Siemens DLC Installation Instructions Manual

Page 1
DLC
HNET
Installation Instruct ions Model DLC
Device Loop Card
INTRODUCTION The Model DLC Device Loop Card from Siemens Industry,
Inc., is the interface for connection of FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular smoke detec­tors, Multi-Criteria detectors including Carbon Monoxide, manual stations, monitor devices, and control devices to the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular System. The DLC uses one network address on the system. The application program that is loaded into the on­board microprocessor controls the DLC operation.
The DLC contains 12 LEDs for diagnosis of problems. Ground fault detection is provided by the loop.
All field devices connected to the DLC are addressed and tested using the Device Programming Unit (DPU).
Z O N E 1
Z O N E 2
RESET
POWER
CARD FAIL
HNET FAIL
GND FAULT
ALARM
TROUBLE
ZONES STATUS
CLASS A OPEN
CLASS A RETURN
SHORT
CLASS A OPEN
CLASS A RETURN
SHORT
OPERATION The DLC initializes, operates, and maintains all devices
residing on the loop. The DLC communicates all relevant device and event information, such as alarms and troubles, to the System CPU. The sensitivity of any intelligent smoke detector and the logic functions of any intelligent output devices can be checked and adjusted from the Operator Interface (OI) through the DLC. All information about the devices on the loop can be displayed on the OI. The DLC allows the System polarity insensitive devices to be connected without generating errors.
The DLC supports only one loop (two isolated parallel zones) of up to 252 FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular intelligent field devices as well as device accessories (relay bases, audible bases, and remote lamps) in any combination. The microprocessor controls the on-board isolator to isolate either zone from the loop if one of them is shorted. When one zone is isolated from the loop, the other zone will still work.
The on-board microprocessor provides the DLC with the ability to function and initiate alarm conditions even if the main FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular CPU fails.
HUNDREDS
TENS
ONES
Figure 1 DLC Device Loop Card
P/N 315-033090-17
Building
Siemens Siemens
Siemens
Siemens Siemens
TT
ecec
hnologies Dihnologies Di
T
ec
hnologies Di
TT
ecec
hnologies Dihnologies Di
IndustryIndustry
Industry
IndustryIndustry
visionvision
vision
visionvision
,,
Inc. Inc.
,
Inc.
,,
Inc. Inc.
Page 2
Multi-Criteria detectors (Table 1) are supported by the OI, FW version 9.02 and later, and the DLC with Firmware version 06.xx and later. The DLC can be made backwards compatible in systems using OI, P/N 500-033070, with DLC Firmware version 05.06 or earlier.
The OI collaborates with the DLC FW to identify compatibility with the Multi-Criteria detectors (Table 1). In cases where the OI does not support the Multi-Criteria detectors, the OI will specify “Configuration Process Failure”, and illuminate the “TROUBLE” LED on the DLC. In cases where Multi-Criteria detectors are not used, the DLC can be reprogrammed with the FW version 05.06 or earlier. The compatibil­ity chart is as follows:
reilraedna50.8noisrevIOretaldna20.90noisrevIO
reilraedna60.50noisrevCLD
retaldnaxx.60noisrevCLD
KOKO
BUORT(elbitapmocnIKO
)DELEL
Controls and Indicators The front panel of the DLC contains one reset switch, 12 LEDs, and three HNET
address switches, as shown in Figure 1. A reset switch is located on the top of the front panel. Pushing the reset switch re-initializes the DLC operation.
The LEDs follow the reset switch and their functions are defined as follows:
POWER (Green) Normally ON. When illuminated, indi-
cates the power for the DLC is applied to the card.
CARD FAIL (Yellow) Normally OFF. When illuminated, indi-
cates the card microprocessor has failed.
HNET FAIL (Yellow) Normally OFF. When illuminated, indi-
cates that the HNET communication with the DLC has terminated and the card goes into degrade mode.
GND FAULT (Yellow) Normally OFF. When illuminated, indi-
cates that the DLC has detected either a negative or positive ground fault on its field wiring.
ALARM (Red) Normally OFF. When illuminated, indicates
TROUBLE (Yellow) Normally OFF. When illuminated, indi-
Siemens Industry, Inc. Building Technologies Division
that the DLC has detected an alarm.
cates that the DLC has detected a trouble on its field wiring; or incapability between firmware in either the OI, DLC, or both.
