The reproduction, transmission or
use of this document or its contents
is not permitted without express
written authority. Offenders will be
liable for damages. All rights,
including rights created by patent
grant or registration of a utility
model _or_ design,_are_ reserved.
English
Print No.: RXL2-120.812.01.02.02 Doc. Gen. Date:10.04
Replaces: RXL2-120.812.01.01.02
0 - 2Revision
ChapterPageRevision
allall02
Document revision level
The document corresponds to the version/revision level effective at the time of system delivery.
Revisions to hardcop y documentation are not automatically distributed.
Please contact your local Siemens office to order current revision levels.
Disclaimer
The installation and service of equipment described herein is to be performed by qualified personnel
who are employed by Siemens or one of its affiliates or who are otherwise authorized by Siemens or
one of its affiliates to provide such services.
Assemblers and other persons who are not employed by or otherwise directly affiliated with or authorized by Siemens or one of its affiliates are directed to contact one of the local offices of Siemens or
one of its affiliates before attempting installation or service procedures.
LITHOSTAR MultilineRXL2-120.812.01Page 2 of 4Siemens AG
SystemRev. 0210.04CS PS 24Medical Solutions
6 ______ Changes to previous version _____________________________________6 - 1
LITHOSTAR MultilineRXL2-120.812.01Page 4 of 4Siemens AG
SystemRev. 0210.04CS PS 24Medical Solutions
General Remarks1
Items included in the Shipment1
The system was prestaged, tested and programmed in the factory with all components.
System start-up and the function checks required should be performed in accordance with
Start-up Instructions, RXL2-120.034.01.
The system is operational once installation and start-up have been completed.
The system is shipped in the following sections:
• LITHOSTAR Multiline - basic unit.
• Generator power unit cabinet, equipped with components and boards.
• H1 HF high voltage transformer.
• Two standard cabinets.
• Control console.
• Accessories/cover panels.
Requirements1
- The preinstallation work steps must have been completed in accordance with Planning
Guide (PG) RXL2-120.021.01.
- Prior to the installation, the power line connection must be completed and provided
with a system breaker, an emergency OFF switch, and ground fault detector as
specified in the Planning Guide (PG) RXL2-120.021.01.
- The hardware for mounting the unit to the floor (Liebig expansion bolts /mounting plate)
must be installed per Installation Instructions RXL2-120.038.01...
- The condition of the access route within the building, as well as the condition of the
room in which the unit is to be installed, must be in compliance with the project
drawings and the data listed under the ”General Installation and Conditions of
Shipment - Med. Technology Division”.
1 - 1
Text Emphasis1
• ”Cautions” are information provided with special emphasis when there is the potential
for damage to the equipment.
• ”Notices” are information provided with special emphasis to facilitate proper use of the
equipment or proper execution of a procedure.
• All texts referring to adjustments or installation steps marked with symbol”” have to
be confirmed by the subcontractor or the Siemens engineer in the installation protocol
(register 3 of logbook).
p
Replacement of damaged or Lost Screws1
• Damaged or lost screws may be replaced only with steel screws which meet the
requirements of DIN 267 and must be rated in the specified hardness class.
• All Allen screws used must be classified as hardness class 8.8.
Siemens AGRXL2-120.812.01Page 1 of 4LITHOSTAR Multiline
Medical SolutionsRev. 0210.04CS PS 24System
1 - 2General Remarks
Safety notes1
• The general safety notes for medical products must be observed in the performance of
work and checks.
Yellow enameled Parts1
• All parts of the unit and of components that are painted with yellow/red enamel are
shipping brackets which may be removed only in accordance with the Installation
Instructions.
Test Equipment and Tools (Service Tools Cataloque)1
• Tool kit for Installation engineers
• Torque wrench (20 to 100 Nm)
• Digital Multimeter
Installation auxiliary devices1
Transport carr iage roller set 11 53 654 G5338
The roller set must be ordered if the system
is not installed by the "Erlangen carrier".
