Siemens FDOOT241-9, FDOOT221, FDOOT241-8, FDO241, FDO221 Technical Manual

...
Building Technologies
Fire Safety & Security Products
FDOOT241-9, FDOOT241-8,
FDOOT221, FDO241, FDO221,
FDT241, FDT221
Automatic fire detectors
Technical specifications and availability subject to change without notice.
© 2006-2009 Copyright Siemens Building Technologies, Inc.
We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.
3
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
1
About this document ....................................................................................7
2 Safety............................................................................................................11
2.1 Safety notices................................................................................................11
2.2 Safety regulations for the method of operation .............................................13
2.3 Standards and directives complied with........................................................15
3 Structure and function................................................................................16
3.1 Overview .......................................................................................................16
3.1.1 Detectors with ASAtechnology (S-LINE) ....................................... 16
3.1.2 Detector with detection algorithms (C-LINE) .................................17
3.1.3 Details for ordering ........................................................................17
3.2 S-LINE and C-LINE.......................................................................................18
3.2.1 C-LINE ........................................................................................... 19
3.2.2 S-LINE ...........................................................................................20
3.3 Detectors .......................................................................................................22
3.3.1 Neural fire detector ........................................................................22
3.3.1.1 Variants of the FDOOT241-9 ....................................23
3.3.2 Wide-spectrum smoke detector .....................................................24
3.3.3 Heat detector .................................................................................25
3.4 Function.........................................................................................................26
3.4.1 Parameter sets...............................................................................26
3.4.2 Danger levels.................................................................................26
3.4.3 Diagnosis levels .............................................................................27
3.4.4 Line separator................................................................................29
3.4.5 Automatic recognition of the detector line protocol........................29
3.4.6 Internal alarm indicator ..................................................................29
3.4.7 Connection of external alarm indicators ........................................29
3.4.8 Renovation mode...........................................................................30
3.4.9 Test mode ......................................................................................30
3.4.10 Behavior in degraded mode...........................................................30
3.4.11 Interface to service devices ...........................................................31
3.4.12 Line tester ......................................................................................31
3.5 Mechanical setup ..........................................................................................32
3.6 Options ..........................................................................................................33
3.6.1 Detector base FDB221/FDB221-AA..............................................33
3.6.2 Detector base FDB201/FDB201-AA..............................................33
3.6.3 Detector base FDB222 ..................................................................34
3.6.4 Detector base FDB202 ..................................................................34
3.6.5 Sounder base FDSB291................................................................34
3.6.6 Sounder base FDSB292................................................................35
3.6.7 Base attachment FDB291..............................................................35
3.6.8 Base attachment humid FDB293...................................................35
3.6.9 Base adapter FDB281 ...................................................................36
3.6.10 Detector heating unit FDBH291.....................................................36
3.6.11 Designation plate FDBZ291...........................................................36
3.6.12 Designation plate DBZ1193A ........................................................37
3.6.13 Detector locking device FDBZ293 .................................................37
3.6.14 Dummy detector FDX291 ..............................................................37
3.6.15 Detector dust cap FDZ291............................................................. 37
3.6.16 Protective cage DBZ1194..............................................................38
Table of contents
4
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3.6.17 EMC-protective cage FDBZ294 .....................................................38
3.6.18 Micro terminal DBZ1190-AA ..........................................................38
3.6.19 Connection terminal DBZ1190-AB.................................................39
3.6.20 M20 x 1.5 metal cable gland ..........................................................39
4 Project engineering.....................................................................................40
4.1 Compatibility..................................................................................................40
4.2 Ambient features ...........................................................................................40
4.3 Parameter sets: Neural fire detector .............................................................42
4.3.1 Neural fire detector FDOOT241-x (sensor mode 0) ......................42
4.3.1.1 Description.................................................................42
4.3.1.2 Application .................................................................44
4.3.1.3 Specification ..............................................................45
4.3.2 Neural fire detector FDOOT241-x (sensor mode 1, 'Heat detector')46
4.3.3 Neural fire detector FDOOT241-x (sensor mode 2, 'Smoke
detector') ........................................................................................47
