Siemens LED-3,LED-4 Installation Instructions Manual

Installation Instructions
Model LED-3/4 Remote Annunciator for use with the SXL-EX Control Panel (For indoor use only in dry environments)
Fire Safety
INTRODUCTION
The Model LED-3/4 Remote Annunciator from Siemens Builidng Technologies, Inc., shown in Figure 1 is an eight zone annunciator containing sixteen LEDs. The LEDs can be used to indicate the alarm, supervisory, or trouble status of initiating zones.
A maximum of 2 Remote Annunciators can be added to each SXL-EX system so that the status of 8 zones can be displayed at two different locations.
In addition, a green polling LED on the back of the annunciator indicates the status of the annunciator when troubleshooting the installation.
ELECTRICAL OPERATING
Input Power 24 VDC (no LEDs on) 10mA
Output Power
TABLE 1
CHARACTERISTICS
2mA per ALARM/SUPERVISORY/ TROUBLE LED 42mA max (all LEDs on)
Remove all system power before
installation, first battery and then AC.
(To power up, connect AC first, then the battery.)
INSTALLATION GUIDELINES
Install in accordance with NFPA 72, NEC Article 760, and any applicable local codes.
ANNUNCIATOR INSTALLATION
Setting the Address for SXL-EX
Set the address of the module using switch S1 located on the back of the module.
To set address 1:
Set SW1 of S1 to OFF Set SW2-SW6 of S1 to ON
To set address 2:
Set SW2 of S1 to OFF Set SW1 and SW3-SW6 to ON
Figure 1
LED-3/4 Remote Annunciator
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
P/N 315-093066-11
Any other setting causes a trouble indication on the panel. There also would be no activity from the annunciator or from the polling LED, DS17, which is located next to the S1 switch.
Wiring
Connect the system wiring to the TB1 terminals
BACKFRONT
on the annunciator module. Refer to Table 2, Table 3, and Figure 2 for proper wiring connec­tions and cable length.
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
1
TABLE 2
Terminal Connections
Terminal Function
3. After the system is tested, tighten the mount­ing screws.
4. Fill in the appropriate information for each zone on the card provided.
24V
DATA
-V
ER
Provides power to circuitry Serial communication line Return line Earth Return
TABLE 3
Maximum Cable Length vs. Wire Size
AWG Cable Length
14 16 18
Observe the wiring polarity when making con­nections. Damage may result from incorrect wiring.
2000 feet 2000 feet 1000 feet
Mounting
1. Mount the annunciator semiflush using a single gang electrical backbox.
2. DO NOT tighten the mounting screws since the module may have to be removed during troubleshooting (when looking for activity from the polling LED, DS17, on the back of the module.
PROGRAMMING THE SXL-EX SYSTEM FOR THE LED-3/4 MODULE
Enabling the Program Mode
Enter level 9 of the programming mode.
1. Press the RESET and DRILL keys at the same time. The TROUBLE LED lights, and the letter E appears on the seven segment display.
2. Enter the password by pressing the appropriate keys:
ACK = 1 DRILL = 3 RESET = 2 SILENCE = 4
Then press the SILENCE key.
The seven segment display either shows F, to indicate an incorrect password, or A, to indicate that the password is accepted. If the letter F appears, repeat Steps 1 and 2. If the letter A appears, continue to the next step.
3. Press the ACK key once to enter the Pro­gram mode. The PROGRAM/TEST LED on the front panel lights and the display shows the letter P.
seven segment
To UL listed SXL-EX Control Panel Aux Port TB-3 (Power Limited) Style 4 Supervised
Positive and Negative Ground Fault Detected at <20K for Terminals on TB-1
Power Limited
+24V -V DATA ER
Polling LED
ON
S1 S1
TB-1 TB-1
Figure 2
LED-3/4 Wiring Connections
2
+24V -V DATA ER
Polling LED
ON
DS17DS17
Loading...
+ 2 hidden pages