Siemens FireSeeker FS-100 Installation, Operation And Maintenance Manual

Page 1
Fire Safety
FireSeeker Fire Alarm Control Panel Model FS-100
Installation, Operation, and Maintenance Manual
Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview Boulevard Florham Park, NJ 07932 Brampton, Ontario L6T 5E4 CN
P/N 315 -699461-1 (447290 )
Technical Manuals Online! - http://www.tech-man.com
Page 2
FS-100 Installation & Operation Manual
Table of Contents
INTRODUCTION ................................................................................................................................1
CONTROL UNIT LIMITATIONS .......................................................................................................1
PREFACE.......................................................................................................................................2
DESCRIPTIONS.................................................................................................................................3
SYSTEM DESCRIPTION .................................................................................................................3
HARDWARE CONFIGURATION ......................................................................................................3
MINIMUM CONTROL UNIT CONFIGURATION .................................................................................4
Power Supply ..............................................................................................................................4
Addressable Device Circuit...........................................................................................................4
Notification Appliance Circuits .......................................................................................................4
RS485 Communications Circuit.....................................................................................................4
Status Relays ..............................................................................................................................4
OPTIONAL CONTROL UNIT CONFIGURATION...............................................................................4
Municipal Tie Board .....................................................................................................................4
RS232 Communication Board.......................................................................................................4
DACT Board ................................................................................................................................4
BATTERY SETS .............................................................................................................................5
AUXILIARY MODULES....................................................................................................................5
Remote LCD Annunciator.............................................................................................................5
Serial Relay Unit and Serial Relay Extender ..................................................................................5
Serial Annunciator Unit and Serial Annunciator Extender................................................................5
ADDRESSABLE DEVICES ..............................................................................................................5
Siemens Addressable Detectors ...................................................................................................5
Variable Thresholds .....................................................................................................................5
Operator Alerts ............................................................................................................................6
Other Siemens Addressable Devices ............................................................................................6
Heat Detectors .............................................................................................................................6
Addressable Modules (Monitor and Control) ..................................................................................6
Manual Stations ...........................................................................................................................6
PROCESSOR CONTROLLED OUTPUT ZONES ..............................................................................6
Output Soundi ng Patterns ............................................................................................................6
Control of Audible Silencing ..........................................................................................................6
Audible Silence Inhibit..................................................................................................................6
EVENT HISTORY............................................................................................................................7
GENERAL DESIGN FEATURES......................................................................................................8
Environmental..............................................................................................................................8
Power Limiting .............................................................................................................................8
Ground Fault Detection ................................................................................................................8
Transient Protection .....................................................................................................................8
Security Functions .......................................................................................................................8
REGULATORY STANDARDS ..........................................................................................................8
Federal Communications Commission ...........................................................................................8
Underwriters Laboratories .............................................................................................................8
GENERAL SPECIFICATIONS..........................................................................................................9
Environmental..............................................................................................................................9
Primary Supply ............................................................................................................................9
Secondary and Trouble Power Supply...........................................................................................9
Auxiliary Power Outputs ...............................................................................................................9
Status Relays ..............................................................................................................................9
Notification Appliance Circuits .......................................................................................................9
RS485 Communications Circuit................................................................................................... 10
P/N 315 -699461 i
Technical Manuals Online! - http://www.tech-man.com
Page 3
FS-100 Installation & Operation Manual
Addressable Device Circuit.........................................................................................................10
Municipal Tie (Optional Municipal Tie Board Model FS-MT)..........................................................10
RS232 Output (Optional RS232 Board Model FS-232) .................................................................10
DACT Circuit (Optional DACT Board Model FS-DACT).................................................................11
CONTROL UNIT OPERATION.......................................................................................................... 12
OPERATION INSTRUCTI ONS .......................................................................................................12
A. Standby Condition .................................................................................................................12
B. Alarm Condition .................................................................................................................... 12
2) Waterflow Alarms..................................................................................................................12
3) Positive Alarm Sequence (PAS)............................................................................................. 12
4) Pre-Signal ............................................................................................................................ 12
C. Trouble Condition ................................................................................................................. 13
D. Supervisory Condition ........................................................................................................... 13
E. Maintenance .........................................................................................................................13
ADDITIONAL OPERATING PROCEDURES ...................................................................................14
A. Lamp Test............................................................................................................................14
B. Drill......................................................................................................................................14
C. Recall .................................................................................................................................. 14
D. Pre-Alarm .............................................................................................................................14
E. General Alarm ...................................................................................................................... 14
F. Tornado ................................................................................................................................14
G. History ................................................................................................................................. 15
FS-100 OPERATING INSTRUCTIONS ........................................................................................... 16
FS-RD OPERATING INSTRUCTIONS............................................................................................17
CONTROL UNIT INSTALLATION ..................................................................................................... 18
PARTS SUPPLIED ........................................................................................................................18
CAUTION ..................................................................................................................................... 18
CONTROL UNIT LOCATION ......................................................................................................... 18
ENCLOSURE MOUNTING .............................................................................................................18
A. Surface Mounting Instructions................................................................................................19
B. Semi-Flush Mounting Instructions .......................................................................................... 20
C. Knock -Outs..........................................................................................................................21
D. Main Board Installation..........................................................................................................21
E. AC Supply Connection .......................................................................................................... 21
F. Transformer Installation ......................................................................................................... 22
G. Front Plate Assembly............................................................................................................ 22
H. Front Plate Mounting............................................................................................................. 22
I. Door Assembly......................................................................................................................23
J. Battery Installation.................................................................................................................23
K. Powering the Control Unit......................................................................................................23
L. Checking Supervised Circuits .................................................................................................24
M. Optional Modules ................................................................................................................. 24
N. System Wiring ...................................................................................................................... 24
O. Check System Operation ...................................................................................................... 24
SYSTEM WIRING .............................................................................................................................25
CONTROL UNIT WIRING OVERVIEW...........................................................................................25
WIRING SEPARATION ..................................................................................................................25
WIRING SEPARATION ..................................................................................................................26
PRIMARY AND SECONDARY POWER WIRING ............................................................................ 26
STATUS RELAYS AND AUXILIARY POWER OUTPUTS WIRING ................................................... 27
System Power Requirement Calculations .................................................................................... 27
Auxiliary Power Supply ...............................................................................................................27
Battery Size Calculations............................................................................................................27
NAC WIRING ................................................................................................................................28
P/N 315 -699461 ii
Technical Manuals Online! - http://www.tech-man.com
Page 4
FS-100 Installation & Operation Manual
RS485 COMMUNICATIONS CIRCUIT............................................................................................ 29
Remote Device Power................................................................................................................ 29
Remote Device Data..................................................................................................................29
ADDRESSABLE DEVICE CIRCUIT ................................................................................................30
Addressable Device Wiring Diagrams ..........................................................................................30
Addressable Detectors ............................................................................................................... 33
FS-DPT Photoelectric Detector with Thermal ............................................................................... 33
FS-DT Thermal Detector ............................................................................................................ 33
FS-DP Photoelectric Detector ..................................................................................................... 33
DB-11, ADBX-11 and DBX-11RS Detector Bases ........................................................................33
AD-11P and ADX -11PR Air Duct Housing ....................................................................................33
LIM-1 Line Isolator Module ......................................................................................................... 33
Addressable Modules.................................................................................................................34
Transmit & Receive Interface Modules ........................................................................................ 34
FS-CZM Conventional Zone Module ........................................................................................... 34
PROGRAMMING THE CONT ROL UNIT............................................................................................ 35
MAIN BOARD JUMPER................................................................................................................. 35
KEYPAD PROGRAMMING ............................................................................................................35
PROGRAMMING SECURITY.........................................................................................................35
MAINTENANCE ...............................................................................................................................36
GENERAL....................................................................................................................................36
QUICK TEST (WALK TEST) .......................................................................................................... 37
APPENDIX A- REFERENCE INFORMATION ....................................................................................38
WIRE SELECTION GUIDES .......................................................................................................... 38
Resistance of Solid Copper Wire .................................................................................................38
Notification Appliance Circuit Wire Selection Guide......................................................................38
Addressable Device Circuit Wire Selection Guide .........................................................................39
BATTERY SIZE CALCULATIONS .................................................................................................. 40
APPENDIX B- COMPATIBLE DEVICES............................................................................................42
DEVICES FOR ADDRESSABLE DEVICE CIRCUITS ...................................................................42
FS-100 Addressable Modules ..................................................................................................... 42
FS-100 Addressable Detectors ................................................................................................... 42
FS-100 Detector Bases .............................................................................................................. 42
FS-100 Accessories ................................................................................................................... 42
DEVICES FOR NOTIFICATION APPLIANCE CIRCUITS.................................................................42
APPENDIX C: TROUBLESHOOTING ...............................................................................................43
DEFINITIONS FOR EVENT HISTORY ENTRIES ............................................................................ 43
A. General................................................................................................................................43
B. System Troubles ...................................................................................................................44
C. System Events ..................................................................................................................... 45
APPENDIX-D: INSTALLA TION INSTRUCTIONS ...............................................................................46
APPENDIX-E: GLOSSARY..............................................................................................................47
P/N 315 -699461 iii
Technical Manuals Online! - http://www.tech-man.com
Page 5
FS-100 Installation & Operation Manual
INTRODUCTION
CONTROL UNIT LIMITATIONS
This control unit must be installed with compatible initiating devices (smoke detectors, etc.) and notification devices (horn, lights, etc.) connected to it. Electrical ratings of the initiation and notification appliances must be compatible with the electrical ratings of the control unit and must be properly interconnected. The wiring used for interconnection must be large enough to carry the total current for all appliances without excessive voltage drop.
