DELTA profil Display and control unit UP 585 5WG1 585-2AB_1
DELTA style Display and control unit UP 584 5WG1 584-2AB_1
DELTA ambiente Display and control unit UP 586 5WG1 586-2AB_1
Product DELTA profil DELTA style DELTA ambiente
Display and control
unit
Frames
Intermediate frames ---
5WG1 585-2AB01 pearl grey
5WG1 585-2AB11 titanium white
5WG1 585-2AB21 anthracite
5WG1 585-2AB71 silver
cut out frames --- ---
5WG1 585-2AB11 titanium white
5WG1 584-2AB21 basalt black
5WG1 584-2AB41 platinum metallic
ordered separately from the DELTA ranges
5TG1 328 titanium white
5TG1 368 basalt black
5TG1 328-1 platinum metallic
5WG1 586-2AB01 arctic white
---
B1 Driver with bus connection *)
B2 Frame
B3 Intermediate frame (only for DELTA style)
B4 Display unit *)
B5 Fixing screw *)
B6 Blende *)
*) Lieferumfang
B6
B1
B2
B3
B4
B5
Diagram 1: Installation of the display unit
Product and Applications Description
The display unit is used to indicate freely programmable
messages. A message generally consists of read-only
text and placeholders.
The display unit can be freely configured with different
fonts, characters and symbols. Depending on the parameter settings, it is possible to assign alarm functions
to the messages. The display is carried out via a graphical LC display. If Arial font is used in 12 pt, 5 lines can be
displayed. The LC display contains green/yellow backlighting which can be switched on and off via software.
The output of an alarm tone can also be set.
The various messages can be selected by pressing the
two push buttons on the display unit. It is also possible
to operate selectable bus functions with two further
push buttons.
The display unit is placed on the bus driver module
together with the relevant frame. It can only function in
connection with this bus driver module and an appropriate application program i.e. the display unit consists
of the device [hardware] and the application program
[software].
The frames are not included with supply and must be
ordered separately. The intermediate frame should be
used for DELTA style.
DELTA profil Display and control unit UP 585 5WG1 585-2AB_1
DELTA style Display and control unit UP 584 5WG1 584-2AB_1
DELTA ambiente Display and control unit UP 586 5WG1 586-2AB_1
With the help of ETS, the application programs can be
selected and the specific parameters and addresses can
be assigned.
Application programs
01 07 Graphical display unit 801501
(for ETS2 version 1.2 or later)
01 07 Graphical display unit 801502
(for ETS3 version 1.0 or later)
• The graphical display unit can indicate up to 16 dif-
ferent messages about the states of bus devices using
various fonts or symbols and can also actively modify
these states.
• The display unit has backlighting as well as a buzzer.
Both the backlighting and the buzzer can be set, optionally active or passive mode.
• In the event of an alarm, a signal is sent on the bus
and the selected message simultaneously flashes in
the centre of the display unit (the frequency can be
set).
Note:
The application programs can be used only with ETS2
version 1.2 or later versions of the ETS.
Installation instructions
• The device can be used for fixed installations, in dry
interior spaces and for integration into a flush socket.
DANGER
V
• The device may only be installed and commissioned
by an authorized electrician.
• The device may not be inserted in the same box as
230 V devices.
• The device may be used in switch sockets, if VDE
approved devices have been used.
• The prevailing safety and accident regulations must
be observed.
• The device may not be opened.
• For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.
Technical data
Power supply
• via the bus line
Operating elements
• 2 push buttons for operating the display function
• 2 push buttons for operating the selectable bus func-
tions
• 1 learning button under the cover for toggling be-
tween normal mode / addressing mode
Display elements
• LC display (contains green/yellow backlighting which
can be switched on and off via software)
• 1 red LED for checking the bus voltage and for dis-
playing normal mode / addressing mode
Number of messages
• 16 (freely selectable)
Number of characters per message
• up to 30 characters per line depending on the font
• up to 3 lines
Alarm functions
• priority display of alarm messages
• optical display (flashing)
• acoustic signal (signal tone)
• acoustic feedback via push button action
Connections
• KNX/EIB bus terminal
Mechanical data
• Housing: plastic
• Dimensions (L x W x D):
- Display unit UP 584, UP 585, UP 586:
65 x 65 x 20 mm (without spring)
65 x 65 x 33 mm (including spring)
- Driver: 71 x 71 x 16 mm
• Weight: approx. 100 g
• Fire load: approx. 1500 kJ ± 10 %
• Installation: The display unit is mounted on the rele-
vant bus driver module. It cannot be plugged onto the
standard type of bus coupler and no other operator
interfaces can be operated on the driver.