4.3.4 Neural fire detector FDOOT221.....................................................48
4.3.4.1 Description.................................................................48
4.3.4.2 Application .................................................................48
4.3.4.3 Specification ..............................................................48
4.4 Parameter sets: Wide-spectrum smoke detector..........................................49
4.4.1 Wide-spectrum smoke detector FDO241 ......................................49
4.4.1.1 Description.................................................................49
4.4.1.2 Application .................................................................49
4.4.1.3 Specifications ............................................................50
4.4.2 Wide-spectrum smoke detector FDO221 ......................................51
4.4.2.1 Description.................................................................51
4.4.2.2 Application .................................................................51
4.4.2.3 Specification ..............................................................51
4.5 Parameter sets: Heat detector ......................................................................52
4.5.1 Heat detector FDT241 ...................................................................52
4.5.1.1 Description.................................................................52
4.5.1.2 Specifications ............................................................53
4.5.2 Heat detector FDT221 ...................................................................54
4.5.2.1 Description.................................................................54
4.5.2.2 Specifications ............................................................54
4.6 Default settings..............................................................................................55
4.7 Application examples ....................................................................................56
5 Mounting / Installation ................................................................................57
5.1 Required space .............................................................................................57
5.2 Detector base FDB201/221...........................................................................58
5.3 Detector base FDB202/222...........................................................................59
5.4 Base attachment FDB291 .............................................................................60
5.5 Base attachment humid FDB293 ..................................................................61
5.6 Base adapter FDB281...................................................................................62
5.7 Detector locking device FDBZ293.................................................................63
5.8 Designation plate FDBZ291 ..........................................................................64
5.9 Designation plate DBZ1193A ........................................................................64
5
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
5.10 Detector heating FDBH291 ...........................................................................65
5.10.1 Installation of the detector heating unit..........................................65
5.10.2 Connection of the detector heating unit.........................................66
5.11 Protective cages............................................................................................67
5.11.1 Installation of the protective cages ................................................67
5.11.2 Grounding of the EMC-protective cage FDBZ294.........................67
5.12 Cable entry....................................................................................................68
5.12.1 Auxiliary terminals DBZ1190-AA/-AB ............................................69
5.13 Detector lines ................................................................................................69
5.13.1 Connection diagram (addressed) ..................................................70
5.13.1.1 Use of unshielded cables .......................................... 70
5.13.1.2 Use of shielded cables ..............................................71
5.13.2 Connection diagram (collective) ....................................................73
5.13.2.1 Use of unshielded cables .......................................... 74
5.13.2.2 Use of shielded cables ..............................................75
5.13.3 Connection diagram (MS8)............................................................76
5.13.3.1 Use of unshielded cables .......................................... 76
5.13.3.2 Use of shielded cables ..............................................77
5.14 Detector dust cap FDZ291 ............................................................................78
6 Commissioning ...........................................................................................79
7 Maintenance / repair ...................................................................................80
7.1 Status polling with the detector exchanger and tester ..................................80
7.2 Performance check .......................................................................................80
7.3 Testing detectors...........................................................................................81
7.3.1 Testing detectors with detector exchanger and tester...................82
7.3.2 Testing detectors without detector exchanger and tester..............82
8 Specifications ..............................................................................................83
8.1 Technical data FDOOT241-x, FDOOT221 ...................................................83
8.1.1 General (irrespective of the detector line) .....................................83
8.1.2 Detector lines .................................................................................85
8.2 Technical data FDO221, FDO241.................................................................89
8.3 Technical data FDT221, FDT241.................................................................. 91
8.4 Dimensions....................................................................................................93
8.5 Environmental compatibility ..........................................................................93
9 Index .............................................................................................................94
6
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
About this document
7
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
1 About this document
Goal and purpose
This document contains information on automatic fire detectors. Consistent compliance with the instructions guarantees correct and safe use.
