Siemens DESIGO PX, DESIGO PXA40-RS Series, DESIGO PXA40-RS1, DESIGO PXA40-RS2, DESIGO PXC001.D Series Manual

...
Page 1
s
9
223
System controllers
PXC001.D PXC001 PXA40-RS...
for the integration of third-party devices and systems in Desigo
-E.D
Integration platforms and system controllers for third-party devices and
systems via KNX, Modbus, M-Bus and other protocols into the automation level via BACnet
System controllers for the integration of Desigo RXB/RXL room controllers
Native BACnet devices with communication via BACnet/LonTalk or
BACnet/IP
BTL label (BACnet communications passed the BTL test)
Comprehensive management and system functions (alarm management,
time scheduling, trends, remote management, access protection etc.)
Supports operation via local or network-compatible operator units PXM…
CM1N9223en_01 2014-04-04
Building Technologies
Page 2
Use
System controllers
Type
or SCL over BACnet/LonTalk
PXC001.D or SCL over BACnet/IP
PXC001-E.D Option modules
Type
Up to 800 data points
PXA40-RS1
M- Bus and Modbus: up to 2000 data points)
PXC001.D PXC001-E.D
PXA40-RS1
PXA40-RS2 Interfaces
KNX
X
--
--
Serial RS232
X
--
--
Serial RS485
X
--
--
Network functions
Integration KNX
2000 DP
--
--
Integration M-Bus
250 DP
800 DP
2000 DP
Integration Modbus
250 DP
800 DP
2000 DP
Integration SCL
250 DP
800 DP
1000 DP
Option modules are "hot-pluggable"
Functions
Type summary
The system controllers support the integration of Desigo RXB/RXL room controllers as well as third-party devices and systems via KNX, Modbus or M­Bus etc. in the automation level using BACnet/LonTalk or BACnet/IP
Mapping and monitoring of third-party disciplines as HVAC, light, SPS etc.
Functionality as freely programmable system controllers for standard or
proprietary protocol applications
The system controllers provide the infrastructure to hold and execute the system and application specific functions. They are freely programmable.
Comprehensive management and system functions are available:
Alarm management
Time scheduling
Trends
Access protection
Equipment combinations
System-Controller for the integration of KNX, M-Bus, Modbus
System-Controller for the integration of KNX, M-Bus, Modbus
SCL: up to 1000 data points,
PXA40-RS2
PXA40-… option modules can be plugged and unplugged when the automation station is operating.
The functionality is available immediately after inserting.
The functionality disappears approx.1 minute after unplugging.
2 / 10
Siemens PXC001 System controllers CM1N9223en_01 Building Technologies 2014-04-04
Page 3
Ordering
1
Plastic housing
2a 2b
Front cover PXM40-RS... option module
3
Plug-in screw terminal block (operating voltage)
4
Plug-in screw terminal block (LONWORKS bus, PXC001.D only)
5
Network interface RJ45 (BACnet / IP, PXC001-E.D only)
6
LED indicators for communication
7
LED indicators for device and system status
8
Service pin (Network identification)
9
RJ45 Interface for operator unit and tool (RJ45, PXC001.D only)
10
Plug-in screw terminal block (RS485)
11
RS232 interface
12
Plug-in screw terminal block (KNX)
13
RJ45 interface (ETS tool for service use)
14
KNX programming pin
15
RJ45 interface for operator unit or PX KNX tool
16
Slider for mounting on DIN rail
RX TX
SERVICE
RX TX
RS232/RS485
KNX
SERVICE
INFO
COMM
LOW BATT
FAULT
RUN
HMI/TOOL
HMI
5
4
CLB
CLA
1 2
3
678
RS485
RS232
9 10
CE -
SERVICE
KNX
TOOL
CE +
2b
9223z16
Product number
Stock number
Designation
PXC001.D
S55372-C113
System controllers ( BACnet/LonTalk)
PXC001-E.D
S55372-C114
System controllers (BACnet/IP)
PXA40-RS1
S55372-C115
Option module RS1
PXA40-RS2
S55372-C116
Option module RS2
PXC001...
Mechanical design
The compact construction enables the devices to be mounted on a standard mounting rail.
PXA40-RS...
