Siemens DESIGIO 30 User Manual

Page 1
DESIGO 30
295
3
Use / Functions
Service terminal
Hand-held terminal with three operating levels, easy-to-read display panel and user-friendly key pad, for commissioning, tuning and servicing of HVAC systems incorporating controllers in the DESIGO 30 range.
The service terminal is connected to the LON bus, so allowing the user access (depending on operating level) to the data from the connected DESIGO 30 devices.
The basic procedure for operation is as follows:
Menu and data points are selected using the four navigation keys. Selected points are displayed in inverse video, and adjustable values can be modified with the + and keys. Modified values are accepted with
esc
key.
enter
, and functions are terminated with the
BCS
Operating levels
Password
50169A
1
?
esc
+
Operating level 1: (level on start-up): For access to all the controller values needed
Operating level 2: Controller tuning based on the check list. Operating level 3: Access to all controller data (for specially trained service
Factory settings:
– Operating level 1 = A – Operating level 2 = B – Operating level 3 = C
2
3
4
for normal operation (plant status, all inputs and outputs, set­points and time programmes). Simple commissioning using the check lists.
engineers and system contractors).
Key 1 Display 2 Info key 3 Edit keys 4 Navigation keys
Siemens Building Technologies CA2N3295E / 03.1999 Landis & Staefa Division 1/4
Page 2
Mounting
The BCS is designed primarily as a hand-held operator terminal. As an alternative, a bracket is available, which can be screwed onto any surface. The service terminal can be clipped onto this bracket when not in use. The BCS may, however, also be mounted in a control panel front, if required. The service cable, which incorporates the LON bus and power supply, can be plugged into the service socket of a controller.
Accessories
Operating notes
Menu tree
– Case for protection of service terminal (e.g. in tool boxes) and User Manual, R23 – Service cable, 3 m long – Wall bracket. See Manual R21 section 04.20 for detailed installation instructions.
BCS settings
Overview
Overview
Opera t i ng level
Subnet selection
Comms. pr otocol
Internal setting
Data representation
Language information
2)
3)
2)
Opera t i ng level 1
Opera t i ng level 2
Opera t i ng level 3
Definition devices
2)
OverviewOverview
Device registration
Remove device
3)
2)
Check ne twork
3)
2)
2)
2)
3)
Alarms / Network time
2)
Overview
Last 32 alarms
Set bus time / date
2)
2)
2)
Device list
Overview
Device 1 (RC.., BCE, BCS, APED30)
Device n
Overview
(e.g. RCK-WU) Important datapoints Week program Date program Proportional seq. Y1 Proportional seq. Y3 Proportional seq. Y5 Value of cascade Setpoint reset Regulation sensor X1 Shift sensor X2 Setpoint E x t ernal Output He at ing Y1 Output Cooling Y3 Output heat Y5 Output Digital Y2 Alarm Output Clock Frost sensor X4 Output Frost Control relay Step 1 Control relay Step 2 Struc ture data Alarm summaries Device data
60269EN
2)
2)
2)
2)
2)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
2)
Display and indication
Display
The display window accommodates 10 lines of 26 characters each. The first two lines display the controller and the menu option. The remaining eight lines are used to display the data associated with the selected menu.
Field Symbol Description
a Path (two lines) b Data field (eight lines) a / b Forced value
Alarm Unstructured controller Undefined device
Battery discharged c More data to the left d More data to the right e BCS busy
Activity on bus
Bus error f Alarm received
Fields and symbols
a
5051 1
defc
ggbb
g
Position indicators, more data in direction of arrow
CA2N3295E / 03.1999 Siemens Building Technologies 2/4 Landis & Staefa Division
Page 3
Keypad
Examples of display and operation
Start-up
Key Description
Navigation
Select menu item
keys Edit keys Modify data in selected menu (modifiable data is shown in
inverse video):
+ –
esc
Info key
Increase / decrease value or On / Off
enter
: Transmit the data entered
Terminate function (without transmitting any data entered) Display codes or abbreviations in full (Hold key down; the
information remains in the display window until the Info key is
?
released)
Fast keys
The navigation keys and the + and – keys have a double action: light pressure for slow, and heavy pressure for fast operation. This allows you to jump quickly from a menu option or data point to the next, or to the bottom of the display.
50503EN
Device list
Overview
001:Ventilation East 001:Ventilation West 001:Heating system A 002:Heating system B 003:Heating,basement
On start-up, the BCS display provides an overview of the devices connected to the bus. Use the navigation keys to select a device. The selected device will be shown in inverse video. Use
enter
to jump to the relevant menu. Press ? to display detailed information about the selected item.