The control unit must be connected to a dedicated primary electrical source that has a high degree of reliability and adequate capacity for this control unit. The only means of disconnecting this power source shall be available only to authorized personnel and clearly marked "Fire Alarm Circuit Control".
The control unit must also have connected to it a battery set (24v) that has enough capacity to properly operate the system for 24 or 60 (depending on system type) hours standby and 5 minutes alarm per NFPA 72 (chapter 1). These batteries do lose capacity with age. Batteries must be replaced when they fail to provide the control unit with the required standby and alarm power or after 4 years, whichever happens first. These batteries must be checked for performance at least two (2) times a year or more often if local requirements dictate.
Fire alarm control units cannot last forever. Even though this control unit was made to last for the expected life of the fire alarm system, any part could fail at any time. Therefore a regular test program should be followed and documented to make sure that each part of the system is tested as in Chapter 7 of NFPA 72 or more often if dictated by local code requirements. Malfunctioning units must be replaced or repaired immediately by factory authorized service personnel.
NOTE: This control unit is designed to show an alarm condition when the initiating devices connected to it detect specific conditions. These conditions may or may not represent a life-threatening condition. Also, evacuation of a building or area unnecessarily may subject individuals to an unnecessary hazard. Therefore, it is most important that the building owner, manager, or representative promulgate, distribute, and/or post instructions describing steps to be taken when the fire alarm control unit signals any alarm condition. These instructions should be developed in cooperation and conformance with representatives of the local authority having jurisdiction.
As a backup or precautionary measure, it is strongly suggested that one of these steps should be to notify the local fire department of an abnormal condition even where the DACT option (or similar device) is included in the system.
P/N 315 -699461 1
Technical Manuals Online! - http://www.tech-man.com
Page 6
FS-100 Installation & Operation Manual
PREFACE
Along with the use of this instruction manual, the appropriate following standards and the manufacturer's instructions for initiating and notification devices should be used to install and maintain a functioning fire alarm signaling system.
NFPA 70 National Electrical Code NFPA 72 National Fire Alarm Code NFPA 101 Life Safety Code For other standards that may apply contact the authority having jurisdiction.
For NFPA publications, contact: National Fire Protection Association
Batterymarch Park Quincy, Massachusetts 02269
P/N 315 -699461 2
Technical Manuals Online! - http://www.tech-man.com
Page 7
FS-100 Installation & Operation Manual
DESCRIPTIONS
SYSTEM DESCRIPTION
The FS-100 is an advanced modular fire alarm control unit. It features addressable/analog detection, programming, and memory capability. Its base configuration includes one addressable device circuit, with four conventional notification appliance circuits.
The basic FS-100 control unit mounts in a 14-3/8" x 14-3/8" back-box with overall cover size of 14-3/4" x 14-21/32". Operating controls and indicators are mounted inside a secure door. An 80-character LCD display provides specific indications for addressable devices while LEDs indicate general panel status.
Semi-flush mounting kits are available for the enclosure.
HARDWARE CONFIGURATION
The main board mounts in the rear of the enclosure. The power supply is physically contiguous with the main board. The FS-100 main board provides the interface for external analog system connections, for the addressable device circuit, four notification appliance circuits, remote signaling and indicating interfaces, and connection of the main system power supply. Optional boards mount on the main board.
The display board mounts on the front plate, allowing it to carry the controls and displays which must be accessible.
All normal operation is controlled from the front of the control unit via push-button switches. Displays are provided by an 80-character, alphanumeric, backlit LCD display and by discrete LED indicators for major control unit functions.
The 80-character LCD display is used to display event data, including alarms and troubles, identification of zone or device, and presentation of history. The display is controlled by a set of four push-button switches commanding the control processor. A back light is included in the display to assure visibility in low light, but to conserve power, it is only activated during a reported event or on operation of a display control switch.
Individual LEDs on the panel are provided to indicate SYSTEM ALARM, PREALARM, SUPERVISORY, ALARM SILENCED, SYSTEM TROUBLE and AC POWER ON. Direct push-button controls are provided for ALARM SILENCE, TROUBLE SILENCE/ACKNOWLEDGE, MENU and SYSTEM RESET.
P/N 315-699461 3
Technical Manuals Online! - http://www.tech-man.com
Page 8
FS-100 Installation & Operation Manual
MINIMUM CONTROL UNIT CONFIGURATION
Power Supply
A 3A, 24V nominal power supply provides all operating power to the control unit for both standby and alarm conditions. Sufficient battery charging capability is available to charge sealed lead-acid batteries within code requirements for 60 hour quiescent plus 5 minutes alarm. The cabinet will hold batteries only up to 7 AH. The back-up battery is 24V, maintained by floating on the power supply. The power supply is physically contiguous with the main board.
Addressable Device Circuit
The FS-100 control unit has one addressable device circuit that is programmed for connection to Siemens addressable devices. The addressable device circuit drives up to 60 addressable initiating devices, detectors and/or modules. Each detector and module can support one output device.
Notification Appliance Circuits
The FS-100 control unit has four independent notification appliance circuits (NACs). Each circuit can be selected to give continuous output or one of eight sounding patterns available in the control unit. There is also a system coder capable of zone coded operation. All of the NACs are power limited and can be wired for Class A (Style Z) or Class B (Style Y) operation.
RS485 Communications Circuit
The FS-100 control unit has an RS-485 Communications Circuit that will drive up to 16 remote LCD annunciators and 8 Serial Relay Units and Serial Annunciator Units on the RS485 communication line.
Status Relays
Three dry relay contacts are provided. These contacts are dedicated to alarm, trouble and supervisory indications. The relay contacts are form C and are rated 1A @ 28VDC resistive.
OPTIONAL CONTROL UNIT CONFIGURATION
A maximum control unit configuration can include all of the minimum configuration items plus additions as noted below. Details of these accessories are given in Appendix D.
Municipal Tie Board
The Siemens Model FS-MT municipal tie board provides local energy and polarity reversal connections. The polarity reversal connections provide a trouble circuit and an alarm circuit with optional trouble output.
RS232 Communication Board
The Siemens Model FS-232 RS-232 communication board will allow event data to a serial printer or terminal.
DACT Board
The Siemens Model FS-DACT Digital Alarm Communication Transmitter board will send control unit status data to a remote receiving station.
P/N 315-699461 4
Technical Manuals Online! - http://www.tech-man.com
Page 9
FS-100 Installation & Operation Manual
BATTERY SETS
The FS-100 control unit is designed to use only sealed lead-acid or equivalent batteries for back-up power. The system enclosure can house 7 AH, 24VDC battery sets, Model BT-33.
AUXILIARY MODULES
Remote LCD Annunciator
The Siemens FS-RD remote LCD annunciator consists of a backlit 80 character LCD alphanumeric display, 4 menu buttons, 4 dedicated buttons for operator interaction, 6 LED indicators, and a security key-switch. The display and controls on the annunciator are the same as those on the front of the control unit, including a key -switch for security. The back light operates only when the data are being accessed, to conserve power.
Up to sixteen annunciators may be addressed by the communications circuit, but some may require auxiliary power supplies, depending on the total accessory power loading.
Serial Relay Unit and Serial Relay Extender
The Siemens FS-RU includes a processor board and a relay board. The processor board receives commands from the control unit for activating the relays and transmits supervision and control functions to the control unit. The processor board can control up to 3 FS-RE8 relay boards. Each relay board provides 8 relays with form C contacts. The control unit can address up to 8 FS-RU Serial Relay Units and/or FS-SAU Serial Annunciator Units. Auxiliary power supplies will be required to power units beyond the control unit capability.
Serial Annunciator Unit and Serial Annunciator Extender
The Siemens FS-SAU includes a processor board and an annunciator driver board. The processor board receives commands from the control unit for activating the outputs and transmits supervision and control functions to the control unit. The processor board can control up to 4 FS-SAE16 annunciator driver boards. Each driver board provides 16 supervised outputs for LEDs or incandescent lamps. The control unit can address up to 8 FS-RU Serial Relay Units and/or FS-SAU Serial Annunciator Units. Auxiliary power supplies will be required to power units beyond the control unit capability.
ADDRESSABLE DEVICES
Siemens Addressable Detectors
The control unit processor sends the sensitivity and pre-alarm settings to the detectors and polls the detectors as to their status. The detector determines normal, trouble, pre-alarm or alarm conditions and relays the status to the control unit.
Variable Thresholds
The obscuration level for alarm can be adjusted from the control unit on a permanent or time-variable basis. This facility also means that the control unit can display information on individual points for maintenance or service.
P/N 315-699461 5
Technical Manuals Online! - http://www.tech-man.com
Page 10
FS-100 Installation & Operation Manual
Operator Alerts
The control unit can trigger an alarm or trouble automatically on the occurrence of a number of conditions of the detector. These include:
Maintenance alert
Pre-alarm alert
No response
Incorrect response
Other Siemens Addressable Devices Heat Detectors
Addressable heat sensing detectors may be intermixed on the circuit for locations where heat sensing may be the most effective detection mode.
Addressable Modules (Monitor and Control)
In addition to detectors, the circuit can communicate with addressable modules, allowing initiating devices or notification appliances with local power sources, and supervising the power sources.
