Use (cont´d)
LAE10 For the supervision of oil burners with an active selenium photocell detec-
tor RAR… in intermittent operation
LFE10 For the supervision with an ionization probe (gas burners) or with UV de-
tectors QRA… (gas, oil or dual-fuel burners, with or without ignition spark
proving) in intermittent operation
LFE50 For the supervision with UV detectors QRA50… / QRA51…(gas, oil or
dual-fuel burners) in intermittent or continuous operation
All units comply with the relevant European standards for oil, gas and forced draft
burners of any fuel throughput.
The LEC1... can control the following burner plant components:
Fan motor, flue gas fan, air damper, ignition transformer, 1 to 3 fuel valves, load controller, and an external fault signaling device.
A load controller with 3-position output can be connected.
Design, control sequence and adjustment facilities of the control unit make it suitable
for use on combustion plants of any size and type, be it in connection with expanding
flame or interrupted pilot burners, continuously operating burners or any other special
burners.
- Prepurge time adjustable between 8 and 63 seconds
- Operation with or without postpurging
- Fully automatic control of air damper possible, irrespective of the actuator run time
- Possibility of air pressure check in connection with functional control of the air
pressure switch prior to startup
- Choice of ignition: Direct ignition with pilot burner, with or without ignition spark
proving
- Preignition time can be set to «Long» (during the prepurge time) or «Short» (3
seconds, e.g. for forced draft gas burners)
- 1st and 2nd safety time adjustable between 0 and 9 seconds
- Automatic extraneous light test during burner off periods and during the purging
times (with lockout in the event of faulty flame signals)
- Semi-automatic burner startup and operation possible
- Built-in lockout warning lamp
- Electrical remote reset facility
- Cover with 2 additional sealing screws to provide protection against tampering
(refer to «Dimensions»)
- Continuous display of the program sequence in the cover’s viewing window
- In the event of a fault, the program indicator shows the operating phase during
which the fault occurred
- Motor of the programming mechanism can be switched off to simplify burner ad-
justments
- Camshaft can be rotated manually
The following types of
flame safeguards are
available:
Special features