Siemens DF-30, DF-30A Installation, Application, And Technical Instructions

Page 1
INSTALLATION, APPLICATION, AND TECHNICAL INSTRUCTIONS
Models DF-30/30A Flame Detectors
Fire Safety
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN
Page 2
INTRODUCTION
The SIEMENS DF-30 and DF-30A detectors (See Figure 1) are plug-in, two-wire flame detectors which respond to ultraviolet radia­tion. The detectors use an ultraviolet sensitive gas filled tube to see a flame.
When activated, the DF-30 has a 5-second delay before alarm; the DF-30A delays 10 seconds before alarm. If the activating radiation is not sustained for the delay period, the detector sees it as an inci­dental light (not a fire) and does not alarm.
Figure 1
DF-30 and DF-30A Detector
2
Page 3
DF-30 detectors are designed to protect hazards where an antici­pated fire will develop quickly with little or no incipient (smoldering) stage where ignition is virtually instantaneous (e.g., flammable liquids, combustible gases, etc.).
The DF-30 detectors use a low profile surface mounting base, Model DB-3S. Each base may be attached to either a 4-inch octagonal or square electrical box or a single gang switchbox. The DB-3S base uses screw/clamp terminals for all electrical connec­tions, self-wiping contacts for reliability, and contains provisions for an optional concealed locking mechanism to prevent unauthorized removal.
The DF-30 detectors are capable of operating one remote alarm indicator or auxiliary relay. These detectors are protected by a rectifier against input polarity reversal of the supply lines.
DETECTOR OPERATION
The DF-30 detectors use an ultraviolet sensitive gas filled tube which operates on the Geiger-Mueller principle. This tube con­sists of an anode and a cathode sensitive to ultraviolet wave lengths of 1850 to 2600 Angstroms. Both electrodes are energized by the high voltage generated within the detector from the low volt­age which is applied to the detector.
When ultraviolet rays (photons) reach the cathode, it ionizes the gas molecules, causing them to emit electrons. As the number of ionized particles increases, an electrical current flows between the electrodes. In this way, the ultraviolet rays generate a pulsed electrical signal which is digitally counted. If the signal is still pre­sent when the counting delay cycle is complete, the detector locks into alarm and must be reset at the control panel by inter­rupting the power.
The DF-30s are designed to respond in 5 seconds to an 8W Halogen lamp directly in the line-of-sight at a distance of 50 cen­timeters. The DF-30As respond in 10 seconds to the same source.
3
Page 4
TECHNICAL DATA
Detector Type Ultraviolet
Wave Length Response 1850-2600 Angstroms
(185-260 nm)
Vision Angle (effective) 50° minimum
100° maximum
Input Voltage 19 VDC to 24 VDC
Quiescent Current (Non-alarm) 500µA maximum at 21±3 VDC
Alarm Current 65mA typical
Inrush Current 3mA maximum for 50 msec
Alarm Indicator Internal red LED is on steady
when detector is in alarm.
Alarm Processed by System 3. Must be
reset at the control panel.
Remote Alarm Indicator Connection available. Indicator
blinks every 3 seconds. Total current of 100mA maximum must be limited by the control panel and DF-30 design.
Auxiliary Relay Model RR-3: DPDT, 120 VAC, 2A.
Total current 90mA maximum must be limited by the control panel and DF-30 design.
Temperature Application Range +14° F (-10°C) to + 122°F (+50°C)
Relative Humidity Application Range 0 to 90%
Pressure Application Range (Tested) 460 to 1060 mm water
Response Time (Alarm activation delay) 5 sec (DF-30), 10 sec (DF-30A)
Sensitivity Factory set
Installation Surface mount
4
Page 5
TECHNICAL DATA (continued)
Electrical Connection Through base with screw/clamp
terminals
Physical Size 5
Electrical Wiring Two-wire 18 AWG thermoplastic
Weight 1 pound (45 kilograms)
Maximum detectors per circuit (ZN-30 or ZU-35) 5 detectors
e in (143 mm) width
(See Figure 1)
in conduit. 18 AWG limited energy shield cable
APPLICATION DATA
Flame detectors are essentially line-of-sight devices. That is, the detector must be mounted where it can see the flame directly.
Pay particular attention to blind spots, such as intervening struc­tural beams and columns, ducts, chutes, or belts. Any other opaque objects or materials  including heavy personnel traffic  must also be considered.
In hazards which include conveyor belts, the line-of-sight of the detector must clear not only the belt, but a full conveyor load as well.
Among the materials that are opaque (non-transmitting) to ultra­violet radiation are ordinary glass and transparent plastics.
The DF-30 detector alarms after a 5-second view of a flame of sufficient intensity and should be used in hazards where a fast response is necessary, such as volatile material handling areas, and where there are no other sources of ultraviolet rays which may cause false alarms. The DF-30A responds after a 10-second exposure to flame (at the design intensity) and can be used in hazards where the fire is expected to develop at a slower rate.