Manual Stations
Addressable manual stations may be intermixed on the circuit with proper response programmed into the control unit.
PROCESSOR CONTROLLED OUTPUT ZONES
While the notification appliance circuits are essentially hardware circuits, the fact that the outputs are commanded and controlled by the processor does provide more versatility than in a total hardware system. All functional selections are included in the control unit programming process.
Output Sounding Patterns
The notification appliance circuits are operable in different sounding patterns. Any circuit is selectable to any of eight software-generated patterns or continuous sounding. For convenience, three of the patterns are preprogrammed for March Time, Temporal, and Californian patterns.
Control of Audible Silencing
It is possible to select an “auto-silence” mode, adjustable from 0 to 255 minutes. Each notification appliance circuit programmed for alarm silence sequence, will be silenced upon time-out of the auto­silence timer. The alarm silenced LED will flash, indicating the auto-silence time-out.
Audible Silence Inhibit
In addition to designation of waterflow zones, the entire control unit may be programmed to inhibit audible silence for 0, 1, 3, or 6 minutes from the last alarm. System reset may also be inhibited.
P/N 315-699461 6
Technical Manuals Online! - http://www.tech-man.com
Page 11
FS-100 Installation & Operation Manual
EVENT HISTORY
The control unit includes a non-volatile memory recording up to 500 system events. Identified alarm, trouble, supervisory trouble, and other significant events will be recorded along with the date and time of occurrence, and can be inspected by operating front panel push buttons.
Events recorded in the history are:
Alarm, Trouble, or Supervisory conditions.
Drill, Tornado, Recall and General Evacuation.
Activation of NACs or modules used for sounders or strobes.
Unit used for command functions. (Silence, acknowledge, reset, etc.)
PAS_INHIBIT switch activation.
Alarm silence (manual and automatic).
System reset.
Power up.
Entry to Programmer Mode.
Secondary configuration edited.
Validity check on backup configuration. (Errors detected or no errors detected)
Running of comparison function. (Same or different)
Replacement of primary configuration.
Execution of Auto-program.
Exit from Programmer Mode.
System time or date change.
Input point disable/enable.
Start and stop of walk test.
Expiration of Walk Test Timer.
Expiration of re-ring timer.
Alarm/trouble/supervisory Acknowledgment.
Trouble/supervisory restored to normal.
Alarm verification counter rollover.
Pre-alarm activation.
Pre-alarm acknowledgment/restore.
Alarm of zone with no outputs.
Activation of points defined for logging.
Sensor maintenance alerts
P/N 315-699461 7
Technical Manuals Online! - http://www.tech-man.com
Page 12
FS-100 Installation & Operation Manual
GENERAL DESIGN FEATURES
Environmental
All hardware is suitable for use in an interior or protected location.
Power Limiting
The AC power and battery wiring are not power limited. All other circuits leaving the control unit are power limited, provided the proper installation rules are maintained.
Ground Fault Detection
The control unit provides ground fault detection and a ground fault will trigger the common fault buzzer and system trouble LED.
Transient Protection
Transient protection devices are provided where needed to meet the requirements of UL864.
Security Functions
Processor control and addressing allow inclusion of several functions to assure security of the system. Multi-lev el password protection of programming functions prevents unauthorized configuration changes. Device type supervision: If the type reported by an addressable sensor or module, does not agree with
the configuration, the system reports a trouble. Device address supervision: The system checks that all configured devices on the addressable device
circuit and the RS485 circuit responds to an address poll. If a configured device is missing, the system reports a trouble. The system also polls unused addresses periodically. If a device responds to such a poll of a non-configured device, the system reports a trouble. Two devices addressed the same also cause a trouble to be reported.
REGULATORY STANDARDS
The FS-100 control unit meets the requirements of industry and government regulatory agencies as noted.
Federal Communications Commission
The FS-DACT meets the requirements of the Code of Federal Regulations (CFR 47), Part 68, for connection of equipment to the public switched telephone network.
Underwriters Laboratories
The FS-100 Fire Alarm control unit is listed under UL Standard 864 for compliance to NFPA Standard 72 for fire service
P/N 315-699461 8
Technical Manuals Online! - http://www.tech-man.com
Page 13
FS-100 Installation & Operation Manual
GENERAL SPECIFICATIONS
Operating specifications for the FS-100 are as follows:
Environmental
Operating temperature 32 - 120°F (0 - 49°C)
Relative humidity Up to 85% @ 86°F (30°C)
Primary Supply
Primary Input Voltage: 120 VAC (60 Hz) nominal (FS-100-120)
Maximum primary input current: 1.3A at 120 VAC
Secondary and Trouble Power Supply
24 volt lead-acid battery set:
Maximum Charge Voltage: 27.8 VDC
Maximum Charge Current: 1.0 A
Maximum Input Current: 3.5A
Battery capacity: 7-38 A.H. (over 7 A.H. requires separate enclosure)
Auxiliary Power Outputs
Current:
0.5 amp maximum available for auxiliary power outputs, RS485 circuit and option boards
0.4 amp maximum per power output
Non-Resettable Power Outputs
Power limited Voltage: 24 VDC nominal Ripple: 1.5 VAC maximum
Resettable Power Output
Power limited Voltage: 24 VDC nominal Ripple: 1.5 VAC maximum
Status Relays
Includes alarm, supervisory and trouble relays.
Contact Rating:
1 A, 28 VDC maximum, resistive
Form “C” Contact
Notification Appliance Circuits
Four Class A, Style Z/Class B, Style Y circuits
Power limited
Supervised
Maximum Standby Current: 3.4mA
Alarm Voltage: 24 VDC nominal
Maximum Alarm Current per circuit: 1.5 A
Total Maximum Alarm Current (all circuits): 2.5 A
Maximum Ripple: 16 VAC
Maximum Loop Drop Voltage: 1.0 VDC
P/N 315-699461 9
Technical Manuals Online! - http://www.tech-man.com
Page 14
FS-100 Installation & Operation Manual
RS485 Communications Circuit
Power limited
Supervised
Voltage: 24 VDC nominal
Current:
0.5 amp maximum available for auxiliary power outputs, RS485 circuit and option boards
0.4 amp maximum for RS485 circuit
Maximum wire loop resistance: 25 ohms/line
Communications: RS485
Addressable Device Circuit
Power limited
Supervised
Voltage: 24 VDC nominal
Maximum Current (shorted): 0.25A
Maximum wire loop resistance: 20 ohms/line
One Style 4 or 6 circuit
60 detectors and modules max.
1 accessory output per device
Municipal Tie (Optional Municipal Tie Board Model FS- MT)
CA Reverse Polarity: Selectable for Alarm with Trouble or Alarm only operation
Power limited
Supervised by receiver for short or open circuit.
Supervised by control unit for grounded circuit.
Voltage: 24 VDC nominal
Current: 0.020A maximum (normal or trouble)
Current: 0.025A maximum (shorted)
Ripple: 1.5 VAC maximum
CT Reverse Polarity: Programmable for Trouble or Supervisory or either operation
Power limited
Supervised by receiver for short or open circuit.
Supervised by control unit for grounded circuit.
Voltage: 24 VDC nominal
Current: 0.020A maximum (normal or alarm)
Current: 0.025A maximum (shorted)
Ripple: 1.5 VAC maximum
LE Local Energy
Not power limited
Supervised for open or grounded circuit by control unit.
Voltage: 24 VDC nominal
Standby Current: 0.007A maximum
Alarm Current: 0.400A maximum
Ripple: 1.5 VAC maximum
Maximum wire loop resistance: 30 ohms
Trip coil impedance: 14.5 ohms
RS232 Output (Optional RS232 Board Model FS- 232)
Power limited
Not supervised
Voltage Range: -15 VDC to +15 VDC
Maximum Current (shorted): 0.050A
Baud Rate: 4800
Maximum wire loop resistance: 25 ohms
P/N 315-699461 10
Technical Manuals Online! - http://www.tech-man.com
Page 15
FS-100 Installation & Operation Manual
DACT Circuit (Optional DACT Board Model FS- DACT)
Power limited
Supervised for short or open circuit
Maximum Voltage: 60 VDC
P/N 315-699461 11
Technical Manuals Online! - http://www.tech-man.com
Page 16
FS-100 Installation & Operation Manual
CONTROL UNIT OPERATION
OPERATION INSTRUCTIONS
A. Standby Condition
In normal standby operation, the green AC POWER ON LED should be illuminated and no other indicator operating. The display will show the system name, “System Normal” announcement and the current date, day, and time.
B. Alarm Condition
1) GENERAL ALARMS
a) In case of alarm, the system alarm LED will operate in a flashing mode and the buzzer will sound.
Local audible and visual signals and remote alarm signals will operate, and the LCD panel display will indicate the zone or point initiating the alarm.
b) On receipt of an alarm, proceed in accordance with the established emergency plan. Assure that all
personnel are accounted for, and notify the Fire Department.
c) To silence the audible after evacuation, where permitted by the codes and control unit programming,
press ALARM SILENCE. The alarm audible will be silenced, the alarm silence LED will be illuminated and a system trouble indicated. Operating the ACKNOWLEDGE button will silence the local buzzer and change the LED alarm indicator from flashing to steady.
2) Waterflow Alarms
Alarms detected on zones designated “waterflow” indicate sprinkler operation and the audible alarms cannot be silenced in this condition. Operation of alarm silence will produce no effect.