P/N 315-033090-172
Page 3
CLASS A OPEN–ZONE 1 (Yellow) Normally Off. When illuminated, indi-
cates a Zone 1 wire is open if the loop was set to Class A.
CLASS A RETURN–ZONE 1 (Yellow) Normally Off. When illuminated, indi-
cates a Zone 1 return wire is reversed if the loop was set to Class A.
SHORT–ZONE 1 (Yellow) Normally Off. When illuminated, indi-
cates a Zone 1 wire short.
CLASS A OPEN–ZONE 2 (Yellow) Normally Off. When illuminated, indi-
cates a Zone 2 wire is open if the loop was set to Class A.
CLASS A RETURN–ZONE 2 (Yellow) Normally Off. When illuminated, indi-
cates a Zone 2 return wire is reversed if the loop was set to Class A.
SHORT–ZONE 2 (Yellow) Normally Off. When illuminated, indi-
cates a Zone 2 wire short.
Three rotary dial switches at the bottom of the front panel are used to set the HNET network address of the DLC. All field devices connected to the DLC are addressed and tested using the Device Programming Unit (DPU). Refer to the DPU Manual, P/N 315-033260 for further information.
Siemens Industry, Inc. Building Technologies Division
P/N 315-033090-173
Page 4
PRE-INSTALLATION Set the three-digit HNET network address for the DLC using the three rotary dial
HNET
switches located near the bottom of the front panel. (Refer to Figure 1 for the
HUNDREDS
TENS
ONES
location of the switches.) The address for the DLC must be the same as the address selected for it in the Zeus Programming Tool. To set the address, turn the pointers on each of the three dials to the numbers for the selected address. For example, if the address is 123, set the pointer for the HUNDREDS dial to “1”, set the pointer for the TENS dial to “2”, and set the pointer for the ONES dial to “3”. The range of allowable addresses is from 001 to 251 (leading zeros must be used).
INSTALLATION The DLC plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin DIN
connectors and can occupy any slot in the card cage. (Refer to Figure 2.)
Insert the DLC card into the card guides rightside up (lettering on the front panel is legible)
Slide the card in until the card edge connectors contact the receptacles on the motherboard.
Verify that the DIN connectors of the card and the card­cage are aligned properly. The card can only be plugged into the card cage in one direction; if it does not align, DO NOT FORCE the card.
Figure 2 Installing The DLC
WIRING
Place thumbs on the front panel adjacent to the captive screws and gently apply even pressure on the card until the connectors seat in the receptacles on the motherboard.
Secure the card with the captive screws.
Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery.)
All field wiring to the DLC is connected to the terminal blocks of the CC-5 card cage slot in which it is installed.
To Connect External Wiring
1. Loosen the screw of the terminal by turning it counterclockwise.
2. Insert the wire into the side of the terminal block.
3. Tighten the screw of the terminal block by turning it clockwise.
Connect +24V from the PSC-12 to terminal 17 and -24V from the PSC-12 to terminal 18 of the slot in the CC-5 where the DLC will be installed. (Refer to Figure 3.)
Siemens Industry, Inc. Building Technologies Division
P/N 315-033090-174
Page 5
12345678
910111213141516
CLASS A WIRING*
NO T-TAPPING ALLOWED
BOTH ZONES MUST BE WIRED AS CLASS A
12345678
910111213141516
CLASS B WIRING**
T-TAPPING ALLOWED
BOTH ZONES MUST BE WIRED AS CLASS B
NOTES:
1. NO END OF LINE DEVICE REQUIRED.
2. BOTH CIRCUITS SUPERVISED AND POWER LIMITED PER NEC 760.
3. POSITIVE OR NEGATIVE GROUND FAULT DETECTED AT <50K OHMS ON TERMINALS 1-8.
4. FOR CLASS A CIRCUITS DO NOT TERMINATE SHIELDS (OPTIONAL) ON THE RETURN RUN.
*OPERATES IN FULL CONFORMANCE WITH STYLE 6 (ULC DCLA)
ZONE 1
ZONE 1
INITIATING
DEVICE
INITIATING
DEVICE
CC-5
CC-5
LINE 1
LINE 1
LINE 1 (RETURN)
LINE 1 (RETURN)
LINE 1 (OUT)
LINE 1 (OUT)
ZONE 2
ZONE 2
LINE 2
LINE 2
LINE 2 (OUT)
LINE 2 (OUT)
LINE 2 (RETURN)
LINE 2 (RETURN)
NOT USED
NOT USED
NOT USED
NOT USED
**OPERATES IN FULL CONFORMANCE WITH STYLE 4 (ULC DCLB)
SHIELD (OPTIONAL) TERMINATE IN ENCLOSURE WITH THE DLC. TERMINATE AT ONE END ONLY. TERMINATE TO EARTH GROUND.