Materials1
• Loctite 22120 48 874 RV090
• Oil f or high voltage transf ormer H1
for refilling only , if required
99 00 952
LITHOSTAR MultilineRXL2-120.812.01Page 2 of 4Siemens AG
SystemRev. 0210.04CS PS 24Medical Solutions
General Remarks1 - 3
Component Overview1
SC
3rd Monitor (Option)
PCMonitor
DICOM
Monitor
(Option)
Patient monitor
(Option)
Monitor I + II
Ultrasound unit
(Option)
Operating
system
unit
Multispot
or DICOM
Connect
(Options)
Diamentor
(Option)
Polydoros LX
AC
”HPE”
charger
N12
Shock
wave
controller
Cooling
unit
Water
prepara-
tion
A13
VIDEO-
MED
-DIM-
Image
storage
N11
System
controller
M16
Power
supply
A12
Siemens AGRXL2-120.812.01Page 3 of 4LITHOSTAR Multiline
Medical SolutionsRev. 0210.04CS PS 24System
1 - 4General Remarks
Component Overview1
SC
3rd Monitor (Option)
PCMonitor
DICOM
Monitor
(Option)
Patient monitor
(Option)
Monitor I + II
Ultrasound unit
(Option)
Operating
system
unit
Multispot
or DICOM
Connect
(Options)
Diamentor
(Option)
Polydoros SX
AC
”HPE”
charger
N12
Shock
wave
controller
Cooling
unit
Water
prepara-
tion
A13
VIDEO-
MED
-DIM-
Image
storage
N11
System
controller
M16
Power
supply
A12
LITHOSTAR MultilineRXL2-120.812.01Page 4 of 4Siemens AG
SystemRev. 0210.04CS PS 24Medical Solutions
System Installation2
Preparation2
Preinstallation work2
2 - 1
p
p
p
p
• Check the condition of the table installation plate (floor plate).
• Check the cable feed-throughs for cabinets, system control console, and the unit for
usability.
Options: Monitor trolley and/or Patient monitor2
• Check the cable feed-throughs for the Patient monitor for usability.
• Make sure that there is sufficient space for a Patient monitor.
Siemens AGRXL2-120.812.01Page 1 of 14LITHOSTAR Multiline
Medical SolutionsRev. 0210.04CS PS 24System
2 - 2System Installation
Cable lead-in
(on both sides)
Polydoros
SX 65
N12
N11
Polydoros
LX 30
M16
Mounting holes
AC
Fig. 1Fig. 2
A13
A12
Cable lead-in from below
Generator and Cabinet Installation
Hand grip indentations
(on both sides)
2
Cable
lead-in from
the back
NOTICE
Do not insert the H1 high-voltage transformer until the generator
is cabled in the power cabinet.
With the exception of the cooling unit and the high voltage charger, the cabinets are
shipped from the factory completely assembled and are individually crated.
We recommend setting up and bolting down the generator according to the project plan or
Figure 1 before installing the remaining cabinets.
Polydoros LX2
• Mark on the floor and drill the four mounting holes for the generator cabinet at its
intended location using the supplied template.
• Drill the holes and insert the Liebig anchors that are included in the shipment (Fig. 2).
• Remove all transport safety brackets from the generator.
• Take the generator off the pallet.
• If necessary, knock out the cable inlet in the generator cabinet for interconnections with
the adjacent cabinet. Install the edge protection strip (service package).
• Mount the generator in place b y inserting the 4 hex bolts into the Liebig screw anchors.
LITHOSTAR MultilineRXL2-120.812.01Page 2 of 14Siemens AG
SystemRev. 0210.04CS PS 24Medical Solutions
System Installation2 - 3
1
4
2
Fig. 3
3
Polydoros SX 652
• Move the power cabinet into its location.
• Attach the top of the cabinet to the wall with retaining brackets to prevent the cabinet
from tilting.
p
• If required, the cabinet can also be bolted to the floor.
• If required, remove the cover for the corresponding cable inlet on the generator cabinet.
• Mov e cabinets A12 and A13 to their location according to the project plan or the above
example (Fig. 1).