Siemens PXC001 System controllers CM1N9223en_01 Building Technologies 2014-04-04
3 / 10
Page 4
The terminal blocks are removable for easy wiring.
LED
Color
Activity
Function
Continuously OFF
No power
Rapid flashing
Firmware missing / corrupt
BATT
Continuously ON
Battery empty– replace!
Flashing
Communication
INFO
Red
Freely programmable
command
command
2s
1s
21s
5 Hz 5 Hz
9222z02
2s
1s
Terminal blocks
LED indicators
Service pin
Communication
RS232/RS485: RX (Green) : TX (Yellow) KNX: RX (Green) TX (Yellow) Service (Red)
The other LEDs have the following meaning:
Service pin
RUN
FAULT
LOW
COMM
SERVICE (Ethernet, PXC001­E.D)
SERVICE (LonTalk, PXC001.D)
Green Continuously ON
Red Continuously OFF
Continuously ON
Red Continuously OFF
Red Continuously ON
Continuously OFF
Red Continuously OFF
Continuously ON Flashing Flashing per wink command *)
Red Continuously OFF
Continuously ON
Flashing Flashing per wink
command *)
Power OK
OK Fault
Battery OK
Connection to switch OK No connection to switch
OK No connection to switch No IP address configured Physical identification of system controller after receipt of wink
ONWORKS node is configured
L
Faulty L
ONWORKS chip, or service pin
currently depressed
ONWORKS node is not configured
L Physical identification of system
controller after receipt of wink
Wink command pattern:
*)
Identification of the system controller in the IP network or L
ONWORKS network
See "Commissioning".
Engineering
See the PX open documents in folder CM110761.
4 / 10
Siemens PXC001 System controllers CM1N9223en_01 Building Technologies 2014-04-04
Page 5
Mounting
Load plant operating program
Setting parameters and configurations
Wiring test
Network connection
Download
Restart
Commissioning
Force Firmware
The devices can be snapped onto standardized rails.
The power supply, LonTalk, RS485 and KNX connections have plug-in screw terminal blocks. The other interfaces are quick plug-in connections.
Instead of the front cover a PXA40-RS... option module can be fitted on the device.
In order to prevent equipment damage and/or personal injuries always follow local safety regulations and the required safety standards.
The plant operating program is downloaded using the CFC from XWP – locally via the automation station's RJ45 interface or via the network (BACnet/IP or BACnet/LonTalk).
Use the PX Design tool in XWP for setting the control parameters and the configuration data. Data visible on the network may also be edited with an operator unit PXM20 / PXM20-E (BACnet / LonTalk or BACnet / IP).
Part of the data can also be edited locally using the operator unit PXM10 (not available for PX KNX).
Use the Point Test Tool.
The network addresses are configured with XWP. For unique identification in the network (BACnet/IP or BACnet/LonTalk), press the Service button with a long, pointed object or send a wink command to the appropriate system controller (service LED blinks).
Variant via V24: If the Force Firmware Download Key is pressed for approx. 10 s during a restart (reset), the current D-MAP program is deleted from the FLASH. The system controller waits briefly for the signal to activate the FWLoader and then starts the system controller.
IP variant: (for PXC001-E.D, significantly faster than via V24) Press the Force Firmware Download key for 5 seconds (without hitting the reset button).
Prerequisite: A node setup of the controller has been conducted and no application is loaded or it was deleted in the CFC by clear/reset (communication settings remain – which would not be the case when restart erasing by pressing the reset key).
Siemens PXC001 System controllers CM1N9223en_01 Building Technologies 2014-04-04
For details see the Firmware Download Tool User's guide, CM110626.
Press the Reset button to force a restart
5 / 10
Page 6
Disposal: Seal battery terminals with tape.
Service
Lithium
Lithium
Position of
buttons and batteries
Note
Battery life
Replacing the battery
STOP
Firmware upgrades
Maintenance
Caution!
The KNX programming pin is situated next to the KNX terminal block and the KNX tool plug
The real time clock is backed by a lithium battery type CR2032
Life span without charge: min. 10 years.
Life span with battery operation (cumulative): up to 1 month.
After the "Battery low" event
1)
the remaining life span under load is several
days.