Target groups
The information in this document is intended for the following target groups:
Target group Activity Qualification
Product Manager z Is responsible for information
passing between the manufacturer and regional company.
z Coordinates the flow of information
between the individual groups of people involved in a project.
z Has obtained suitable specialist training for
the function and for the products.
z Has attended the training courses for
Product Managers.
Project Manager z Coordinates the deployment of all
persons and resources involved in the project according to the schedule.
z Provides the information required to
run the project.
z Has obtained suitable specialist training for
the function and for the products.
z Has attended the training courses for Project
Managers.
Project Engineer z Parameterizes the product
according to country-specific and customer-specific requirements.
z Checks operability and releases the
product for commissioning at the place of installation.
z Searches for and corrects
malfunctions.
z Has obtained suitable specialist training for
the function and for the products.
z Has attended the training courses for Project
Engineers.
Installation personnel z Assembles and installs the product
components at the place of installation.
z Carries out a performance check
following installation.
z Has received specialist training in the area of
building installation technology or electrical installations.
Maintenance personnel z Carries out all maintenance work.
z Checks that the products are in
perfect working order.
z Searches for and corrects
malfunctions.
z Has obtained suitable specialist training for
the function and for the products.
About this document
8
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
Document identification
Position Information
Title page z Product type
z Product designation z Document type
Last page, bottom left z Document ID
ID_ModificationIndex_Language_COUNTRY
z Edition date
Last page, bottom right z Manual
z Register
Conventions for text marking
Markups
Special markups are shown in this document as follows:
Requirement for a behavior instruction
Intermediate result of a behavior instruction
End result of a behavior instruction
'Text' Quotation, reproduced identically
<Key> Identification of keys
Supplementary information
The
i
symbol identifies supplementary information such as a tip for an easier
way of working.
Supplementary information is labeled using the 'i' symbol.
About this document
9
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
Technical terms
Term Explanation
AI Alarm indicator
ASA Advanced Signal Analysis
DA Detection algorithms
C-LINE Fire detector for standard applications
S-LINE Fire detector for sophisticated applications
ES Product version
FDnet Addressed detector line (field device net)
FET Field Effect Transistor
GMT Limit value detection technology (collective)
LED Light-emitting diode
MC link Maintenance and Commissioning Link; interface to the detector
exchanger and tester
MS8 Pulse detection technology (addressed); also known as PMT
PMT Pulse detection technology (addressed); also known as MS8
SIGMASYS Fire detection system
Reference documents
Document ID Title
008331 List of compatibility
007227 FDUD292 detector exchanger and tester
009718 FDUD293 intelligent detector tester
008250 FDUL221 line tester
010030 Fire detector application guideline
About this document
10
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
History of changes
Document ID Edition date Brief description
007004_k_en_-- 04.2009 Sensitivities for FDOOT241-x with High
Suppression now 2.3 and 8 %/m. Accessories with order no. Detector base FDB2x1-AA with 1 micro terminal. FDSB291 compatible with heat detector FDT2xx
(as of ES ≥43). Connection diagram for shielded cables.
007004_j_de_-- 07.2008 Safety instructions revised
Technical data restructured
007004_i_de_-- 02.2008 Chap. 4.3.1.3: Only parameter set 8 doesn't satisfy
the EN 54-7 and CEA 4021 standards. Parameters set 0 added to chaps. 4.3.2 and 4.3.3. Index added.
007004_h_de_-- 02.2008 FM approvals supplemented.
IP protection category for FDB291/FDB293 corrected.
Structure in chap. 'Detector lines' uniform. Various corrections to parameter sets of
FDOOT241-x, FDO241 and FDT241. KMK in chap. 8.1.4: Par. sets specified more
precisely. New chapters 'Default settings' and 'Protective
cages'. New options:
- Detector base FDB202/FDB222
- Dummy detector FDX291
007004_g_de_-- 10.2007 Cross-reference list of detector names added in
chap. 'Overview'. Display texts for detector exchanger and tester
added in 'Diagnosis levels' chapter. Various corrections to FDOOT241-x parameter sets.