3) Positive Alarm Sequence (PAS)
a) Activation of a point programmed for PAS, including two-stage manual stations, activates the Alarm
LED, display and buzzer (pulsing), but delays all other outputs (system and user) for 15 seconds.
b) Operation of the ACKNOWLEDGE button within 15 seconds will add 165 seconds to the timer value,
to make the total delay 180 seconds.
c) If an ALARM SILENCE button is pressed or the sensor returns to a normal reading before the
extended PAS delay time, the alarm sequence is aborted.
d) An alarm condition on a sensor programmed for direct alarm response (such as the key switch on a
manual station) will over-ride the PAS timer and activate the outputs.
4) Pre- Signal
a) A point activated by a PRE -SIGNAL alarm activates the alarm relay, alarm DACT, city tie, alarm
LEDs and buzzers, and all user programmed outputs normally, but does not activate any NACs.
b) Operation of the ALARM SILENCE button less than 180 seconds after initiation of the alarm prevents
operation of the NACs. c) Failure to act within 180 seconds will result in activation of the NACs. d) Receipt of another pre-signal or standard alarm during the delay period immediately sounds the
NACs. e) A SYSTEM RESET is required to return the zone and input point to normal, whether or not the NACs
were activated. NOTE: Do not reset the system until the alarm condition has been cleared. The LCD display on the will indicate the area in which the alarm was detected. The detector initiating the alarm will display a light. If more than one zone is in alarm, the last zone to be alarmed will be indicated on the display.
P/N 315-699461 12
Technical Manuals Online! - http://www.tech-man.com
Page 17
FS-100 Installation & Operation Manual
f) When the alarm condition has been corrected, return the system to standby operation by pressing the
SYSTEM RESET button.
C. Trouble Condition
a) In case of a trouble condition, the system trouble LED and any programmed trouble LEDs will be
flashing, the LCD display will identify the problem, and the buzzer will sound. Refer to the applicable
section of the system manual to determine the probable cause of the trouble and the action to be
taken. b) When a trouble has been noted, the buzzer may be silenced by pressing the ACKNOWLEDGE
button. The trouble LEDs will change to a continuous display. If the trouble has not been corrected
when the trouble re-ring timer expires, the trouble display will revert to its original condition and the
buzzer resound. c) If the control unit is programmed for trouble acknowledge required, when the indicated trouble
condition has been cleared, the system will revert to standby condition after the ACKNOWLEDGE
button is pressed. Note: Some trouble conditions require a system reset to restore the control unit.
D. Supervisory Condition
Supervisory conditions are indicated similar to regular system trouble conditions except that when a supervisory condition is cleared, the cleared condition continues to be indicated until it is acknowledged.
E. Maintenance
In order to insure continued safe and reliable operation of the fire alarm system, periodic inspection and testing should be performed in accordance with applicable NFPA 72 standards.
CAUTION: If the system has remote connections to the Fire Department or other monitor, be sure to disable the remote signals and/or notify the remote monitoring station before performing test operations.
For any required service, refer to the system manual or contact a factory authorized representative.
P/N 315-699461 13
Technical Manuals Online! - http://www.tech-man.com
Page 18
FS-100 Installation & Operation Manual
ADDITIONAL OPERATING PROCEDURES
In addition to the basic fire alarm instructions above, several features are included to facilitate maintenance and increase the versatility of the system. Following are procedures to call up these functions.
A. Lamp Test
To operate the lamp test, press the MENU button. The LCD display will change to a MENU screen. Press the button next to the “More” indication twice. Then press the button by the “Lamp Test” indication. All lamps on the unit being operated will then light. Operating the button next to “Esc” will then return the control unit to normal display. Note that the lamp test operates the indicators only on the unit being operated, and no record is reported to system history.
B. Drill
To activate a fire alarm drill, proceed as follows:
1. Press "MENU".
2. On the MENU display, select "More".
3. At the next screen, select "DRILL".
4. At the next screen, select "Yes".
5. Operate ALARM SILENCE to terminate drill signal.
C . Recall
To signal recall after a drill, proceed as follows:
1. Press "MENU".
2. At the next screen, select "More".
3. Select "RECALL".
6. At the next screen, select "Yes".
4. Operate ALARM SILENCE to terminate recall signal.
D. Pre- Alarm
1. A pre-alarm condition is annunciated by Pre-alarm LEDs and buzzers on the control unit and RS485
LCD Annunciators and RS485 Remote Processors. The LEDs flash and buzzers are on steady until
acknowledgment.
2. Acknowledging the Pre-alarm condition puts LEDs on steady and buzzers off.
3. If pre-alarm has been acknowledged and restores to normal, the condition clears. If the system
proceeds into an alarm condition, the pre-alarm condition clears whether or not it has been
acknowledged and is replaced by alarm.
E. General Alarm
To activate a general alarm, proceed as follows:
1. Press "MENU".
2. On the MENU display, select "GENERAL ALARM".
3. At the next screen, select "Yes".
4. Silence and reset the system as with any alarm.
F. Tornado
To activate a tornado alarm, proceed as follows:
1. Press "MENU".
2. On the MENU display, select "TORNADO".
3. At the next screen, select "Yes".
4. Operate ALARM SILENCE to terminate tornado signal.
P/N 315-699461 14
Technical Manuals Online! - http://www.tech-man.com
Page 19
FS-100 Installation & Operation Manual
G. History
The last 500 system events are time-tagged and recorded for review in the user level event history. This history is available to anyone with the door key, but may be erased only at the maintenance security level.
1. Operation of history:
a) New events overwrite old when filled.
b) Printer (if used) records all events.
c) For more information see the event history section
2. Access to history: To recall past events, proceed as follows:
a) Press MENU button.
b) Operate button identified as "More".
c) Operate button identified as "More".
d) Operate button identified as "View History".
e) Operate upper left button for previous event display.
f) Operate lower left button for next event display.
g) Operate upper right button to exit to MENU DISPLAY.
P/N 315-699461 15
Technical Manuals Online! - http://www.tech-man.com
Page 20
FS-100 Installation & Operation Manual
FS-100 OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the System Alarm LED flashes, LCD will display alarm conditions and the panel buzzer sounds. Local audible and visual signals and remote alarm signals operate.
When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has been received at the Fire Department.
Authorized Personnel Only
To silence the alarm:
To silence the notification appliances after evacuation, where permitted, press the Alarm Silence switch. The notification appliances and panel buzzer will be silenced, and LED indications will change from flashing to continuous. The Alarm Silenced LED will be lit.
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a predetermined time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by pressing the System Reset switch.
Trouble Operation
Trouble is indicated by:
System Trouble LED flashes LCD will display trouble conditions Panel buzzer sounds
To silence the trouble buzzer:
Press the Trouble Silence switch. The Trouble Silenced LED lights and the specific trouble LED(s) may change to continuous display. When the trouble condition has been cleared, you may need to reset the panel to restore to a normal standby condition.
Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not to initiate a fire alarm sequence
Normal Standby Condition
The green AC Power On LED will be lit and no other indicators on.
For service, contact: ___________________________________________ Telephone Number: _________________________________________ __
Frame these instructions and mount them near the control unit for operator reference.
P/N 315-699461 16
Technical Manuals Online! - http://www.tech-man.com
Page 21
FS-100 Installation & Operation Manual
FS-RD OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the System Alarm LED flashes, LCD will display alarm conditions and the buzzer sounds. Local audible and visual signals and remote alarm signals operate.
When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has been received at the Fire Department.
Authorized Personnel Only
To silence the alarm:
To silence the notification appliances after evacuation, where permitted, turn the Button Enable keyswitch to the ON position and press the Alarm Silence switch. The notification appliances and buzzer will be silenced, and LED indications will change from flashing to continuous. The Alarm Silenced LED will be lit.
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a predetermined time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by turning the Button Enable keyswitch to the ON position and then pressing the System Reset switch.
Trouble Operation
Trouble is indicated by:
System Trouble LED flashes LCD will display trouble conditions Buzzer sounds
To silence the trouble buzzer:
Turn the Button Enable keyswitch to the ON position and press the Trouble Silence switch. The System Trouble LED changes from flashing to continuous display. When the trouble condition has been cleared, you may need to reset the panel to restore to a normal standby condition.
Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not to initiate a fire alarm sequence
Normal Standby Condition
The green Power On LED will be lit and no other indicators on.
For service, contact: ___________________________________________ Telephone Number: ___________________________________________
Frame these instructions and mount them near the annunciator for operator reference.
P/N 315-699461 17
Technical Manuals Online! - http://www.tech-man.com
Page 22
FS-100 Installation & Operation Manual
CONTROL UNIT INSTALLATION
PARTS SUPPLIED
Back-box Assembly (black or red) Door Assembly (black or red) Transformer Assembly (120VAC) #6-32 Locking Nuts (6) Front Plate Assembly #6-32 x 1/4” Screws (16) Main Board #8-32 Self-tapping Screw, (4) Display Board 24K Ohm 1/2W Resistor (4) Cable Assembly, 16 Pin Screwdriver Clear Lexan Window Owner’s Manual Overlay Operating Instructions Programming Keypad 120 Ohm 1/2W Resistor (2)
The fire alarm control unit must be mounted in a properly accessible location as required by applicable codes. Any auxiliary battery box or other accessory not connected through a protective device or a circuit designed for remote connection must be within the same room and connected through electrical conduit. Installation is to be done only by qualified personnel who have thoroughly read and understood these instructions.