Signal interference substances that must be considered are UV absorbing gases and vapors. Ammonia is such a vapor, but others of more importance in the industrial environment are toluene,
ethylene, and similar solvents. Therefore, when considering protection of equipment where paint is in use, be sure to con­sider the concentrations of the solvents present.
5
Page 6
RELATIVE SENSITIVITY
(Refer to Figure 2)
When installing the DF-30 detectors, the relative sensitivity should be considered. The detector sensitivity varies from 80 to 100% of the design sensitivity depending on the angle of the flame. Figure 2 shows maximum sensitivity.
Figure 2
Directional Sensitivity
INSTALLATION
Install the detectors in accordance with NFPA guidelines and local codes.
DETECTOR PLACEMENT
Mount flame detectors in locations where ultraviolet rays from sources other than a fire will not cause false alarms.
Be careful to prevent structural reflecting materials, such as glass and metal, from reflecting nuisance ultraviolet rays from areas which are otherwise out of the detectors line-of-sight.
Common sources of ultraviolet radiation which can cause an un­wanted alarm include the electrical energy arc associated with:
Welding Heavy duty circuitbreakers High voltage discharges from transformers, power lines, etc. Gas burners (Ignitors)
Where necessary, shield the detectors from these sources of UV energy to prevent unwanted alarms.
6
Page 7
Conduct an analysis of the hazard to determine the most probable sources of flame. Then install the detectors at a point which provides:
1. The most direct line-of-sight.
2. The required angle for optimum sensitivity.
3. Shielding from sources of unwanted alarm.
Review the overall situation of the hazard frequently to assure that changes in structural or usage conditions have not blocked the view of the detectors. Such changes must be avoided and/or promptly remedied.
ENVIRONMENTAL EFFECTS
The sensitivity of the DF-30 detectors is essentially unaffected by the environmental factors of temperature, atmospheric pressure, humidity, and supply voltage.
The variations in detector performance with changes in these condi­tions were tested within the ranges given in the TECHNICAL DATA section and are negligible.
DETECTOR WIRING
Connect the detector as shown in Figure 3, and wire to the control panel following the wiring connection drawing installed or referenced on each control panel. Duplicate wiring information is also contained in the Installation, Operation, and Maintenance Manual provided with every control panel.
A maximum of five DF-30 detectors may be connected on a single circuit (such as ZN-30 or ZU-35). The detector requires a two-wire circuit of 18 AWG thermoplastic fixture wire enclosed in conduit, or 18 AWG limited energy shielded cable without conduit, if permitted by local building codes.
CAUTION: Do not use looped wire under terminal 5. Break wire run to provide supervision of connection.
To initiating circuit of
End-of-line
Siemens Building
device capacitor,
Technologies, Inc. System 3 Control Panel
5 6
1b
1a
P/N 100-115588
Connect for listed remote and/or DF-30A detectors can be lamp or relay. 40mA max connected on a single circuit at 24V (1 per detector) ( ZN-30 or ZU-35)
5 6
50 MFD, 50 VDC
1b
1a
NOTE: A maximum of five DF-30
Figure 3
Installation/Wiring Diagram
7
Page 8
DETECTOR MOUNTING
The detector comes with a separate base which attaches to a standard 4-inch square or octagonal electrical box or a single gang switchbox, with the box size and depth required by the National Electrical Code for the number and size of conduit used.
NOTE: When using a remote relay, a 4-inch square, deep electrical
box must be used.
Connect the base as described in the Installation Instructions, P/N 315-083225, provided with the base assembly.
INSTALLATION OF DETECTOR HEAD
1. Align notch in detector cover to raised surface on outer ring of base. Refer to Figure 4.
2. Push detector head into base and rotate clockwise to make the electrical connections. The detec­tor automatically stops and locks into place.
3. To remove the detector head, push it up into the base while rotating the detector head counterclock­wise until a stop is reached. Then pull downward to separate from base.
Figure 4
MAINTENANCE
Clean the dust from the detector head by using the suction of a vacuum cleaner. Disconnect the power during cleaning. Clean the detector at least every 6 months depending on the detector envi­ronment and NFPA Standard 72 National Fire Alarm Code, Chapter 5 and CAN/ULC-S524.
Contamination of the detector window could prevent the entry of radiation, and thus prevent operation of the detector. The detector viewing surface should be carefuliy cleaned as necessary, using rubbing alcohol and a soft nonabrasive cloth.
UNDER NO CIRCUMSTANCES IS THE DETECTOR HEAD TO BE DISASSEMBLED. DO NOT ATTEMPT FIELD REPAIRS. THE DETECTOR IS FACTORY REPAIRABLE ONLY.
P/N 315-092604-4
Loading...