EMC-protective cage FDBZ294 included in options. 'Mode' replaced by 'sensor mode'. Supplements in the 'Technical data':
- Line separator
- IP protection categories
- LPCB approvals
- Standard EN 54-17 Images with language texts replaced by language-
neutral images
007004_f_de_-- 09.2006 Complete revision (devices with ES ≥ 30 included)
007004_e_de_-- 04.2005 Chapters 5.1, 5.3, 5.5.3, 5.7.2, 5.8.1, 5.8.2, 6.11.1,
6.11.2, 9.3.2, 9.3.3, 9.4, 9.5
007004_d_de_-- 01.2005 Chapters 4.4.1, 5, 9.3.1, 9.3.4, 9.3.6 and 9.4
adapted
007004_c_de_-- 12.2004 Text in chapter 0, titles 5.5.1, 5.5.2, 5.5.3 adapted
007004_b_de_-- 11.2004 Document layout adapted, parameter sets adapted,
various minor changes
007004_a_de_-- 06.2004 First edition
Safety
11
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
2 Safety
2.1 Safety notices
The safety notices must be observed in order to protect people and property.
The safety notices in this document contain the following elements:
z Symbol for danger
z Signal word
z Nature and origin of the danger
z Consequences if the danger occurs
z Measures or prohibitions for danger avoidance
Symbol for danger
This is the symbol for danger. It warns of risks of injury.
Follow all measures identified by this symbol to avoid injury or death.
Additional danger symbols
These symbols indicate general dangers, the type of danger or possible consequences, measures and prohibitions, examples of which are shown in the following table:
General danger
Explosive atmosphere
Voltage/electric shock
Laser light
Battery
Heat
Safety
12
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
Signal word
The signal word classifies the danger as defined in the following table:
Signal word Danger level
DANGER DANGER identifies a dangerous situation, which will result
directly in death or serious injury if you do not avoid this situation.
WARNING WARNING identifies a dangerous situation, which may result
in death or serious injury if you do not avoid this situation.
CAUTION CAUTION identifies a dangerous situation, which could result
in slight to moderately serious injury if you do not avoid this situation.
NOTICE
NOTICE
identifies possible damage to property that may
result from non-observance.
How risk of injury of presented
Information about the risk of injury is shown as follows:
WARNING
Nature and origin of the danger
Consequences if the danger occurs
z Measures / prohibitions for danger avoidance
How possible damage to property is presented
Information about possible damage to property is shown as follows:
NOTICE
Nature and origin of the danger
Consequences if the danger occurs
z Measures / prohibitions for danger avoidance
Safety
13
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
2.2 Safety regulations for the method of operation
National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, assembly, installation, operation or disposal of the product apply at the place of operation, then these must also be taken into account together with the safety regulations in the product documentation.
Electrical installations
WARNING
Electrical voltage
Electric shock
z Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
z Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
z Lock volt-free areas to prevent them being switched back on again by mistake.
z Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
z Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
z Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside of installation.
z Produce earthing as stated in local safety regulations.
Assembly, installation, commissioning and maintenance
z If you require tools such as a ladder, these must be safe and must be intended
for the work in hand.
z When starting the fire control panel ensure that unstable conditions cannot
arise.
z Ensure that all points listed in the 'Testing the product operability' section below
are observed.
z You may only set controls to normal function when the product operability has
been completely tested and the system has been handed over to the customer.
Safety
14
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
Testing the product operability
z Prevent the remote transmission from triggering erroneously.
z If testing building installations or activating devices from third-party companies,
you must collaborate with the people appointed.
z The activation of fire control installations for test purposes must not cause
injury to anyone or damage to the building installations. The following instructions must be observed:
‒ Use the correct potential for activation; this is generally the potential of the
building installation. ‒ Only check controls up to the interface (relay with blocking option). ‒ Make sure that only the controls to be tested are activated.
z Inform people before testing the alarming control devices and allow for possible
panic responses.
z Inform people about any noise or mist which may be produced.
z Before testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.
Modifications to the system layout and products
Modifications to the system and to individual products may lead to faults, malfunctioning and safety risks. Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions.
