.75 AMP
P10
1
D2300CP/MOI-7
F2
BATTERY
20A
ALD-2I LOOP 2
ALD-2I LOOP 1
MNET
MNET XMIT
P4
S1
PRINTER
F4
MOM-4
15 AMP
P12
1
MNET GND FAULT
DISCONNECT
EXPANSION
TB10
1
4
3
1
2
MPS-6 MPS-12
F1
MPS-6 8AMP
F6
BATTERY CHARGER 5AMP
P20
1
ALD GND FAULT
DISCONNECT
JP7JP8
P7 3
1
S7
S4
P6
MOM-4
P14P1
MMB-3
TB8
4
XNET
CB1 NAC1
CB2 NAC2
TB5
12
CZM-1
POWER
P13
1
MMB GND FAULT
DISCONNECT
DS2
DS3
ALD GND FAULT
DS5
DS6
DS4
DS8
JP2
JP3
MMB GND FAULT
P18
DS1
POLLING
JP6JP5
3
1
2
S2
TO ANN
P18
P11
UTILITY PORT
P8
1
JP1
JP4
OFF ON
CZM-1 POWER
TAMPER SWITCH
P17
31
NAC 2
NAC 1
SPV
TRBL
ALR
10
2AMP
F3
TB6
8
6
TB7
4
2
1
P9
TB4
9
7
5
3
1
+ +
11
_ _
9
+
+
7
_ _
5
+ +
3
_
1
_
C
NC
8
NO
C
6
NC
NO
4
C
NC
2
NO
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
DO NOT USE
Figure 2
MMB-3 Main Board
2
Page 3
2. Secure in place using the hardware provided.
Be sure the screws and nuts are tight, as they pro­vide the earth ground connection for the MMB-3.
3. Place the removable terminal blocks from Hardware kit P/N 545-649036 on the appropriate terminals and secure in place.
CONFIGURATION
The MMB-3 has two jumpers—jumper P7 for MNET and jumper P17 for Real Time clock— which must be set for proper operation. Refer to Figure 2 for the location of the jumpers.
MNET
To configure the MNET port (TB1) for either Style 4 or Style 7 operation, set jumper P7 on the MMB-3 to one of the four settings listed below that is applicable to your system configuration.
1. If the MNET port (TB1) is not being used on the MMB-3 and there is no NET-7/7M in the system configuration, then set the jumper to positions 1 and 2.
2. If the MNET port (TB1) is configured as Style 4, then set the jumper to positions 1 and 2.
3. If the MNET port is (TB1) configured as Style 7, then set the jumper to positions 1 and 2. Remember to update MMB-3 MNET STYLE 7 in the CSGM to display YES. Configurations 1, 2, and 4 should be set to NO.
NOTE: In settings 1-3, the user can upload a
CSG-M configuration in the customary method through P5 (To Programmer).
4. If you are not using the MNET port, but are using a NET-7/7M in your MMB-3 configuration, then set the jumper to positions 2 and 3.
NOTE: If setting 4 is used, the CSG-M
configuration MUST uploaded through P1 on any NET-7/7M that is on the Style 7 MNET. You cannot upload a CSG-M configuration through P5 on the MMB-3 in this configuration.
IMPORTANT NOTE
An MXL panel cannot have a NET-7/7M in the system and use the MNET Port (TB1) on the MMB-3.
Real Time Clock
The second jumper on the MMB-3 is P17 which must be set for the real time clock to operate properly.
• Move the jumper to the on position (position 2 and 3) to provide backup battery power to the real time clock.
Internal Wiring
To complete the MMB-3 internal wiring connec­tions, follow the steps below, skipping those that do not apply to your MXL System.
1. Main Power Connections
Primary power for the MMB-3 is provided by the MPS-6 or MPS-12. Both of these mount in the lower right-hand corner of the MXL enclosure. Follow the instructions below for the appropriate power supply.
MPS-6 — Install the MPS-6 (See Instructions, P/N 315-090334). mains disconnected, connect the MPS-6 power cable to P1 of the MMB-3. Be sure
that the jumper assembly is installed in P14 of the MMB-3. If this jumper is not installed, the MMB-3 will detect a permanent AC fail or indicate auxiliary power voltage is low.
