Siemens MM55, MM12, MM75, MM110, MM150 Operating Instructions Manual

...
Page 1
© Siemens plc 1997
G85139-H1750-U049-B
26/09/97
Contents
Safety Instructions..............................................................2
1. OVERVIEW ......................................................................3
2. INSTALLATION ...............................................................4
4. OPERATING MODES....................................................17
5. SYSTEM PARAMETERS...............................................20
6. FAULT CODES..............................................................34
7. SPECIFICATIONS..........................................................35
8. SUPPLEMENTARY INFORMATION .............................37
MICROMASTER
Operating Instructions
Page 2
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
Safety Instructions
Before installing and putting this equipment into operation, please read these safety instructions and warnings carefully and all the warning labels attached to the equipment. Make sure that the warning labels are kept in a legible condition and replace missing or damaged labels.
WARNING
This equipment contains dangerous voltages and controls dangerous rotating mechanical parts. Loss of life, severe personal injury or property damage can result if the instructions contained in this manual are not followed.
Only suitable qualified personnel should work on this equipment, and only after becoming familiar with all safety notices, installation, operation and maintenance procedures contained in this manual. The successful and safe operation of this equipment is dependent upon its proper handling, installation, operation and maintenance.
MICROMASTERS operate at high voltages.
Only permanently-wired input power
connections are allowed. This equipment must be grounded (IEC 536 Class 1, NEC and other applicable standards).
If a Residual Current-operated protective
Device (RCD) is to be used, it must be an RCD type B.
Machines with a three phase power supply,
fitted with EMC filters, must not be connected to a supply via an ELCB (Earth Leakage Circuit-Breaker - see DIN VDE 0160, section
6.5).
The following terminals can carry dangerous
voltages even if the inverter is inoperative:
- the power supply terminals L/L1, N/L2, L3.
- the motor terminals U, V, W.
Only qualified personnel may connect, start
the system up and repair faults. These personnel must be thoroughly acquainted with all the warnings and operating procedures contained in this manual.
Certain parameter settings may cause the
inverter to restart automatically after an input power failure.
This equipment must not be used as an
‘emergency stop’ mechanism
(see EN 60204,
9.2.5.4)
If motor thermal protection is required, then an
external PTC must be used. (
Refer to Sectio
n
2.3.5.)
Lowering the fan tray on Frame Size C
MICROMASTER exposes rotating parts
.
Power must be isolated prior to this operation.
CAUTION
Children and the general public must be
prevented from accessing or approaching the equipment!
This equipment may only be used for the
purpose specified by the manufacturer. Unauthorised modifications and the use of spare parts and accessories that are not sold or recommended by the manufacturer of the equipment can cause fires, electric shocks and injuries.
Keep these operating instructions within easy
reach and give them to all users!
European Low Voltage Directive
The MICROMASTER product range complies with the requirements of the Low Voltage Directive 73/23/EEC as amended by Directive 98/68/EEC. The units are certified for compliance with the following standards:
EN 60146-1-1 Semiconductor converters - General requirements
and line commutated converters
EN 60204-1 Safety of machinery - Electrical equipment of
machines
European Machin ery Directive
The MICROMASTER inverter series does not fall under the scope of the Machinery Directive. However, the products have been fully evaluated for compliance with the essential Health & Safety requirements of the directive when used in a typical machine application. A Declaration of Incorporation is available on request.
European EMC Directive
When installed according to the recommendations described in this manual, the MICROMASTER fulfills all requirements of the EMC Directive as defined by the EMC Product Standard for Power Drive Systems EN61800-3.
UL and CUL listed.
ISO 9001
Siemens plc operates a quality management system which complies with the requirements of ISO 9001.
Page 3
1. OVERVIEW English
© Siemens plc 1997 G85139-H1750-U049-B
3
2
6/09/9
7
1. OVERVIEW
The MICROMASTERS are a range of frequency inverters for controlling the speed of three phase AC motors. Various models are available, ranging from the compact 120 W single phase input MICROMASTER up to the 7.5 kW three phase input MICROMASTER.
The inverters are microprocessor-controlled and use state of the art IGBT technology for reliability and flexibility. A special pulse-width modulation method with selectable ultrasonic pulse frequency permits extremely quiet motor operation. Inverter and motor protection is provided by comprehensive protective functions.
Features:
Easy to install, program and commission.
Closed loop control using a Proportional, Integral (PI) control loop function.
High starting torque with automatic starting boost.
Remote control capability via RS485 serial link using the USS protocol with the ability to control up to 31
inverters.
A comprehensive range of parameters is provided to enable the inverters to be configured for use in almost any application.
Membrane-type front panel controls for simple operation.
Built-in non-volatile memory for storing parameter settings.
Factory default parameter settings pre-programmed for European and North American requirements.
Output frequency (and hence motor speed) can be controlled by one of five methods:
(1) Frequency setpoint using the keypad. (2) High resolution analogue setpoint (voltage input). (3) External potentiometer to control motor speed. (4) Fixed frequencies via binary inputs. (5) Serial interface.
Built-in DC injection brake with special COMPOUND BRAKING.
Integral RFI filter on single phase input inverters (MM12 - MM300).
Acceleration/deceleration times with programmable smoothing.
Fully programmable single relay output incorporated.
External Options connector for optional multi-language Clear Text Display (OPM2) or optional PROFIBUS
module.
Automatic recognition of 2, 4, 6 or 8-pole motors by software.
Integral software-controlled cooling fan.
Fast Current Limit (FCL) for reliable trip-free operation.
Compact design and the ability to mount inverters side by side provides greater space saving.
Page 4
English 2. INSTALLATION
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
4
2. INSTALLATION
2.1 Wiring Guidelines to Minimi se the Effects of EMI
The inverters are designed to operate in an industrial environment where a high level of Electro-Magnetic Interference (EMI) can be expected. Usually, good installation practices will ensure safe and trouble-free operation. However, if problems are encountered, the following guidelines may prove useful. In particular, grounding of the system 0V at the inverter, as described below, may prove effective. Figure 1 illustrates how an RFI suppression filter should be installed.
(1) Ensure that all equipment in the cubicle is well earthed using short, thick earthing cable connected to
a common star point or busbar. It is particularly important that any control equipment that is connected to the inverter (such as a PLC) is connected to the same earth or star point as the inverter via a short, thick link. Flat conductors (e.g. braids or metal brackets) are preferred as they have lower impedance at high frequencies.
The return earth from motors controlled by the inverters should be connected directly to the earth connection (PE) on the associated inverter.
(2) Wherever possible, use screened leads for connections to the control circuitry. Terminate the ends of
the cable neatly, ensuring that unscreened wires are as short as possible. Use cable glands whenever possible.
(3) Separate the control cables from the power connections as much as possible, using separate
trunking, etc. If control and power cables cross, arrange the cables so that they cross at 90° if possible.
(4) Ensure that contactors in the cubicle are suppressed, either with R-C suppressors for AC contactors
or ‘flywheel’ diodes for DC contactors, fitted to the coils. Varistor suppressors are also effective. This is particularly important if the contactors are controlled from the relay on the inverter.
(5) Use screened or armoured cables for the motor connections and ground the screen at both ends via
the cable glands.
(6) If the drive is to be operated in an Electro-magnetic noise-sensitive environment, the RFI footprint
filter kit should be used to reduce the conducted and radiated interference from the inverter. For optimum performance, there should be a good conductive bond between filter and metal mounting plate.
On no account must safety regulations be compromised when installing inverters!
Page 5
2. INSTALLATION English
© Siemens plc 1997 G85139-H1750-U049-B
5
2
6/09/9
7
When cable glands cannot be used, terminate screen to metal panel by removing cable sheath.
MAINS POWER
CABLE
MOTOR
CABLE *
CONTROL
CABLE
SCREENED
CABLE
SCREENED
CABLE
* Note: Screen must be terminated
at the motor.
When attempting to meet specific EMC limits by using a filter, the following points must be observed:
(1) All cables to and from the inverter (including control
cables) must be screened using suitable glands.
(2) The control cable must be kept separate from the motor
and mains cables.
EARTH STUD
FILTER UNIT
Note: There must be a good
conduc tive bond between filter and
metal panel.
Connect to Mains and
PE terminals on Inverter
EARTH STUD
(under)
Figure 1: Example of an RFI Suppression Filter Installation
Page 6
English 2. INSTALLATION
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
6
2.2 Mechanical Installation
WARNING
THIS EQUIPMENT MUST BE EARTHED. To guarantee the safe operation of the equipment it must be installed and commissioned properly
by qualified personnel in compliance with the warnings l aid dow n in these operating i nstructions. Take particular note of the general and regional installation and safety regulations regarding wor
k
on dangerous voltage installations (e.g. VDE), as well as the relevant regulations regarding the correct use of tools and personal protective gear.
The mains input and motor terminals can carry dangerous voltages even if the inverter is inoperative. Use insulated screwdrivers only on these terminal blocks.
Environmental Requirements
Hazard Notes Ideal Installation
Temperature
Altitude
Shock
Vibration
Electro-Magnetic Radiation
Atmospheric Pollution
Water
Overheating
Min. = 0°C Max. = 50°C
If the Inverter is to be installed at an altitude > 1000 m, derating will be required.(Refer to DA 64 Catalogue).
Do not drop the inverter or expose to sudden shock.
Do not install the inverter in an area where it is likely to be exposed to constant vibration.
Do not install the inverter near sources of electro-magnetic radiation.
Do not install the inverter in an environment which contains atmospheric pollutants such as dust, corrosive gases, etc.