Modules and spare parts
z Components and spare parts must comply with the technical specifications
defined by Siemens. Only use products specified or recommended by Siemens.
z Only use fuses with the specified fuse characteristics.
z Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery type recommended by Siemens.
z Batteries must be disposed of in an environmentally friendly manner. Observe
national guidelines and regulations.
Disregard of the safety regulations
Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation. This applies in particular to the following damage:
z Personal injuries or damage to property caused by improper use and incorrect
application
z Personal injuries or damage to property caused by disregarding safety
instructions in the documentation or on the product
z Personal injury or damage to property caused by poor maintenance or lack of
maintenance
Safety
15
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
Disclaimer
We have checked that the content of this document matches the hardware and software described. Despite this, we cannot rule out deviations and cannot therefore assume liability for them matching completely. The details in this document are checked regularly and any corrections needed included in subsequent editions.
We are grateful for any suggestions for improvement.
2.3 Standards and directives complied with
A list of the standards and directives complied with is available from your Siemens contact.
Structure and function
16
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3 Structure and function
3.1 Overview
In this document the following detectors are summarized under the term "Automatic fire detectors":
z Neural fire detector FDOOT2x1-x
z Wide-spectrum smoke detector FDO2x1
z Heat detector FDT2x1
The same detectors may have different names, depending on the document type.
Detector type Designation 1 (e.g. in technical documentation
etc.)
Designation 2 (e.g. in catalog sheets etc.)
FDOOT221 Neural fire detector Multi-sensor smoke detector, neural DA
FDOOT241-x Neural fire detector Multi-sensor smoke detector, neural ASA
FDO221 Wide-spectrum smoke detector Smoke detector, FDnet wide spectrum DA
FDO241 Wide-spectrum smoke detector Smoke detector, FDnet wide spectrum ASA
3.1.1 Detectors with ASAtechnology (S-LINE)
Neural fire detector FDOOT241-9
Neural fire detector FDOOT241-8
Wide-spectrum smoke detector
FDO241
Heat detector FDT241
Can be used either addressed in FDnetor collectively
Can be used either addressed in MS8/PMT or in FDnet
Can be used addressed on the FDnet
Can be used addressed on the FDnet
Can be set as neural fire detector, wide-spectrum smoke detector or heat detector on the part of the software
Selectable detection behavior thanks to application-specific ASA parameter sets
Structure and function
17
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3.1.2 Detector with detection algorithms (C-LINE)
Neural fire detector FDOOT221
Wide-spectrum smoke detector FDO221
Heat detector FDT221
Can be used addressed on the FDnet
Selectable detection behavior thanks to different DA parameter sets
3.1.3 Details for ordering
Type Order no. Designation
FDOOT241-9 A5Q00004813 Neural fire detector
FDOOT241-8 A5Q00004663 Neural fire detector
FDO241 A5Q00004811 Wide-spectrum smoke detector
FDT241 A5Q00004812 Heat detector
FDOOT221 A5Q00001566 Neural fire detector
FDO221 A5Q00001565 Wide-spectrum smoke detector
FDT221 A5Q00001567 Heat detector
Structure and function
18
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3.2 S-LINE and C-LINE
Regarding the detectors, there are two product lines: S-LINE and C-LINE. They differ regarding the different detector variants and functionalities in both the detectors and control panels. The application range of the S-LINE detectors is wider than that of the C-LINE detectors.
Application range
fast / sensitive
Response behavior slow / insensitive
S-LINE
C-LINE
Few Deceptive phenomena Many
z
S-LINE detectors are suited to applications where many deceptive phenomena have to be expected, or fast fire detection is required.
z C-LINE detectors are suited to applications where few deceptive phenomena
have to be expected.
FDnet devices of the S-LINE and C-LINE can be combined on the same detector
line.
Structure and function
19
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3.2.1 C-LINE
The C-LINE detectors are characterized by a very high detection reliability combined with a high immunity to deceptive phenomena. The detectors have two parameter sets, by means of which they can be adapted to the conditions prevailing at the installation location.