MPS-12 — Install the MPS-12 (See MPS-12 Instructions, P/N 315-092030). Remove and discard the jumper assembly installed in P14 of the MMB-3. Disconnect the AC mains. Connect the MMB-3.
2. Battery Power Connection
The MMB-3 kit includes a battery cable (wiring harness). Use the harness to connect the 24V backup batteries to P2 of MMB-3.
3. MOM-4 Optional Module Card Cage
There are two connections between the MMB-3 and the MOM-4 board.
a. The first is the 24V power connection.
P3 provides backward compatibility with the MMB-1 and should only be used when replacing an MMB-1. P3 is limited to 2 amps. The MMB-3 allows the use of
MPS-12 power cable to P14 of
MPS-6
With the AC
either
3
Page 4
an MPS-6 or an MPS-12.
TB9 terminals 1 and 2 supply 24V to the MOM-4 with a maximum of 6 amps (MPS-6) or 12 amps (MPS-12) available. This output must be derated by the total current drawn from NAC1 (1.5A max), NAC2 (1.5A max) and the CZM-1/-1B6, power (1A max) on the MMB-3. Connect TB9, 1 and 2 on the MMB-3 to TB6, 1 and 2 on the MOM 4. Refer to Figure 3 for the wiring diagram.
b. The second connection provides 5V
power and the communication interface. Connect the 8-wire ribbon cable from P7 on the MOM-4 to P6 on the MMB-3.
Field Wiring (Refer to Figure 2)
The screw terminals for the field wiring circuits are located on the left, right and bottom edges of the MMB-3. They are labeled TB1 through TB9.
The field wiring circuits available are:
CZM-1/-1B6 power Analog device loop 1 Analog device loop 2 Notification appliance circuit 1 (Styles Y and Z) Notification appliance circuit 2 (Styles Y and Z) Common alarm relay Common supervisory relay Common trouble relay Style 4 RS-485 Network (MNET)
The following sections describe each circuit type and give the related instructions. Refer also to the wiring diagrams.
14 AWG MIN 6A MAX (MPS-6) 12A MAX (MPS-12) 18-31 VDC NOT POWER LIMITED
TB9
3
2
1
DO NOT USE
_
+
MMB-3
Auxiliary 24V Power (Special Application)
Auxiliary power is available on TB5, terminals 9 through 12. The circuit is power limited per NEC Article 760 and is rated at 1 amp, 18-31 VDC.
This power supply is for use with the CZM-1/-1B6 Remote Conventional Zone module. Figure 4 shows Class B wiring; Figure 5 shows Class A wiring. The jumpers shown in Figure 4 are optional. They are not required if the proper settings are made in CSG-M Rev. 17.01 or higher.
Class B wiring can be used to obtain the maxi­mum of 20 CZM-1B6s. Each Class B wire run can support a maximum of 10 CZM-1B6s, 4 ohms max. Multiple Class B power connections can be used provided you do not exceed the rating above (20 CZM-1B6s max and 4 ohms per run max). For example, you could have four individual Class B power runs, for a total of 20 devices (6, 4, 3, and 7 CZM-1B6s), each of the four runs not exceeding 4 ohms resistance.
JUMPERS ARE OPTIONAL FOR MMB-3. REFER TO CSG-M REV. 17.01 FOR CONFIGURATION.
12
11
+ _
10
9
TB5
CZM-1B6 Supervised Auxiliary Power –
Positive and negative ground fault detected at <30K ohms for TB5 (9-12).
Refer to Wiring Specification for MXL, MXL-IQ and MXLV Systems,
P/N 315-091772 revision 6 or higher, for additional wiring information.
T-TAPPING ALLOWED
Figure 4
Class B Wiring
Special Application
CZM-1B6
CLASS B WIRING
CZM-1B6
CZM-1B6
P6
CABLE P/N 555-190967 SUPPLIED WITH MOM-4
MOM-4
TB6
_
2 1
+
P7
Figure 3
MOM-4 24V Connection
*The terms Class A and Class B do not apply to 24V power, but are used for illustrative purposes only.