Take care to site the inverter away from potential water hazards. e.g. Do not install the inverter beneath pipes that are subject to condensation.
Ensure that the inverter’s air vents are not obstructed. Make sure that there is an adequate air-flow through the cabinet, as follows:
1. Using the formula below, calculate the airflow required. Air-flow (m3 / hr) = (Dissipated Watts / T) x 3. 1
2. Install cabinet cooling fan(s) if necessary,
Note:
Typical dissipation (Watts) = 3% of inverter rating. T = Allowable temperature rise within cabinet
in °C.
3.1 = Specific heat of air at sea level.
160 mm
100 mm
Page 7
2. INSTALLATION English
© Siemens plc 1997 G85139-H1750-U049-B
7
2
6/09/9
7
DIN Rail
Depth D
W
H2H1
F
= 4.5 mm
Depth D
W
HH1
= 4.8 mm (B) = 5.6 mm (C)
W1
Frame Size A Frame Sizes B and C
Frame size B:
4 bolts M4 4 nuts M4
4 washers M4
2 bolts M4
2 nuts M4
2 washers M4
Frame size C:
4 bolts M5
4 nuts M5
4 washers M5
H
H2
Tightening Torque
(with washers fi tted)
2.5 Nm Frame size A and B
3.0 Nm Frame size C
Model
MMxxx
1 AC 230 V
Class A
Filter
MMxxx/2
1/3 AC 230 V
Without
Filter
MMxxx/3
3 AC 380 -
500 V
Without
Filter
Frame Sizes
(all measurements in m m)
MM12 MM25 MM37 MM55 MM75 MM110 MM150 MM220 MM300 MM400 MM550 MM750
A A A A A B B C C
-
-
-
A A A A A B B C C C
-
-
-
­A A A A A B B
C C C
H W D H1 H2 W1 F
A = 147 x 73 x 141 160 175 - 55 B = 184 x 149 x 172 174 184 138 - C = 215 x 185 x 195 204 232 174 -
Figure 2: Mechanical Installation Diagram
Page 8
English 2. INSTALLATION
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
8
2.3 Electrical Installation
The electrical connectors on the MICROMASTER are shown in Figure 3. Connect the cables to the power and control terminal blocks in accordance with the information supplied in sections 2.3.1 - 2.3.4. Ensure that the leads are connected correctly and the equipment is properly earthed as shown in Figure 3.
CAUTION
The control, power supply and motor leads must be laid separately. They must not be fed through the same cable conduit/trunking.
Use screened cable for the control lead. Use Class 1 60/75oC copper wire only (for UL compliance). Tightening torque for the power (mains input and motor) terminals is 1.1 Nm.
To tighten up the power/motor terminal screws use a 4 - 5 mm cross-tip screwdriver.
2.3.1 Power and Motor Connections - Frame Size A
Ensure that the power source supplies the correct voltage and is designed for the necessary current
(see
section 7)
. Ensure that the appropriate circuit-breakers/fuses with the specified current rating are connected
between the power supply and inverter
(see section 7)
.
Connect the power and motor connections as shown in Figure 3.
WARNING
Isolate the supply before making or changing connections. Ensure that the motor is configured for the correct supply voltage.
Single/three phase 230 V
MICROMASTERS m ust not be connected to a 400 V thr ee phase supply.
When synchronous machines are connected or when coupling several motors in parallel, the inverter must be operated with voltage/frequency control characteristic (P 077= 0 or 2).
Page 9
2. INSTALLATION English
© Siemens plc 1997 G85139-H1750-U049-B
9
2
6/09/9
7
Control
Terminals
Mains Input
Terminals
Motor Term i nals
V
U
PE
PE
L/L1
N/L2
L3
W
FUSES
CONTACTOR
FILTER
(Class B only)
N
L
MICROMASTER
NL3L2
L1PEPEPEWWV
V
UUFUSES
TYPICAL INSTALLATION
CONTACTOR
FILTER
L3
MICROMASTER
L1
L2
L3
L2
L1PEPEPEWWVVU
U
MOTOR
MOTOR
THREE PHASE
SINGLE PHASE
Figure 3: Power Connections
Page 10
English 2. INSTALLATION
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
10
2.3.2 Power and Motor Connections - Frame Size B
The terminal arrangement for frame size B is identical to frame size A
(see Figure 3)
. However, before the wires can be connected to the terminal blocks, you must lower the terminal access panel and secure the cables to the gland plate.
Refer to Figures 3 and 4. Proceed as follows:
1. Insert the blade of a small screwdriver into slot A on the side of the inverter and press in the direction of
the arrow. At the same time, apply finger pressure to clip B on the other side of the access panel and press in the direction of the arrow.
This will release the access panel, which will then swing down on its rear-mounted hinges.
2. Remove the gland plate by applying pressure to release clips C and D in the direction of the arrows.
3. Secure each cable to the correct hole in the gland plate, ensuring that the exposed wires are long enough
to reach the terminal blocks.
4. Before refitting the gland plate, feed the control wires (if used) through hole 1 and the mains input and
motor wires through hole 2. IT IS MOST IMPORTANT THAT THE MOTOR AND CONTROL WIRES ARE KEPT APART.
5. Refit the gland plate. Ensure that the release clips snap into position.
6. Connect the wires to the terminal blocks as shown in Figure 3. (See section 2.3.4 for information about
connecting the control wires.)
7. Close the terminal access panel.
E
F
G
D
A
B
C
A & B: Term inal cover release tabs C & D: Gland plate release tabs E: Control cable input (16. 2 mm diameter; accepts cables up to 10 mm dia meter) F: Mains cable input (22.8 mm diameter; accepts ca bles up to 14.5 mm diameter) G: Motor cable input (22.8 mm diameter; accepts cables up to 14 .5 mm diameter)
Figure 4: Power Connections Access Diagram - Frame Size B
Page 11
2. INSTALLATION English
© Siemens plc 1997 G85139-H1750-U049-B
11
2
6/09/9
7
2.3.3 Power and Motor Connections - Frame Size C
The terminal arrangement for frame size C is identical to frame size A
(see Figure 3)
. However, before the wires can be connected to the terminal blocks, you must lower the fan housing and secure the cables to the gland plate.
Refer to Figure 5 and proceed as follows:
1. While supporting the fan housing with one hand, insert the blade of a screwdriver into slot A on the
underside of the inverter and press upwards to release the securing tab. Lower the fan housing, allowing it to swing out to the right on its side-mounted hinges.
2. Applying pressure to the gland plate release clips B and C in the direction of the arrows. Swing the plate
out to the left on its side-mounted hinges,
3. Secure each cable to the correct hole in the gland plate, ensuring that the exposed wires are long enough
to reach the terminal blocks.
4. Connect the wires to the terminal blocks as shown in Figure 3. (See section 2.3.4 for information about
connecting the control wires.) IT IS MOST IMPORTANT THAT THE MOTOR AND CONTROL WIRES ARE KEPT APART.
5. Swing the gland plate back into the base of the inverter. Ensure that the release clips snap into position.
6. Swing the fan housing back into the base of the inverter.
F
E
D
B
A
C
A: Fan housing release tab B & C: Gland plate release tabs D: Control cable input (16.2 mm diameter; accepts cables up to 10 mm diameter) E: Mains cable input (22.8 mm diameter; accepts cables up to 14.5 mm diameter) F: Motor cable input (22.8 mm diameter; accepts cables up to 14.5 mm diameter)
Figure 5: Power Connections Access Diagram - Frame Size C
Page 12
English 2. INSTALLATION
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
12
2.3.4 Control Connections
1234856791011
Power Supply
(+10 V, max. 10 mA )
Analog ue Input
(0/2 - 10 V)
(input impedance = 70 k Ω)
Output Relay
(normally open)
max. 0.4 A / 110 V AC
1 A / 30 V DC
(resistive rating)
Digital Inputs
(7.5 - 33 V, max. 5 mA)
Power Supply
for
PI Feed back
Transducer or other
load
(+15 V, max. 50 mA)
P10+0VAIN+
AIN-
P15+
DIN1
DIN2
DIN3
RL1B
(NO)
RL1C
(COM)
0V
Control Terminal Block
Insert small blade screwdriver
(max. 3.5 mm) as shown while
inserting control wire from below.
Front Panel
RS485 D-type
N-
0V
5V
(max.250 mA)
P+
615
9
Figure 6: Control Connections
Page 13
2. INSTALLATION English
© Siemens plc 1997 G85139-H1750-U049-B
13
2
6/09/9
7
2.3.5 Motor Overload Protection
When operated below rated speed, the cooling effect of fans fitted to the motor shaft is reduced. Consequentially, most motors require de-rating for continuous operation at low frequencies. To ensure that motors are protected against overheating under these conditions, a PTC temperature sensor must be fitted to the motor and connected to the inverter control terminals as shown in Figure 7.
Note: To enable the trip function, set parameter P051, P052 or P053 =19.
MOTOR
PTC
1k
897
Inverter Contro l Terminals
Figure 7: Motor Overload PTC Connection
2.3.6 Block Diagram
P
Jog
M
PE U, V, W
3 ~
CPUADSI
2 3 4
5 6
10 11
PE
1/3 AC 230 V 3 AC 380 - 500 V
L/L1, N/L2 or L/L1, N/L2, L3
1
7
+10V0V–+24 VORORV:0 - 10 V
2 - 10 V
AIN+
AIN-
DIN1
DIN2
DIN3PERL1
≥ 4.7 k
~
RL1B
RL1C8+15V
0V9Power Supply for
PI Feedback
Transducer
or other load.
RS485
Figure 8: Block Diagram
Page 14
English 3. FRONT PANEL CONTROLS & BASIC OPERATION
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
14
3. FRONT PANEL CONTROLS & BASIC OPERATION
3.1 Front Panel Controls
CAUTION
The digital frequency setpoint has been set at 5.00 Hz in the factory. This means that, it is not necessary to enter a frequency setpoint via the button or parameter P005 in order to test that the motor turns following a RUN command.
All settings must only be entered by qualified personnel, paying particular attention to the safety precautions and warnings.
The parameter settings required can be entered using the three parameterisation buttons (P, and ) on the front panel of the inverter. The parameter numbers and values are indicated on the four digit LED display.
FORWARD / REVERSE
Button
LED Display
RS485
Interface
RUN
Button
STOP
Button
Removable Cover Strip
JOG
Button
UP / INCREASE
Frequency
DOWN / DECREASE
Frequency
Parameterisation
Button
P
Jog
Pressing this button while the inverter is stopped causes it to start and run at the preset jog frequency. The inverter stops as soon as the button is released. Pressing this button while the inverter is running has no effect. Disabled if P123 = 0.
Press to start the inverter. Disabled if P121 = 0.
Press to stop the inverter.
LED Display
Displays frequency (default), parameter numbers or parameter values (when P is pressed) or fault codes. Press to change the direction of rotation of the motor. REVERSE is indicated by a minus sign (values < 100) or a flashing decimal point (values > 100). Disabled if P122 = 0
Press to INCREASE frequency. Used to change parameter numbers or values to higher settings during the parameterisation procedure. Disabled if P124 = 0.
Press to DECREASE frequency. Used to change parameter numbers or values to lower settings during the parameterisation procedure. Disabled if P124 = 0.
Press to access parameters. Disabled if P051 - P053 = 14 when using digital inputs.
Figure 9: Front Panel
Jog
P
Page 15
3. FRONT PANEL CONTROLS & BASIC OPERATION English
© Siemens plc 1997 G85139-H1750-U049-B
15
2
6/09/9
7
3.2 Basic Operation
Refer to section 5 for a full description of each parameter.
3.2.1 General
(1) The inverter does not have a main power switch and is live when the mains supply is connected. It waits,
with the output disabled, until the RUN button is pressed or for the presence of a digital ON signal at terminal 5 (rotate right) or terminal 6 (rotate left) -
see parameters P051 - P053
.
(2) If output frequency is selected to be displayed (P001 = 0), the corresponding setpoint is displayed
approximately every 1.5 seconds while the inverter is stopped.
(3) The inverter is programmed at the factory for standard applications on Siemens four-pole standard