Operating mode: Signal processing with detection algorithms
The following figure shows signal processing with C-LINE detectors in a diagram.
C
Sensory
Signal analysis
Algorithms
Result
Danger level
Standard ambience
Selection of parameter
The signals captured by the sensor technology are transmitted to the algorithm. The algorithm analyses and evaluates the course of the signals (signal intensity, rate of rise and fluctuation). The algorithms are set by selecting the parameter set, which sets the detectors to the expected types of fire and ambient influences.
Structure and function
20
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3.2.2 S-LINE
Properties
In contrast to the C-LINE detectors, S-LINE detectors have the following features:
z Dynamic influence on the parameter sets
z Pattern recognition
z Real time interpretation of the situation
z Process- and time-controlled switchover of the parameter sets
Signal processing of the S-LINE detectors is based on ASAtechnology (ASA = Advanced Signal Analysis). ASAtechnology can also be characterized as second generation algorithms. Signal processing with ASAtechnology permits optimum adaptation of the detector behavior to the particular ambient conditions.
S-LINE detectors are characterized by their unique detection reliability and high immunity to deceptive phenomena.
Operating mode: Signal processing with ASAtechnology
The following figure shows signal processing with S-LINE detectors in the form of a diagram.
C
Dynamic influence of parameter
Environment
Evaluation of the situation
Danger level
Result
Algorithms
Signal analysis
Sensory
Sensory
The signals captured by the sensory are transmitted to the algorithm. The algorithms are set by selecting the parameter set.
Structure and function
21
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
Algorithms
In comparison to the detection algorithms (DA), the individual parameters of the selected parameter set can be adapted with ASAtechnology. A real time interpretation of the situation leads to a dynamic influence on the algorithm. This results in a broadening of the application range of the parameter set and thus of the detector. The detector reacts more sensitively in the event of fire, and more robustly in the event of deceptive phenomena.
Switching over the parameter set
In addition to the selection of the parameter set, the S-LINE detectors enable time­or process-controlled switching over of the parameter sets (Manned/Unmanned switchover). Thanks to this function, the detector can be used in places where the situation changes regularly and frequently (e.g. kitchen, production hall).
Downloadable parameter sets
Detectors of the S-LINE have several permanently programmed parameter sets. For special applications new, additional parameter sets can be downloaded in the field (depending on the control panel).
Structure and function
22
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3.3 Detectors
3.3.1 Neural fire detector
The neural fire detector is a multiple criteria fire detector and is equipped with two optical and two thermal sensors. The following neural fire detectors are available:
z FDOOT241-9
z FDOOT241-8
z FDOOT221
The following table shows the most important differences between the neural fire detectors.
Parameter FDOOT241-9 FDOOT241-8 FDOOT221
Signal processing ASAtechnology ASAtechnology Detection algorithms
Communication protocol z FDnet
z Collective
z FDnet z MS8
z FDnet
Structure and function
1 2
3
4
1 Heat sensors 3 Forward scatterer
2 Backward scatterer 4 Labyrinth
The detector has a sophisticated opto-electronic measuring chamber with two optical emitters, an optical receiver and two thermal sensors.
The transmitters illuminate the smoke particles from different angles. One sensor acts as forward scatterer, the other as backward scatterer. The scattered light then hits the receiver (photodiode) and generates a measurable electric signal.
The combination of a forward and backward scatterer facilitates an optimum detection and the differentiation of light and dark particles, which leads to a homogenous response behavior and optimizes the differentiation of wanted signals and deceptive phenomena.
Structure and function
23
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
In addition, the heat sensors make it possible to detect fires without smoke generation.
The combination of optical and thermal sensor signals optimizes detection reliability. This has the following advantages:
z Early detection of all types of fire, whether they generate light or dark smoke, or
no smoke at all.
z The neural fire detector can be operated at a lower sensitivity level and thus
achieves a higher immunity against false alarms which may otherwise be
caused by cold aerosols (e.g. by smoking, electrical welding, etc.). In the case
of an open fire, the smoke sensitivity is heightened by the temperature
increase, which means that a detection reliability level that is comparable to
that of the wide-spectrum smoke detector can be achieved.
