Hand-held terminal with three operating levels, easy-to-read display panel and
user-friendly key pad, for commissioning, tuning and servicing of HVAC systems
incorporating controllers in the DESIGO 30 range.
The service terminal is connected to the LON bus, so allowing the user access
(depending on operating level) to the data from the connected DESIGO 30 devices.
The basic procedure for operation is as follows:
Menu and data points are selected using the four navigation keys. Selected points are
displayed in inverse video, and adjustable values can be modified with the + and
keys. Modified values are accepted with
esc
key.
enter
, and functions are terminated with the
BCS
–
Operating levels
Password
50169A
1
?
esc
+
–
Operating level 1:(level on start-up): For access to all the controller values needed
Operating level 2:Controller tuning based on the check list.
Operating level 3:Access to all controller data (for specially trained service
Factory settings:
– Operating level 1 = A
– Operating level 2 = B
– Operating level 3 = C
2
3
4
for normal operation (plant status, all inputs and outputs, setpoints and time programmes). Simple commissioning using the
check lists.
Siemens Building TechnologiesCA2N3295E / 03.1999
Landis & Staefa Division1/4
Page 2
Mounting
The BCS is designed primarily as a hand-held operator terminal. As an alternative, a
bracket is available, which can be screwed onto any surface. The service terminal can
be clipped onto this bracket when not in use. The BCS may, however, also be mounted
in a control panel front, if required. The service cable, which incorporates the LON bus
and power supply, can be plugged into the service socket of a controller.
Accessories
Operating notes
Menu tree
– Case for protection of service terminal (e.g. in tool boxes) and User Manual, R23
– Service cable, 3 m long
– Wall bracket. See Manual R21 section 04.20 for detailed installation instructions.
BCS settings
Overview
Overview
Opera t i ng level
Subnet selection
Comms. pr otocol
Internal setting
Data representation
Language information
2)
3)
2)
Opera t i ng level 1
Opera t i ng level 2
Opera t i ng level 3
Definition devices
2)
OverviewOverview
Device registration
Remove device
3)
2)
Check ne twork
3)
2)
2)
2)
3)
Alarms / Network time
2)
Overview
Last 32 alarms
Set bus time / date
2)
2)
2)
Device list
Overview
Device 1 (RC.., BCE, BCS, APED30)
Device n
Overview
(e.g. RCK-WU)
Important datapoints
Week program
Date program
Proportional seq. Y1
Proportional seq. Y3
Proportional seq. Y5
Value of cascade
Setpoint reset
Regulation sensor X1
Shift sensor X2
Setpoint E x t ernal
Output He at ing Y1
Output Cooling Y3
Output heat Y5
Output Digital Y2
Alarm
Output Clock
Frost sensor X4
Output Frost
Control relay Step 1
Control relay Step 2
Struc ture data
Alarm summaries
Device data
60269EN
2)
2)
2)
2)
2)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
2)
Display and indication
Display
The display window accommodates 10 lines of
26 characters each. The first two lines display the
controller and the menu option. The remaining
eight lines are used to display the data
associated with the selected menu.
FieldSymbolDescription
aPath (two lines)
bData field (eight lines)
a / bForced value
Alarm
Unstructured controller
Undefined device
Battery discharged
cMore data to the left
dMore data to the right
eBCS busy
Activity on bus
Bus error
fAlarm received
Fields and symbols
a
5051 1
defc
ggbb
g
Position indicators, more data in direction of arrow
CA2N3295E / 03.1999Siemens Building Technologies
2/4Landis & Staefa Division
Page 3
Keypad
Examples of display
and operation
Start-up
KeyDescription
Navigation
Select menu item
keys
Edit keysModify data in selected menu (modifiable data is shown in
inverse video):
+ –
esc
Info key
Increase / decrease value or On / Off
enter
↵
: Transmit the data entered
Terminate function (without transmitting any data entered)
Display codes or abbreviations in full (Hold key down; the
information remains in the display window until the Info key is
?
released)
Fast keys
The navigation keys and the + and – keys have a double action: light pressure for
slow, and heavy pressure for fast operation. This allows you to jump quickly from a
menu option or data point to the next, or to the bottom of the display.