motors. When using other motors it is necessary to enter the specifications from the motor’s rating plate into parameters P081 to P085
(see Figure 10)
. Note: Access to these parameters is not possible
unless P009 has been set to 002 or 003.
3 Mot
IEC 56 IM B3
cosϕ 0,81 cosϕ 0,81
1LA5053-2AA20 Nr. E D510 3053 IP54 Rot. KL 16 I.Cl.F
12 022
60 Hz 440 V Y
0,34 A 0,14 kW
3310 /min
220
/380 V
/Y
0,12
2745
VDE 0530 S.F. - 1,15
/min
P081
P084
P083 P082 P085
0,61/0,35 A
50 Hz
kW
Figure 10: Typical Motor Rating Plate Example
Note: Ensure that the inverter is configured correctly to the motor, i.e. in the above example delta
terminal connection is for 220 V.
3.2.2 Initial Testing
(1) Check that all cables have been connected correctly
(section 2)
and that all relevant product and
plant/location safety precautions have been complied with. (2) Apply mains power to the inverter. (3) Ensure that it is safe to start the motor. Press the RUN button on the inverter. The display will change to 5.0
and the motor shaft will begin to turn. It will take one second for the inverter to ramp up to 5 Hz. (4) Press the STOP button. The display will change to 0.0 and the motor slow to a complete stop within one
second.
Page 16
English 3. FRONT PANEL CONTROLS & BASIC OPERATION
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
16
3.2.3 Basic Operation - 10 Step Guide
The basic method of setting up the inverter for use is described below. This method uses a digital frequency setpoint and requires only the minimum number of parameters to be changed from their default settings. It assumes that a standard Siemens four-pole motor is connected to the inverter
(see section 3.2.1 if a different
motor type is being used)
.
Step /Action Button Display
1. Apply mains power to the inverter. The display will alternate between the actual frequency (0.0 Hz) and the
requested frequency setpoint (5.0 Hz default).
2. Press the parameterisation button.
3. Press the button until parameter P005 is displayed.
4. Press P to display the current frequency setpoint (5 Hz is the factory default setting).
5. Press the button to set the desired frequency setpoint (e.g. 35 Hz).
6. Press P to lock the setting into memory.
7, Press the button to return to P000.
8. Press P to exit the parameterisation procedure. The display will alternate between the current frequency and the requested
frequency setpoint.
9. Start the inverter by pressing the RUN button. The motor shaft will start to turn and the display will show that the inverter
is ramping up to the setpoint of 35 Hz.
Note
The setpoint will be achieved after 7 seconds (35 Hz/50 Hz x 10 s *).
If required, the motor’s speed (i.e. frequency) can be varied directly by using the ∆ ∇ buttons. (Set P011 to 001 to enable the new frequency setting to be retained in memory during periods when the inverter is not running.)
10. Switch the inverter off by pressing the STOP button. The motor will slow down and come to a controlled stop (takes 7 s **).
* Default ramp-up time is 10 s to reach 50 Hz (defined by P002 and P013). ** Default ramp-down time is 10 s from 50 Hz (defined by P003 and P013).
P
P
P
P
Page 17
4. OPERATING MODES English
© Siemens plc 1997 G85139-H1750-U049-B
17
2
6/09/9
7
4. OPERATING MODES
4.1 Digital Control
For a basic startup configuration using digital control, proceed as follows: (1) Connect control terminal 5 to terminal 8 via a simple on/off switch. This sets up the motor for clockwise
rotation (default). (2) Apply mains power to the inverter. Set parameter P009 to 002 or 003 to enable all parameters to be
adjusted. (3) Check that parameter P006 is set to 000 to specify digital setpoint. (4) Set parameter P007 to 000 to specify digital input (i.e. DIN1 (terminal 5) in this case) and disable the front
panel controls. (5) Set parameter P005 to the desired frequency setpoint. (6) Set parameters P081 to P085 in accordance with the rating plate on the motor
(see Figure 10)
.
Note: In many cases, when default factory parameters are used, the default stator resistance set in
P089 will generally suit the default power rating set in P085. Should the inverter and motor ratings differ greatly, it is recommended that the stator resistance of the motor is measured and entered manually into P089. Continuous Boost (P078) and Starting Boost (P079) are dependent on the value of Stator Resistance - too high a value may cause overcurrent trips
(7) Set the external on/off switch to ON. The inverter will now drive the motor at the frequency set by P005.
4.2 Analogue Control
For a basic startup configuration using analogue voltage control, proceed as follows: (1) Connect control terminal 5 to terminal 8 via a simple on/off switch. This sets up the motor for clockwise
rotation (default). (2) Connect a 4.7 k potentiometer to the control terminals as shown in Figure 6 or connect pin 2 (0V) to pin
4 and a 0 - 10 V signal between pin 2 (0V) and pin 3 (AIN+). (3) Apply mains power to the inverter. Set parameter P009 to 002 or 003 to enable all parameters to be
adjusted. (4) Set parameter P006 to 001 to specify analogue setpoint. (5) Set parameter P007 to 000 to specify digital input (i.e. DIN1 (terminal 5) in this case) and disable the front
panel controls. (6) Set parameters P021 and P022 to specify the minimum and maximum output frequency settings. (7) Set parameters P081 to P085 in accordance with the rating plate on the motor
(see Figure 10).
Note: In many cases, when default factory parameters are used, the default stator resistance set in
P089 will generally suit the default power rating set in P085. Should the inverter and motor ratings differ greatly, it is recommended that the stator resistance of the motor is measured and entered manually into P089. Continuous Boost (P078) and Starting Boost (P079) are dependent on the value of Stator Resistance - too high a value may cause overcurrent trips
(8) Set the external on/off switch to ON. Turn the potentiometer (or adjust the analogue control voltage) until
the desired frequency is displayed on the inverter.
Page 18
English 4. OPERATING MODES
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
18
4.3 Stopping the Motor
Stopping can be achieved in several ways:
Cancelling the ON command or pressing the OFF button (O) on the front panel causes the inverter to
ramp down at the selected ramp down rate
(see P003)
.
OFF2 - operation causes the motor to coast to a standstill
(see parameters P051 to P053)
.
OFF3 - operation causes rapid braking
(see parameters P051 to P053)
.
DC injection braking up to 250% causes a rapid stop
(see P073)
.
4.4 If the Motor Does Not Start Up
If the display shows a fault code, refer to Section 6. If the motor does not start up when the ON command has been given, check that the ON command is valid,
check if a frequency setpoint has been entered in P005 and check that the motor specifications have been entered correctly under parameters P081 to P085.
If the inverter is configured for operation via the front panel (P007 = 001) and the motor does not start when the RUN button is pressed, check that P121 = 001 (RUN button enabled).
If the motor does not run after parameters have been changed accidentally, reset the inverter to the factory default parameter values by setting parameter P944 to 001 and then pressing P.
4.5 Local and Remote Control
The inverter can be controlled either locally (default), or remotely via a USS data line connected to the RS485 D-type connector on the front panel. (Refer to parameter P910 in section 5 for the available remote control options.)
When local control is used, the inverter can only be controlled via the front panel or the control terminals. Control commands, setpoints or parameter changes received via the RS485 interface have no effect.
When operating via remote control the inverter will not accept control commands from the terminals.
Exception: OFF2 or OFF3 can be activated via parameters P051 to P053 (refer to parameters P051 to P053 in section 5).
Several inverters can be connected to an external control unit at the same time. The inverters can be addressed individually.
For further information, refer to the following documents
(available from your local Siemens office)
:
E20125-B0001-S302-A1 Application of the USS Protocol in SIMOVERT Units 6SE21 and
MICROMASTER (German)
E20125-B0001-S302-A1-7600 Application of the USS Protocol in SIMOVERT Units 6SE21 and
MICROMASTER (English)
Page 19
4. OPERATING MODES English
© Siemens plc 1997 G85139-H1750-U049-B
19
2
6/09/9
7
4.6 Closed Loop Control
4.6.1 General Description
The MICROMASTER provides a PI control function for closed loop control
(see Figure 11)
. PI control is ideal for temperature or pressure control, or other applications where the controlled variable changes slowly or where transient errors are not critical. This control loop is not suitable for use in systems where fast response times are required.
Note: The closed loop function is not designed for speed control, but can be used for this provided that fast
response times are not required.
When closed loop PI control is enabled (P201 = 002), all setpoints are calibrated between zero and 100%, i.e. a setpoint of 50.0 = 50%. This allows general purpose control of any process variable that is actuated by motor speed and for which a suitable transducer is available.
Setpoint
Scaling
P211, P212
Feedback
Sample
Rate
P205
Low Pass
Filter
P206
P
P202
I
P203, P207
Acceleration/ Deceleration
Ramp
P002, P003
Motor
M
Process
e.g. fan
Transducer
P208
+
P201 = 000
Feedback
(e.g. duct pressure)
P201 = 002
Closed Loop Mode Disabled
Closed Loop Mode Enabled
P210
Feedback
Monitor
Figure 11: Closed Loop Control
4.6.2 Hardware Setup
Connect the outputs from the external feedback transducer to control terminals 3 and 4. This analogue input accepts a 0/2 - 10 V signal, has 10-bit resolution and permits a differential (floating) voltage. Ensure that the values of parameters P023 and P024 are set to 000 and that P006 is set to 000 or 002.
15 V dc power for the feedback transducer can be supplied from terminals 8 and 9 on the control block.
4.6.3 Parameter Settings
Closed loop control cannot be used unless P201 is first set to 002. Most of the parameters associated with closed loop control are shown in Figure 11. Other parameters which are also associated with closed loop control are as follows:
P001 (value = 007) P061 (value = 012 or 013) P210 P220
Descriptions of all closed loop control parameters are provided in section 5. For further detailed information about PI operation refer to the Siemens DA 64 Catalogue.
Page 20
English 5. SYSTEM PARAMETERS
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
20
5. SYSTEM PARAMETERS
Parameters can be changed and set using the membrane-type buttons to adjust the desired properties of the inverter, such as ramp times, minimum and maximum frequencies etc. The parameter numbers selected and the setting of the parameter values are indicated in the four digit LED display.
Note: If you press the or button momentarily, the values change step by step. If you keep the buttons
pressed for a longer time, the values scroll through rapidly.
Access to parameters is determined by the value set in P009. Check that the key parameters necessary for your application have been programmed.
Note: In the following parameter table:
Indicates parameters that can be changed during operation. ‘