CAUTION
It is recommended that the print ed circuit boards be removed for any procedure that may cause dust, metal shavings, grease or any such matter that may affect the circuit boards and/or parts. There may be several sources of power into the control unit. Each source must be disconnected prior to installing or removing modules, connecting or disconnecting wiring, and programming jumpers.
CONTROL UNIT LOCATION
The control unit should be located near an exit at ground level, where the normal ambient temperature is maintained within the control unit specification (See General Specifications in Section III). The unit should be in an area that is free of dust, vibration, moisture and condensation.
ENCLOSURE MOUNTING
Follow the appropriate instructions for surface or semi-flush mounting.
P/N 315-699461 18
Technical Manuals Online! - http://www.tech-man.com
Page 23
FS-100 Installation & Operation Manual
A. Surface Mounting Instructions
To mount the enclosure:
1. Mount the enclosure at a convenient height for viewing indicators and operating switches.
2. Use four #10 lag screws (not supplied) to secure the control unit to the wall. The screw type and
length must support the control unit, options and battery set. Note: You may need a different screw type, depending on the wall material.
3. Any auxiliary power supply or battery enclosure may be mounted immediately below the main
enclosure, close nipple, allowing a minimum of 1 inch in between the enclosures for clearance
between the doors. Keeping the wire run to the control unit short will keep the voltage drop to a
minimum.
P/N 315-699461 19
Technical Manuals Online! - http://www.tech-man.com
Page 24
FS-100 Installation & Operation Manual
B. Semi- Flush Mounting Instructions
To mount the enclosure:
1. Mount the enclosure at a convenient height for viewing indicators, and operating switches.
2. Use four #10 lag screws (not supplied) to secure the control unit to the wall. The screw type and
length must support the control unit, options and battery set. Note: You may need a different screw type, depending on the wall material.
3. The back-box can be mounted up to 3 1/2 inches into the wall. Place the semi-flush trim around the
back-box and affix to the wall with four #10 x 3/4 inch wood screws (provided with trim). Note: You may need a different screw type, depending on the wall material.
4. Any auxiliary Power Supply or battery enclosure may be mounted immediately above or below the
main enclosure, close nipple, allowing a minimum of 3 inches in between the enclosures for
clearance between the semi-flush trims. Keeping the wire run to the control unit short will keep the
voltage drop to a minimum.
P/N 315-699461 20
Technical Manuals Online! - http://www.tech-man.com
Page 25
FS-100 Installation & Operation Manual
C. Knock- Outs
1. To prepare the enclosure for electrical wiring, break out the appropriate conduit entry points. Note
the wiring diagram requirements for non-power limited and power limited wiring separation.
2. Attach conduit (if required) and run wires as required. Label each field cable for future reference.
D. Main Board Installation
1. Secure the board to the back of enclosure using six of the provided #6-32 x 1/4 screws.
E. AC Supply Connection
1. Wire the AC supply to terminal block TB2 on the main board. The supply should originate from a separate, fused circuit. It should be provided with a breaker or other means of isolation.
2. Observe the wiring order -- the bottom terminal is ground and must be wired back to the electrical panel ground (earth) bonding point or another good ground acceptable to the authority having jurisdiction and the electrical inspector. The neutral wire must be taken back to the electrical panel neutral distribution bar and must not be grounded.
/!\ Dangerous voltages will be present on this terminal block and on other components surrounding it and the transformer when the AC supply is turned on. Do not touch.
P/N 315-699461 21
Technical Manuals Online! - http://www.tech-man.com
Page 26
FS-100 Installation & Operation Manual
F. Transformer Installation
1. Place the transformer assembly over the studs on the left side of the enclosure. Mounting the
transformer can be accomplished before mounting the enclosure if desired.
2. Secure the transformer using four #6-32 locking nuts.
3. Plug the transformer assembly into connector P5 on the Main Board.
G. Front Plate Assembly
1. Secure Display Board to Plate Assembly using ten #6-32x1/4” screws.
2. Apply Overlay to Plate Assembly.
H. Front Plate Mounting
1. Plug the Cable Assembly into connector P4 of the Display Board and to connector P1 of the Main
Board.
2. Secure the Front Plate Assembly to backbox using four #8-32 self-tapping screws.
P/N 315-699461 22
Technical Manuals Online! - http://www.tech-man.com
Page 27
FS-100 Installation & Operation Manual
I. Door Assembly
1. Secure the Lexan window to door assembly using four #6-32 locking nuts.
2. Place the Door Assembly onto hinges of the Back-box Assembly.
J. Battery Installation
Warning: Improper battery connections or shorting battery terminals may
damage the system and/or batteries and may cause personal injuries.
Place the batteries in the space provided in the bottom of the back-box. If larger than 7 AH battery set is required, a separate enclosure must be used. The Siemens Model BB-55 may be used for battery sets 55 AH and smaller. The FS-100 battery charging circuitry can only support systems requiring up to 38 AH battery sets.
The control unit uses a 24V battery set. Connect the two 12V batteries (or four 6V batteries) in series with #12 AWG wire, minimum. Route the battery leads to the left of the enclosure and up to the battery termination block, TB5. The battery leads are not power-limited.
Observe polarity. Connect the B- terminal from the main board into the black or - terminal of the battery set and the B+ terminal from the main board into the red or + terminal of the battery set.
K. Powering the Control Unit
Apply AC power to the control unit. AC POWER ON LED, SYSTEM TROUBLE LED, and the trouble buzzer should be on.
P/N 315-699461 23
Technical Manuals Online! - http://www.tech-man.com
Page 28
FS-100 Installation & Operation Manual
L. Checking Supervised Circuits
To check the supervised circuits of the control unit:
1. Place a 24K ohm resistor (color-coded: red, yellow, orange) across each set of NAC terminals.
2. Push SYSTEM RESET button.
3. The SYSTEM TROUBLE LED, and the trouble buzzer should be off.
4. Discard 24K ohm resistors after initial testing is complete
M. Optional Modules
Follow the installation instructions provided in Appendix D.
N. System Wiring
Before connecting the field wiring, check the wiring for opens, shorts, grounds and stray voltages.
Warning: Damage may result if a high voltage insulation tester is
used on wiring while connected to the control unit.
Terminate the field wiring to the main board in accordance with the diagrams in Section V and the system design documents.
NOTE: All wiring must be in accordance with local codes and the National Electrical Code. Use
only FPL, FPLR and/or FPLP as des cribed in Article 760 of the National Electric Code.
O. Check System Operation
Check for proper operation of all the system functions. See Section II for Operation Instructions.
P/N 315-699461 24
Technical Manuals Online! - http://www.tech-man.com
Page 29
FS-100 Installation & Operation Manual
1. Main Board
SYSTEM WIRING
Basic system wiring and detector siting must be in accordance with NFPA 72 or other instructions from the appropriate local authority. Unit connections and limitations are as indicated on the wiring diagram included below.
Devices that may be satisfactorily used with the control unit are shown in the compatible device listing in Appendix B.
Wire reference data are included in Appendix A.
CONTROL UNIT WIRING OVERVIEW
The overall arrangement of boards in the control unit is shown in the following diagram.
1
2. FS-DACT board or FS-MT board * (Note: When using FS-DACT, the FS-232 cannot be used)
3. FS-232 RS-232 Interface Board
3
2*
P/N 315-699461 25
Technical Manuals Online! - http://www.tech-man.com
Page 30
FS-100 Installation & Operation Manual
24V Battery Set
120VAC 60Hz
AC
Keep All Non-Power Limited Wiring Separate from Power Limited Wiring
A. Non-power limited - High Voltage
WIRING SEPARATION
All high voltage and non-power limited wiring must be kept separate from power limited wiring. A ¼” separation must be maintained, with high voltage and non-power limited wiring running in separate conduit openings from power limited wiring.
E C A
F
(AC power) or B
B. Non-power limited - High Voltage
1
2*3
C. Power limited D. Non-power limited
(AC power) or A
(Battery If external enclosure required)
E. Non-power limited
(Phone line or local energy box) F. Power limited or G G. Power limited or F
B G
D
PRIMARY AND SECONDARY POWER WIRING
The AC main connections and the battery connections must be made along the left-hand side of the board. Route all high voltage and non-power limited wiring together and away from power limited wiring.
1.3A max., Supervised Non-Power Limited
GND
Technical Manuals Online! - http://www.tech-man.com
P/N 315-699461 26
(7 to 38AH)
Supervised
Non-Power Limited
Page 31
FS-100 Installation & Operation Manual
+
Status Relay Contacts
Auxiliary Power Outputs
(Maximum current of all auxiliary outputs,
A O C
A O C
A C O
Relay Designation:
STATUS RELAYS AND AUXILIARY POWER OUTPUTS WIRING
The right lower edge of the main board provides for connection of contacts and auxiliary power connections.
A – Common O – Normally Open
C – Normally Closed
ALARM TROUBLE SUPERVISORY
- + - R - + -
(Shown in normal standby condition)
1A@28VDC max., Resistive
For Power Limited Source, Unsupervised
0.4A max.@24VDC nominal
Unsupervised, Power Limited
RS485 Circuit and option boards is 0.5A.)