CLASS A WIRING
12
10
TB5
11
9
NO T-TAPPING ALLOWED
CZM-1B6
Figure 5
CZM-1B6 Supervised Auxiliary Power –
Class A Wiring
4
Page 5
seciveDelbitapmoC
6B1-MZC7-553590-513N/P
6B-PC
I8-603590-513N/P
61-DOM7-038090-513N/P
7-IOM7-997290-513N/P
A5-SP8-763290-513N/P
7N5-SP21-927290-513N/P
KM3-727840-513N/P
C5-/5-B
C6-/6-BKM4-227840-513N/P
CF3-/C-/F3-/3-CCR6-566840-513N/P
thginKtneliS
9215/8215
53-RS8-196780-513N/P
D4-/D3-/D2-HDS
D8-/D7-/D6-/D5-/
§
1-SN
§
REWOPV42YRAILIXUA SECIVEDELBITAPMOC
noitallatsnI
snoitcurtsnI
Electrical Specifications for the Analog Device Loops
1. Electrical ratings: SUPERVISORY: 30 V unfiltered full wave
(peak), 30mA max
ALARM: 30 V unfiltered full wave
(peak), 30mA max (60 devices in alarm)
2. All wiring must be in accordance with Article 760 of NEC or the local building codes. Refer to Figure 6.
3. Only the list of devices in the Analog Device Loops - Compatible Devices table may be used. A maximum of 60 devices may be
13N/P
5-492390-5
connected to a single loop.
4. No end of line device is required.
5. Both circuits are power limited per NFPA 70,
3-184940-513N/P
3-904580-513N/P
noitidEht8468LUrepdetsiL
NEC. Each detector, or group of detectors, requires a two-wire circuit of 18 AWG minimum. For additional wiring information, refer to the Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 315-092772.
Analog Device Loops 1 and 2 (TB2 and TB3)
These two ALD-2I loops each support up to 60 analog type devices.
To install a device for Class B, refer to Figure 6 and the electrical specifications.
To install a device for Class A, refer to Figure 6 and the electrical specifications.
TB2
TB3
4
4
SUPERVISED, POWER LIMITED PER NEC 760
CLASS B WIRING*
_
3
3
+
2
2
1
1
JUMPERS ARE OPTIONAL FOR MMB-3. REFER TO CSG-M REV. 17.01 FOR CONFIGURATION.
T-TAPPING ALLOWED
*OPERATES IN FULL COMFORMITY WITH STYLE 4
INITIATING DEVICE
6. Total circuit resistance must not exceed 100 ohms.
Maximum capacitance:
0.4μF line to line
0.8μF line to ground
7. T-tapping is NOT allowed on Class A loops.
The jumpers shown in Figure 6 for Class B
8. wiring are optional. They are not required if the proper settings are made in CSG-M Rev. 17.01 or higher.
CLASS A WIRING**
NO
T-TAPPING ALLOWED
TB2
TB3
4
4
3
3
2
2
1
1
SUPERVISED, POWER LIMITED PER NEC 760
_
_
+
+
**OPERATES IN FULL COMFORMITY WITH STYLE 6
Positive and negative ground fault detected at <40K ohms for TB2 (1-4) and TB3 (1-4).