’ Indicates that the value of this factory setting depends on the rating of the inverter.
To increase the resolution to 0.01 when changing frequency parameters, instead of pressing P momentarily to return to the parameter display, keep the button pressed until the display changes to ‘- -.n0’ (n = the current tenths value, e.g. if the parameter value = ‘055.8’ then n = 8). Press or to change the value (all values between .00 and .99 are valid) and then press P twice to return to the parameter display.
If parameters are changed accidentally, all parameters can be reset to their default values by setting parameter P944 to 1 and then pressing P.
Page 21
5. SYSTEM PARAMETERS English
Parameter Function Range
[Default]
Description / Notes
© Siemens plc 1997 G85139-H1750-U049-B
21
2
6/09/9
7
P000
Operating display - This displays the output selected in P001.
In the event of a fault, the relevant fault code (Fxxx) is displayed (see section 6). In the event of a warning the display flashes. If output frequency has been selected (P001 = 0) and the inverter is OFF, the display alternates between the selected frequency and the actual frequency.
P001
Display mode 0 - 8
[0]
Display select ion:
0 = Output frequency (Hz) 1 = Frequency setpoint (i.e. speed at whi ch inverter i s set to run)
(Hz)
2 = Motor current (A) 3 = DC-link voltage (V) 4 = Not used 5 = Motor RPM 6 = USS status (see section 8.2) 7 = Closed loop control setpoint (% of full scale) 8 = Output voltage
P002
Ramp up time (seconds) 0 - 650.00
[10.00]
This is the time taken for the motor to accelerate from standstill to the maximum frequency as set in P013.
Setting the ram p up ti me t oo short can cause the invert er to t rip (f ault code F002 - overcurrent).
Frequency
f
max
0 Hz
Time
Ramp up
time
(0 - 650 s)
P003
Ramp down time (seconds) 0 - 650.00
[10.00]
This is the time taken for t he mot or to decelerat e from maximum frequency (P013) to standstill.
Setting the ram p down ti me t oo short can cause the invert er to t rip (f ault code F001 - overvoltage).
This is also the period for which DC inj ection braki ng is applied (see P073)
Frequency
f
max
0 Hz
Time
Ramp down
time
(0 - 650 s)
Page 22
English 5. SYSTEM PARAMETERS
Parameter Function Range
[Default]
Description / Notes
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
22
P004
Smoothing (seconds) 0 - 40.0
[0.0]
Used to smooth the acceleration/deceleration of the m otor (useful in
applications where it is important to avoid ‘jerking’, e.g. conveyor systems, te xtiles, etc.).
Smoothing is only effective if the ramp up/down ti m e exceeds 0.3 s.
Frequency
f
max
(P013)
0 Hz
Time
Total acceleration time
= 15 s
P002 = 10 s
P004
= 5 s
P004
= 5 s
Note: The smoot hing curve for deceleration is based on the ram p
up gradient (P002) and is added to the ramp down time set by P003. Therefore, the ramp down tim e is af fected by changes to P002.
P005
Digital frequency setpoint (Hz) 0 - 400.00
[5.00]
Sets the frequency that the inverter will run at when operated in digital mode. Only effective if P006 set to ‘0’.
P006
Frequency setpoint source selection
0 - 2
[0]
Sets the control mode of the inverter.
0 = Digital. The inverter runs at the f requency set in P005.
Alternatively, if P007 is set t o zero, the frequency may be controlled by setting any two of bi nary inputs P051 - P053 t o values of 11 and 12.
1 = Analogue. Control via analogue input signal. 2 = Fixed frequency or motor potentiometer. Fixed frequency is
only selected if the value of at least one binary input (P051 ­P053) = 6, 17 or 18.
Notes: (1) If P006 = 1 and t he inverter is set up for rem ote
control operation, the analogue i nputs remain active.
(2) Motor potentiometer setpoints via digital inputs
are stored when P011 = 1.
P007
Keypad control 0 - 1
[1]
0 = Front panel buttons disabled (except STOP, and ). Control is
via digital inputs (see parameters P051 - P053). and may st ill be used to control frequency provided that P124 = 1 and a digital input has not been selected to perform this function.
1 = Front panel buttons enabled (can be individually disabled
depending on the setting of parameters P121 - P 124). Note: The digital inputs for RUN, REVERSE, JOG and increase/
decrease frequency are disabled.
P009
Parameter protection setting 0 - 3
[0]
Determines which parameters can be adjusted:
0 = Only parameters from P001 to P009 can be read/set. 1 = Parameters from P001 to P009 can be set and all other
parameters can only be read.
2 = All parameters can be read/set but P009 automatically resets to 0
when power is removed.
3 = All parameters can be read/set.
Page 23
5. SYSTEM PARAMETERS English
Parameter Function Range
[Default]
Description / Notes
© Siemens plc 1997 G85139-H1750-U049-B
23
2
6/09/9
7
P011
Frequency setpoint memory 0 - 1
[0]
0 = Disabled 1 = Enabled after switch-off. i.e. The setpoint alterations made with
the / buttons or digital inputs are stored even when power has been removed from the inverter.
P012
Minimum motor frequency (Hz) 0 - 400.00
[0.00]
Sets the minimum motor frequency (must be less than the value of P013).
P013
Maximum motor frequency (Hz) 0 - 400. 00
[50.00]
Sets the maximum mot or frequency.
P014
Skip frequency 1 (Hz) 0 - 400.00
[0.00]
A skip frequency can be set with this parameter to avoid the effect s of mechanical resonance. Frequencies within +/-(value of P019) of this setting are suppressed. Stationary operation is not possible within t he suppressed frequency range - the range is just passed through.
P015
Automatic restart after mains failure.
0 - 1
[0]
Setting this parameter to ‘1’ enables the inverter t o restart automatically after a mains break or ‘brownout’, provided the run/stop switch is still closed, P007 = 0 and P910 = 0, 2 or 4.
0 = Disabled 1 = Automatic restart
P016
Start on the fly 0 - 2
[0]
Allows the inverter to start onto a spinning motor. Under normal circumstances the inverter runs t he mot or up from 0 Hz.
However, if the motor is still spinning or is being driven by the load, it will undergo braking before running back up to the setpoint - t his can cause an overcurrent trip. By using a f lying restart , t he invert er ‘hom es in’ on t he motor's speed and runs it up from that speed to the set point . Note: If the motor has stopped or is rotati ng slowly, some ‘rocking’ m ay occur as the inverter senses the direction of rot ati on prior t o restart ing. (See also P020)
0 = Normal restart 1 = Flying restart after power up, fault or OFF2 ( if P 018 = 1). 2 = Flying restart every time (useful in circumstances where the
motor can be driven by the load).
P017
Smoothing type 1 - 2
[1]
1 = Continuous smoothing (as defined by P004). 2 = Discontinuous smoothing. This provides a fast unsmoothed
response to STOP commands and requests to reduce frequency.
Note: P 004 m ust be set to a value > 0.0 for this parameter to have
any effect.
P018
Automatic restart after fault 0 - 1
[0]
Automatic restart after fault:
0 = Disabled 1 = The inverter will attempt to restart up to 5 times after a fault. If
the fault is not cleared after the 5th attempt, the invert er will remain in the fault state until reset.
WARNING: While waiting to re-start, the display will flash. This
means that a start is pending and may happen at any time. Fault codes can be observed in P930.
P019
Skip frequency bandwidth (Hz) 0 - 10.00
[2.00]
Frequencies set by P014, P027, P028 or P029 that are wit hin +/- the value of P019 are suppressed.
P020
Flying start ramp time (seconds) 0.50 - 25.0
[5.0]
Used in conjunction with P016 (set longer times if persistent F002 trips occur).
P021
Minimum analogue frequency (Hz) 0 - 400.00
[0.00]
Frequency corresponding to the lowest analogue input value, i.e. 0 V or 2 V. This can be set to a higher value than P022 to give an inverse relationship between analogue input and frequency output (see diagram in P022).
Page 24
English 5. SYSTEM PARAMETERS
Parameter Function Range
[Default]
Description / Notes
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
24
P022
Maximum analogue frequency (Hz)
0 - 400.00
[50.00]
Frequency corresponding to the highest analogue input value, i.e. 10 V, determined by P023. This can be set to a lower value than P021 to give an inverse relationship between analogue input and frequency output.
i.e.
Note: The output frequency is limited by values entered for
P012/P013.
P023
Analogue input function 0 - 2
[0]
0 = 0 V to 10 V 1 = 2 V to 10 V 2 = 2 V* to 10 V
* The inverter will come to a controlled stop if V < 1 V.
WARNING: The motor can automatically run without a
potentiometer or voltage source connected between pins 3 and 4.
WARNING: With P023=2, the inverter will automatically start
when V goes above 1 V. This equally applies to analogue and digital control (i.e. P006 = 0 or 1).
P024
Analogue setpoint addition 0 - 2
[0]
If the inverter is not in analogue mode (P006 = 0 or 2), set ting this
parameter to ‘1’ causes the analogue input value to be added.
0 = No addition. 1 = Addition of the analogue setpoint (defined by P023) t o the
fixed frequency or the motor potentiomet er frequency.
2 = Scaling of digital/fixed setpoint by analogue input (P023) in
the range 0 - 100%.
Note: By selecting a combination of reversed negative fixed
frequency settings and analogue setpoint addition, it is possible to configure the inverter for ‘centre zero’ operation with a +/-5 V supply or a 0 - 10 V potentiometer so t hat the output frequency can be 0 Hz at any position, including the centre position.
P027
Skip frequency 2 (Hz) 0 - 400.00
[0.00]
See P014.
P028
Skip frequency 3 (Hz) 0 - 400.00
[0.00]
See P014.
P029
Skip frequency 4 (Hz) 0 - 400.00
[0.00]
See P014.
P031
Jog frequency right (Hz) 0 - 400.00