Changing the operating level
Two-column table
Week (7-day) programme
BCS Setti ng s Operating level
Password ?
> < ABCDEFGHIJKLMNOPQRSTUVWXYZ
abcdefghijklmnopqrstuvwxyz 0123456789+–_/!•?$äöü
Ventilati on East
Important datapoints
X1 =21.0°C X2 =14.0°C X3 =23.0°C X4 =10.0°C Y1 =5.3V Y3 =0.0V FRIND =On Y2 =0.0V
Ventilation East
Week progra mme
Mo Tu We Th Fr Sa Su
0 2 4 6 8 10 12 14 16 18 20 22 24
06:00 On 21:30 Off
--:-- ---­Copy to : ...
YD1 =On YD2 =Off CLCK =Auto I W =20.0°C MODE =Auto XB =5.0°C XON =5.0°C FCOF =1.0K
50504EN
Use the navigation keys to select the letters or numbers required, and press + to write them in the data entry field or – to delete them. When you leave the data field after making changes to the name, you will be asked to confirm the data entered. Press
enter
to complete the input process. The same dis­play is used to enter a unique name when registering a device on the bus, and for password entry.
50505Aen
Modifying a value:
Use the navigation keys to select the value. If modi­fiable, the value will be displayed in inverse video. Prepare to modify value by pressing + / – . The value will flash. Modify the value with + / – keys. Accept the new value with
enter
or press
esc
the new value (the original value will be retained).
50506Aen
When a day is selected with the navigation keys, the associated switch programme will be displayed automatically. The days are also marked (with thick or thin bars) to display the switch-on and switch-off times graphically. To define a time programme, enter the switch-on and switch-off times with the + / keys and confirm with
enter
. To copy a complete switch programme, move to the "Copy to ..." option and use the + / – keys to select the day. Press
enter
to accept. To delete switch times, use the –
key to set switch states to – – – and press
to abandon
enter
.
Fr Sa
24
50502EN
To define a date programme, select the required date with the navigation keys and set with + or delete
Su
with the – key. When you leave this option you will be asked to confirm the data entered. Acknowledge
25
with
enter
. Use the navigation keys (left, right, down)
Date programme
Ventilation East Date programme
Mo
JUNE 1995
TuWeTh
6 7 8 9 10 11
5
12
13
14 15 16 17 18
19
21
20 27 282930
26
1 2 3 4
22 23
to move to the previous or next month. Use esc or the up-navigation key to exit to the path area.
Siemens Building Technologies CA2N3295E / 03.1999 Landis & Staefa Division 3/4
Page 4
Graphics
Ventilation East
Proportional sequence Y1
V 8
4
Ventilation East
Setpoint re se t
K
-30
30
0
50507EN
Changing a value on the graph:
Select the value with the navigation keys. If it is
K
modifiable, the value will be shown in inverse video. Prepare the modification with + / – . The value will flash. Modify the value with the + / – keys.
50508EN
enter
Press
to adopt the new value, or press
esc
to
abandon it (the original value will be retained).
Technical data
Power supply
Connection
Communication
Weight / Dimensions
Cleaning
General ambient conditions
2
-10
252
2
32 °C
Supply voltage Low voltage (SELV) Nominal voltage AC 24 V, 50/60 Hz
– Admissible tolerance +15 / –10 %
Power consumption Max. 200 mA
Connection RJ45 socket Service cable 3 m, RJ45 connector at each end (comms and power)
LON with BACnet protocol
– Connection 2-wire (comms only, without AC 24 V) – Max. cable length 1100 m (unscreened) – Bus termination On rear, set by switch
Weight (excluding packaging) 0.38 kg Dimensions (W x H x D) 110 x 210 x 45 mm
Cleaning Use a damp cloth only. Use soap or solvent only.
Do not allow moisture to enter the housing.
Conditions of use For indoor use Temperature range
– Operation 5 ... 45 °C – Storage –25 ... 70 °C
Ambient humidity 10 ... 90 %rh, non-condensing
Safety
Dimensions
Product safety EN 61010-1
– Overvoltage category II
– Contamination level 2 Electrical safety SELV-E (PELV to IEC 364-4-41) Conformity This product meets the requirements for CE marking
V
ED
All dimensions in mm
110
210
45
5061 1
130
85
Wall bracket
47
50612
1999 Siemens Building Technologies Ltd. Replaces R21-07.50
CA2N3295E / 03.1999 Siemens Building Technologies 4/4 Landis & Staefa Division