The neural fire detectors FDOOT241-8/9 may as well be applied either as optical smoke detectors or as out-and-out heat detectors. This is possible by selecting one of the following sensor modes (with the detector exchanger and tester or on the control panel):
z Sensor mode 0: Application as neural fire detector
z Sensor mode 1: Application as heat detector
z Sensor mode 2: Application as smoke detector
In sensor mode 1 or 2 the parameter sets of the heat detector FDT241 or of the wide-spectrum smoke detector FDO241, respectively, can be selected. Then, these neural fire detectors behave like the heat detector FDT241 or smoke detector FDO241.
3.3.1.1 Variants of the FDOOT241-9
The neural fire detector FDOOT241-9 is available in three different variants A, B and C. The compatibility differs depending on the variant. The following table provides an overview of the compatibility of the different variants. Refer to document 008331 'List of compatibility' for compatibility details.
Variants Part number Product version Compatibility
FDnet Collective control
panels from Germany
Collective control panels from Switzerland
A A5Q00004813 < 13 X X
B A5Q00015955 13 ≤ ES < 30 X only CZ10
C A5Q00004813 ≥ 30 X X X
Notes
z Variant B has been available only as kit (FDOOT241-9M) consisting of the
neural fire detector and the detector base FDB201.
z The specifications of variant B largely correspond to those of variant A. Any
possible deviations are marked accordingly in this document.
z Variant C is available both as single detector and as kit (FDOOT241-9M).
Structure and function
24
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
The following figure shows how the different variants are marked (to the left: Variant B; to the right: Variants A and C).
3.3.2 Wide-spectrum smoke detector
The wide-spectrum smoke detector is an optical smoke detector with an optical sensor. It works according to the principle of forward scattering. This detector reacts with extreme sensitivity to light fire aerosols. The following wide-spectrum smoke detectors are available:
z FDO241 (with ASAtechnology)
z FDO221 (with detection algorithms)
Structure and function
1
2
1 Labyrinth 2 Forward scatterer
The wide-spectrum smoke detector has the same measuring chamber as the neural fire detector, however, it has only a forward scatterer. The increased sensitivity makes the early detection of smoldering and open fires possible.
Structure and function
25
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3.3.3 Heat detector
The heat detector is a pure heat detector with two thermal sensors. The following heat detectors are available:
z FDT241
z FDT221
The following table indicates the most important differences between the two heat detectors.
Parameters FDT241 FDT221
Signal processing ASAtechnology Detection algorithms
Alarm activation by: z Temperature increase
z Reaching the maximum
temperature
z Temperature increase
Setup and function
1
1 Heat sensors
Thanks to the two sensors, a total failure can be avoided if one of the two sensors fails or breaks down.
Structure and function
26
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3.4 Function
3.4.1 Parameter sets
The parameter sets influence the detection behavior of the detectors and specifically set them to the expected fire phenomena and ambient influences in the environment to be monitored.
All parameter sets are programmed in the detectors. During commissioning, the optimum parameter set must be selected for the conditions at the place of installation. On a FDnet detector line, this is carried out at the control panel. On a collective or MS8 detector line this is done with the detector exchanger and tester.
On a FDnet detector line, the parameter set must always be set explicitly. Unless a parameter set is selected in collective or MS8 operation, the detector works with the default parameter set '0'. In this case the number of the selected parameter set is always '0'.
See also
Parameter sets: Neural fire detec
tor [J 42]
Parameter sets: Wide-spectrum s
moke detector [J 49]
Parameter sets: Heat detector [J 52]
3.4.2 Danger levels
The detector's signal processing efficiently distinguishes between fire events and deceptive phenomena. The basis for reaching a danger level is not only given by measured values exceeding a "response threshold"; moreover, the smoke density progression is observed over a longer period of time and assessed by the algorithms.
