Siemens HMS-2S, HMS-SA Installation Instructions Manual

Installation Instructions Models HMS-2S / HMS-SA
Dual Stage Manual Pull Station (For Canadian Two-Stage Applications) Single Stage Manual Pull Station with Auxiliary Contacts
INTRODUCTION The Model HMS-2S/-SA Manual Station from Siemens
Industry, Inc., is a field installed addressable device containing advanced control panel communication technology. This technology, which provides two­direction communication with the control panel, produces an Intelligent Initiating Device.
Figure 1 HMS Cover
PROGRAMMING Refer to Figure 1 to locate the opening on the HMS cover that allows access to the INSTRUCTIONS
programming holes which are on the HMS printed circuit board.
PROGRAMMING
To connect the HMS to the DPU Programmer/Tester,
POINTS
insert the plug from the DPU cable provided with the Programmer/Tester into the opening on the HMS as shown in Figure 2. Because HMS devices are polarity insensitive, the programming plug can be inserted into the programming holes in either direction.
To prevent potential damage to the DPU DO NOT connect an HMS to the DPU until at least one wire is removed from terminals 1 or 2 of the HMS.
LOCATING TAB
Figure 2 Connecting the DPU Plug
OPENING TO PROGRAMMING POINTS
PLUG FROM
DPU
Follow the instructions in the DPU Manual (P/N 315-033260) to program the HMS to the desired address. Record the device address on the label located on the HMS front panel. The HMS can now be installed and wired to the system.
OPERATION The HMS manual station operates with the FireFinder-XLS Control Panel via the DLC
Device Loop Card.
The HMS-2S/-SA manual station housing has a pull down lever that locks in position after releasing a spring loaded switch. (See Figure 4.) To indicate the manual station is activated, the pull down lever remains down and locked until the station is physically reset. The HMS-2S/-SA manual station has a set of normally closed auxiliary contacts which are available for releasing door holders and magnetic door locks.
The HMS-2S has a keyswitch which can activate a second address.
The unit is reset by opening the hinged housing cover with an Allen key and then closing and locking the cover, or by returning the keyswitch to its original position.
Siemens Industry, Inc.
P/N 315-033430-6
Building Technologies Division
WIRING
NOTES:
1. Recommended wire sizes:
1
2
3
PIGTAIL LEADS
DLC LINE 1
DLC 2LINE
DLC 1LINE
DLC 2LINE
TO NEXT ADDRESSABLE DEVICE
FROM INITIATING CONTROL PANEL OR PREVIOUS ADDRESSABLE DEVICE
EARTH GROUND
PROGRAMMABLE N/C AUX CONTACT 24 VDC, 2A (DOOR HOLDER OR A MAGNETIC LOCK RELEASE, ETC.) ONLY CONNECT TO POWER LIMITED SOURCE
2. Wire larger than 14 AWG can damage the connector.
3. When using shielded cable without metal raceway or with
4. When using shielded cable with metal raceway, the wiring shields
5. When using metal raceway without shielded cable, connect the
6. Metal raceway should be thoroughly grounded throughout the system.
7. Addressable Device Loop ratings:
18 AWG minimum, 14 AWG maximum
nonmetallic raceway, the shields should be terminated at the device ground terminal. If the device box is already grounded by another means, such as being mounted to a grounded structure, the wire shields should be continuous and must be grounded solely at the point of origin; for example, at the control panel.
shall be continuous and grounded solely at the point of origin. The device ground terminal shall be connected to the grounded device box.
device ground terminal to the grounded device box.
Voltage: 31V max.
18V min. (pulsing)
Current maximum: 1mA
Figure 3 HMS-2S / HMS-SA Wiring Information
In supervisory: HMS-2S / HMS-SA draws 1mA.
8. The HMS-2S / HMS-SA is a polarity insensitive device. Line 1 and Line 2 can be either line of the loop.
The use of limited energy cable is not allowed.
INSTALLATION Distribute the manual station boxes throughout the protected area so that they
are unobstructed, readily accessible, and located in the normal exit path. Place the manual station according to the regulations of the authorities having jurisdiction.
Surface Mounting Mount the backplate to a Model MC-5 Backbox as shown in Figure 4.
Flush Mounting Mount the backplate to a user supplied single gang switchbox as shown in Figure 4.
Do not overtighten the screws. Overtightening may distort the backplate.
BACKPLATE
SURFACE
MOUNTING
ENCLOSURE
Figure 4 Mounting The HMS
2¾ in.
KEYSWITCH
LOCKING
SCREW
HOUSING
MODEL
MC-5
NAMEPLATE
FLUSH
MOUNTING
ENCLOSURE
4 in.
5½ in.
HOUSING HINGED
TO BACKPLATE
BACKPLATE
3½ in.
3½ INCH DEEP
SWITCH BOX
(USER SUPPLIED)
3 in.
ELECTRICAL RATINGS
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
tnerruC.xaMAm1
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
pooLCLD-SF/CLD
P/N 315-033430-6
Loading...