[5.00]
Jogging is used to advance the motor by small amounts. It is controlled via the JOG button or with a non-latching switch on one of the digital inputs (P051 to P053).
If jog right is enabled (DINn = 7), this parameter controls the f requency at which the inverter will run when the switch is closed. Unlike other setpoints, it can be set lower than the minimum frequency.
P032
Jog frequency left (Hz) 0 - 400.00
[5.00]
If jog left is enabled (DINn = 8), this parameter controls t he f requency at which the inverter will run when the switch is closed. Unlike other setpoints, it can be set lower than the minimum frequency.
f
V
P021
P021
P022
P022
Page 25
5. SYSTEM PARAMETERS English
Parameter Function Range
[Default]
Description / Notes
© Siemens plc 1997 G85139-H1750-U049-B
25
2
6/09/9
7
P041
Fixed frequency 1 (Hz) 0 - 400.00
[5.00]
Valid if P006 = 2 and P053 = 6 or 18.
P042
Fixed frequency 2 (Hz) 0 - 400.00
[10.00]
Valid if P006 = 2 and P052 = 6 or 18.
P043
Fixed frequency 3 (Hz) 0 - 400.00
[15.00]
Valid if P006 = 2 and P051 = 6 or 18.
P044
Fixed frequency 4 (Hz) 0 - 400.00
[20.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17 .
P045
Inversion fixed setpoints for fixed frequencies 1 - 4
0 - 7
[0]
Sets the direction of rotation for the fixed frequency:
FF 1 FF 2 FF 3 FF4
P045 = 0 ⇒⇒⇒⇒ P045 = 1 ⇐⇒⇒⇒ P045 = 2 ⇒⇐⇒⇒ P045 = 3 ⇒⇒⇐⇒ P045 = 4 ⇒⇒⇒⇐ P045 = 5 ⇐⇐⇒⇒ P045 = 6 ⇐⇐⇐⇒ P045 = 7 ⇐⇐⇐⇐
Fixed setpoints not inverted. Fixed setpoints inverted.
P046
Fixed frequency 5 (Hz) 0 - 400.00
[25.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P047
Fixed frequency 6 (Hz) 0 - 400.00
[30.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P048
Fixed frequency 7(Hz) 0 - 400.00
[35.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P050
Inversion fixed setpoints for fixed frequencies 5 - 7
0 - 7
[0]
Sets the direction of rotation for the fixed frequency:
FF 5 FF 6 FF 7
P050 = 0 ⇒⇒⇒ P050 = 1 ⇐⇒⇒ P050 = 2 ⇒⇐⇒ P050 = 3 ⇒⇒⇐ P050 = 4 ⇒⇒⇒ P050 = 5 ⇐⇐⇒
P050 = 6 or 7 ⇐⇐⇐
Fixed setpoints not inverted. Fixed setpoints inverted.
Page 26
English 5. SYSTEM PARAMETERS
Parameter Function Range
[Default]
Description / Notes
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
26
P051 Selection control function, DIN1 0 - 19
(terminal 5), fixed frequency 3 [1] or binary fixed frequency bit 0.
P052 Selection control function, DIN2 0 - 19
(terminal 6), fixed frequency 2. [2] or binary fixed frequency bit 1.
P053 Selection control function, DIN3 0 - 19
(terminal 7), fixed frequency 1 or binary fixed frequency bit 2. [6]
Value
0 1 2 3 4 5 6 7 8 9
10 11
12 13
14 15
16 17
18 19
Function of P051 to P053
Input disabled ON right ON left Reverse OFF2 ** OFF3 ** Fixed frequencies 1 - 3 Jog right Jog left Remote operation Fault code reset
Increase frequency * Decrease frequency * Disable analogue input (setpoint is 0.0 Hz) Disable the ability to change parameters Enable dc brake
Do not use
Binary fixed frequency control (fixed frequencies 1 - 7) As 6, but input high will also request RUN * External trip/PTC
Function,
low state
­Off Off Normal OFF2 OFF3 Off Off Off Local Off
Off Off Analogue on
enabled Off
­Off
Off Yes (F012)
Function,
high state
­On right On left Reverse On On On Jog right Jog left Remote Reset on rising edge Increase Decrease Analogue disabled disabled
Brake on
­On
On No
* Only effective when P007 = 0. ** See section 4.3.
Binary Coded Fixed Frequency Mapping
(P051, P052, P053 = 17)
DIN3
(P053)
DIN2
(P052)
DIN1
(P051) STOP 0 0 0 RUN to FF1 (P041) 0 0 1 RUN to FF2 (P042) 0 1 0 RUN to FF3 (P043) 0 1 1 RUN to FF4 (P044) 1 0 0 RUN to FF5 (P046) 1 0 1 RUN to FF6 (P047) 1 1 0 RUN to FF7 (P048) 1 1 1
P056
Digital input debounce time 0 - 2
[0]
0 = 12.5 ms 1 = 7.5 ms 2 = 2.5 ms
Page 27
5. SYSTEM PARAMETERS English
Parameter Function Range
[Default]
Description / Notes
© Siemens plc 1997 G85139-H1750-U049-B
27
2
6/09/9
7
P061
Selection relay output RL1 0 - 13
[6]
Value Relay function Active
3
0 No function assigned (relay not active) Low 1 Inverter is running High 2 Inverter frequency 0.0 Hz Low 3 Motor run right has been selected High 4 External brake on (see parameters P063/P064) Low 5 Inverter frequency less than or equal to minimum
frequency
Low
6 Fault indication
1
Low
7 Inverter frequency greater than or equal to set point High 8 Warning active
2
Low
9 Output current greater t han or equal to P065 High
10 Motor current limit (warning)
2
Low
11 Motor over temperature (warning)
2
Low
12 Closed loop motor LOW speed limit High 13 Closed loop motor HIGH speed limit High
1
Inverter switches off (see parameter P930 and section 6).
2
Inverter does not switch off (see parameter P931).
3
‘Active low’ = relay OPEN. ‘Active high’ = relay CLOSED.
P062
Electro-mechanical brake option control
0 - 4
[0]
This operates in the same manner as the external brake control (described in P063/P064), except that the relay is not activat ed.
0 = Normal stop mode 1 - 3 = Do not use 4 = Combination stop mode
P063
External brake release delay (seconds)
0 - 20.0
[1.0]
Only effective if t he relay output is set t o control an ext ernal brake (P061 =
4). In this case when the inverter is switched on, it will run at the minimum frequency for the time set by t his paramet er before releasing t he brake control relay and ramping up (see illustrati on in P064).
P064
External brake stopping time (seconds)
0 - 20.0
[1.0]
As P063, only effective if the relay output is set to control an ext ernal brake. This defines the period for which the inverter continues to run at the minimum frequency after ramping down and while the ext ernal brake is applied.
Notes: (1) Settings for P063 and P064 should be slightly longer
than the actual time taken for t he ext ernal brake t o apply and release respectively.
(2) Setting P063 or P064 to too high a value, especially
with P012 set to a high value, can cause an overcurrent warning or trip as the inverter attempts to move a locked motor shaft.
P065
Current threshold for relay (A ) 0 - 99.9
[1.0]
This parameter is used when P061 = 9. The relay switches on when the motor current is greater than the value of P 065 and switches off when the current falls to 90% of the value of P 065 (hysteresis).
ON OFF
t
P063
A
t
P064
A
f
f
B
t
A = Brake applied
B = Brake removed
Page 28
English 5. SYSTEM PARAMETERS
Parameter Function Range
[Default]
Description / Notes
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
28
P066
Compound braking 0 - 1
[1]
0 = Off 1 = On. Permits faster ramp-down times and enhances stopping
capability.
P073
DC injection braking (%) 0 - 250
[0]
This stops the motor by applying a DC current. This causes heat to be generated in the motor rather than t he invert er and holds the shaf t stationary until the end of the braking period. Braking is effective for t he period of time set by P003.
The DC brake can be activated using DIN1 - DIN3 (braking is active for as long as the DIN is high - see P051 - P053).
WARNING: Frequent use of long periods of dc injection braking
can cause the motor to overheat. If DC injection braking is enabled via a digital input
then DC current is applied for as long as the digital input is high. This causes heat in the motor.
P074
I2t motor derating 0 - 1
[1]
0 = Disabled 1 = Enabled. Causes an F074 trip if the motor exceeds the I2t calculation.
The time taken to trip is dependent on t he diff erence between t he overload current and the nominal mot or current rat ing st ored in P 083 ­typically a 150% overload will result in a switch-off in 1 - 2 minutes.
WARNING: Where motor thermal pro tection is r equi red , an external
PTC must be used.
P076
Pulse frequency 0 - 7
[0 or 4]
Sets the pulse frequency (from 2 to 16 kHz) and the PWM mode. If silent operation is not absolutely necessary, the losses in the inverter as well as the RFI emissions can be reduced by selecting lower pulse frequencies.
0/1 = 16 kHz (230 V default) 2/3 =8 kHz 4/5 = 4 kHz (400 V default) 6/7 =2 kHz
Note: When P076 = 0/1, the display of the current at frequencies
below 10 Hz is less accurate.
400V inverters require the continuous current rating reduced for operation below 5Hz, when operating at switching frequencies greater than 4kHz and with boost values greater than 100% (P078 + P079). These are typically as follows:
Model P076 =
0 or 12 or 3
MM37/3- MM750/3 50%xP083 80%xP083
Page 29
5. SYSTEM PARAMETERS English
Parameter Function Range
[Default]
Description / Notes
© Siemens plc 1997 G85139-H1750-U049-B
29
2
6/09/9
7
P077
Control mode 0 - 2
[1]
Controls the relationship between the speed of the motor and the voltage supplied by the inverter. One of two modes can be selected:
0/1 = Linear voltage/f requency
Use this curve for synchronous motors or motors connected in parallel.
2 = Quadratic voltage/frequency relationship
This is suitable for centrifugal pumps and fans.
P078
Continuous boost (%) 0 - 250
[100]
Operates continuously over the whole frequency range. For many applications it is necessary to increase low frequency torque.
This parameter sets the start-up voltage at 0 Hz to adjust the available torque for low frequency operation. 100% setting will produce rated motor current at low frequencies.
WARNING: If P078 is set too high, o verh eating of the motor
and/or an overcurrent trip (F002) can occur.
P079
Starting boost (%) 0 - 250
[0]
For drives which require a high initial starting torque, it is possible to set an additional current (added to the setting in P078) during ramping. This is only effective during initial start up and until the frequency setpoint is reached.
Note: This increase is in addition to P078.
P081
Nominal frequency for motor (Hz)
0 - 400.00
[50.00]
P082
Nominal speed for motor (RPM)
0 - 9999
[