• The splash guard has to be installed between the control cabinet A 12 and the shoc k
wave cabinet A13. If necessary , turn it around.
• Install the side walls of the cabinets.
• Within the scope of validity of the UL regulations (e.g. USA) the metal case should not be
removed due to fire protection.
• Install the enclosed screw (1/Fig. 3) with nut (2/Fig. 3) to a cabinet to connect the cabinet.
Then move the second cabinet to its position and tighten with nut (4/Fig. 3) and flat
washer (3/Fig. 3).
• Move the cabinets to their final position and bolt them to the wall and the floor.
Installing and Connecting the High Voltage Charger2
• Unpack the charging unit, place it on the rails provided in the shock wave cabinet above
the electronics unit N12 and secure it on the front using 4 screws.
• Connect the power line cable at N12 (1 on L1, 2 on N and ge/gn on PE).
• Plug in the cable from the N12, K108 to the charger controller on the charger.
Siemens AGRXL2-120.812.01Page 3 of 14LITHOSTAR Multiline
Medical SolutionsRev. 0210.04CS PS 24System
2 - 4System Installation
a
ca. 1200
ca. 2300
b
ca. 1100
ca. 2400
2
Fig. 4Fig. 5
c
ca. 1100
ca. 2620
Installing and Connecting the Cooling Unit2
• Place the cooling system on the rails provided in the shock wave cabinet A13 (under the
N12 electronics unit), slide it into position and secure it on the front using two screws.
• Insert the hoses in the appropriate connections according to marking, and ensure that
they lock into position.
• Plug the power line connector for the cooling system into the socket on the electronics
unit at N12.X3.
• Connect the protective conductor between the cooling system and the shock wave
cabinet.
CAUTION
To avoid the risk of excessive heat build-up, make sure that the
ventilation inside and outside the cabinet is always sufficient.
Setting Up the Unit2
• Place the four transport rollers (2/Fig. 4) onto the transport carriage on the yellow
shipping frame at (c/Fig. 5) and bolt them in place.
• Remove the shipping pallet from the unit.
Lift the unit with the help of the spindles and pull the transportation pallets out to the side.
• Depending on the dimensions of the transport route, it may be necessary to reposition
the rollers on the carriage (Pos. a or b in Fig. 5) and bolt them in place.
For this reason, the unit should be lowered on an appropriate wooden base.
CAUTION
When lowering the unit, the cable harnesses must not be damaged.
• Move the unit to its installation location and place it next to the mounting plate.
LITHOSTAR MultilineRXL2-120.812.01Page 4 of 14Siemens AG
SystemRev. 0210.04CS PS 24Medical Solutions
System Installation2 - 5
Fig. 6Fig. 7
• Put the insulation plates on top of the thoroughly cleaned mounting plate (Fig. 6)
(the drill holes for the equipment must not be covered).
• Uncoil the four cable harnesses that are permanently connected to the unit and lay them
out (Fig. 7).
• Guide the free ends of the cable harnesses into the opening in the mounting plate, and
into the corresponding cabinets via the cable conduits.
NOTICE
The cable harnesses are color-coded:
- blue for the shock wave cabinet
- green for the control cabinet
- yellow for the generator
The correspondingly color-coded target connections are located
in the cabinets.
Siemens AGRXL2-120.812.01Page 5 of 14LITHOSTAR Multiline
Medical SolutionsRev. 0210.04CS PS 24System
2 - 6System Installation
8 x
4 x
Fig. 8Fig. 9
• Move the unit so that it is positioned correctly over the mounting plate and so that it is
level i.e., lower all four transport rollers evenly (Fig. 8).
• Mount the unit using 12 bolts and insulating sleeves on the floor. Apply Loctite 221 on the
bolt threads to secure them (Fig. 9):
- 8x Recessed socket headM 8 x 4 tighten to 24 Nm, ± 10%
- 4x Hex headM10 x 25
(The bolts are contained in the box with service materials.)
• Remove the entire transport device.
• Remove the yellow shipping brackets on the W-drive.
• Measure the resistance to ensure that the unit is electrically isolated on the mounting
plate.