Figure 6
Wiring the ALD-2I Analog Loops
5
Page 6
SPOOLECIVEDGOLANA
SECIVEDELBITAPMOC
elbitapmoC
seciveD
§
1-MZC
esaB
—9-527090-513N/P
noitallatsnI
snoitcurtsnI
6B1-MZC— 7-553590-513N/P
*11-TPF/11-PF
TPDA
11-BD
P
-BDhtiwS3-BD 01-129590-513N/P
01-129590-513N/
HI06/I06-DISR3X-BD,S3-BD2-782090-513N/P
HAI06/AI06-DISR3X-BD,S3-BD2-782090-513N/P
HBI06/BI06-DI
I3-DA
A
IRX3-D
6-432390-513N/P 5-532390-513N/P
H1/1-ILISR3X-BD,S3-BD4-783590-513N/P
HA1/A1-ILISR3X-BD,S3-BD4-783590-513N/P
HB1/B1-ILI
I3-DA
IRX3-DA
6-432390-513N/P 5-532390-513N/P
1-TPLI/1-PLISR3X-BD,S3-BD8-495290-513N/P
PLI
)d(1-PLI
3-DA
PLIRX3-DA
6-432390-513N/P 5-532390-513N/P
**2-PLISR3X-BD,S3-BD5-820590-513N/P
†)d(**2-PLI
PLI3-DA
DA
PLIRX3-
6-432390-513N/P 5-532390-513N/P
1-TLIS3-BD1-633390-513N/P
02/01-ISM— 3-309090-513N/P
B02/B01-ISM— 7-923390-513N
/P
F6B-ISM— 5-203590-513N/P
6BM-ISM— 1-316390-513N/P
§
R6B/D6B/6B-IRT
§
M6B-IRT
§
SMM-IRT
§
DTM-IRT
—3-513390-513N/P
—2-584940-513N/P
—1-745996-513N/P
—1-845996-513N/P
R/D/S-IRT4-184940-513N/P
.erawmrifretaerg
.erawmrif
§
.noitacilppatcudtops
.noitidEht8468LUrepdetsiL
ro0.01.veRVLXM/LXMhtiwelbitapmocylnosi11-TPF/PFehT*
retaergro0.8.veRVLXM/LXMhtiwelbitapmocylnosi2-PLIehT**
ebtsumnoitacilppaTCUDeht,derugifnocsiM-GSCehtnehW
anirognisuohtcudriananidesusiecivedehtnehwdetceles
Notification Appliance Circuits (TB7, 1-4 and TB6, 5-8) (Refer to Figure 7)
1. These circuits are for notification appliances only, NFPA 72 Local. For NFPA 72 Municipal Tie or NFPA 72 Leased Line, use the Model CSM-4.
2. All wiring must be in accordance with Article 760 of NEC or local building codes.
3. Both notification appliance circuits are power limited to NFPA 70 and NEC.
4. Electrical ratings: Special Application
Supervisory: 16 to 32 V unfiltered full
wave, 12mA max
Alarm: 16 to 32 V unfiltered full
wave, 1.5A max
5. Resistor end of line assembly:
P/N 140-049098
6. Maximum loop resistance: 3 ohms max
7. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
8. The jumpers for Class B NAC circuits can be removed if the resistor assembly is placed on terminals 1 and 4 and/or 5 and 8.
9. For synchronized notification appliances, use of either a DSC, DSC-W, or PAD-3 is required.
CLASS B WIRING
TB6 TB7
8
7
6
5
TB6 TB7
8
7
6
5
TB6 TB7
8
7
6
5
4
+
3
2
_
1
OPTIONAL CLASS B WIRING (MMB-3 ONLY)
4
+
3
2
_
1
NOTIFICATION APPLIANCES
+
4
+
3
2
_
1
_
NOTIFICATION APPLIANCES
(STYLE Y)
(STYLE Y)
CLASS A WIRING
(STYLE Z)
NOTIFICATION APPLIANCES
RES EOL ASSEMBLY
2.2K,1/2W, P/N 140-049098
RES EOL ASSEMBLY
2.2K,1/2W P/N 140-049098
RES EOL ASSEMBLY
2.2K,1/2W P/N 140-049098
Positive and negative ground fault detected at <30K ohms
for TB6 (5-8) and TB7 (1-4).
Figure 7
Wiring Notification Appliance Circuits
(Polarity Shown In Supervisory)
6
Page 7
Common Alarm Relay
The common alarm relay changes state when­ever a fire alarm is detected. The relay is rated 2A, 30 VDC/120 VAC resistive. See Figure 8 for the wiring connections. Use only with power limited/Class 2 circuits.
Common Supervisory Relay
The supervisory relay changes state whenever a supervisory trouble is detected. It may be used for alternate functions if programmed by CSG-M for them. The relay is rated 2A, 30 VDC/120 VAC resistive.