System Power Requirement Calculations
Device Item Max.(Amps) Total (Amps) FS-100 Control Unit 0.200 0.200
Addressable Device Circuit Power # of Devices X 0.0002 Amps Auxiliary Power Outputs * Depends on devices installed FS-MT Municipal Tie Board 0.055 FS-232 RS232 Communication Board 0.008 FS-DACT Dialer Communicator Board 0.054 FS-RD Remote LCD Annunciator * 0.030 FS-RU/RE8 Serial Relay Unit * 0.030 FS-SAU/SAE16 Serial Annun. Unit * 0.030 Total must not exceed 0.75 Amps
Auxiliary Power Supply
* Connect a UL Listed auxiliary supply when the power requirement calculation indicates that an additional source is required.
Battery Size Calculations
For calculation of battery size requirements see appendix A.
Technical Manuals Online! - http://www.tech-man.com
P/N 315-699461 27
Page 32
FS-100 Installation & Operation Manual
Notification Appliance Circuit
Notification Appliance Circuit
- + -
+
See Typical
See Typical
NAC Rating:
NAC WIRING
At the right hand side of the main board the terminal blocks are used for the connection of notification appliances. Four individual NACs marked A through D are provided and the polarity shown is when the NAC is activated.
24K 1/2W
Style Y, Class B
Supervised, Power Limited
See P/N315-096363 for
Polarity shown in activated condition
Compatible Devices
Style Z, Class A
Supervised, Power Limited
See P/N 315-096363 for
Compatible Devices
Wiring above
Wiring above
Alarm Voltage: 24VDC nominal Max. Alarm Current: 1.5A Max. Ripple: 16VAC Max. Wire Voltage Drop: 1.0VDC Max. Standby Current: 1.0mA
NOTE: The maximum current for all NACs is 2.5A.
Technical Manuals Online! - http://www.tech-man.com
P/N 315-699461 28
Page 33
FS-100 Installation & Operation Manual
Serial Interface Circuit
for Compatible Devices
RS485 COMMUNICATIONS CIRCUIT
The RS485 communication circuit can address up to 16 standard annunciators and/or 8 remote processors to drive graphic annunciation or relay modules. Devices on the circuit may be connected up to 4000 feet from the control unit. At the top of the main board the terminal blocks are used for the connection of remote serial devices.
See Installation & Operation Manual Appendix D
24VDC nominal, 0.4A max.
Wire Resistance-25 ohms/line (4000’ max)
Wire Type-Twisted Pair for data
Supervised, Power Limited
Remote Device Power
When connecting devices on the RS485 communications circuit, a limited amount of current is available from the control unit. If more current supply is required for the connected devices, auxiliary power must be provided to each insufficiently powered device. Each address on the circuit must be fully powered from either control unit or auxiliary power (no combined source can be configured).
Remote Device Data
When connecting devices on the RS485 communications circuit, the data wires must be daisy chained and with no T-taps to preserve the integrity of the data. Each end (two places) must be terminated with a 120 ohm termination resistor. The following diagrams show typical examples using the proper wiring.
P/N 315-699461 29
Technical Manuals Online! - http://www.tech-man.com
Page 34
FS-100 Installation & Operation Manual
Addressable Device Circuit
ADDRESSABLE DEVICE CIRCUIT
The basic configuration of the FS-100 control unit includes one addressable device circuit. The devices are polled by the control unit every few seconds and input or output functions communicated to determine device status or function. The control unit monitors all device addresses for alarm and trouble conditions.
Style 4 or 6/7 Operation
(set jumper P1 for proper style)
24VDC nominal
Wire Resistance-20 ohms/line
See Installation & Operation Manual Appendix B
Supervised, Power Limited
for Compatible Devices
Style
6/7
4
Addressable Device Wiring Diagrams
Proper connections for UL Listed compatible addressable devices are indicated below. Refer also to the instruction sheets packed with each device.
Detectors and modules may be wired together according to several NFPA defined wiring styles. The wiring style that is appropriate for your installation should be determined from the relevant building codes and the Authority Having Jurisdiction.
P/N 315-699461 30
Technical Manuals Online! - http://www.tech-man.com
Page 35
FS-100 Installation & Operation Manual
SUPERVISED,
TO OPTIONAL
BRANCH(ES) OF
Style 4 wiring permits branching of circ uit connections. The control equipment supervises modules because they are active and must respond periodically to the control unit’s interrogation.
ADDRESSABLE DEVICE CIRCUIT
WIRING / OPERATION COMPARABLE TO NFPA STYLE “4”
POWER LIMITED
LOOP CIRCUIT
Note:
Addressable Devices:
Detectors, Monitor Modules, or Control Modules up to a maximum of 60 devices per addressable device circuit. Maximum of 20 devices per Isolator Module. Maximum of 12 Isolator Modules per addressable device circuit.
P/N 315-699461 31
Technical Manuals Online! - http://www.tech-man.com
Page 36
FS-100 Installation & Operation Manual
SUPERVISED,
Style 6 provides redundant communication paths.
ADDRESSABLE DEVICE CIRCUIT
WIRING / OPERATION COMPARABLE TO NFPA STYLE “6”
POWER LIMITED
Note:
Addressable Devices:
Detectors, Monitor Modules, or Control Modules up to a maximum of 60 devices per addressable dev ice circuit. Maximum of 20 devices between Isolator Modules. Maximum of 12 Isolator Modules per addressable device circuit.
P/N 315-699461 32
Technical Manuals Online! - http://www.tech-man.com
Page 37
FS-100 Installation & Operation Manual
Addressable Detectors
Each detector uses an address between 01 and 60 on the addressable device circuit. All device addresses are programmed into the device using the FS-DPI Device Programmer Unit. When installed, the device is regularly scanned by the control unit and checked for its current sensor status. The control unit will interpret and respond to the analog data as programmed. Each time the device is scanned the integral green visible LEDs will flash. In the event of an alarm condition the red LEDs will flash at a faster rate.
FS- DPT Photoelectric Detector with Thermal
The FS-DPT Photo/Thermal Detector allows programmable analog sensitivity with fixed thermal temperature of 135° F. It requires a DB -11, DB-X11RS, ADBX-11, AD-11P, or ADX-11PR base.
FS- DT Thermal Detector
The FS-DT Thermal Detector is a fixed 135° F detector. It requires a DB-11, DB-X11RS, ADBX-11, AD­11P, or ADX-11PR base.
FS- DP Photoelectric Detector
The FS-DP Photoelectric Detector allows programmable analog sensitivity. It requires a DB-11, DB­X11RS, ADBX-11, AD-11P, or ADX-11PR base.
DB- 11, ADBX-11 and DBX- 11RS Detector Bases
The DB-11 base is a standard base designed for use with all FS-Series addressable and all 11-Series conventional detectors. The DB-11 provides connection to an optional remote LED lamp (RLI-1 or RLI-2 lamp).
The ADBX-11 audible detector base is designed for use with all FS-Series addressable detectors. The ADBX-11 provides means to obtain a local audible alarm at the specific detector location. The integral horn on the ADBX-11 will sound when either the detector installed in the base has latched into the alarm state, or when criteria developed through logic programming is met. It will remain on until the detector is successfully reset, or the logic criteria are no longer met. A separate 24VDC power source is required to operate the integral horn.
The DBX-11RS relay detector base is designed for use with all FS-Series addressable detectors. The DBX-11RS provides a local Form C relay at the specific detector location. The relay on the DBX-11RS will energize when either the detector installed in the base has latched in the alarm state, or when criteria developed through logic programming is met. It will remain energized until the detector is successfully reset, or the logic criteria are no longer met. The contact is rated at 3A, 120VAC, or 3A, 30VDC resistive.
AD- 11P and ADX-11PR Air Duct Housing
The AD-11P Air Duct Housing and the ADX-11PR Air Duct Housing are used with the FS-DP addressable photo detector. Both housings provide a means to mount the FS-DP in an air duct for proper operation of the detector in an air stream. The ADX-11PR also has an integral Form C contact that operates similarly to the DBX-11RS relay base.
LIM- 1 Line Isolator Module
The LIM -1 Line Isolator Module is designed for use with FS-Series addressable detectors and provides short circuit isolation on the indicating device circuit. Each LIM-1 can support up to 20 devices. The system is limited to 12 LIM -1s on the circuit.
P/N 315-699461 33
Technical Manuals Online! - http://www.tech-man.com
Page 38
FS-100 Installation & Operation Manual
Addressable Modules
Each addressable module uses an address between 01 and 60 on the addressable device circuit. All module addresses are programmed into the module using the FS-FPI Programmer / Tester. When installed, the module is regularly scanned by the control unit and checked for its current circuit status. The control unit will interpret and respond to the analog data as programmed. Each time the module is scanned the integral green visible LEDs will flash. In the event of an alarm condition the red LEDs will flash at a faster rate.
Transmit & Receive Interface Modules
The FS-TRI-S monitor module provides a single Style "B" (2-wire) initiating circuit for normally open dry contact fire alarm and supervisory (tamper) devices. The FS-TRI-S is designed to mount directly inside a 4" square junction box, and has screw terminals for all field connections. The FS-TRI-S may be used to monitor manual stations, waterflow switches, tamper (supervisory) switches or other dry, normally open contact initiation devices. It uses a single module address between 01 and 60.
The FS-TRI-M monitor module functions exactly as the FS-TRI-S, except that it is smaller than the FS­TRI-S, and it uses flying leads for field connections. The FS-TRI-M’s small size and light weight design allows it to be installed inside a single gang box, or behind a device being monitored without being rigidly mounted.