*
*
*
*
ZONE 1 ZONE 2
LINE 1 (OUT)
12345678
910111213141516
LINE 1 (RETURN)
LINE 2 (RETURN)
LINE 1 (OUT)
LINE 2 (OUT)
DO NOT USE
LINE 1 (RETURN)
ONE SLOT OF CC-5
17 18 19 20 21 22 23 24
24V-
24V+
DO NOT USE
TO 24VDC FROM THE PSC-12
Figure 3 Wiring The 24VDC Power Lines To The DLC Slot In The CC-5
LINE 2 (RETURN)
LINE 2 (OUT)
Figure 4 DLC Wiring Diagram
Siemens Industry, Inc. Building Technologies Division
P/N 315-033090-175
Page 6
The DLC circuit can be wired Style 4 (Class B) or Style 6 (Class A). On-board switches controlled by microprocessor allow selection of Class A or B without using jumpers for Class B. The DLC field circuit wiring does not require twisted, shielded wire. It can be installed in conduit containing low voltage power, notification appli­ance circuits, audible and speaker zone circuits, and RS-485 and other data circuits without restrictions.
Electrical connections for the two zones are shown in Figure 4. The wiring style is set in the Zeus Programming Tool without using external jumpers. Once the wiring style is set, both zones will be set to the same style.
Do not wire the two zones in different styles.
If the return wires in either zone are reversed (in a Class A configuration), the CLASS A RETURN LED associated with the affected zone will be illuminated. Switch the two return wires to remove this trouble. Eliminate all other troubles before completing the installation.
COMPATIBILITY 1. The DLC supports only FireFinder-XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular intelligent devices. The compatibility identifiers for the compat­ible devices are the model numbers listed in Table 1 for UL 864 and in Table 2 for UL2572. Use any combination of those listed in Table 1 or Table 2, as applicable.
2. The DLC supports one loop (with 2 isolated zones) of up to 252 FireFinder­XLS/Desigo Fire Safety Modular/Cerberus PRO Modular intelligent field devices. Up to 252 devices can be distributed in either zone, but the total number is limited. For example, if 100 devices are in Zone 1, then the number of the devices in Zone 2 must be 152 or less.
3. All circuits are power limited to NFPA 70 per NEC 760. The DLC supports the use of 12-22 AWG non-shielded, non-twisted, thermoplastic fixture wire without conduit, if permitted by local building codes.
4. No end of line device is required.
5. Total circuit resistance of each zone must not exceed 50 ohms when 252 devices are loaded into one zone. (Refer to the chart on page 7.)
Maximum capacitance: 0.5μF between line+ and line-
1. 0 μF between line and chassis
6. T-tapping is not allowed on Class A loops.
7. All models are UL and ULC listed.
8. The Multi-Criteria detectors are programmed using the DPU. The SBGA-34 base, connected to a ZIC-4A, P/N 500-033050, or ZIC-8B, P/N 500-648670, can be used to create Temporal 4 tones in conjunction with the Carbon Monoxide enabled detectors FDOOTC441 and OOHC941. Using these detectors with the ABHW-4S or ABHW-4B, the selection of tones are chosen using the panel’s configuration tool.
Siemens Industry, Inc. Building Technologies Division
P/N 315-033090-176
Page 7
1ELBAT
seciveDelbitapmoCCLD
468LUrof
elbitapmoC
seciveD
derew
oppooLB4-WHBA
S4-WHBA **P11-DA
RHX-2DA
11-HBDA
RH-DA
11-BD
RH-BD
**294ZBDF
RH-294ZBDF
OICDF
224
*124ODF
*144TOODF
*144CTOODF
*124TODF
*124TDF
PCH
11-PFH
11-TPFH
*129IH
MILH
S2-SMH M-SMH S-SMH
AS-SMH
D-SMH
IRTH
D­M-IRTH R-IRTH S-IRTH
MZH
CH-DELI WH-DELI
1-MIL
*129HO
*149HOO
*149CHOO
*129PO
CH-LR WH-LR
*43-AGBS
/P
derewoplanretxEB4-WHBA
6egapno8rebmuneeS*
.rotcetedehtfognitartnerruc
noitallatsnI
snoitcurtsnI
05.7
78550401V6AN
52.0
78550401V6AN/P
52.0
88550401V6AN/P
00.0
956590-513N/P
50.0
807940-513N/P
00.0
012330-513N/P
50.0
082330-513N/P
00.0
391490-513N/P
-513N/P
AN/P
30-513N/P
V6AN/P
50.0
022330
00.0
66863301V6AN/P
50.0
66863301V6AN/P
00.1
26642301V6AN/P
82.0
62932301V6AN/P
86.