50503EN
Device list
Overview
001:VentilationEast
001:VentilationWest
001:Heating system A
002:Heating system B
003:Heating,basement
On start-up, the BCS display provides an overview of
the devices connected to the bus. Use the navigation
keys to select a device. The selected device will be
shown in inverse video. Use
enter
to jump to the
relevant menu. Press ? to display detailed
information about the selected item.
YD1 =On
YD2 =Off
CLCK =Auto I
W =20.0°C
MODE =Auto
XB =5.0°C
XON =5.0°C
FCOF =1.0K
50504EN
Use the navigation keys to select the letters or
numbers required, and press + to write them in the
data entry field or – to delete them. When you leave
the data field after making changes to the name, you
will be asked to confirm the data entered. Press
enter
to complete the input process. The same display is used to enter a unique name when registering
a device on the bus, and for password entry.
50505Aen
Modifying a value:
Use the navigation keys to select the value. If modifiable, the value will be displayed in inverse video.
Prepare to modify value by pressing + / – . The value
will flash. Modify the value with + / – keys. Accept
the new value with
enter
or press
esc
the new value (the original value will be retained).
50506Aen
When a day is selected with the navigation keys, the
associated switch programme will be displayed
automatically. The days are also marked (with thick
or thin bars) to display the switch-on and switch-off
times graphically. To define a time programme, enter
the switch-on and switch-off times with the + /
keys and confirm with
enter
. To copy a complete
switch programme, move to the "Copy to ..." option
and use the + / – keys to select the day. Press
enter
to accept. To delete switch times, use the –
key to set switch states to – – – and press
to abandon
–
enter
.
Fr Sa
24
50502EN
To define a date programme, select the required
date with the navigation keys and set with + or delete
Su
with the – key. When you leave this option you will
be asked to confirm the data entered. Acknowledge
25
with
enter
. Use the navigation keys (left, right, down)
Date programme
Ventilation East
Date programme
Mo
JUNE
1995
TuWeTh
6 7 8 9 10 11
5
12
13
14 15 16 17 18
19
21
20
27 282930
26
1 2 3 4
22 23
to move to the previous or next month. Use esc or
the up-navigation key to exit to the path area.
Siemens Building TechnologiesCA2N3295E / 03.1999
Landis & Staefa Division3/4
Page 4
Graphics
Ventilation East
Proportional sequence Y1
V
8
4
Ventilation East
Setpoint re se t
K
-30
30
0
50507EN
Changing a value on the graph:
Select the value with the navigation keys. If it is
K
modifiable, the value will be shown in inverse video.
Prepare the modification with + / – . The value will
flash. Modify the value with the + / – keys.
50508EN
enter
Press
to adopt the new value, or press
esc
to
abandon it (the original value will be retained).
Technical data
Power supply
Connection
Communication
Weight / Dimensions
Cleaning
General ambient conditions
2
-10
252
2
32 °C
Supply voltage Low voltage (SELV)
Nominal voltageAC 24 V, 50/60 Hz
– Admissible tolerance+15 / –10 %
Power consumptionMax. 200 mA
ConnectionRJ45 socket
Service cable3 m, RJ45 connector at each end (comms and power)
LON with BACnet protocol
– Connection2-wire (comms only, without AC 24 V)
– Max. cable length1100 m (unscreened)
– Bus terminationOn rear, set by switch
Weight (excluding packaging)0.38 kg
Dimensions (W x H x D)110 x 210 x 45 mm
CleaningUse a damp cloth only. Use soap or solvent only.
Do not allow moisture to enter the housing.
Conditions of use For indoor use
Temperature range
– Operation 5 ... 45 °C
– Storage–25 ... 70 °C
Ambient humidity10 ... 90 %rh, non-condensing
Safety
Dimensions
Product safetyEN 61010-1
– Overvoltage categoryII
– Contamination level2
Electrical safetySELV-E (PELV to IEC 364-4-41)
ConformityThis product meets the requirements for CE marking
V
ED
All dimensions in mm
110
210
45
5061 1
130
85
Wall bracket
47
50612
1999 Siemens Building Technologies Ltd.Replaces R21-07.50
CA2N3295E / 03.1999Siemens Building Technologies
4/4Landis & Staefa Division