The FS-TRI-D monitor module is similar to the FS-TRI-S, except that it provides two Style ‘B” initiating circuits for normally opened dry contact fire alarm and supervisory (tamper) devices. The FS-TRI-D uses two consecutive module addresses between 01 and 60 on the addressable device circuit.
The FS-TRI-R monitor module is similar to the FS-TRI-S, except that it also provides a programmable remote relay which operates a Form C contact within the module. Both the initiating circ uit and the relay output share the same address.
FS- CZM Conventional Zone Module
The FS-CZM addressable conventional zone module allows the addressable device circuit to interface and monitor two-wire conventional smoke detectors or normally open contact initiation devices. All two­wire detectors being monitored must be UL compatible with the module. The FS-CZM communicates the status of a single zone of conventional detectors to the control panel via the addressable device circuit. When the panel scans the module, it transmits the status of one zone of two-wire detectors to the control unit. Status conditions are reported as normal, open, or alarm. The FS-CZM uses a single module address between 01 and 60 on the addressable device circuit.
P/N 315-699461 34
Technical Manuals Online! - http://www.tech-man.com
Page 39
FS-100 Installation & Operation Manual
PROGRAMMING THE CONTROL UNIT
MAIN BOARD JUMPER
Factory setting is shown. P1 – Addressable Device Circuit Wiring Style
Style 6/7
Style 4
KEYPAD PROGRAMMING
Customized programming of the FS-100 control unit may be accomplished through a keypad included in the control unit. A sixteen-key, telephone-style keypad mounts on the front panel within the cabinet. The keypad may also be easily removed if desired. See the Siemens Programmer’s Manual (P/N 315-
699490) for detailed information of system programming.
PROGRAMMING SECURITY
The following levels of security protect the system from unauthorized use:
User – Locked Door
Maintenance – Locked Door and 4-digit Maint Password
Technician – Locked Door and 5-digit Tech Password
The User and Maintenance Levels are also accessible from the Remote LCD Annunciator.
P/N 315-699461 35
Technical Manuals Online! - http://www.tech-man.com
Page 40
FS-100 Installation & Operation Manual
MAINTENANCE
GENERAL
Device sensitivity may be read out and alarm thresholds controlled on a per-point basis, as well as setting overall percent obscuration and day/night variations. Individual points may also be disabled for service.
To perform these functions on the unit, enter the 4-digit maintenance password into the control unit or LCD annunciator. When the menu is displayed, select the desired function or sub-function and press the appropriate operating button. When the function is complete, the menu will provide a command for exiting the maintenance mode.
Note that any abnormal condition, such as disabled points, will report a trouble. Confirmation of disabling or re-enabling a point is required to complete the action, but acknowledgment of the trouble is not required, since
it resulted from operator action.
Activation of an alarm condition or a timeout after no button activity terminates Maintenance mode.
The system may automatically scan the operating points and report to a printer, facilitating NFPA 72 test requirements. The control unit may perform this scan once a day, with the time selectable by the user.
To initiate a non-programmed automatic test cycle, enter the 4-digit maintenance password into the control unit or LCD annunciator. When the menu is displayed, select Auto-test and press the associated switch. The Auto-test cycle will be completed and the control unit returns to normal. Results will be displayed on the display (anomalies only) or the printer (full data) according to the selected mode.
The system will automatically monitor drift of quiescent sensor output levels and report a maintenance alert if a preset level is passed, or if a sensor drifts too quickly. This maintenance alert is annunciated as a trouble.
The system may be programmed to report the number of times the alarm verify function is initiated by device, time of day, and/or day of week, allowing location of environmental problems. This datum is available on the display as described in paragraph 1 above.
The system may be programmed to alert the operator when scheduled maintenance is required.
A 500 event history is maintained, with all events available for chronological review at the operator
level. This history may be cleared only with the Maintenance Level Code. For details on included data and use of the history, see operation instructions.
To clear history when data has been read out and restoration of memory space is desired. Activate maintenance mode as described above and follow menu instructions for clearing the event history.
P/N 315-699461 36
Technical Manuals Online! - http://www.tech-man.com
Page 41
FS-100 Installation & Operation Manual
QUICK TEST (WALK TEST)
CAUTION: If the control unit has remote connections to the Fire Department or other monitor, be sure to disable the remote signals and notify the remote monitoring station before performing test operations, since an off-normal condition will be indicated.
Quick test is possible in one of two modes, (silent or audible) and is selectable on a per-zone basis. Any number of zones may be placed into test at the same time, but only one mode of quick test operation is possible for the whole system at one time. Points not in quick test operate normally. Quick test operation initiates a system trouble condition.
In the silent mode, all alarm outputs are disabled and only the front panel indications and remote annunciator LEDs operate. In the audible mode all system sounders will sound momentarily as each or device is alarmed.
The system maintains a counter of the number of activation’s during the quick test and reports this value when quick test mode is exited.
Quick test terminates into alarm if more than one device activates simultaneously, or if a device does not return to normal after being activated within a configurable length of time.
Quick test terminates automatically into normal standby mode using a timer. The value of the timer is configurable. The timer can be configured to limit the total time of the quick test (i.e. the timer is started only when quick test is entered), or to limit the time between device activation’s (i.e. the timer is re-started after each activation).
Alarm activation’s that occur in a system or zone in quick test or by a point in quick test cause the event to be logged and printed. No other action is taken.
To initiate quick test, enter maintenance mode as described above and follow menu instructions to configure and initiate the test.
Initiation of General Evacuation from the control unit, an RS485 LCD Annunciator, or an RS485 Remote Processor causes termination of quick test and starts the normal alarm sequence.
Quick test may be terminated by a menu selection or by timeout (set at 5 to 30 minutes) from the last test activation. Timeout system reactivation is annunciated by a 1/2 second on, 1/2 second off pattern from system sounders programmed for drill use. A device in alarm condition when quick test is exited causes the normal alarm sequence.
NOTE: When any problem is observed with the system, refer to the troubleshooting chart in Appendix C. For any required service, contact a
factory-authorized representative.
P/N 315-699461 37
Technical Manuals Online! - http://www.tech-man.com
Page 42
FS-100 Installation & Operation Manual
APPENDIX A- REFERENCE INFORMATION
This appendix provides reference for the following topics:
Wire selection guides
Battery size calculations
WIRE SELECTION GUIDES
Resistance of Solid Copper Wire
AWG Ohms per Thousand Feet*
18 8.08 16 5.08 14 3.19 12 2.01 *NEC Chapter 9, Table 8.
Notification Appliance Circuit Wire Selection Guide
Each Notification Appliance Circuit must not have a voltage drop greater than 1 volt. The following chart is based on the following premises:
The entire load is at the end of the wire run (worst case).
Resistance is of solid copper wire
Contact your local distributor or the factory if further information is needed in your circumstances.
Maximum Wire Loop Distance (Feet)
Signal Load (A) 18 AWG 16 AWG 14 AWG 12 AWG
0.1 1,237 1968 3134 4975
0.25 495 787 1253 1990
0.5 247 393 626 995
0.75 165 262 417 663
1.0 123 196 313 497
1.25 99 157 250 398
1.5 82 131 208 331
P/N 315-699461 38
Technical Manuals Online! - http://www.tech-man.com
Page 43
FS-100 Installation & Operation Manual
Addressable Device Circuit Wire Selection Guide
Each addressable device circuit must meet the following requirements:
Total loop resistance - 40 ohm maximum.
Total loop capacitance - 0.28uF maximum (56pF/ft. max.)
Twisted pair wire.
Unshielded cable.
Low capacitance cable.
High velocity of propagation cable - 60% minimum.
Each loop runs separate from all other circuits.
Run + out and - out separately from + in and - in.
Different models or types of cable should not be in the same loop.
Maximum Wire Loop Distance (Feet)
(Includes all branches of a Style 4 loop)
Wire size: 18AWG 16AWG 14AWG * 12AWG
Wire length: 6150 9750 10,000 10,000 Cable length: 3075 4875 5,000 5,000
* The terminal blocks on the FS-100 are rated for a maximum of 14AWG wire.
P/N 315-699461 39
Technical Manuals Online! - http://www.tech-man.com
Page 44
FS-100 Installation & Operation Manual
BATTERY SIZE CALCULATIONS
Standby Current (A.) Alarm Current (A.) FS-100 Control Unit 0.110 0.200 FS-MT Municipal Tie
Module Alarm 0.028 0.028 NA + Standby (note 5) + NA Alarm (note 5) NA + FS-232 RS232
Module Alarm 0.008 0.008 NA + FS-DACT Module Standby 0.038 0.038 + NA Alarm 0.054 0.054 NA + FS-RD Remote Standby 0.020 X = + NA Annunciator Display Alarm 0.030 X = NA + FS-RU Serial Standby 0.010 X = + NA Relay Unit Alarm 0.170 X = NA + FS-RE16 Serial Standby 0.000 X = + NA Relay Extender Alarm 0.160 X = NA + FS-SAU Serial Standby 0.015 X = + NA Annunciator Unit Alarm (note 4) 0.040 X = NA + FS-SAE16 Serial Standby 0.005 X = + NA Annunciator Ext. Alarm (note 4) 0.000 X = NA + Addressable Devices Catalog # Quantity X Current (A.) Standby X = + NA Alarm X = NA + Standby X = + NA Alarm X = NA + Standby X = + NA Alarm X = NA + Standby X = + NA Alarm X = NA + End of Line Relay Catalog # Quantity X Current (A.) X = + + Notification Appliances Catalog # Quantity X Current (A.) X = NA + X = NA + X = NA + X = NA + Other (Aux. DC) = + + TOTAL
Standby 0.005 0.005 + NA
Standby 0.008 0.008 + NA
P/N 315-699461 40
Technical Manuals Online! - http://www.tech-man.com
Page 45
FS-100 Installation & Operation Manual
Total Standby Current
(from above)
Total Alarm Current
(from above)
A.H. for
Standby
+ = X 1.25 =
Notes:
1. An additional multiplier is included to compensate for the higher discharge rate in alarm. Battery capacity decreases with age.