DELTA profil Display and control unit UP 585 5WG1 585-2AB_1
DELTA style Display and control unit UP 584 5WG1 584-2AB_1
DELTA ambiente Display and control unit UP 586 5WG1 586-2AB_1
Electrical safety
• Degree of pollution (according to IEC 60664-1): 2
• Type of protection (according to EN 60529): IP 20
• Protection class (according to IEC 61140): III
• Overvoltage category (according to IEC 60664-1): III
• Bus: safety extra-low voltage SELV DC 24 V
• Device complies with EN 50090-2-2 and IEC 60664-1
EMC requirements
• complies with EN 50081-1, EN 50090-2-2 and
EN 61000-6-2
Environmental conditions
• Climatic withstand capability: EN 50090-2-2
• Ambient operating temperature: - 5 ... + 45 °C
• Storage temperature: - 25 ... + 70 °C
• Relative humidity [not condensing): 5 % to 93 %
Reliability
• Rate of failure: 572 fit
Markings
• KNX EIB
CE mark
• In accordance with the EMC guideline (residential and
functional buildings) and the low voltage guideline
Location and function of the operating elements
2
Diagram 2: Location of the display and operating ele-
ments
A1 LC display (LCD) for indicating the messages
A2 Push buttons for scrolling through the lines
(UP / DOWN)
A3 Push buttons for controlling the selectable bus
functions
Installation of the driver
General description
The display unit is placed on the driver together with
the relevant frame.
The driver with bus connection is inserted in boxes of
60 mm ∅ using screw fixing.
The connection to the bus line is carried out via plug-in
screwless terminals for single-core conductors.
The driver with bus connection should be mounted so
that the interface is located at the bottom (Diagram 3).
This ensures that the display unit that is connected to
the interface is mounted in the correct operational position.
Diagram 3: Installation of the driver with bus
C1 Installation box (60 mm Ø according to
DIN 49073)
C2 Slots for fixing
C3 Driver with bus connection
C4 Interface
C5 Fixing screws
Bus terminal
The bus terminal (D2) is located at the rear of the driver.
DELTA profil Display and control unit UP 585 5WG1 585-2AB_1
DELTA style Display and control unit UP 584 5WG1 584-2AB_1
DELTA ambiente Display and control unit UP 586 5WG1 586-2AB_1
Connecting the bus cable
(Diagram 4)
− The bus terminal (D2) is suitable for single-core con-
ductors with 0.6 ... 0.8 mm Ø.
− The bus terminal (terminal block) (D2) consists of two
components (D2.1, D2.2), each with four terminal
contacts, Diagram 7.
− Strip the insulation from the conductor (D3) and place
in the terminal (D2) (red = +, grey = -).
Diagram 4: Connecting the bus cable
Installation of the display
B1
B2
B3
B4
B5
B6
B1 Driver with bus connection
B2 Frames
B3 Intermediate frame (only for DELTA style)
B4 Display unit
B5 Screws for fixing the display unit onto the
driver B1
B6 Cover
- Place the display unit (B4) with B6 and the relevant
frame (B2) onto the driver (B1).
- Remove the cover (B6) from the display unit as de-
scribed under ‘Dismantling’ in order to program the
physical address.
- Secure the display unit (B4) with the two screws (B5).
- Now program the physical address.
The location of the programming button and the programming LED is indicated in Diagram 5.
- Remove the protective film from the LC display,
Diagram 6c.
- Place the cover (B6) on the display unit again (B4).
Location of the programming button and
programming LED
Programming LED
Programming-
button
Diagram 5: Location of the programming button and LED
is also indicated on a non-configured LCD if
bus voltage has been applied
Dismantling
- Remove the cover as described in Diagram 6a or 6b.
Caution:
Do not touch any components apart from the programming button (Diagram 6) as damage could otherwise be
caused.
- Loosen the fixing screws (B5).
- Place the cover (B6) back on the display unit (B4).
- Remove the frame (B2) together with the display unit
- Loosen the screws of the driver in the flush-type box
- Separate the bus driver module from the bus cable
DELTA profil Display and control unit UP 585 5WG1 585-2AB_1
DELTA style Display and control unit UP 584 5WG1 584-2AB_1
DELTA ambiente Display and control unit UP 586 5WG1 586-2AB_1
Removing the cover
(Diagram 6a and 6b)
Variant 1: Gently press the sides of the cover together
and tilt.
Abziehen derAbdeckung
Diagram 6a: Variant 1
Variant 2: The cover has an opening at the top in the
centre for removal. Place the screwdriver at
the opening and lift the top of the cover forwards with the screwdriver.
Diagram 6b: Variant 2
Diagram 6c: Removing the protective film
Removing/inserting the bus terminal (Diagram 7)
− To remove the bus terminal, carefully insert the
screwdriver in the wire entry slot in the grey section
of the bus terminal (D2.2) and pull the bus terminal
(D2) out of the driver (D1).
− To insert the bus terminal, place the bus terminal (D2)
in the guide slot of the driver with bus connection
(D1) and press the bus terminal (D2) downwards until
it reaches the stop.
Do not jumper bus connections as there is a
Note:
danger of shorting the device.
D 2
D 2
D 2.3
D 2.2
D 2.1
D 1
Diagram 7: Removing the bus terminal
Disconnecting the bus cable
(Diagram 8)
− Remove the bus terminal (D2) as shown in Diagram 8
and pull out the conductor (D3) of the bus cable by
simultaneously rotating backwards and forwards.
DELTA profil Display and control unit UP 585 5WG1 585-2AB_1
DELTA style Display and control unit UP 584 5WG1 584-2AB_1
DELTA ambiente Display and control unit UP 586 5WG1 586-2AB_1
Dimension Driver
Dimensions in mm
71
Dimension Display unit
Dimensions in mm
65
65
71
20
16
33
General Notes
• The operating instructions must be handed over to the
client.
• Any faulty device should be returned to the local
Siemens office.
• If you have further questions concerning the product
please contact our technical support: