Siemens Lithostar Multiline Installation instructions

LITHOSTAR Multiline

SP

System

Installation Instructions

for Subcontractors and Siemens Technicians

 

 

 

 

© Siemens AG 2004

 

The reproduction, transmission or

 

use of this document or its contents

 

is not permitted without express

 

written authority. Offenders will be

 

liable for damages.

All rights,

 

including rights created by patent

 

grant or registration of a utility

 

model _or_ design,_are_ reserved.

 

English

 

Print No.: RXL2-120.812.01.02.02

Doc. Gen. Date:

10.04

Replaces: RXL2-120.812.01.01.02

0 - 2

 

 

Revision

 

 

 

 

Chapter

Page

Revision

 

 

 

 

 

all

all

02

 

 

 

 

 

Document revision level

The document corresponds to the version/revision level effective at the time of system delivery. Revisions to hardcopy documentation are not automatically distributed.

Please contact your local Siemens office to order current revision levels.

Disclaimer

The installation and service of equipment described herein is to be performed by qualified personnel who are employed by Siemens or one of its affiliates or who are otherwise authorized by Siemens or one of its affiliates to provide such services.

Assemblers and other persons who are not employed by or otherwise directly affiliated with or authorized by Siemens or one of its affiliates are directed to contact one of the local offices of Siemens or one of its affiliates before attempting installation or service procedures.

LITHOSTAR Multiline

RXL2-120.812.01

Page 2 of 4

Siemens AG

System

Rev. 02 10.04

CS PS 24

Medical Solutions

Contents

0 - 3

 

Page

1 _______General Remarks _______________________________________________ 1 - 1

Items included in the Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 1 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 1 Text Emphasis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 1 Replacement of damaged or Lost Screws . . . . . . . . . . . . . . . . . . . . . . . 1 - 1

Safety notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

- 2

Yellow enameled Parts . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . .

.

. 1

- 2

Test Equipment and Tools (Service Tools Cataloque) . . . . . . . . .

. . . . . . .

.

. 1 - 2

Installation auxiliary devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 2 Materials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 2 Component Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 3 Component Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 4

2 _______System Installation _____________________________________________ 2 - 1

Preparation . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . 2 - 1

Preinstallation work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 1

Options: Monitor trolley and/or Patient monitor . . . . . . . . . . . . . . . . . . . 2 - 1

Polydoros LX . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . 2 - 2

Polydoros SX 65 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 3

Installing and Connecting the High Voltage Charger

. . . . . . . . . . . . . . . . . . 2 - 3

Installing and Connecting the Cooling Unit . . . . . . . . . . . . . . . . . . . . . . . 2 - 4

Setting Up the Unit . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . 2 - 4

Installing the Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 7

Installing the Components for the System Controller . . . . . . . . . . . . . . . . . . 2 - 9

Setting Up the Console Table . . . . . . . . . . .

. . . . . .

. . .

. . . .

. .

.

. 2 - 9

Positioning/Connecting the Monitors . . . . . . .

. . . . . .

. . .

. . . .

. .

.

. 2 - 9

Positioning the Keyboard and the PC Mouse . . . . . . . . . . . . . . . . . . . . 2 - 9 Connecting the Footswitch, Tableside Control Console,

Shock Wave Trigger Mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 9 Back panel of the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 10 Positioning/Connecting the Operating System Unit (PC) . . . . . . . . . . . . . 2 - 10 Cover the cable outlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 10 Positioning/Connecting DICOM Connect (Option). . . . . . . . . . . . . . . . . 2 - 10 Positioning/Connecting the Multiformat Camera (Option) . . . . . . . . . . . . . 2 - 11 Positioning/Connecting the Diamentors (Option) . . . . . . . . . . . . . . . . . 2 - 11 Installing the TV camera on the 23" I.I. . . . . . . . . . . . . . . . . . . . . . . . . 2 - 12 Installing the TV camera on the 33" I.I. . . . . . . . . . . . . . . . . . . . . . . . . 2 - 12 Checking the temperature of the image intensifier . . . . . . . . . . . . . . . . . . 2 - 12 Installing the Collimator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 13 Installing the Diamentor (Option) . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 13

3 _______Connections with POLYDOROS LX 30 _____________________________ 3 - 1

General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 1 Connections and cable locations in the A12 electronics cabinet . . . . . . . . . . . . 3 - 2

Siemens AG

RXL2-120.812.01

Page 3 of 4

LITHOSTAR Multiline

Medical Solutions

Rev. 02 10.04

CS PS 24

System

0 - 4

Contents

 

 

 

Page

Connections/cable locations in the generator cabinet (Part A) . . . . . . . . . . . . .

3 - 3

Connections of the options and their cable locations in the A12

 

 

 

electronics cabinet and generator AC . . . . . . . . . . . . . . . . . . . . . . . . .

3 - 6

Connections and cable locations in the A12 electronics cabinet

 

 

 

and in the control console . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . .

.

3 - 8

Connections/cable locations in the A13 shock wave cabinet . . .

. . . . . . . . . .

.3 - 11

Connections/Cable Locations in the Generator Cabinet (Part. B)

. . . . . . . . . .

.3 - 13

Connections/harness locations in the generator cabinet (Part C)

. . . . . . . . . .

.3 - 16

Fastening of plug, Sonoline. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 - 20

4 ______ Connections with POLYDOROS SX 65 _____________________________4 - 1

General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4

- 1

Connections and cable locations in the A12 electronics cabinet . . . . . . . . . . . .

4 - 2

Overview of cable run in the power cabinet . . . . . . . . . . . . . . . . . . . . . .

4 - 3

Connections/harness locations in the generator cabinet (Part A) . . . . . . . . . . .

4 - 4

Connections of the options and their cable positions in the A12

 

 

electronics cabinet and generator AC . . . . . . . . . . . . . . . . . . . . . . . . .

4 - 6

Connections and cable locations in the A12 electronics cabinet

 

 

and in the control console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4

- 8

Connections/cable locations in the A13 shock wave cabinet . . . . . . . . . . . . . .4 - 11 Overview of cable run in the power cabinet . . . . . . . . . . . . . . . . . . . . . .4 - 13 Connections/cable locations in the generator cabinet . . . . . . . . . . . . . . . . .4 - 14 Overview of cable run in the power cabinet . . . . . . . . . . . . . . . . . . . . . .4 - 18 Connections/harness locations in the generator cabinet (Part C) . . . . . . . . . . .4 - 19 Monitoring devices and indicators for radiation protection . . . . . . . . . . . . . . .4 - 20 Fastening of plug, Sonoline. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 - 24

5 ______ Final Work Steps _______________________________________________5 - 1

Attaching the remaining panels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 1 Adapting the Other Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 2

6 ______ Changes to previous version _____________________________________6 - 1

LITHOSTAR Multiline

RXL2-120.812.01

Page 4 of 4

Siemens AG

System

Rev. 02 10.04

CS PS 24

Medical Solutions

General Remarks

1 - 1

Items included in the Shipment

The system was prestaged, tested and programmed in the factory with all components. System start-up and the function checks required should be performed in accordance with Start-up Instructions, RXL2-120.034.01.

The system is operational once installation and start-up have been completed.

The system is shipped in the following sections:

LITHOSTAR Multiline - basic unit.

Generator power unit cabinet, equipped with components and boards.

H1 HF high voltage transformer.

Two standard cabinets.

Control console.

Accessories/cover panels.

Requirements

-The preinstallation work steps must have been completed in accordance with Planning Guide (PG) RXL2-120.021.01.

-Prior to the installation, the power line connection must be completed and provided with a system breaker, an emergency OFF switch, and ground fault detector as specified in the Planning Guide (PG) RXL2-120.021.01.

-The hardware for mounting the unit to the floor (Liebig expansion bolts /mounting plate) must be installed per Installation Instructions RXL2-120.038.01...

-The condition of the access route within the building, as well as the condition of the room in which the unit is to be installed, must be in compliance with the project drawings and the data listed under the ”General Installation and Conditions of Shipment - Med. Technology Division”.

Text Emphasis

”Cautions” are information provided with special emphasis when there is the potential for damage to the equipment.

”Notices” are information provided with special emphasis to facilitate proper use of the equipment or proper execution of a procedure.

All texts referring to adjustments or installation steps marked with symbol” p ” have to be confirmed by the subcontractor or the Siemens engineer in the installation protocol (register 3 of logbook).

Replacement of damaged or Lost Screws

Damaged or lost screws may be replaced only with steel screws which meet the requirements of DIN 267 and must be rated in the specified hardness class.

All Allen screws used must be classified as hardness class 8.8.

Siemens AG

RXL2-120.812.01

Page 1 of 4

LITHOSTAR Multiline

Medical Solutions

Rev. 02 10.04

CS PS 24

System

1 - 2

General Remarks

Safety notes

The general safety notes for medical products must be observed in the performance of work and checks.

Yellow enameled Parts

All parts of the unit and of components that are painted with yellow/red enamel are shipping brackets which may be removed only in accordance with the Installation Instructions.

Test Equipment and Tools (Service Tools Cataloque)

Tool kit for Installation engineers

Torque wrench (20 to 100 Nm)

Digital Multimeter

Installation auxiliary devices

Transport carriage roller set

11 53 654 G5338

 

The roller set must be ordered if the system

 

is not installed by the "Erlangen carrier".

Materials

Loctite 221

20 48 874 RV090

Oil for high voltage transformer H1

99 00 952

 

for refilling only, if required

 

LITHOSTAR Multiline

RXL2-120.812.01

Page 2 of 4

Siemens AG

System

Rev. 02 10.04

CS PS 24

Medical Solutions

General Remarks

1 - 3

Component Overview

 

SC

Patient monitor

Diamentor

 

 

 

 

(Option)

 

 

 

 

 

(Option)

 

 

 

 

 

 

 

 

 

 

 

 

 

HPE

VIDEO-

 

 

 

 

 

charger

MED

 

 

 

 

 

 

-DIM-

 

 

 

 

 

N12

 

3rd Monitor (Option)

Ultrasound unit

 

Shock

 

(Option)

 

wave

Image

 

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

storage

 

 

 

 

 

 

 

DICOM

 

 

 

Cooling

N11

 

 

 

 

 

PC-

 

 

 

unit

 

Monitor

 

 

 

 

Monitor

Monitor I + II

 

 

System

(Option)

 

 

 

 

 

Operating

Polydoros LX

 

controller

 

 

 

 

 

 

 

 

system

 

 

M16

 

 

 

unit

 

 

 

 

 

Multispot

 

Water

 

 

 

 

 

prepara-

Power

 

 

 

or DICOM

 

 

 

 

 

tion

supply

 

 

 

Connect

 

 

 

 

 

 

 

 

 

 

(Options)

AC

A13

A12

 

 

 

 

Siemens AG

RXL2-120.812.01

Page 3 of 4

LITHOSTAR Multiline

Medical Solutions

Rev. 02 10.04

CS PS 24

System

1 - 4

General Remarks

Component Overview

 

SC

Patient monitor

Diamentor

 

 

 

 

 

 

 

 

 

(Option)

(Option)

 

 

 

 

 

 

 

 

 

 

 

 

 

HPE

VIDEO-

 

 

 

 

 

charger

MED

 

 

 

 

 

 

-DIM-

 

 

 

 

 

N12

 

3rd Monitor (Option)

Ultrasound unit

 

Shock

 

(Option)

 

wave

Image

 

 

 

 

 

 

 

 

 

controller

storage

 

 

 

 

 

 

 

DICOM

 

 

 

Cooling

N11

 

 

 

 

 

PC-

 

 

 

unit

 

Monitor

 

 

 

 

Monitor

Monitor I + II

 

 

System

(Option)

 

 

 

 

 

Operating

Polydoros SX

 

controller

 

 

 

 

 

 

 

 

system

 

 

M16

 

 

 

unit

 

 

 

 

 

Multispot

 

Water

 

 

 

 

 

prepara-

Power

 

 

 

or DICOM

 

 

 

 

 

tion

supply

 

 

 

Connect

 

 

 

 

 

 

 

 

 

 

(Options)

AC

A13

A12

 

 

 

 

LITHOSTAR Multiline

RXL2-120.812.01

Page 4 of 4

Siemens AG

System

Rev. 02 10.04

CS PS 24

Medical Solutions

System Installation

2 - 1

 

Preparation

 

p

Preinstallation work

 

Check the condition of the table installation plate (floor plate).

 

p

Check the cable feed-throughs for cabinets, system control console, and the unit for

 

usability.

 

p

Options: Monitor trolley and/or Patient monitor

 

Check the cable feed-throughs for the Patient monitor for usability.

 

p

Make sure that there is sufficient space for a Patient monitor.

 

Siemens AG

RXL2-120.812.01

Page 1 of 14

LITHOSTAR Multiline

Medical Solutions

Rev. 02 10.04

CS PS 24

System

2 - 2

System Installation

 

 

 

Cable lead-in

Hand grip indentations

 

 

 

(on both sides)

 

 

 

(on both sides)

 

 

 

 

Polydoros

 

 

 

 

SX 65

N12

 

 

 

 

 

N11

 

2

 

 

 

 

Polydoros

 

 

 

 

LX 30

 

 

 

 

 

 

M16

 

Cable

 

 

 

Mounting holes

 

 

 

lead-in from

 

 

 

 

AC

A13

A12

Cable lead-in from below

the back

 

Fig. 1

 

 

Fig. 2

 

Generator and Cabinet Installation

 

 

 

 

 

 

NOTICE

 

 

Do not insert the H1 high-voltage transformer until the generator

 

 

 

 

is cabled in the power cabinet.

 

 

 

 

 

 

 

 

 

 

 

 

 

With the exception of the cooling unit and the high voltage charger, the cabinets are shipped from the factory completely assembled and are individually crated.

We recommend setting up and bolting down the generator according to the project plan or Figure 1 before installing the remaining cabinets.

Polydoros LX

Mark on the floor and drill the four mounting holes for the generator cabinet at its intended location using the supplied template.

Drill the holes and insert the Liebig anchors that are included in the shipment (Fig. 2).

Remove all transport safety brackets from the generator.

Take the generator off the pallet.

If necessary, knock out the cable inlet in the generator cabinet for interconnections with the adjacent cabinet. Install the edge protection strip (service package).

Mount the generator in place by inserting the 4 hex bolts into the Liebig screw anchors.

LITHOSTAR Multiline

RXL2-120.812.01

Page 2 of 14

Siemens AG

System

Rev. 02 10.04

CS PS 24

Medical Solutions

System Installation

2 - 3

1 4

2

3

Fig. 3

Polydoros SX 65

Move the power cabinet into its location.

Attach the top of the cabinet to the wall with retaining brackets to prevent the cabinet from tilting.

If required, the cabinet can also be bolted to the floor.

If required, remove the cover for the corresponding cable inlet on the generator cabinet.

Move cabinets A12 and A13 to their location according to the project plan or the above example (Fig. 1).

The splash guard has to be installed between the control cabinet A 12 and the shock wave cabinet A13. If necessary, turn it around.

Install the sidewalls of the cabinets.

Within the scope of validity of the UL regulations (e.g. USA) the metal case should not be removed due to fire protection.

Install the enclosed screw (1/Fig. 3) with nut (2/Fig. 3) to a cabinet to connect the cabinet. Then move the second cabinet to its position and tighten with nut (4/Fig. 3) and flat washer (3/Fig. 3).

p Move the cabinets to their final position and bolt them to the wall and the floor.

Installing and Connecting the High Voltage Charger

Unpack the charging unit, place it on the rails provided in the shock wave cabinet above the electronics unit N12 and secure it on the front using 4 screws.

Connect the power line cable at N12 (1 on L1, 2 on N and ge/gn on PE).

Plug in the cable from the N12, K108 to the charger controller on the charger.

Siemens AG

RXL2-120.812.01

Page 3 of 14

LITHOSTAR Multiline

Medical Solutions

Rev. 02 10.04

CS PS 24

System

2 - 4

System Installation

 

a

 

ca. 1200

 

ca. 2300

 

b

 

ca. 1100

 

ca. 2400

 

c

 

2

 

ca. 1100

 

ca. 2620

Fig. 4

Fig. 5

Installing and Connecting the Cooling Unit

Place the cooling system on the rails provided in the shock wave cabinet A13 (under the N12 electronics unit), slide it into position and secure it on the front using two screws.

Insert the hoses in the appropriate connections according to marking, and ensure that they lock into position.

Plug the power line connector for the cooling system into the socket on the electronics unit at N12.X3.

Connect the protective conductor between the cooling system and the shock wave cabinet.

CAUTION To avoid the risk of excessive heat build-up, make sure that the ventilation inside and outside the cabinet is always sufficient.

Setting Up the Unit

Place the four transport rollers (2/Fig. 4) onto the transport carriage on the yellow shipping frame at (c/Fig. 5) and bolt them in place.

Remove the shipping pallet from the unit.

Lift the unit with the help of the spindles and pull the transportation pallets out to the side.

Depending on the dimensions of the transport route, it may be necessary to reposition the rollers on the carriage (Pos. a or b in Fig. 5) and bolt them in place.

For this reason, the unit should be lowered on an appropriate wooden base.

CAUTION When lowering the unit, the cable harnesses must not be damaged.

Move the unit to its installation location and place it next to the mounting plate.

LITHOSTAR Multiline

RXL2-120.812.01

Page 4 of 14

Siemens AG

System

Rev. 02 10.04

CS PS 24

Medical Solutions

System Installation

2 - 5

Fig. 6

Fig. 7

Put the insulation plates on top of the thoroughly cleaned mounting plate (Fig. 6) (the drill holes for the equipment must not be covered).

Uncoil the four cable harnesses that are permanently connected to the unit and lay them out (Fig. 7).

Guide the free ends of the cable harnesses into the opening in the mounting plate, and into the corresponding cabinets via the cable conduits.

NOTICE

The cable harnesses are color-coded:

-blue for the shock wave cabinet

-green for the control cabinet

-yellow for the generator

The correspondingly color-coded target connections are located in the cabinets.

Siemens AG

RXL2-120.812.01

Page 5 of 14

LITHOSTAR Multiline

Medical Solutions

Rev. 02 10.04

CS PS 24

System

2 - 6

System Installation

8 x

4 x

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 8

 

 

 

 

 

Fig. 9

 

Move the unit so that it is positioned correctly over the mounting plate and so that it is level i.e., lower all four transport rollers evenly (Fig. 8).

Mount the unit using 12 bolts and insulating sleeves on the floor. Apply Loctite 221 on the bolt threads to secure them (Fig. 9):

- 8x Recessed socket head

M 8 x 4 tighten to 24 Nm, ± 10%

- 4x Hex head

M10 x 25

(The bolts are contained in the box with service materials.)

Remove the entire transport device.

Remove the yellow shipping brackets on the W-drive.

Measure the resistance to ensure that the unit is electrically isolated on the mounting plate.

Carefully feed through the cable harnesses. Store any excess cable lengths. Roll them up without kinks.

Do not place any excess cable or cable loops in the unit frame, since they may come into contact with the moving energy chain and become damaged.

Do not block the movement of the energy chain.

CAUTION Excess cable lengths may not be stored in the cabinets.