0
55642301V6AN/P
57.0
75642301V6AN/P
82.0
43932301V6 03932301V6AN/P
82.0
068430-513N/P
00.1
092330-513N/P
08.0
092330-513N/P
08.0
23932301V6AN/P
82.0
071330-513N/P
00.1
034330-513N/P
09.0
0543
09.0
002330-513N/P
09.0
034330-513N/P
09.0
002330-513N/P
09.0
574940-513N/P
03.1
084940-513N/P
03.1
574940-513N/P
03.1
574940-513N/P
03.1
58430-513N/P
0
00.1
736840-513N/P
00.1
736840-513N/P
00.1
255940-513N/P
67.0
63932301V6AN/P
82.0
95642301V6AN/P
86.0
16642301V6AN/P
57.0
82932301
82.0
50.0
032330-513N/P
50.0
032330-513N/P
08.2
82438301V6AN/P
iwgnisuohtcudriarofgnitartnerrucehT.rotceted
tnerruCxaM
)Am(CLDmorF
tuohtiwgnisuoHtcuDriAehtrofCLDmorfnwardtneruconsierehT**
ehtsirotcetedht
seciveD
224OICDF PCH MILH
D-IRTH M-IR
TH
R-IRTH S-IRTH
1-MIL
2ELBAT
seciveDelbitapmoCCLD
2752LUrof
elbitapmoC
noitallatsnI
snoitcurtsnI
26642301V6AN/P 068430-513N/P 071330-513N/P 574940-513N/P 084940-513N/P 574940-513N/P 574940-513N/P 255940-513N/P
ELECTRICAL RATINGS
Siemens Industry, Inc. Building Technologies Division
tnerruCenalPkcaBV420
tnerruCV42lanimreTwercSecivedrepAm8.0+Am001
tnerruCenalPkcaBV2.6xamAm002
SV42ecivedrepAm8.0+Am541
tnerruCybdnat
xamCDV03:pooLeciveD)detimilrewop(xamAm573
P/N 315-033090-177
Page 8
260
250
240
230
220
210
200
190
180
170
160
150
140
130
120
110
Line Resistance (Ohms)
100
90
80
70
60
50
40
30
20
10
110
60 13050
100
120
150 21090 20080
160 220
180
170 230
19070 140
240
250
260
Max Current Load of Devices
DLC LINE RESISTANCE vs MAX CURRENT LOAD OF DEVICES
Note 1: The total number of devices in two zones can not exceed 252.
Note 2: The total current load in two zones cannot exceed 350ma.
Note 3: Max line resistance of each zone must not exceed 50 ohms if 252ma loaded.
For CE applications in Siemens E100 systems refer to
Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).
Siemens Industry, Inc. Building Technologies Division
P/N 315-033090-178
Page 9
Cyber security disclaimer
Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept.
It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security concept that is customized to individual security needs. Such a security concept may result in additional site-specific preven­tive action to ensure that the building comfort, fire safety, security management or physical security system for your site are operated in a secure manner. These measures may include, but are not limited to, separating networks, physically protecting system components, user awareness programs, defense in depth, etc.
For additional information on building technology security and our offerings, contact your Siemens sales or project department. We strongly recommend customers to follow our security advisories, which provide infor­mation on the latest security threats, patches and other mitigation measures.
http://www.siemens.com/cert/en/cert-security-advisories.htm
Siemens Industry, Inc. Building Technologies Division
P/N 315-033090-179
Page 10
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
Siemens Canada, Ltd. 1577 North Service Road East Oakville, Ontario L6H 0H6 Canada
Siemens AG I BT FS SYS MCH D-81379 München
P/N 315-033090-17
Document ID A6V10239107
Loading...