2. The Standby current + Alarm current must never exceed 3.0 Amps
3. The following states the maximum standby current allowed using a 38 AH battery set: 60 hours of standby time is 0.5 Amps 24 hours of standby time is 1.2 Amps
4. Does not include lamp or LED current, add separately.
5. When using the FS-MT Municipal Tie Module add the following currents for standby and alarm:
Type of Municipal Tie Connection Standby Alarm
Local Energy + 0 + 0 Reverse Polarity Alarm Output (CA) Alarm Alarm w/Trouble Reverse Polarity Trouble Output (CT) + 0.020 + 0.020
A.H. for
Alarm
Hours of Standby Required per
NFPA 72 Standard (4, 24 or 60)
A. x ____ Hours =
5 Minutes of Alarm Operation
A. x 0.33 Hours =
per NFPA 72 Standard*
Calculated
A.H.
De-rating
Factor
+ 0.020 + 0
A.H. Required
Battery Capacity
+ 0.020 + 0.020
AH for Standby
AH for Alarm
P/N 315-699461 41
Technical Manuals Online! - http://www.tech-man.com
Page 46
APPENDIX B- COMPATIBLE DEVICES
DEVICES FOR ADDRESSABLE DEVICE CIRCUITS FS- 100 Addressable Modules
Model No. Description
FS-MS Manual Station FS-MS-LFA Manual Station – Local Fire Alarm FS-MSD Manual Station – Dual Action FS-MSD-LFA Manual Station – Dual Action – Local Fire Alarm FS-MSM Manual Station – Metal FS-TRI-S Transmit-Receive Interface – Single Monitor Circuit FS-TRI-D Transmit-Receive Interface – Dual Monitor Circuit FS-TRI-R Transmit-Receive Interface – Dual Monitor Circuit with Programmable Relay FS-CZM Conventional Zone Module
FS- 100 Addressable Detectors
Model No. Description
FS-DP Photo Detector FS-DPT Photo/Thermal Detector FS-DT Thermal Detector, Fixed Temperature
FS- 100 Detector Bases
Model No. Description
DB-11 Standard Base ADBX -11 Audible Base DB-X11RS Relay Base AD-11P Standard Duct Housing AD-11XPR Duct Housing with Relay
FS- 100 Accessories
Model No. Description
LIM-1 Line Isolator Module RLI-1 Remote LED Annunciator, Round (for 4” Octagon Box Mounting) RLI-2 Remote LED Annunciator, Rectangular (for Single Gang Box Mounting)
Notes:
1. Up to a maximum of 60 devices, detectors and modules may be used on the addressable device
circuit.
2. For specific wiring and installation information, read the instructions provided with each device.
DEVICES FOR NOTIFICATION APPLIANCE CIRCUITS
See Siemens P/N 315-096363 for compatible notification appliances.
P/N 315-699461 42
Technical Manuals Online! - http://www.tech-man.com
Page 47
APPENDIX C: TROUBLESHOOTING
DEFINITIONS FOR EVENT HISTORY ENTRIES
A. General
ENTRY INDICATES
ALARM General alarm ALRM Alarm AVCntr Alarm Verify counter Blank Plain alarm CrossZone cross zone point CZ1A Cross zone CZ1B Cross zone CZ2A Cross zone CZ2B Cross zone DETECTOR General alarm HEAT Thermal sensor LCDxx LCD Annunciator xx MAIN Main panel MANL PULL Manual pull station Mntc Detector maintenance alert PAS Positive alarm sequence PAS INHBT PAS inhibit switch PHOTO Photoelectric sensor PRE SIGNL pre-signal PreA Pre-alarm SUPERVSRY Supervisory SUPR Supervisory TRBL Trouble TROUBLE Trouble USERx User-defined input x WATERFLOW Waterflow
P/N 315-699461 43
Technical Manuals Online! - http://www.tech-man.com
Page 48
B. System Troubles
ENTRY INDICATES
AC Trouble AC input low or off AddrLp 1 DBLSHT Double short trouble on addressable loop 1 AddrLp 1 OPEN Open circuit trouble on addressable loop 1 AddrLp 1 SHORT Short circuit trouble on addressable loop 1 BATT Trouble Battery input low or off CITY Trouble Local Energy circuit open CM1aa NoRespons Programmed control module not responding on loop 1 at address aa CM1aa DataError More than one device responding on loop 1 at address aa CM1aa OPEN Control module NAC wiring open on loop 1 at address aa CM1aa SHORT Control module NAC wiring shorted on loop 1 at address aa DACT Acct Trb DACT account reporting trouble DACT Com Trouble DACT communication trouble with main processor DACT PL x Trouble Open or short on DACT phone line x FLASH FATAL Trb Configuration Flash memory trouble GRND FAULT Trbl Ground Fault trouble LCDxx NoRespons LCD Annunciator xx programmed but is not responding LCDxx Not Pgmd LCD Annunciator xx is not programmed but is responding LCDxx Trouble LCD Annunciator xx reports trouble ADD00 Addr=00 Device on the loop responded to address 00 ADDaa Not Pgmd Device responding is not programmed on loop address aa ADDaa NoRespons Device not responding ADDaa Mult. Add Resp More than one device responding on the loop at address aa ADDaa Com Trb Device responses are not valid on the loop address aa ADDaa Inc. Dev. ID Device responding is not the type programmed on the loop address aa ADDaa OPEN Device IDC wiring open on loop 1 address aa ADDaa Tst Flt Detector is not entering or exiting test mode on loop address aa ADDaa TRBL Sensor needs maintenance on loop 1 address aa ADDaa MaintAlrt Sensor needs cleaning on loop 1 address aa ADDaa TestValue Not receiving valid sensor test reading on loop l address aa MNLP Bad Msg Main processor to loop processor communication trouble MNLP Fifo Xmit Main processor to loop processor communication trouble MNLP NoRespons Main processor to loop processor communication trouble NACxx Trouble NAC xx wiring is open or shorted PC Pgmr Trb Control unit is not receiving communication from PC QuickTest Abort Quick Test Timer expired causing abnormal exit of Quick Test Trb Reminder Trouble Reminder timer expired
RD 33 LED on serial annunciator board trouble
P/N 315-699461 44
Technical Manuals Online! - http://www.tech-man.com
Page 49
C. System Events
ENTRY INDICATES/NOTES
Alarm Silenced MAIN, LCDxx shown on bottom line All AV Ctrs Clr All AV counters cleared AutoProgram Run Auto programming function run Backup Cnfg Check Backup configuration validated, result on bottom line Backup Cnfg Edit Backup configuration edited CMlaa ActvnCnfd Non-relay CM activation confirmed by trouble input on ConfigsCompared Backup and primary configurations compared, result on bottom line ConfigsSwapped Backup and Primary configurations swapped EventHist Clear Event History cleared Mnt Levl Enter Entered Maintenance level Mnt Levl Exit Exited Maintenance level Mnt Levl PW Changed Changed Maintenance level password MM1aa Disabled MAIN or LCDxx shown on bottom line MM1aa Enabled MAIN or LCDxx shown on bottom line NACxx Active Confirm NAC activation confirmed Panel Reset MAIN, LCDxx shown on bottom line Power Up PriConfigCopied Primary configuration copied to backup QuickTest Exit Exited Quick Test, MAIN or LCDxx shown on bottom line QuickTest Start Started Quick Test, MAIN or LCDxx shown on bottom line SN1aa AV CtrClr AV counter for sensor SN1aa cleared SN1aa AV CtrRll Alarm Verification counter rolled over to 0 SN1aa Disabled MAIN or LCDxx shown on bottom line SN1aa Enabled MAIN or LCDxx shown on bottom line System Date Changed Changed system date, old and new dates shown on lines 3 and 4 System Time Changed Changed system time, old and new times shown on lines 3 and 4 Tech Levl Enter Entered Tech level Tech Levl Exit Exited Tech level Tech Levl PW Changed Changed Tech level password User Levl Enter Entered User level User Levl Exit Exited User level
P/N 315-699461 45
Technical Manuals Online! - http://www.tech-man.com
Page 50
APPENDIX-D: INSTALLATION INSTRUCTIONS
This Appendix provides installation instructions for the following option modules and accessories: Model No. Installation Instructions P/N
FS-MT Municipal Tie Module 315-699462
FS-232 RS232 Board 315-699463
FS-DACT Serial Digital Communicator 315-699464
FS-RD Remote LCD Annunciator 315-699465
FS-RU Serial Relay Unit 315-699466
FS-RE8 Serial Relay Extender
FS-SAU Serial Annunciator Unit 315-699468 FS-SAE16 Serial Annunciator Extender
FS-AE Fire Alarm Accessory Enclosure 315-699470
P/N 315-699461 46
Technical Manuals Online! - http://www.tech-man.com
Loading...