Siemens DXR2.E10PL-102BK, DXR2.E10PLX-102BK, DXR2.M10PL-102BK, DXR2.M10PLX-102BK Installation Instruction

Siemens Industry, Inc. A6V11416604 2018-07-11 1 / 4
s
Smoke Control Compliant Actuating DXR
DXR2.E10PL-102BK DXR2.E10PLX-102BK DXR2.M10PL-102BK
DXR2.M10PLX-102BK
Installation Instruction
Product Numbers
Accessories
985-124
499 OHM Resistor Assembly Kit
Smoke Control Compliance
Parts for Smoke Control Compliance
Smoke Control Listed Small Equipment
Controller Enclosure
540-155K ,
540-155D
Smoke Control Listed Large Equipment
Controller Enclosure
550-002K
UL Listed Class 2 transformer with
120Vac 50/60 HZ 0.5A primary with hub
and 24 Vac 96VA
TR100VA004
Smoke Control Compliance
The following instructions and information apply if used for smoke control sequence.
Install Smoke Control Listed products, enclosure and trans­former (see Parts for Smoke Control Compliance section for more information).
Input Rating:
- 24V 60 HZ 72 VA
Digital Output (DO) are the only I/O suitable for smoke con­trol application. Digital Output (DO) Electrical Ratings:
24 Vac, 6VA per DO/maximum 40 VA total.
Connection from the DXR2 to the field panel is a maximum 4000 feet, 24 AWG minimum.
Wiring Range:
- Transformer: primary 14 AWG  - 24 Vac Input Power: 14 to 18 AWG  - DO: AI: 18 to 20 AWG  - DI: 18 AWG  - LAN: 20 to 24 AWG
KNX port (11 and 12) not used or connected for smoke control application
All circuits are power limited; FLN is RS-485 or Ethernet.
See the following documents for more information on configuring smoke control applications:
Smoke Control Systems Application and Engi-
neering Manual (125-1806)
Smoke Control System Application Guide
(125-1816)
NFPA and UL Standards Relevant to Smoke
Control System Application Guide (125-1817)
NOTE: The 24 Vac relay module is not applicable for smoke control application.