]
These parameters must be set for the motor used.
P083
Nominal current for mot or (A)
0.1 - 99.9
[

]
Read the specifications on the motor’s rating plate (see Figure 10 in section 3.2.1).
P084
Nominal voltage for motor (V)
0 - 1000 [

]
Note: The inverter’s default setting vary according to the power rating.
P085
Nominal power for motor (kW/hp)
0 - 100.0
[

]
P089
Stator resistance ()
0.01-100.00 [

]
The stator resistance of the motor should be entered in this parameter. The value entered should be the resistance between any two phases with the motor connected. The m easurem ent should be made at the
inverter output terminals with power off. Note: If the value of P089 is too high then an overcurrent trip
(F002) may occur.
P091
Serial link slave address 0 - 30
[0]
Up to 31 inverters can be connected via the serial link and controlled by a computer or PLC using the USS protocol. This parameter set s a unique address for the inverter.
VN (P084)
f
N
(P081)
V
N
f
0/1
2
V
max
Page 30
English 5. SYSTEM PARAMETERS
Parameter Function Range
[Default]
Description / Notes
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
30
P092
Serial link baud rate 3 - 7
[6]
Sets the baud rate of the RS485 serial int erface (USS protocol):
3 = 1200 baud 4 = 2400 baud 5 = 4800 baud 6 = 9600 baud 7 = 19200 baud
Note: Some RS232 to RS485 converters are not capable of
baud rates higher than 4800.
P093
Serial link timeout (seconds) 0 - 240
[0]
This is the maximum permissible period between two incoming data telegrams. This feature is used to turn off the inverter in the event of a communications failure.
Timing starts after a valid data telegram has been received and if a further data telegram is not received within the specified time period, the inverter will trip and display fault code F008.
Setting the value to zero switches off the control.
P094
Serial link n o minal system se tpoint (Hz)
0 - 400.00
[50.00]
Setpoints are transmitted t o the inverter via the serial link as percentages. The value entered in this parameter represents 100% (HSW = 4000H).
P095
USS compatibility 0 - 2
[0]
0 = Compatible with 0.1 Hz resolution 1 = Enable 0.01 Hz resolution 2 = HSW is not scaled but represents the actual frequency value to
a resolution of 0.01 Hz (e.g. 5000 = 50 Hz).
P099
Option module type 0 - 1
[0]
0 = Option module not present 1 = PROFIBUS module (enables parameters relating to PROFI BUS)
P101
Operation for Europe or USA 0 - 1
[0]
This sets the inverter for European or USA supply and motor frequency:
0 = Europe (50 Hz) 1 = USA (60 Hz)
Note: After setting P101 = 1 the inverter must be re-set to factory
defaults. i.e. P944 = 1 to aut omatically set P013 = 60 Hz, P081 = 60 Hz, P082 = 1680 rpm and P085 will be displayed in hp.
P111
Inverter power rating (kW/hp) 0.0 - 50.00
[

]
Read-only parameter that indicates the power rating of the inverter in kW. e.g. 0.55 = 550 W
Note: If P101 = 1 then the rating is displayed in hp.
P112
Inverter type (model) 1 - 7
[

]
Read-only parameter.
1 = MICROMASTER series 2 (MM2) 2 = COMBIMASTER 3 = MIDIMASTER 4 = MICROMASTER Junior (MMJ) 5 = MICROMASTER series 3 (MM3) 6 = MICROMASTER Vector (MMV) 7 = MIDIMASTER Vector (MDV)
P113
Inverter type (power rating) 0 - 29
[