• Carefully feed through the cable harnesses. Store any excess cable lengths. Roll them
up without kinks.
Do not place any excess cable or cable loops in the unit frame, since they may come into
contact with the moving energy chain and become damaged.
Do not block the movement of the energy chain.
CAUTION
Excess cable lengths may not be stored in the cabinets.
• Remove the transport safety bracket from the I.I. collision protection.
LITHOSTAR MultilineRXL2-120.812.01Page 6 of 14Siemens AG
SystemRev. 0210.04CS PS 24Medical Solutions
System Installation2 - 7
K
Fig. 10Fig. 11
Installing the Covers2
For all visible surfaces, special paneling screws with 2.5 Allen sockets have been provided.
• The required scre ws and washers are already counted out and packed in plastic bags.
CAUTION
Before installing the covers, connect eac h metal co ver to gr ound;
the connections are provided in the unit and on the cover panels
themselves.
• Secure the two lateral strips on the unit base frame with three paneling screws for each
( /Fig. 10).
• Install the rear metal roll-down sash in the unit base frame on the left and the right
( /Fig. 11); for this, the mounting brackets must be installed on the inside of the frame.
• Attach the cover (K/Fig. 11) for the cable routing using two paneling screws.
Siemens AGRXL2-120.812.01Page 7 of 14LITHOSTAR Multiline
Medical SolutionsRev. 0210.04CS PS 24System
2 - 8System Installation
Fig. 12Fig. 13
A
B
Fig. 14
• At this point you have to route the SONOLINE cables (see chapter 3, page 18 or
chapter 4, page 22) if the ultrasound option is being installed.
• Insert the two-part base frame cover and mount it in place using four paneling screws for
each part ( /Fig. 12).
• Install the kick plates on both table legs and fasten them together (Fig. 13).
• Attach the paneling to the underside of the shock head support (A/Fig.14).
• In the front section of the base frame (B/Fig. 14), use black plastic plugs to seal the two
holes for mounting the transport carriage.
LITHOSTAR MultilineRXL2-120.812.01Page 8 of 14Siemens AG
SystemRev. 0210.04CS PS 24Medical Solutions
System Installation2 - 9
PCMonitor
Fig. 15Fig. 16
DICOM
Monitor
(Option)
Monitor I + II
Operating
system
unit
Multispot
or DICOM
Connect
(Options)
Installing the Components for the System Controller2
Setting Up the Console Table2
The cable outlet (A/Fig. 16) is set up at the factory for downward cable feed-through.
However, it is possible to route the cables to the back by punching out one of the perforated openings.
p
• Route the cable from the control console table to the control cabinet.
A
C
B
• If the Diamentor option is present, route the Diamentor cable from the electronics cabinet
to the console table.
Positioning/Connecting the Monitors2
• Place the monitors on the control console table as shown in Fig. 15 and connect them
per their designations.
Positioning the Keyboard and the PC Mouse2
• Place the keyboard and the PC mouse on the control console table.
• Connect the cable to the keyboard.
Connecting the Footswitch, Tableside Control Console,
Shock Wave Trigger Mechanism2
• Connect the tableside control without the holder (optional) (B/Fig. 16) and the (C/Fig. 16)
shock wave release control to the console table.
• Connect the footswitch for fluoroscopy (optional) either to the console table or to the unit:
- Right back panel of the unit,
- Under the foot support at the control console table.
• Connect the tableside control with the holder to the unit.
• Connect the unit footswitch (optional) on the right in back of the unit.
Siemens AGRXL2-120.812.01Page 9 of 14LITHOSTAR Multiline
Medical SolutionsRev. 0210.04CS PS 24System
2 - 10System Installation
1 Keyboard port
X51
7
2
4
2 Mouse port
4 Monitor power line connector
6 Monitor port
7 Power line connector
X50 Respirator-ECG signal interface
X51 DUEP port
X50
LM - Control Unit
Fig. 17
Back panel of the PC2
Positioning/Connecting the Operating System Unit (PC)2
• Open the door on the console table and pull out the PC slide-out shelf.