Remove the transport safety bracket from the I.I. collision protection.

LITHOSTAR Multiline

RXL2-120.812.01

Page 6 of 14

Siemens AG

System

Rev. 02 10.04

CS PS 24

Medical Solutions

System Installation

2 - 7

 

K

Fig. 10

Fig. 11

Installing the Covers

For all visible surfaces, special paneling screws with 2.5 Allen sockets have been provided.

The required screws and washers are already counted out and packed in plastic bags.

CAUTION Before installing the covers, connect each metal cover to ground; the connections are provided in the unit and on the cover panels themselves.

Secure the two lateral strips on the unit base frame with three paneling screws for each ( /Fig. 10).

Install the rear metal roll-down sash in the unit base frame on the left and the right

( /Fig. 11); for this, the mounting brackets must be installed on the inside of the frame.

Attach the cover (K/Fig. 11) for the cable routing using two paneling screws.

Siemens AG

RXL2-120.812.01

Page 7 of 14

LITHOSTAR Multiline

Medical Solutions

Rev. 02 10.04

CS PS 24

System

Siemens Lithostar Multiline Installation instructions

2 - 8

System Installation

Fig. 12

Fig. 13

A

B

Fig. 14

At this point you have to route the SONOLINE cables (see chapter 3, page 18 or chapter 4, page 22) if the ultrasound option is being installed.

Insert the two-part base frame cover and mount it in place using four paneling screws for each part ( /Fig. 12).

Install the kick plates on both table legs and fasten them together (Fig. 13).

Attach the paneling to the underside of the shock head support (A/Fig.14).

In the front section of the base frame (B/Fig. 14), use black plastic plugs to seal the two holes for mounting the transport carriage.

LITHOSTAR Multiline

RXL2-120.812.01

Page 8 of 14

Siemens AG

System

Rev. 02 10.04

CS PS 24

Medical Solutions

System Installation

2 - 9

DICOM

PC-

Monitor

Monitor (Option) Monitor I + II

Operating system unit

Multispot or DICOM Connect (Options)

A

C

B

Fig. 15

Fig. 16

Installing the Components for the System Controller

Setting Up the Console Table

The cable outlet (A/Fig. 16) is set up at the factory for downward cable feed-through. However, it is possible to route the cables to the back by punching out one of the perforated openings.

pRoute the cable from the control console table to the control cabinet.

If the Diamentor option is present, route the Diamentor cable from the electronics cabinet to the console table.

Positioning/Connecting the Monitors

Place the monitors on the control console table as shown in Fig. 15 and connect them per their designations.

Positioning the Keyboard and the PC Mouse

Place the keyboard and the PC mouse on the control console table.

Connect the cable to the keyboard.

Connecting the Footswitch, Tableside Control Console,

Shock Wave Trigger Mechanism

Connect the tableside control without the holder (optional) (B/Fig. 16) and the (C/Fig. 16) shock wave release control to the console table.

Connect the footswitch for fluoroscopy (optional) either to the console table or to the unit:

-Right back panel of the unit,

-Under the foot support at the control console table.

Connect the tableside control with the holder to the unit.

Connect the unit footswitch (optional) on the right in back of the unit.

Siemens AG

RXL2-120.812.01

Page 9 of 14

LITHOSTAR Multiline

Medical Solutions

Rev. 02 10.04

CS PS 24

System

2 - 10

System Installation

 

1

Keyboard port

X51

2

Mouse port

4

Monitor power line connector

 

 

6

Monitor port

 

7

Power line connector

X50 Respirator-ECG signal interface

X51 DUEP port

7

2

X50

4

LM - Control Unit

1

6

Fig. 17

Back panel of the PC

Positioning/Connecting the Operating System Unit (PC)

Open the door on the console table and pull out the PC slide-out shelf.

Position the operating system unit on PC slide-out shelf and secure it from below.

Connect the cables for the mouse, the keyboard, the monitors and the DUEP cable at the PC (Fig. 17).