Fire detectors can transmit the following danger levels to the control panel:
Danger level Meaning Comment
0 No danger Normal condition
1 Check situation A different parameter set should
potentially be selected (inappropriate application)
2 Warning Possible danger
3 Alarm Fire
Notes
z The evaluation of the danger level and the decisions to be taken (e.g. activation
of remote transmission) are configured in the control panel.
z On a collective line only the danger levels 0 and 3 can be transmitted to the
control panel.
Structure and function
27
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3.4.3 Diagnosis levels
For the most part, the detector monitors its function by itself. The signals of all sensors are permanently monitored. In particular, the temperature sensors, light emitters, and light receivers are monitored to ensure that they are functioning correctly. Signal processing takes account of the monitoring results and adapts its behavior accordingly.
The following diagnosis levels are derived from the different control measurements:
z Normal
z Observe information
z Replacement recommended
z Replacement necessary
z Fault
See the table below for details.
A fault message is signaled in the event of a fatal error that makes the proper function of the detector impossible. To correct the cause of the fault, additional information is available in the detector. This information may be displayed, for example, by the detector exchanger and tester FDUD29x (for details see documents 007227 and 009718).
Structure and function
28
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
Information displayed on the detector exchanger and tester
Meaning Measures
'No deviation' Normal, no fault is present
The detector is fully functional
None
'maybe excha.' 1 Observe information
The detector is fully functional
z FDOOT:
Slightly soiled
Check cause during periodic maintenance
'advice excha.' 1 Replacement recommended
Detector is still functional, in spite of minor problems
z FDOOT:
Average soiling Untypical sensor values caused by
environmental influence
z FDO:
Average soiling
z Remedy the cause during the next
maintenance
z Replace detector if necessary
'needed excha.' 1 Replacement necessary
Detection possibly restricted; alarming is still possible
z FDOOT:
Heavily soiled, failure of one optical
sensor
Failure of one or both thermal sensors
z FDO:
Heavily soiled
z Call maintenance service z Replace detector
Fault present Detection is no longer guaranteed, or
invalid parameter setting
z FDOOT:
Failure of both optical sensors
z FDO:
Failure of the optical sensor
z FDT:
Failure of one or both thermal sensors
z Remedy cause z Adjust parameter setting z Replace detector
Supply fault z Check detector line voltage
z Replace detector
Software error (watchdog error) Replace detector
Memory error Replace detector
Any fault message 2
Communication error involving detector and control panel
Remedy cause
1
The information displayed on the detector exchanger and tester is always in English; no translation into the corresponding language.
2
This status can be displayed together with another status, e.g. 'needed excha.' (replacement necessary).
Structure and function
29
Building Technologies 007004_k_en_--
Fire Safety & Security Products 16.04.2009
3.4.4 Line separator
All FDnet devices are equipped with a line separator.
The FDnet device is equipped with electronic switches which isolate the defective part in case of a short-circuit on the detector line. The rest of the detector line remains serviceable. On a loop line all FDnet devices remain fully functional after a simple error.
3.4.5 Automatic recognition of the detector line protocol
The two multiple protocol detectors FDOOT241-9 and -8 may communicate via different detector line protocols. These detectors recognize the protocol on the detector line (e.g. FDnet or collective) and automatically switch to the protocol in question. This functionality facilitates commissioning in case of modernization, as no actions need to be taken on the detector itself. See document 008331 'List of compatibility' for exceptions.
3.4.6 Internal alarm indicator
The detectors have an internal alarm indicator. The internal alarm indicator shows the operating condition of the detector (see table).
Operating condition Flashing mode of the AI
Normal AI flashes weakly every 4 seconds
Test AI flashes weakly every 0.5 seconds
Alarm AI lights up every second
3.4.7 Connection of external alarm indicators
Two external alarm indicators can be connected to every detector. In the FDnet the alarm indicator can be connected to any detector; activation of the alarm indicator can be programmed in the control panel.
Instead of an optical alarm indicator that flashes in the event of an alarm, the sounder base is provided with an acoustic alarm indicator.
See also
Connection diagram (addressed) [J 70] Connection diagram (collective) [J 73] Connection diagram (MS8) [J 76]
Loading...
+ 67 hidden pages