The trend data and the actual parameters stored in the SDRAM memory are backed by a Lithium battery type FR6/AA AA.
Life span without charge: min. 10 years.
Life span with battery operation (cumulative): up to 1 month.
After the "Battery low" event
1)
the remaining life span under load is approx.
15 hrs.
1) "Battery low" event: The "LOW BATT" LED lights up when one of the batteries' charge is low, and the automation station automatically sends a system event.
To change the battery, remove the front cover. The battery can be removed indefinitely as long as the unit has power. Insert new battery correctly (+ / –).
• Note the special disposal notes on Li batteries.
A wrist-strap and grounding cable must be used to avoid hardware
damage through electrostatic discharge (ESD).
Firmware and operating system stored in non-volatile Flash ROM. Flash ROM memory can be easily updated on the plant, when a new firmware version is available.
Disposal
The devices are classified as waste electronic equipment in terms of the European Directive 2012/19/EU (WEEE) and should not be disposed of as unsorted municipal waste. The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. Lithium batteries: May catch fire, explode or leak. Do not short circuit, charge, disassemble, dispose of in fire, heat above 100°C, or expose to water.
6 / 10
Siemens PXC001 System controllers CM1N9223en_01 Building Technologies 2014-04-04
Page 7
Technical data
General device data
Operating voltage
AC 24 V ± 20%
Rated voltage
AC 24 V
Safety extra-low voltage SELV or Extra-low voltage PELV
HD 384 Operating frequency
50/60 Hz
Energy consumption
Max. 3.5 VA
External fusing (compulsory)
External fuse protection for secondary current: Slow blow fusible link Max. 10 circuit breaker Max. 13 A type C, or transformer with secondary current limitation of max. 10 A
Operating data
Processor
Motorola Power PC MPC885
Storage
64MB SDRAM / 32MB FLASH (96MB total)
Data backup in event of power failure
Battery Backup of realtime clock Lithium CR2032 (field replaceable)
Battery operation (cumulative): 1 month Without load: 10 years
Battery backup for SDRAM 1 x FR6/AA Lithium (field replaceable)
Battery operation (cumulative): 1 month Without load: 10 years
Interfaces, communication
Building Level Network
LonWorks FT5000 Transceiver
BACnet on UDP/IP
(RJ45, shielded)
Local Communication
PXM10 (RS232)
Tool (RJ45)
-­Local Communication (HMI)
PXM10 (RS232)
PXM20 (BACnet/LonTalk) (RJ45)
PXM10 (RS232)
One PXM10 operator unit and one
type.
One PXM10 on RJ45
KNX Tool-Interface
RJ45
CE+, CE–
KNX bus
Interface type
KNX (electrically isolated)
Transceiver
TP-UART
Bus current
5 mA
Baud rate
9.6 kbit/s
Bus topology, bus termination
Refer to KNX manual
RS232 interface
Baud rate
300, 600, 1200, 2400, 4800, 9600,
(depends on software)
Data bits
7 or 8 (depending on software)
Stop bits
1 or 2 (depending on software)
Parity
None, even or odd
(depending on software)
Flow control
Xon/Xoff, hardware or none
(depending on software)
Cable length
9-core standard screened cable Max. 3 m
A,
PXC001.D PXC001-E.D
(HMI, Tool)
Twisted Pair, 78 kBit/s (Screw terminals)
PXM20 (BACnet/LonTalk, RJ45)
PXM20 per system controller may be connected. But not twice the same
IEEE802.3, Auto-sensing 10 Base-T / 100 Base-TX
19200, 38400
Siemens PXC001 System controllers CM1N9223en_01 Building Technologies 2014-04-04
7 / 10
Page 8
RS485 interface