Connect the power line cable to the operating system unit.

Insert the slide-out shelf. Pay attention to the cable routing in the console.

Cover the cable outlet

In areas where UL regulations apply,(e.g. USA) you must cover the cable outlet with the extra aluminum sheet located in the operating console as fire protection.

Positioning/Connecting DICOM Connect (Option)

Perform installation and startup according to the manual RXL2-120.814.02..

 

 

 

 

 

 

NOTICE

 

 

DICOM can be built into the LITHOSTAR Multiline only if no

 

 

 

 

MULTISPOT is installed.

 

 

 

 

 

 

 

 

 

 

 

 

 

LITHOSTAR Multiline

RXL2-120.812.01

Page 10 of 14

Siemens AG

System

Rev. 02 10.04

CS PS 24

Medical Solutions

System Installation

2 - 11

Positioning/Connecting the Multiformat Camera (Option)

Connect the Multispot per the designations and place it on the console table as shown in Fig.15 and tighten the screws. The cables can be found in the console table (power, video, control cable).

NOTICE

The two Allen screws in the base of the Multispot have to extend into the drilled holes of the intermediate plate in the operating cabinet. Depending on the customer's request, the drilled holes on the front or on the back can be used.

Positioning/Connecting the Diamentors (Option)

Plug the power cable into the multiple socket outlet of the console desk (slide-out-shelf).

Lead the cable up through the free opening.

Connect the cable routed from the measuring chamber of the Diamentor via the adapter cable supplied.

Connect the cable routed from power supply unit at the Diamentor.

Position the Diamentor on the console desk.

Siemens AG

RXL2-120.812.01

Page 11 of 14

LITHOSTAR Multiline

Medical Solutions

Rev. 02 10.04

CS PS 24

System

2 - 12

System Installation

 

2

 

1

Fig. 18

 

Installing the TV camera on the 23" I.I.

Remove the housing (1/Fig. 18) from the TV camera.

Remove the cover of the I.I. optics (black lid).

Remove the set screws on the longer sides of the TV camera.

Place the TV camera on the I.I. and mount it with the two set screws ( /Fig. 18).

Plug in the two connection cables on the TV camera and secure them (Fig. 18).

Clamp the shielding of the camera cable D115.X2 under the clamp.

Reinstall the TV camera housing (1/Fig. 18) but do not secure it.

Connect the protective conductor to the white cover (2/Fig. 18).

Place the white cover (2/Fig. 18) over the TV camera and secure it together with the housing.

Use the white plastic plugs to cover the holes.

Installing the TV camera on the 33" I.I.

The camera has been pre-installed at the factory.

Checking the temperature of the image intensifier

Check the temperature indicators of the image intensifier according to the installation instructions regarding temperature checks with SIRECON units and OPTILIX tubes in RXD0-000.038.01... The results of the evaluation are recorded in the image quality protocol (IQC) during start-up.

LITHOSTAR Multiline

RXL2-120.812.01

Page 12 of 14

Siemens AG

System

Rev. 02 10.04

CS PS 24

Medical Solutions

System Installation

2 - 13

1

1

2

Fig. 19

Fig. 20

Installing the Collimator

Unpack the collimator.

Remove the screws from the transport brackets at the side of the blades close to the focus.

Check the adjustment of the blades close to the focus with the template.

Attach the collimator to the tube unit.

Plug in connector X1 on the collimator.

Secure the wire to the panel using strain relief clamps (1/Fig. 19).

Connect the plug.

Installing the Diamentor (Option)

Remove the cover from the collimator.

Insert the measuring chamber and lead the cable out through the opening (1/Fig. 20).

Reattach the cover to the collimator.

Plug the two connectors together and fix the cable with the cable ties (2/Fig. 20).

Siemens AG

RXL2-120.812.01

Page 13 of 14

LITHOSTAR Multiline

Medical Solutions

Rev. 02 10.04

CS PS 24

System

Loading...
+ 49 hidden pages