Refer to Figure 8 for wiring connections.
Use only with power limited/Class 2 circuits.
Common Trouble Relay
The trouble relay changes state whenever a System trouble is detected. The relay is rated for 2A, 30 VDC/120 VAC resistive. Refer to Figure 8 for the wiring connections. Use only with power limited/Class 2 circuits.
NOTE: This relay is normally energized.
Style 4 Network (MNET)
The MMB-3 provides a Style 4 MNET network for connection to remote power supplies (PSR-1) and annunciators (MOI-1/7, RCC). See Figure 9
wiring instructions.
for
Style 7 Network (MNET)
The MMB-3 provides a Style 7 MNET network for connection to remote power supplies (PSR-1) and annunciators (MOI-7, RCC). See Figure 10 for
wiring instructions.
FUSE REPLACEMENT IN THE MXL SYSTEM
SGNITARESUF
1FtupnI6-SPM
2FlasreveRyrettaB
3FrewoP6B1-MZC
4F
oN
tuptuOV42
)2dna1slanimret,9BT(
,GA3,A8
wolBlamroN
,GA3,A02
wolBlamroN
,GA3,A2
wolBlamr
,GA3,A51
wolBlamroN
9
8
7
6
5
4
3
2
1
TB4
RATINGS
2A, 30 VDC/120 VAC RESISTIVE
CONTACTS ARE SHOWN IN NORMAL STATE
SUPERVISORY
TROUBLE
ALARM
Figure 8
MMB-3 Relay Connections
5FxuAV5
6FregrahCyrettaB
,GA3,A1
wolBlamroN
GA3,A5
mroN
wolBla
For additional wiring information, refer to the Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 315-092772.
ELECTRICAL RATINGS
tnerruCeludoMCDV5evitcAAm0
*tnerruCeludoMCDV42evitcAAm554
Am063
tnerruCeludoMCDV42ybdnatS
.3-BMMehtybderewopsecived
CANsedulcni(
vedenilfodne
roseludomybnwardtnerrucynaedulcnitonseoD*
)seci
7
Page 8
PSR-1
4
3
2
1
TB4
NETWORK
NETWORK
EOLR 120 OHMS, 1/4W, 5% P/N 140-820150
MOI-1/7
PSR-1
TB4
TB1
PSR-1
TB4
4
3
2
1
EOLR 120 OHMS, 1/4W, 5% P/N 140-820150
NO EOLR
NO EOLR
MOI-7
NO EOLR
NO EOLR
PSR-1
TB4
TB1
4
3
2
1
4
3
2
1
SET "MMB-3 MNET STYLE 7"
TO "NO" IN THE CSGM.
2
1
4
3
2
1
NO EOLR
18 AWG MIN 5000 FEET MAX USE TWISTED PAIR OR SHIELDED TWISTED PAIR POWER LIMITED TO NFPA 70 PER NEC 760 MAX VOLTAGE: 8V P-P MAX CURRENT: 150mA
TERMINATE THE SHIELD AT THE MMB-3 CHASSIS ONLY
NO EOLR
SET "MMB-3 MNET STYLE
7" TO "YES" IN THE CSGM.
18 AWG MIN 5000 FEET MAX USE TWISTED PAIR OR SHIELDED TWISTED PAIR POWER LIMITED TO NFPA 70 PER NEC 760 MAX VOLTAGE: 8V P-P MAX CURRENT: 150mA
TERMINATE THE SHIELD AT THE MMB-3 CHASSIS ONLY
RES EOL ASSEMBLY
120 OHMS, 1/4W, 5%
P/N 140-049099
SHIELD
TB1
4
2
CHASSIS
MMB-3
3
1
Positive and negative ground fault
detected at <20K ohms for TB1(1-4).
Figure 9
Style 4 Network (MNET)
SHIELD
TB1
4
3
2
EOLR 120 OHMS,
1/4W, 5%
P/N 140-049099
1
Positive and negative ground fault
detected at <20K ohms for TB1(1-4).
Figure 10
Style 7 Network (MNET)
CHASSIS
MMB-3
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-048860-7
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
Loading...