]
Read-only parameter.
0 = MM12 1 = MM25 2 = MM37 3 = MM55 4 = MM75 5 = MM110 6 = MM150 7 = MM220 8 = MM300
10 =MM12/2 11 =MM25/2 12 =MM37/2 13 =MM55/2 14 =MM75/2 15 =MM110/2 16 =MM150/2 17 =MM220/2 18 =MM300/2 19 =MM400/2
20 =MM37/3 21 =MM55/3 22 =MM75/3 23 =MM110/3 24 =MM150/3 25 =MM220/3 26 =MM300/3 27 =MM400/3 28 =MM550/3 29 =MM750/3
Page 31
5. SYSTEM PARAMETERS English
Parameter Function Range
[Default]
Description / Notes
© Siemens plc 1997 G85139-H1750-U049-B
31
2
6/09/9
7
P121
Enable/disable RUN button 0 - 1
[1]
0 = RUN button disabled. 1 = RUN button enabled (only possible if P007 = 1).
P122
Enable/disable FORWARD/REVERSE button
0 - 1
[1]
0 = FORWARD/REVERSE button disabled. 1 = FORWARD/REVERSE button enabled (onl y possible if P 007 = 1).
P123
Enable/disable JOG button 0 - 1
[1]
0 = JOG button disabled. 1 = JOG button enabled (only possible if P007 = 1).
P124
Enable/disable and buttons
0 - 1
[1]
0 = and buttons disabled. 1 = and buttons enabled (only possible if P007 = 1).
Note: This applies for frequency adjustment only. The buttons can
still be used to change parameter values.
P125
Reverse direction inhibit 0 - 1
[1]
0 = Reverse direction disabled. Inhibits reverse commands from ALL
sources (reverse RUN commands result in forward rot ation)
1 = Normal operation (FORWARD/REVERSE operation allowed)
P131
Frequency setpoint (Hz) 0.00-400.00
[-]
P132
Motor current (A) 0.0 - 99.9
[-]
P134
DC link voltage (V) 0 - 1000
[-]
P135
Motor RPM 0 - 9999
[-]
P137
Output voltage (V) 0 - 1000
[-]
P140
Most recent fault code 0 - 9999
[-]
The last recorded fault code (see section 6) is stored in this parameter. This is a copy of the code stored in P930.
P141
Most recent fault code -1 0 - 9999
[-]
This parameter stores the last recorded fault code prior to that st ored in P140/P930.
P142
Most recent fault code -2 0 - 9999
[-]
This parameter stores the last recorded fault code prior to that st ored in P141.
P143
Most recent fault code -3 0 - 9999
[-]
This parameter stores the last recorded fault code prior to that st ored in P142.
P201
Closed loop mode 0 - 2
[0]
0 = Normal operation (closed loop control disabled). 1 = Not used. 2 = Closed loop control using analogue input for transducer feedback
input.
P202
P gain (%) 0.0 - 999.9
[1.0]
Proportional gain.
P203
I gain (%) 0.00 - 99.99
[0.00]
Integral gain.
0.01% corresponds to the longest integral action tim e.
P205
Sample interval (x 25 ms) 1 - 2400
[1]
Sampling interval of feedback sensor.
P206
Transducer filtering 0 - 255
[0]
0 = Filter off. 1 - 255 = Low pass filtering applied to sensor.
P207
Integral capture range (%) 0 - 100
[100]
Percentage error above which integral term is reset to zero.
P208
Transducer type 0 - 1
[0]
0 = An increase in motor speed causes an increase in sensor
voltage/current output.
1 = An increase in motor speed causes a decrease in sensor
voltage/current output.
Read-only parameters. These are copies of the values stored in P001 but can be accessed directly via the serial link.
Page 32
English 5. SYSTEM PARAMETERS
Parameter Function Range
[Default]
Description / Notes
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
32
P210
Transducer reading (%) 0.0 - 100.0
[-]
Read only. Value is a percentage of full scale of the selected input.
P211
0% setpoint 0.00-100.00
[0.00]
Value of P210 to be maintained for 0% setpoint.
P212
100% setpoint 0.00-100.00
[100.00]
Value of P210 to be maintained for 100% setpoint.
P220
PI frequency cut-off
0 - 1
[0]
0 = Normal operation 1 = Switch off inverter output at or below m i nim um frequency.
P700 P701 P702 P880 P910
Local/Remote mode 0 - 4
[0]
Sets the inverter for local control or remote control over the serial link:
0 = Local control 1 = Remote control (and setting of parameter values) 2 = Local control (but remote control of frequency) 3 = Remote control (but local control of frequency) 4 = Local control (but remote read and write access to
parameters and facility to reset trips)
Note: When operating the inverter via remote control (P910 = 1
or 3), the analogue input remains active when P006 = 1 and is added to the setpoint.
P918
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further details. Access only possible with P099 = 1
P922
Software version 0.00 - 99.99
[-]
Contains the software version number and cannot be changed.
P923
Equipment system number 0 - 255
[0]
You can use this parameter to allocate a unique reference number to the inverter. It has no operational eff ect .
P927
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further details
.
P928
Access only possible with P099 = 1
P930
Most recent fault code 0 - 9999
[-]
The last recorded fault code (see section 6) is stored in this parameter. This parameter can be cleared using the and buttons.
P931
Most recent warning type 0 - 9999
[-]
The last recorded warning is stored in this parameter until power is removed from the inverter:
002 = Current limit active 003 = Voltage limit active 005 = Inverter over-temperature (Internal PTC)
P944
Reset to factory default settings 0 - 1
[0]
Set to ‘1’ and then press P to reset all parameters except P101 to the factory default settings.
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further details. Access only possible with P099 = 1
Page 33
5. SYSTEM PARAMETERS English
Parameter Function Range
[Default]
Description / Notes
© Siemens plc 1997 G85139-H1750-U049-B
33
2
6/09/9
7
P947 P958 P963
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
P967
details.
P968
Access only possible with P099 = 1
P970 P971
EEPROM storage control 0 - 1
[1]
0 = Changes to parameter settings (including P971) are lost when power is removed. 1 = Changes to parameter settings are retained during periods
when power is removed.
WARNING: When using the serial l ink to update the parameter
set held in EEPROM, care must be taken not to exceed the maximum number of write cycl es to this EEPROM - this is approximately 50,000 write cycles. Exceeding this number of write cycles would result in corruption of the stored data and subsequent data loss. The number of read cycles are unlim ited.
Page 34
English 6. FAULT CODES
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
34
6. FAULT CODES
In the event of a failure, the inverter switches off and a fault code appears on the display. The last fault that
occurred is stored in parameter P930. e.g. ‘0003’ indicates that the last error was F003.
Fault Code Cause Corrective Action
F001
Overvoltage Check whether supply voltage is within the limits indicated on the rating plate.
Increase the ramp down time (P003). Check whether the required braking power is within the specified limits.
F002
Overcurrent Check whether the motor power corresponds to the inverter power.
Check that the cable length limits have not been exceeded. Check motor lead and motor for short-circuits and earth faults. Check whether the motor parameters (P081 - P 086) correspond with the motor being used. Check the stator resistance (P089). Increase the ramp-up time (P002). Reduce the boost set in P078 and P079. Check whether the motor is obstructed or overloaded.
F003
Overload Check whether the motor is overloaded.
Increase the maximum motor frequency if a motor with high slip is used.
F005
Inverter overtemperature (internal PTC)
Check that the ambient temperature is not t oo high. Check that the air inlet and outlet are not obstruct ed. Check that the integral fan is working.
F008
USS protocol timeout Check the serial interface.
Check the settings of the bus master and P091 - P093. Check whether the timeout interval is too short (P093).
F010
Initialisation fault / Param eter loss * Check the entire parameter set. Set P009 to ‘0000’ before power down.
F011
Internal interface fault * Switch off power and switch on again.
F012
External trip (PTC) Check if motor is overloaded.
F013
Programme fault * Switch off power and switch on again.
F018
Auto-restart after fault. Automatic re-start af ter fault (P018) is pending.
WARNING: The inverter may start at any time.
F030
PROFIBUS link failure Check the integrity of the link.
F031
Option module to link failure Check the integrity of the link.
F033
PROFIBUS configuration error Check the PROFIBUS configuration.
F036
PROFIBUS module watchdog trip Replace PROFIBUS module
F074
Motor overtemperature by I2t calculation
Check that the motor current does not exceed the value set in P083.
F106
Parameter fault P006 Parameterise fixed frequency(ies) and/or motor potentiom et er on the digital
inputs.
F112
Parameter fault P012/P013 Set param eter P012 < P013.
F151 - F153
Digital input parameter fault Check the settings of digital inputs P051 to P053.
F188
Automatic calibration failure Motor not connected to inverter - connect motor.
If the fault persists, set P088 = 0 and then enter the stator resistance of t he motor into P089 manually.
F201
P006 = 1 while P201 = 2 Change paramet er P 006 and/or P201.
F212
Parameter fault P211/P212 Set param eter P211 < P212.
*
Ensure that the wiring guidelines described in section 2.1 have been complied with.
When the fault has been corrected the inverter can be reset. To do this press button P twice (once to display P000 and the second time to reset the fault ), or erase t he fault via a binary input (see parameters P051 - P053 in section 5) or via the serial interface.
Page 35
7. SPECIFICATIONS English
© Siemens plc 1997 G85139-H1750-U049-B
35
2
6/09/9
7
7. SPECIFICATIO NS
230 V Single Phase MICROMAS T E R I nverters
Order No. (6SE92 ..) 10-7BA40 11-5BA40 12-1BA40 12-8BA40 13-6BA40 15-2BB40 16-8BB40 21-0BC40 21-3BC40 Inverter model MM12 MM25 MM37 MM55 MM75 MM110 MM150 MM220
MM300
c
Input voltage range 1 AC 230 V +/-15% 2 AC 208 V +/-10% Motor output rating
a
(kW / hp)
0.12 /
1
/
6
0.25 /
1
/
3
0.37 /
1
/
2
0.55 /
3
/
4
0.75 / 1
1.1 / 1
1
/
2
1.5 / 2 2.2 / 3 3.0 / 4
Continuous output 350 VA 660 VA 920 VA 1.14 kVA 1.5 kVA 2.1 kVA 2.8 kVA 4.0 kVA 5.2 kVA Output current (nom.)
a
0.75 A 1.5 A 2.1 A 2.6 A 3.5 A 4.8 A 6.6 A 9.0 A 11.8 A
Output current (max. continuous) 0.8 A 1.7 A 2.3 A 3.0 A 3.9 A 5.5 A 7.4 A 10.4 A 13.6 A Input current (I rms) 1.8 A 3.2 A 4.6 A 6.2 A 8.2 A 11.0 A 14.4 A 20.2 A 28.3 A Recommended mains fuse 10 A 16 A 20 A 25 A 32 A Recommended lead Input 1.0 mm
2
1.5 mm
2
2.5 mm
2
4.0 mm
2
cross-section (min.)
Output 1.0 mm
2
1.5 mm
2
2.5 mm
2
Dimensions (mm) (w x h x d) 73 x 175 x 141 149 x 184 x 172 185 x 215 x 195 Weight (kg / lb) 0.85 / 1.9 2.6 / 5.7 5.0 / 11.0
All 1 AC 230 V MICROMASTERS include integrated Class A filters. Optional external Class B filters are available (see section 8.3).
230 V 3 Phase MICROMASTER I n verters
Order No. (6SE92 ..) 10-7CA40 11-5CA40 12-1CA40 12-8CA40 13-6CA40 15-2CB40 16-8CB40 21-0CC40 21-3CC40 21-8CC13 Inverter model MM12/2 MM25/2 MM37/2 MM55/2 MM75/2 MM110/2 MM150/2 MM220/2
MM300/2
c
MM400/2
Input voltage range 1 - 3 AC 230 V +/-15% 3 AC Motor output rating
a
(kW / hp)
0.12 /
1
/
6
0.25 /
1
/
3
0.37 /
1
/
2
0.55 /
3
/
4
0.75 / 1
1.1 / 1
1
/
2
1.5 / 2 2.2 / 3 3.0 / 4 4.0 / 5
Continuous output 350 VA 660 VA 920 VA 1.14 kVA 1.5 kVA 2.1 kVA 2.8 kVA 4.0 kVA 5.2 kVA 7.0 kVA Output current (nom.)
a
0.75 A 1.5 A 2.1 A 2.6 A 3.5 A 4.8 A 6.4A 9.0 A 11.8 A 15.9 A
Output current (max. continuous) 0.8 A 1.7 A 2.3 A 3.0 A 3.9 A 5.5 A 7.0 A 10.4 A 13.6 A 17.5 A Input current (I rms) (1 AC / 3 AC) 1.8 / 1.1 A 3.2 / 1.9 A 4.6 / 2.7 A 6.2 / 3.6 A 8.2 / 4.7 A 11.0 / 6.4 A 14.4 / 8.3 A 20.2 / 1 1.7 A 2 8.3 / 16.3 A - / 21.1 A
Recommended mains fuse
b
10 A 16 A 20 A 25 A
Recommended lead Input 1.0 mm
2
1.5 mm
2
2.5 mm
2
4.0 mm
2
cross-section (min.)
Output 1.0 mm
2
1.5 mm
2
2.5 mm
2
Dimensions (mm) (w x h x d) 73 x 175 x 141 149 x 184 x 172 185 x 215 x 195 Weight (kg / lb) 0.75 / 1.7 2.4 / 5.3 4.8 / 10.5
All 1 AC and 3 AC 230 V MICROMASTERS (excluding MM400/2) are suitable for 208 V operation. All 3 AC 230 V MICROMASTERS can operate on 1 AC 230 V (MM300/2 requires an external line choke, e.g. 4EM6100-3CB).
380 V - 500 V Three Phase MICROMASTER Inverters
Order No. (6SE92 ..) 11-1DA40 11-4DA40 12-0DA40 12-7DA40 14-0DA40 15-8DB40 17-3DB40 21-0DC40 21-3DC40 21-5DC40 Inverter model MM37/3 MM55/3 MM75/3 MM110/3 MM150/3 MM220/3 MM300/3 MM400/3 MM550/3 MM750/3 Input voltage range 3 AC 380 V - 500 V +/-10%
Motor output rating
a
(kW / hp)
0.37 /
1
/
2
0.55 /
3
/
4
0.75 / 1
1.1 / 1
1
/
2
1.5 / 2 2.2 / 3 3.0 / 4 4.0 / 5
5.5 / 7
1
/
2
7.5 / 10
Continuous output 930 VA 1.15 kVA 1.5 kVA 2.1 kVA 2.8 kVA 4.0 kVA 5.2 kVA 7.0 kVA 9.0 kVA 12.0 kVA Output current (nom.) (400 V / 500 V)
a
1.05 /0 .9 5 A 1.5 / 1.3 A 2.0 / 1.8 A 2.8 / 2.5 A 3.7 / 3.3 A 5.2 / 4.6 A 6.8 / 6.0 A 9.2 / 8.1 A 1 1 . 8 / 1 0 . 4 A 15. 8 / 1 3 . 9 A
