Siemens Industry, Inc. A6V11416604 2018-07-11 1 / 4
s
Smoke Control Compliant
Actuating DXR
DXR2.E10PL-102BK
DXR2.E10PLX-102BK
DXR2.M10PL-102BK
DXR2.M10PLX-102BK
Installation Instruction
499 OHM Resistor Assembly Kit
Parts for Smoke Control Compliance
Smoke Control Listed Small Equipment
Controller Enclosure
Smoke Control Listed Large Equipment
Controller Enclosure
UL Listed Class 2 transformer with
120Vac 50/60 HZ 0.5A primary with hub
and 24 Vac 96VA
Smoke Control Compliance
The following instructions and information apply if used for
smoke control sequence.
Install Smoke Control Listed products, enclosure and transformer (see Parts for Smoke Control Compliance section for
more information).
Input Rating:
- 24V 60 HZ 72 VA
Digital Output (DO) are the only I/O suitable for smoke control application. Digital Output (DO) Electrical Ratings:
24 Vac, 6VA per DO/maximum 40 VA total.
Connection from the DXR2 to the field panel is a maximum
4000 feet, 24 AWG minimum.
Wiring Range:
- Transformer: primary 14 AWG
- 24 Vac Input Power: 14 to 18 AWG
- DO: AI: 18 to 20 AWG
- DI: 18 AWG
- LAN: 20 to 24 AWG
KNX port (11 and 12) not used or connected for smoke
control application
All circuits are power limited; FLN is RS-485 or
Ethernet.
See the following documents for more information on
configuring smoke control applications:
Smoke Control Systems Application and Engi-
neering Manual (125-1806)
Smoke Control System Application Guide
(125-1816)
NFPA and UL Standards Relevant to Smoke
Control System Application Guide (125-1817)
NOTE:
The 24 Vac relay module is not
applicable for smoke control
application.