Interface type
RS485, (electrically isolated)
Baud rate, data bits / stop bit(s), parity
As for RS232 (depends on software)
Cable length
Standard RS bus cable Max. 1200 m
Plug-in screw terminal
Solid or stranded conductors
0.25…2.5 mm2 or 2 x 1.5 mm2
Simple cable lengths, cable types
Connection cable Ethernet and PXM20-E
Max. 100 m
Cable type
Standard at least CAT5 UTP (Unshielded Twisted Pair) or STP (Shielded Twisted Pair)
Connection cable LONWORKS bus
See Installation Guide CA110396
Cable type
CAT5
Housing protection standard
Protection standard
IP 20 to IEC 60529
Protection class
Protection class
III to EN 60730
Ambient conditions
Normal operation
To IEC 60721-3-3
Environmental conditions
Class 3K5
Temperature
0...50 °C
Humidity
5…95 % r.h. (non-condensing)
Mechanical conditions
Class 3M2
Transport
To IEC 60721-3-2
Environmental conditions
Class 2K3
Temperature
-25…70 °C
Humidity
5…95 % r.h. (non-condensing)
Mechanical conditions
Class 2M2
Standards, directives and approvals
Product standard
EN 60730-1
CM1T9223xx
CM1T922
Zertifikat
AMEV: Supports profiles AS-A and AS-B to
buildings"
BACnet 2011, V1.1 http://database.ul.com/
Document download
www.hqs.sbt.siemens.com/gip/general/dlc/dl c_mobile_direct.asp?BPZ:PXC001
Environmental compatibility
The product environmental declaration
environmental benefit, disposal)
ISO 14001 (Environment) ISO 9001 (Quality)
Dimensions
See “Dimensions”
Weight
Without / with packaging
PXA-40-RS1, PXA40-RS2
0.635 kg / 0.731 kg
0.048 kg / 0.060 kg
2en_C1
AMEV directive "BACnet in public
CM1E9223 contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging,
PXC001.D, PXC001-E.D
8 / 10
Siemens PXC001 System controllers CM1N9223en_01 Building Technologies 2014-04-04
Page 9
Pin assignment
9222z12
8 7 6 5 4 3 2 1
4. Not used
8. Not used
9215Z01
8 7 6 5 4 3 2 1
4. G/Plus
8. COM1/RxD
9215Z01
8 7 6 5 4 3 2 1
1. LONW
Data A (CLA)
4. G / Plus
8. COM1 / RxD
9280Z03
8 76 5 4 3 21
4. Not used
8. Not used
9281z04
1 2 3 4 5
6 7 8 9
1
DCD
Data carrier detect
6
DSR
Data set ready
2
RXD
Received data
7
RTS
Request to send
3
TXD
Transmit data
8
CTS
Clear to send
4
DTR
Data terminal ready
9
NC
Not connected
5
GND
Signal ground
1 2
3
5
4
CLB
CLA
6
7
8
9 10
CE
-
CE
+
Supply plug
(PXC001.D)
(PXC001-E.D)
(PXC001-E.D)
Plug "HMI" and
(PXC001.D)
Tool plug (KNX)
RS232 plug serial
RS485 plug
KNX plug
LONWORKS plug
Ethernet plug
"HMI" plug
Plug-in screw terminal block
1 AC 24 V 2 Ground 3 Functional earth
Plug-in screw terminal block
4 CLA LonWorks Data A 5 CLB LonWorks Data B
RJ45 socket screened, standard connection in accordance with AT&T256
1. Tx+
2. Tx –
3. Rx +
5. Not used
6. Rx –
7. Not used
1. Unoccupied
2. Unoccupied
3. G0, GND
5. Not used
6. Not used
7. COM1/TxD
"HMI/Tool"
ORKS
2. LONWORKS Data B (CLB)
3. G0 / GND
5. Not used
6. Not used
7. COM1 / TxD
1. KNX data (CE+)
2. KNX data (CE–)
3. Not used
5. Not used
6. Not used
7. Not used
Plug-in screw terminal block 6 + Tx 7 – Rx 8 Screen, connected to functional earth
Siemens PXC001 System controllers CM1N9223en_01 Building Technologies 2014-04-04
Plug-in screw terminal block
9 (CE–) – KNX data cable 10 (CE+) + KNX data cable
9 / 10
Page 10
Dimensions
7
50.2
58
143
46
15
38.5
50.8
70
256
271.5
133,5
149.4
90
44.3
32.5
9223M01
All dimensions in mm
2014 Siemens Switzerland Ltd Subject to change
10 / 10
Siemens PXC001 System controllers CM1N9223en_01 Building Technologies 2014-04-04