• Position the operating system unit on PC slide-out shelf and secure it from below.
• Connect the cables for the mouse, the keyboard, the monitors and the DUEP cable at the
• Connect the power line cable to the operating system unit.
• Insert the slide-out shelf. Pay attention to the cable routing in the console.
Cover the cable outlet2
• In areas where UL regulations apply,(e.g. USA) you must cover the cable outlet with the
Positioning/Connecting DICOM Connect (Option)2
1
PC (Fig. 17).
extra aluminum sheet located in the operating console as fire protection.
6
• Perform installation and startup according to the manual RXL2-120.814.02..
NOTICE
LITHOSTAR MultilineRXL2-120.812.01Page 10 of 14Siemens AG
SystemRev. 0210.04CS PS 24Medical Solutions
DICOM can be built into the LITHOSTAR Multiline only if no
MULTISPOT is installed.
System Installation2 - 11
Positioning/Connecting the Multiformat Camera (Option)2
• Connect the Multispot per the designations and place it on the console table as shown in
Fig.15 and tighten the screws. The cables can be found in the console table (power,
video, control cable).
NOTICE
The two Allen screws in the base of the Multispot have to extend
into the drilled holes of the intermediate plate in the operating
cabinet. Depending on the customer's request, the drilled holes
on the front or on the back can be used.
Positioning/Connecting the Diamentors (Option)2
• Plug the power cable into the multiple socket outlet of the console desk (slide-out-shelf).
• Lead the cable up through the free opening.
• Connect the cable routed from the measuring chamber of the Diamentor via the adapter
cable supplied.
• Connect the cable routed from power supply unit at the Diamentor.
• Position the Diamentor on the console desk.
Siemens AGRXL2-120.812.01Page 11 of 14LITHOSTAR Multiline
Medical SolutionsRev. 0210.04CS PS 24System
2 - 12System Installation
2
1
Fig. 18
Installing the TV camera on the 23" I.I.2
• Remove the housing (1/Fig. 18) from the TV camera.
• Remove the cover of the I.I. optics (black lid).
• Remove the set screws on the longer sides of the TV camera.
• Place the TV camera on the I.I. and mount it with the two set screws ( /Fig. 18).
• Plug in the two connection cables on the TV camera and secure them (Fig. 18).
• Clamp the shielding of the camera cable D115.X2 under the clamp.
• Reinstall the TV camera housing (1/Fig. 18) but do not secure it.
• Connect the protective conductor to the white cover (2/Fig. 18).
• Place the white cover (2/Fig. 18) over the TV camera and secure it together with the
housing.
• Use the white plastic plugs to cover the holes.
Installing the TV camera on the 33" I.I.2
• The camera has been pre-installed at the factory.
Checking the temperature of the image intensifier2
• Check the temperature indicators of the image intensifier according to the installation
instructions regarding temperature checks with SIRECON units and OPTILIX tubes in
RXD0-000.038.01... The results of the evaluation are recorded in the image quality
protocol (IQC) during start-up.
LITHOSTAR MultilineRXL2-120.812.01Page 12 of 14Siemens AG
SystemRev. 0210.04CS PS 24Medical Solutions
System Installation2 - 13
1
1
2
Fig. 19Fig. 20
Installing the Collimator2
• Unpack the collimator.
• Remove the screws from the transport brackets at the side of the blades close to the
focus.
• Check the adjustment of the blades close to the focus with the template.
• Attach the collimator to the tube unit.
• Plug in connector X1 on the collimator.
• Secure the wire to the panel using strain relief clamps (1/Fig. 19).
• Connect the plug.
Installing the Diamentor (Option)2
• Remove the cover from the collimator.
• Insert the measuring chamber and lead the cable out through the opening (1/Fig. 20).
• Reattach the cover to the collimator.
• Plug the two connectors together and fix the cable with the cable ties (2/Fig. 20).
Siemens AGRXL2-120.812.01Page 13 of 14LITHOSTAR Multiline
Medical SolutionsRev. 0210.04CS PS 24System
Loading...
+ 49 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.