Output current (max. continuous) 1. 2 / 1 . 0 6 A 1.6 / 1 . 4 5 A 2.1 / 1 . 9 A 3.0 / 2 . 7 A 4.0 / 3 . 6 A 5.9 / 5. 3 A 7.7 / 6 . 9 A 10 .2 / 9.1A 1 3.2/ 11.8 A 17.0 / 15.2 A Input current (I rms) 2.2 A 2.8 A 3.7 A 4.9 A 5.9 A 8.8 A 11.1 A 13.6 A 17.1 A 22.1 A Recommended mains fuse 10 A 16 A 20 A 25 A Recommended lead Input 1.0 mm
2
1.5 mm
2
2.5 mm
2
4.0 mm
2
cross-section (min.)
Output 1.0 mm
2
1.5 mm
2
2.5 mm
2
Dimensions (mm) (w x h x d) 73 x 175 x 141 149 x 184 x 172 185 x 215 x 195 Weight (kg / lb) 0.75 / 1.7 2.4 / 5.3 4.8 / 10.5
Optional external Class A and Class B filters are available (see section 8.3).
Notes
a
Siemens 4 pole-motor, 1LA5 series or equivalent.
b
Assumes 3-phase supply. If a single phase supply is used, the input current ratings, wire sizes and fuses for single phase
MICROMASTERS will apply.
c
MM300 and MM300/2 require an external choke (e.g. 4EM6100-3CB) and a 30 A mains fuse to operate on a single phase supply.
Page 36
English 7. SPECIFICATIONS
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
36
Input frequency: 47 Hz to 63 Hz Power factor:
λ 0.7 Output frequency range: 0 Hz to 400 Hz Resolution: 0.01 Hz Overload capability: 150% for 60 s, related to nominal current Protection against: Inverter overtemperature
Motor overtemperature
Overvoltage and undervoltage Additional protection: Against short-circuits and earth/ground faults pull-out protection.
Protection against running with no load (open-circuit) Operating mode: 4 quadrants possible Regulation and control: Voltage/frequency curve Analogue setpoint / PI Input:
0 - 10 V/2 - 10 V (recommended potentiometer 4.7 k) Analogue setpoint resolution: 10-bit Setpoint stability: Analogue < 1%
Digital < 0.02% Motor temperature monitoring: l2t control Ramp times: 0 - 650 s Control outputs: 1 relay 110 V AC / 0.4 A; 30 V DC / 1 A
WARNING:External inductive loads must be suppressed in an
appropriate manner
(see section 2.1 (5))
. Interface: RS485 Inverter efficiency: 97% (typically) Operating temperature: 0oC to +50oC Storage/transport temperature: -40oC to +70oC Ventilation: Fan-cooled Humidity: 90% non-condensing Installation height above sea level: < 1000 m
Note: If the Inverter is to be installed at an altitude >1000m,
derating will be required.(Refer to DA 64 Catalogue)
Degree of protection: Frame size A: IP20
(NEMA 1 using accessory kit -
see options
)
Frame sizes B & C:IP20 (NEMA 1)
(National Electrical Manufacturers’ Association) Protective separation of circuits: Double insulation or protective screening Electro-magnetic compatibility (EMC):
See section 8.3
Options / Accessories
Additional RFI suppression filter Clear Text Display (OPM2)
PROFIBUS module (CB15) SIMOVIS software for control via PC Output chokes and line chokes Output filters IP20 (NEMA 1) Acc essory Kit
Please contact your local
Siemens sales office for
further details
Page 37
8. SUPPLEMENTARY INFORMATION English
© Siemens plc 1997 G85139-H1750-U049-B
37
2
6/09/9
7
8. SUPPLEMENTARY INFORMATI ON
8.1 Application Example
Setup procedure for a simple application
Motor: 220 V
1.5 kW output power
Application requirements: Setpoint adjustable via potentiometer 0 - 50 Hz
Ramp up from 0 to 50 Hz in 15 seconds
Ramp down from 50 to 0 Hz in 20 seconds Inverter used: MM150 (6SE9216-8BB40) Settings: P009 = 2 (all parameters can be altered)
P081 - P085 = values given on motor rating plate
P006 = 1 (analogue input)
P002 = 15 (ramp up time)
P003 = 20 (ramp down time) This application is now to be modified as follows:
Operation of motor up to 75 Hz (voltage/frequency curve is linear up to 50 Hz). Motor potentiometer setpoint in addition to analogue setpoint . Use of analogue setpoint at maximum 10 Hz. Ramp times to remain the same.
Parameter adjustments: P009 = 2 (all parameters can be altered)
P013 = 75 (maximum motor frequency in Hz)
P006 = 2 (setpoint via motor potentiometer or fixed setpoint)
P024 = 1 (analogue setpoint is added)
P022 = 10 (maximum analogue setpoint at 10 V = 10 Hz)
8.2 USS Status Codes
The following list gives the meaning of status codes displayed on the front panel of the inverter when the serial link is in use and parameter P001 is set to 006:
001 Message OK 002 Slave address received 100 Invalid start character 101 Timeout 102 Checksum error 103 Incorrect message length 104 Parity fail
Notes
(1) The display flashes whenever a byte is received, thus giving a basic indication that a serial link
connection is established.
(2) If ‘100’ flashes on the display continuously, this usually indicates a bus termination fault.
i.e.
V
f (Hz)
2205075
Page 38
English 8. SUPPLEMENTARY INFORMATION
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
38
8.3 Electro-Magnetic Compatibility (EMC)
All manufacturers / assemblers of electrical apparatus which performs a complete intrinsic function which is placed on the market as a single unit intended for the end user must comply with the EMC directive EEC/89/336 after January 1996. There are three routes by which the manufacturer/assembler can demonstrate compliance:
1.
Self-Certification
This is a manufacturer’s declaration that the European standards applicable to the electrical environment for which the apparatus is intended have been met. Only standards which have been officially published in the Official Journal of the European Community can be cited in the manufacturer’s declaration.
2.
Technical Construction File
A technical construction file can be prepared for the apparatus describing its EMC characteristics.
This file must be approved by a ‘Competent Body’ appointed by the appropriate European government organisation. This approach allows the use of standards which are still in preparation.
3.
EC Type-Examination Certificate
This approach is only applicable to radio communication transmitting apparatus.
The MICROMASTER units do not have an intrinsic function until connected with other components (e.g. a motor). Therefore, the basic units are not allowed to be CE marked for compliance with the EMC directive. However, full details are provided below of the EMC performance characteristics of the products when they are installed in accordance with the wiring recommendations in section 2.1.
Three classes of EMC performance are available as detailed below. Note that these l evels of performance are only achieved when using the default switching frequency (or less) and a maximum motor cabl e length of 25 m.
Class 1: General Industrial
Compliance with the EMC Product Standard for Power Drive Systems EN 68100-3 for use in Second Environment (Industrial) and Restricted Distribution.
EMC Phenomenon Standard Level
Emissions:
Radiated Emissions EN 55011 Level A1 * Conducted Emissions EN 68100-3 *
Immunity:
Electrostatic Discharge EN 61000-4-2 8 kV air discharge Burst Interference EN 61000-4-4 2 kV power cables, 1 kV control Radio Frequency Electromagnetic Field IEC 1000-4-3 26-1000 MHz, 10 V/m
* Limits not required inside a plant
where no other consumers are connected to the same electricity supply transformer.
Page 39
8. SUPPLEMENTARY INFORMATION English
© Siemens plc 1997 G85139-H1750-U049-B
39
2
6/09/9
7
Class 2: Filtered Industrial
This level of performance will allow the manufacturer/assembler to self-certify their appar atus for com pliance with the EMC directive for the industrial environment as regards the EMC performance characteristics of the power drive system. Performance limits are as specified in the Generic Industrial Emissions and Immunity standards EN 50081-2 and EN 50082-2.
EMC Phenomenon Standard Level
Emissions:
Radiated Emissions EN 55011 Level A1 Conducted Emissions EN 55011 Level A1
Immunity:
Supply Voltage Distortion IEC 1000-2-4 (1993) Voltage Fluctuations, Dips, Unbalance,
Frequency Variations
IEC 1000-2-1
Magnetic Fields EN 61000-4-8 50 Hz, 30 A/m Electrostatic Discharge EN 61000-4-2 8 kV air discharge Burst Interference EN 61000-4-4 2 kV power cables, 2 kV control Radio Frequency Electromagnetic Field,
amplitude modulated
ENV 50 140 80-1000 MHz, 10 V/m, 80% AM,
power and signal lines
Radio-frequency Electromagnetic Field, pulse modulated
ENV 50 204 900 MHz, 10 V/m 50% duty cycle,
200 Hz repetition rate
Class 3: Filtered - for residential, commercial and light industry
This level of performance will allow the manufacturer / assembler to self-certify compliance of their apparatus with the EMC directive for the residential, commercial and light industrial environment as regards the EMC performance characteristics of the power drive system. Performance limits are as specified in the generic emission and immunity standards EN 50081-1 and EN 50082-1.
EMC Phenomenon Standard Level
Emissions:
Radiated Emissions EN 55022 Level B1 Conducted Emissions EN 55022 Level B1
Immunity:
Electrostatic Discharge EN 61000-4-2 8 kV air discharge Burst Interference EN 61000-4-4 1 kV power cables, 0.5 kV control
Note:
The MICROMASTERS are intended exclusively for professional applications. Therefore, they do not fall within the scope of the harmonics emissions specification EN 61000-3-2.
Page 40
English 8. SUPPLEMENTARY INFORMATION
G85139-H1750-U049-B
©
Siemens plc 199
7
26/09/97
40
Compliance Table:
Model No. EMC Class
MM12 - MM220 Class 2 MM12/2 - MM300/2 Class 1 MM12/2 - MM220/2 with external filter (see table)
1 phase input only
Class 2* MM150/3 - MM750/3 Class 1 MM150/3 - MM750/3 with external filter (see table) Class 2*
* If the installation of the inverter reduces the radio frequency field emissions (e.g. by installation in a
steel enclosure), Class 3 limits will typically be met.
External Filters:
Model No. Filter Class Filter Part No. Standard
MM12/2 & MM25/2 B 6SE3290-0BA87-0FB0
*
EN 55011 / EN 55022
MM37/2 - MM75/2 B 6SE3290-0BA87-0FB2
*
EN 55011 / EN 55022
MM110/2 & MM150/2 B 6SE3290-0BB87-0FB4
*
EN 55011 / EN 55022
MM220/2 & MM300/2 B 6SE3290-0BC87-0FB4
*
EN 55011 / EN 55022
MM400/2 -
Not available
-
MM37/3 - MM150/3 A
B
6SE3290-0DA87-0FA1 6SE3290-0DA87-0FB1
EN 55011 / EN 55022
MM220/3 & MM300/3 A
B
6SE3290-0DB87-0FA3 6SE3290-0DB87-0FB3
EN 55011 / EN 55022
MM400/3 - MM750/3 A
B
6SE3290-0DC87-0FA4 6SE3290-0DC87-0FB4
EN 55011 / EN 55022
*
Class B filters are for use with 1/3 AC 230V unfiltered units.
8.4 Environmental Aspects
Transport and Storage
Protect the inverter against physical shocks and vibration during transport and storage. The unit must also be protected against water (rainfall) and excessive temperatures
(see section 7).
The inverter’s packaging is re-usable. Retain the packaging or return it to the manufacturer for future use. If the unit has been in storage (non-operational) for more than one year, you must re-form the DC-link
capacitors before use. Refer to your local Siemens sales office for advice on the procedure.
Dismantling and Disposal
The unit can be broken-down to its component parts by means of easily-released screw and snap connectors.
The component parts can be re-cycled, disposed of in accordance with local requirements or returned to the manufacturer.
Documentation
This handbook is printed on chlorine-free paper which has been produced from managed sustainable forests. No solvents have been used in the printing or binding process.
Page 41
8. SUPPLEMENTARY INFORMATION English
© Siemens plc 1997 G85139-H1750-U049-B
41
2
6/09/9
7
8.5 User’s Parameter Settings
Record your own parameter settings in the table below:
Parameter Your
setting
Default
P000 ­P001 0 P002 10.0 P003 10.0 P004 0.0 P005 5.00 P006 0 P007 1 P009 0 P011 0 P012 0.00 P013 50.00 P014 0.00 P015 0 P016 0 P017 1 P018 0 P019 2.00 P020 5.0 P021 0.00 P022 50.00 P023 0 P024 0 P027 0.00 P028 0.00 P029 0.00 P031 5.00 P032 5.00 P041 5.00 P042 10.00 P043 15.00 P044 20.00 P045 0 P046 25.00 P047 30.00 P048 35.00 P050 0 P051 1 P052 2 P053 6 P056 0 P061 6 P062 0 P063 1.0 P064 1.0
Parameter Your
setting
Default
P065 1.0 P066 1 P073 0 P074 1 P076 0/4 P077 1 P078 100 P079 0 P081 50.00 P082

P083

P084

P085

P089

P091 0 P092 6 P093 0 P094 50.00 P095 0 P099 0 P101 0 P111

P112

P113

P121 1 P122 1 P123 1 P124 1 P125 1 P131 ­P132 ­P134 ­P135 ­P137 ­P140 ­P141 ­P142 ­P143 ­P201 0 P202 1.0 P203 0.00 P205 1 P206 0 P207 100 P208 0
Parameter Your
setting
Default
P210 ­P211 0.0 P212 100.00 P220 0 P700 ­P701 0 P702 ­P880 ­P910 0 P918 ­P922 ­P923 0 P927 0 P928 0 P930 ­P931 ­P944 0 P947 ­P958 ­P963 ­P967 ­P968 ­P970 1 P971 1

= Value depends on the
rating of the inverter
Page 42
Herausgegeben vom Bereich Antriebs-, Schalt- und Installationstechnik
Geschäftsgebiet Antriebstechnik Postfach 3269, D-91050 Erlangen
Siemens plc
Sir William Siemens House
Princess Road
Manchester M20 8UR
Änderungen vorbehalten
Specification subject to change without prior notice
G85139-H1750-U049-B
© Siemens plc 1997
Printed in EU
Bestell-Nr. 6SE9286-4AA86
Loading...